TATA STEEL LIMITED

Joda East Iron Mine





RAW MATERIAL HANDLING SYSTEM
(PACKAGE 2 & 3)








DESIGN CRITERIA & SIZING METHODOLOGY - ELECTRICAL
DOCUMENT NO: M5006-E670-001










A 05-09-2008 ISSUED FOR APPROVAL RS RS
REV.
NO
DATE REVISION PREP
BY
PROC
ENG
PROJ
ENG
FUNC
MNGR

PROJ
MNGR
CLIENT
RAW MATERIAL HANDLING SYSTEM Page: 2 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008




CONTENTS



1.0 SCOPE
2.0 STANDARDS AND CODES
3.0 SYSTEM PARAMETERS
4.0 DISTRIBUTION SYSTEM DESIGN
5.0 SUBSTATIONS
6.0 CONTROL PHILOSOPHY
7.0 SAFETY
8.0 MV SWITCHGEAR
9.0 POWER FACTOR CORRECTION AND HARMONIC FILTERING
10.0 POWER TRANSFORMERS
11.0 MOTOR CONTROL CENTRES
12.0 LV BUS DUCTS
13.0 SMALL POWER PLUG/SOCKETS & WELDING
14.0 CABLING
15.0 EARTHING
16.0 LIGHTNING PROTECTION
17.0 ILLUMINATION
18.0 BATTERY & CHARGER SYSTEM
19.0 VVVF DRIVES

RAW MATERIAL HANDLING SYSTEM Page: 3 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



1.0 SCOPE

1.1 This narrative covers the design criteria and philosophy for the electrical scope of work for the
Material Handling package for Joda Mines expansion project of TISCO.


1.2 Included

Primary distribution in the Plant Main Substation to the various Process Units.
Secondary distribution in the plant substations to the process areas.
MV Switchgear
Motor control center
Transformer & NGR selection criteria
Motors selection criteria
Cable selection and typical voltage drop calculations
Selection criteria for Earthing and lightning protection.
LT Bus duct selection criteria
AC Drive selection criteria
PF improvement requirement based on final load list
Selection criteria for Outdoor and indoor lighting and small power.
DC system selection criteria
Cable trays selection criteria

1.3 Battery Limits

Incoming terminals of the Plant Main 3.3kV Switchboard at Bateman built substation room.
NBC-3/3A drives at RLS.


2.0 STANDARDS & CODES

2.1 Statutory Requirements

Indian Electricity Rules
State CEIG Rules
TISCO & Bateman statutory requirements


2.2 Standards

All the relevant Indian Standards and codes of practice applicable to the equipment and
installation for the scope of work defined above. The reference to the specific IS is taken
under the respective chapter.

IEC standards and codes of practice applicable to the equipment and installation for the
scope of work defined above. The reference to the specific IEC is taken under the
respective chapter.


RAW MATERIAL HANDLING SYSTEM Page: 4 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008




3.0 SYSTEM PARAMETERS

3.1 System Voltages

Primary distribution : 3.3kV, 50Hz, +10/-15%
Secondary distribution : 415V, 50Hz, +/-10%, 3ph, 4 wire
(Normal & small drives)
Secondary distribution (large VFDs) : 690V, 50Hz, 3ph, 3 wire
Lighting and small power sockets : 230V, 50Hz, 1ph, 2 wire
Emergency Lighting (DC) : 110VDC, +/-15%
Control Voltages (AC) : 110VAC, 50Hz, +10/-15%
Control Voltage (DC) : 110VDC, +/-15%
UPS Supply : 230V, 50Hz, 1ph
Panel Lighting & Panel/Motor space Htr. : 230VAC, 50Hz, 1ph
Welding socket outlets : 415V, 50Hz, +/-10%

3.2 System Earthing

11kV systems (Upstream) : Resistance grounding
3300V systems : Resistance grounding
690V systems for VFDs : Solidly earthed
415/230V systems : Solidly earthed
110V control power : Solidly earthed

3.3 Design Fault Levels

11kV systems (Upstream) : 25kA for 1 sec
3300V systems : 25kA for 1 sec
690V systems : 50kA for 1 sec
415V systems : 50kA for transformer fed MCCs / DBs
230V Lighting and small power : 10kA for LDBs, UPS DBs etc.

3.4 System Frequency

System Frequency : 50Hz, +/-5%

3.5 Site Conditions

Design Ambient temperature : 45 deg.C max & 0 deg.C min.
Relative humidity : 89%
Altitude : > 1000 mtrs from MSL
Seismic data : Seismic zone-II (Stable zone) as per IS-1893
Soil Resistivity : 400 ohm-meter avg.(based on soil resistivity report)
RAW MATERIAL HANDLING SYSTEM Page: 5 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



4.0 DISTRIBUTION SYSTEM DESIGN


4.1 Primary Distribution

Cable feeders from the existing 3.3kV switchboard at existing RLS substation will feed power
supply to the new 3.3kV switchboard new Plant Main Substation. For this purpose, 2 nos of
spare feeders at the existing substation will be used for feeding the new board.

4.2 Secondary Distribution

The Main Plant Substation will be located close to the new RLS-1 & 2 and TP-2. Therefore, the
transformers, MCCs, VFDs and process control system hardware for this area will be installed in
the same building. The power will be fed to various loads and the new RLS from this main
substation through cables laid on the trays.


4.3 Voltage Variation

The variation in voltage of TSL is controlled by automatic tap changers, and hence will be limited
to +3/-5%. However the equipment will be designed to the voltage variations of +10/-15%.

Cables will be selected on the basis of maximum voltage drop from nominal at motor and other
power user terminals of 3% for running and 15% for starting, except that the latter will be 20%
for motors with fluid coupling. This will be reduced as necessary for specific cases of high inertia
loads. The voltage drop for welding outlets will be limited to 5%.


4.4 Power Factor Correction & Harmonic Filtering

The design calculations for Capacitors, with harmonic filters if necessary, will be carried out and
the suggestions will be provided for maintaining the overall power factor at 0.94. (This latter
figure is assumed for the study, but will have to be reviewed when the tariff structure to be
adopted is known so as to arrive at the economically optimum level.)

4.5 Emergency Power Generation

The requirement of emergency power generator is not envisaged as of now.


5.0 SUBSTATIONS

5.1 General Design

5.1.1 There will be only one building for housing MV switchgear and related equipment, LV
Switchgear, distribution, converter and lighting transformers, Lighting DBs, battery
charger, UPS etc. Control systems, remote I/O, control desk will be installed in the
control rooms which will be above the switchgear room. The control room will be air
conditioned and VFDs will also be installed in this control room with a separation.

5.1.2 Switchrooms and MCC rooms will generally be constructed of brick or block with
concrete floors and concrete or sheeted roofs, the latter with thermal insulation and
ceilings.

5.1.3 Cable will be laid in suitably designed trenches.
RAW MATERIAL HANDLING SYSTEM Page: 6 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



5.1.4 Floors and trench bottoms will be maintained in order to avoid water ingress and
accumulation.

5.1.5 Transformers will be placed in the switchgear room with proper separation.

5.1.6 Equipment access doors will be installed for each room. These doors will also serve as
the emergency exits from the rooms and be fitted with the appropriate hardware. A
personnel access door for each room will also be provided.


6.0 CONTROL PHILOSOPHY

6.1.1 MV circuit breakers will be electrically operated, generally from the switchgear panel itself. LV
circuit breakers will also be electrically operated from the panel.

6.1.2 The feeders from the 3.3kV Intake Substation to the Plant Main Substation will normally be
operated in parallel. The interlocking is therefore required between the buscoupler and the
incomers in such a way that both the incomers are ON only when bus coupler is OFF.

6.1.3 As both the 3.3kV incomer circuit breakers will normally be closed, an alarm will be activated
with a signal to the Main Control Room on the opening of any one of them, whether due to a
fault or switching. This will be achieved through a hard wire connection between MV switchgear
and the RIO at the MCC which in-turn will transfer the signal to the main PLC.

6.1.4 Fault trips resulting from relay operation will be hand reset on the relays. A common signal from
each feeder for faults will be taken to the main control room via MCC RIO panel.

6.1.5 Transformer temperature alarms will be a common input to the control system and will also trip
the MV switchgear breaker.

6.1.6 Direct on line Motors will be controlled by semi-intelligent control systems. Control of each
starter will be directly by the control system, via the hard wired signals between the RIO and the
feeder and this inturn will be controlled via communications bus from the remote I/O to be
installed in MCC with the main control system.

6.1.7 VFD driven motors will be controlled from the main plant PLC via a communication bus.

6.1.8 All the motors will have both manual (LPB) and auto mode of operations.


7.0 SAFETY

7.1 Each drive will have a local mushroom head emergency stop pushbutton.

7.2 Conveyors will, in addition to the emergency stop push-button at the head end, have hard-wired
pull-wire switches along accessible sides.

7.3 Transformers will have emergency push buttons near to the equipment.

7.4 Positive isolation will be provided on all switching points in MCC and necessary locking
arrangements will be provided.


8.0 MV SWITCHGEAR

RAW MATERIAL HANDLING SYSTEM Page: 7 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


8.1 Indoor, draw-out, metalclad switchgear will be included for the New RMHS Substation.

8.2 Circuit breakers will be electrically operated, i.e. electrical closing spring charging, trip release
and closing release.

8.3 Protection and metering will be integral with the switchgear assemblies.

8.4 Voltage transformers will be bus connected.

8.5 The board shall be of IP-4X and outer paint shade shall be RAL-7032 (Siemens grey).

8.6 Will permit extension on both the sides.

8.7 Lockout provisions with breakers racked out will be included.

8.8 Electrical interlocks between the two incomers and the bus coupler will be included such that
only one incomer with bus coupler can be switched on and the other incomer will be off.
Alternatively both the incomers can be switched on only when the bus coupler is off. Mechanical
interlock will also be provided by means of castle key.

8.9 The breakers will be VCBs of type VD4 or equivalent. The incomers and bus coupler breakers
will be of 1250A rating and all the other feeders shall be of 630A rating.

8.10 The main bus will be rated for 1250A and the size will be calculated based on the following
factors:

a. Short Circuit Rating of bus bar i.e. 26.2kA for 1 sec
b. Continuous Rating of bus bar

The short circuit rating of the bus bar will be calculated based on the following method:

A = (Ish X t) / K

Where,

A = Cross sectional area in Sq.mm.
Ish = Fault current in kA
t = Fault clearing time in seconds
K = Constant kA / sq.mm. (K = 0.0799 for Aluminum)


I continuous = I table X K1 X K2 X K3 X K4

Where,

I table = Current carrying capacity at 50C amb. & 90C end temp. (Ref. ABB swgr manual)

K1 = Correction factor for load variations relating to conductivity
= 0.99 for conductivity of 35 m/(.mm2) for Aluminum. (Ref. ABB switchgear manual)

K2 = Correction factor for the deviation in ambient temperature and/or bus bar temperature
= 1.15 for amb. Temp. of 50C & bus bar temp. 90C (Ref. ABB switchgear manual)

K3 = Correction factor for the thermal load variation due to difference in layout = 1.0
(Ref. ABB switchgear manual)
RAW MATERIAL HANDLING SYSTEM Page: 8 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



K4 = Correction factor for the electrical load variation due to difference in layout = 1.0
(Ref. ABB switchgear manual)

K5 = Correction factor for influences specific to location = 1.0
(Ref. ABB switchgear manual)


8.11 Protection

8.11.1 Incomers:
Numerical Overcurrent, IDMT and instantaneous, and earth fault relay SPAJ140C or
equivalent

8.11.2 Transformer Feeders:
Numerical Overcurrent, IDMT and instantaneous, and earth fault relay SPAJ140C or
equivalent
Temperature trip and alarm.
Restricted earth fault

8.11.3 Feeders:
Numerical Overcurrent, IDMT and instantaneous, and earth fault relay SPAJ140C or
equivalent

8.11.4 Bus Coupler:
Numerical Overcurrent, IDMT and instantaneous, and earth fault relay SPAJ140C or
equivalent

8.11.5 General:
Trip circuit supervision for all.

8.12 Normal control supplies
Voltage for spring charging motor mechanism 230V AC, 50Hz

Control voltage for closing, tripping, indication, interlocking, 110V DC
annunciation circuits etc.
Auxiliary power supply for relays, transducers etc. 110V DC

Panel Space Heaters, Cubicle illumination lamp, Plug Socket 230V AC, 50Hz
Circuits of all panels and motor space heaters etc.

230V AC control supplies will be derived from lighting supply source. This will be terminated at Incomer-
1 of the switchgear.


9.0 POWER FACTOR CORRECTION AND HARMONIC FILTERING

Design Methodology
The following factors will be considered for designing the capacitor bank size:
1. The total continuous load on the transformer [A]
RAW MATERIAL HANDLING SYSTEM Page: 9 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


2. The total intermittent load on the transformer [B]
3. The total standby load on the transformer [C]
4. Co incident factor for intermittent loads [k1 = 0.5 considered]
5. Co incident factor for standby loads (which generally used during shut down / maintenance
etc.) [k2 = 0]
6. Power factor of various loads [based on available data sheets of motors]
7. 10% margin for additional capacity
8. Rounding off the calculated kVAr to the nearest standard size available.

The capacitor bank size will be calculated based on the following calculation:
Basic KW / KVA [L] = (A) + (k1 x B) + (k2 x C)
PF1 = KW / KVA
PF2 = 0.94
tan 1 = cos
1
(PF1)
tan 2 = cos
1
(PF2)
Required Reactive Compensation [N] = KW ( tan 1 - tan 2 )
Calculated size with 10% additional capacity [M] = L x 1.10
For the purpose of calculating the load current / KVA, the power factor and efficiency of the motors will
be derived from the data sheets of the motors and in case of non availability of the same, the standard
technical data of ABB/Siemens make motors will be considered for the purpose of this sizing
calculations.
The power factor and efficiency in the case of power feeders will be derived and approximated from the
same data for the largest motor within that load.
Detuned filter will be provided where % VFD load is more than 10%. The harmonic spectrum of the
drives will be considered while designing detuned filters, by the drive manufacturer.


10.0 DISTRIBUTION & CONVERTER DUTY TRANSFORMERS

10.1 The transformers will be AN cooled, dry type, Cast resin, vacuum encapsulated type with
manual off circuit links on primary side for voltage variations for +/-7.5% with steps of 2.5%.

10.2 The transformers will be housed in a suitable enclosure of at least IP-20 and the windings shall
have class-F insulation.

10.3 Transformers will have winding temperature detector / scanner with indication, alarm and trip
functions.

10.4 A lockable push button will be provided on the transformer enclosure for emergency stop.

10.5 Primary side shall have provision for cable connections and the secondary will have a provision
for bus duct for transformers of rating 1600kVA and above. The transformers below 1600kVA
will have cables on the secondary side.

10.6 The impedance will be decided by the fault level, but a minimum impedance of 5.5% (with
tolerance as per IS) will be maintained.
RAW MATERIAL HANDLING SYSTEM Page: 10 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



10.7 The distribution transformers shall be of Dyn11 vector group and the neutral shall be earthed
through NGR of 10A rated continuously.

10.8 There will be 2 nos of transformers feeding each of the incomer of PMCC. The rating of the
transformer will be decided in such a way that in case of stoppage of one of the transformers,
the other is loaded upto a maximum of 90%. The kVA rating of the transformers will be the sum
of the total kVA of the continuous load on PMCC and the total kVA of intermittent load on
PMCC. The following factors considered for designing the transformer size:

The total continuous load on the transformer [A]. The kVA of a motor is calculated by the
formula: kVA = motor kW / (motor efficiency x power factor)
The total intermittent load (such as power supplies, cranes, hoists, heaters etc) on the
transformer [B]
The total standby load on the transformer [C]. (loads which are generally used during failure
of running motors, shut down / maintenance etc.)
The load capacity factor (is the calculated motor mechanical absorbed power divided by the
motor rated power) of 0.90 and diversity factor of 0.90 is considered (total factor 0.90 x
0.90 = 0.81) for the continuous loads. [k1 = 0.81]
Co incident factor for intermittent loads [k2 = 0.5 considered]
Co incident factor for standby loads [k3 = 0]
Power factor of various loads [based on available data]
20% margin for spare / additional capacity
Rounding off the calculated kVA to the nearest standard size available with the
manufacturer.

The transformer size will be calculated based on the following calculation:

Basic size in KVA [L] = (k1 x A) + (k2 x B) + (k3 x C)
Calculated size with 20% additional capacity [M] = L x 1.20

For the purpose of calculating the load current / KVA, the power factor and efficiency of the motors will
be derived from the inputs given by the suppliers and in case of non availability of the same, the
standard technical data of ABB make motors will be considered for the purpose of this sizing
calculations.

The power factor and efficiency in the case of power feeders will be derived and approximated from the
same data for the largest motor within that load.

The adequacy of the transformer rating will be further checked for the maximum demand required and
the voltage drop at the time of starting of the largest direct-on-line motor connected with the PMCC. This
will be calculated with the assumption that the motor will draw 6 times of the load current.

The converter transformer will be designed to take care of the following:
RAW MATERIAL HANDLING SYSTEM Page: 11 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


Prevention of electrostatic transfer of higher surge voltages to the converters.
Mitigation of stray losses due to harmonics.
A metallic shield with an earthing terminal is provided between the primary and the
secondary, in such a way to protect the thyristor from over voltage surges due to the
network.
The transformers shall be designed to suppress harmonic voltages specially the 3rd and 5th
so as to eliminate distortion in wave form and the possibility of circulating currents between
the neutrals of different transformer stations. The Total Harmonic Distortion (%THD) of the
voltage waveform because of harmonics developed due to the drives will be taken care by
the supplier while designing the transformer.

The paint shade of the transformer will be 631 as per IS-5 (dark grey).


11.0 MOTOR CONTROL CENTRES

11.1 MCC construction will be indoor duty, free-standing, metal-enclosed, IP42, back-to-back, form 4
to IEC439 (each starter in a separate compartment with segregated bus compartment and
wireways for external cable entry). The PMCC shall be of single front and non-draw out type.

11.2 The board will be designed for a fault level of 50kA / 1 second.

11.3 Spare space equivalent to approximately 20% of starter and feeder space will be included to
cater for changes and possible future additions.

11.4 The contactors used for the motor starters will be of AC-3 duty.

11.5 Type-2 co-ordination will be generally used for the selection of the components.

11.6 Control supply shall be 110V AC from a common double wound transformer per MCC.

11.7 Both the incomers and the bus couplers shall be equally rated and will be capable of carrying
the total load of both the sections of MCC.

11.8 Normally the bus coupler will be off and the load on each section will be catered by the
respective transformer. In case of one transformer out of service, the bus coupler will be
switched on and the total load will be catered by one transformer.

11.9 A suitable electrical interlock as well as castle interlock will be provided between both the
incomers and the bus couplers.

11.10 Feeders

Each Incoming feeder will comprise of the following:
2 no. - 415V,suitably rated, ACB with O/C, S/C and E/F releases
1 no. - Trip circuit healthy PB
1 no. - Breaker control switch close-neutral-trip (lockable)
1 no. - Control supply failure check relay
1 no. - Panel space heater with MCB &Thermostat
RAW MATERIAL HANDLING SYSTEM Page: 12 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


1 no. - DP switch fuse for DC supply
1 no. - Trip ckt. healthy check indication
1 no. - Digital Multifunction Meter with interface feature for Remote display of Current,
Voltage, Frequency, Active (KW), Reactive (KVAR) and Energy (KWH)
1 set - Phase indicating lamps
1 no. - Ammeter with selector switch
1 no. - Voltmeter with selector switch & Fuse
1 set - CTs of suitable ratio for metering and protection

Each Direct On-Line (DOL) starter feeder will comprise of following:
1 no. - TPN Switch Fuse unit
1 no. - Power contactor
1 no. - Electronic over load relay (EOCR)
1 no. - MCB for space heater (for motors above 30 kW)
1 no. - Auxiliary Relay

Each power feeder will comprise of the following:
1 no. - TPN Switch Fuse unit

Each Reversible Direct On-Line (RDOL) starter feeder will comprise of following:
1 no. - TPN Switch Fuse unit
2 nos. - Power contactor
1 no. - Electronic over load relay (EOCR)
1 no. - MCB for space heater (for motors above 30 kW)
1 no. - Auxiliary Relay

Since the PMCC panels are required to be of Semi-intelligent type, the PMCC line-up shall have
a Remote I/O panel for marshalling of signals to and from the PLC.



11.11 Sizing calculations

Generally the following sizing calculations will be carried out:

Calculation of bus bar and incomer current rating
Sizing of main bus bars for short circuit and thermal rating
Voltage drop for bus bars

Current Rating:

The rating of the PMCC main bus bars and the incomer breaker will be the sum of the total current of
the continuous load on PMCC and the total current of intermittent load on PMCC. The following factors
considered for designing the transformer size:
RAW MATERIAL HANDLING SYSTEM Page: 13 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



The total continuous load on the PMCC main bus [A]. The current of a motor is calculated by
the formula: A = motor kW / (motor efficiency x power factor x kV)
The total intermittent load (such as power supplies, cranes, hoists, heaters etc) on the PMCC
[B]
The total standby load on the PMCC [C]. (loads which are generally used during failure of
running motors, shut down / maintenance etc.)
The load capacity factor (is the calculated motor mechanical absorbed power divided by the
motor rated power) of 0.90 and diversity factor of 0.90 is considered (total factor 0.90 x
0.90 = 0.81) for the continuous loads. [k1 = 0.81]
Co incident factor for intermittent loads [k2 = 0.5 considered]
Co incident factor for standby loads [k3 = 0]
Power factor of various loads [based on available data]
10% margin for spare / additional capacity

The incomer and main bus ampere rating will be calculated based on the following calculation:

Basic size in Amp [L] = (k1 x A) + (k2 x B) + (k3 x C)
Calculated size with 20% additional capacity [M] = L x 1.10

For the purpose of calculating the load current, the power factor and efficiency of the motors will be
derived from the inputs given by the suppliers and in case of non availability of the same, the standard
technical data of ABB make motors will be considered for the purpose of this sizing calculations.
The power factor and efficiency in the case of power feeders will be derived and approximated from the
same data for the largest motor within that load.
Bus bar Sizing:
Short Circuit sizing:
Minimum cross sectional area of aluminum bus bar required during 50kA for 1 sec short circuit is given
by formula:
(I/A) x t = 0.0775 for aluminum
Where, I = Short circuit current in kA
t = Duration of short circuit, 1Sec.
A = Cross section of bus bars in sq.mm

Or, A = (I / 0.0775) x t
A = (50/0.0775) x 1 (putting the value)
A = 645.16 sq.mm

Hence, a minimum value of 750 sq mm is suitable for the bus bars from short circuit point of view.

Thermal Rating:

The thermal rating of the bus bars is calculated based on the values given in Indal chart.

1. Derating due to ambient Temperature Factor (K1):
RAW MATERIAL HANDLING SYSTEM Page: 14 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



It will be observed from the tables supplied by the manufacturer that the values for the bus bar
system are given at ambient of 35C for a temperature rise of 50C. But present ambient is
50C, limiting temperature rise to 35C (bus bar temperature is 85C). Hence, suitable deration
factor is applied to arrive at correct ampere capacity of the bar
Derating factor = (T2 / T1) 0.588
Where T2 = Temperature rise at ambient of 50C
T1 = Temperature rise at ambient of 35C
There fore derating factor = (35 / 50) 0.588 = 0.81

2. Derating due to Enclosure Factor (K2):

K2 is considered as 0.9.
3. Proximity factor (K3):

K3 is taken as 1.0, since the current carrying capacities of the bus bars are obtained from the
Indal chart (Annex-A) for calculation. The de-ration of the bus bars for various combinations is
already taken care of for the proximity effect in the chart.
4. Enclosure material factor (K4):

K4 is not considered for currents < 3200 A. Hence K4 = 1.0

5. The Final Capacity of the Bus Bars:

I = I1 x K1 x K2 x K3 x K4
I
1
= I
0
Indal chart {(width X thickness )actual /(width X thickness )Indal chart }
For example:
If the current rating of a bus bar of size 76.2mm x 9.53mm is 2050A as per Indal chart and the
bus bar available in the market is of 75mm x 10mm, then the current rating of 75 x 10mm bus
bar will be:
I
0
= 2050 (75x10 / 76.2x9.53)
= 2083 A
Where K1, K2, K3, K4 are as defined above
Hence, I = 2083 x 0.81 x 1.0 x 1.0 x 1.0 A = 1687 A

Voltage drop
The adequacy of the bus bars rating will be further checked for the maximum demand required and the
voltage drop at the time of starting of the largest direct-on-line motor connected with the PMCC. This will
be calculated with the assumption that the motor will draw 6 times of the load current.

12.0 LV BUSDUCTS

The busducts shall be provided for the transformers of rating 1600kVA and above. The busduct
shall be of non-segregated, self cooled type. The cooling medium inside the duct will be air. The
Busbars shall be of aluminium with continuous rating as specified below. All buses and
connections shall be able to withstand maximum short circuit current. Space heater shall be
provided. All the three phases will be enclosed in a weather proof, dust tight MS CRCA
enclosure of 2.00mm thick. Outdoor section will be rain proof. Minimum degree of protection of
busduct enclosure will be IP 52 for Indoor and IPW 53 for outdoor section.
RAW MATERIAL HANDLING SYSTEM Page: 15 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



The bus duct shall be designed for carrying the rated current, considering the derating due to
temperature and the other effects.
The LT bus duct shall be of phase non-segregated type with aluminum bus bars enclosed in
sheet steel enclosure for rating up to 3200Amps and in aluminum enclosure for ratings above
3200Amps.
Design of bus duct involves the following:
1. Deration of the current carrying bus bars due to the correction factors.
2. Temperature rise calculation
3. Voltage drop calculation
4. Calculation of short circuit withstand capability of the bus bars
Basic parameters considered during the sizing of the bus ducts:
i) Material of the bus bars shall be Aluminum
ii) The design ambient is 50 Deg C.
iii) Maximum allowable temperature of the bus bars over an ambient of 50 Deg. C shall be
limited to 35 Deg.C.
iv) The enclosure material shall be sheet steel for rating up to 3200Amps and
Aluminum for rating above 3200Amps.
v) The open air rating of the bus bar for 50 Deg. C rise over 35 Deg. C ambient is
considered in Amps as = I
0
(annexure-A)
vi) The current carrying capacity of the bus bars is derived from the Indal chart (Annexure
A) depending on the number of bus bars used.

The current carrying capacity of bus bar sizes not mentioned in the Indal chart is
calculated as:
I
1
= I
0
{(width X thickness )actual /(width X thickness )Indal chart }
vii) The calculated rated current carrying capacity of the bus bars = I
1

viii) The nominal/specified current carrying capacity of the bus bar = I
2


12.1 Correction Factors

The current carrying capacity of the bus bars depends upon various factors due to the
temperature and enclosure. The main factors affecting the rating of a bus bar are:
1. Ambient temperature where the bus duct shall be installed
2. The size of the enclosure.
3. Sleeving and painting of the bus bars
4. Skin and proximity effects.
5. The material of the enclosure.
The above factors are quantified as the correction factors in determining the rating of the bus
bars. These correction factors are calculated as
a) K
1
: Temperature correction factor
RAW MATERIAL HANDLING SYSTEM Page: 16 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


The temperature of the conductor is to be limited to a safe value, at which the metal does not
deteriorate or change its properties. The safe temperature for an aluminum bus bar is 85-90
Deg. C.
In this project we are limiting the end temperature of the bus bar as 85 Deg. C i.e. the allowable
temperature rise of the bus bar over an ambient of 50 Deg. C is 35 Deg. C.
The value of the correction factor considered is 0.815 as per Industrial power engg. And
applications handbook (Annexure-B-1)
b) K
2
: Enclosure size correction factor
The enclosure of the bus duct provides the cooling surface for heat dissipation. The size of the
enclosure has an effect over the temperature rise of the conductors and consequently the
current carrying capacity of the conductor. The enclosure effect and the ventilation conditions of
surroundings are to be considered while designing the bus duct system.
The correction factor for the enclosure is based on the percentage ratio of the cross section
area of conducting bus bar and the enclosure area cross section.
ie (Cross Section Area of bus bar * 100)/Enclosure Cross section = %
The derating factor corresponding to above calculated % is the enclosure correction factor K
2

The derating factor is derived from the enclosed chart in Annexure-B.

c) K
3
: Proximity effect
In ac systems the inductive effect caused by the induced electrical field causes skin and
proximity effects. These effects play a complex role in determining the current distribution
through the cross section of a conductor. The inductance of conductor varies with the depth of
the conductor due to skin effect. In addition to this, the presence of other current carrying
conductors in the vicinity of the conductor has the proximity effect on the conductor. These
effects are to be considered while designing the bus bar system. The correction factor for the
proximity effect is the ratio of the spacing between phases to the width of the conductor.
K
3
is considered as 1, as the current carrying capacities of the bus bars are obtained from the
Indal chart (Annex-A) for calculation. The de-ration of the busbars for various combinations is
already taken care of for the proximity effect in the chart.

d) K
4
: Painting factor
The HT and LT bus bars are painted with non-metallic matt finish paint. As per the Indal
aluminum bus bars, the current rating of the bus bar is increased because of the non-metallic
matt finish paint. Hence there is an increase in the current carrying capacity of the bus bars. The
up rating is approximately 20% more.
(Reference :Indal Aluminum bus bars-Annexure A)

e) K
5
: Enclosure material correction factor.
Depending upon the type of material of the enclosure this factor is decided. For aluminum
enclosure (non magnetic) there is no correction required and hence the factor is 1. For mild
steel enclosures (magnetic material) it is generally considered as 0.95 by all major leading bus
duct manufactures.
The total correction Factor is K is calculated as K= K
1
* K
2
* K
3
* K
4
* K
5

The net current carrying capacity of the bus bar is calculated as
= (Total currents carrying capacity of the bus bars) * (Correction factor K)
RAW MATERIAL HANDLING SYSTEM Page: 17 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


I
1
= I * K

12.2 Temperature rise calculation

Temperature rise is calculated as = (I
1
/ I
2
) = (T
1
/ T
2
) ^ 0.61

(Temperature rise calculation from Copper for Bus bars Copper Development Association
CDA)

Where:
I
1
=Calculated rating in Amps.
I
2
=Specified/Nominal rating in Amps.
T
1
=Max. Temperature rise specified in Deg. C over the ambient
T
2
=Calculated temperature rise in Deg. C over the ambient.

T
2
= T
1
/( I
1
/ I
2
) ^ 1.64

The calculated value of T
2
should be within the design value of the temperature limits.


12.3 Voltage drop calculation

The voltage drop is calculated as Vdrop = 3 *I
2
*L *Z

I
2
= Load current in amps
L = Length in meters
Rdc = DC Resistance in micro hms per meter of conductor at 20 Deg. C(D50S-WP dc
resistance)
Rac = AC Resistance in micro ohms per meter of conductor at 85 Deg. C
20= Resistance- temperature co-efficient per Deg. C. =0.00363. (Indal Aluminum Book see
attached annex-F)
Z= Impedance in micro ohms per meter of conductor

1
= Temperature at which resistance is measured i.e. 20Deg. C

2
= Temperature at which bus bar is operating i.e. 85 Deg. C.
A = Cross section area in cm
2

S= Centre spacing between the two phases in mm
a= Space occupied by conductors of one phase in mm
b=Width of the conductors in mm.

Calculation of the impedance of the bus bar

AC resistance
Rdc at an operating temperature of 85 Deg. C .is taken from annexure C (Indal Aluminum
Book)
=Rdc (1 +20(
2
-
1
)) ohm/meter per conductor

If there are n number of runs then Rac = Rdc (1 +20(
2
-
1
)) /n

The value of Rac is calculated from the skin effect ratio n Rac/ Rdc..
The Rac is calculated as:
Area of cross section per phase =(n * a *b)= A in cm
2


The value of ratio Rac = skin effect* Rdc, the skin effect r is derived from the annexure-D,
corresponding to A cm
2
, on the b/a curve (by appx the interpolation).
I.e. Rac / Rdc = r
RAW MATERIAL HANDLING SYSTEM Page: 18 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



Rac = Rdc * r = 10-3 ohm/1000m per phase.



Reactance
The reactance is calculated from the ratio of conductor spacing to semi perimeter.

For a 3-phase system 1.26 multiplies the ratio. ie

1.26 * (S/(a+b)) = m

The ratio of a/b gives the curve of reference on which the value m value gives the reactance in
micro ohms/meter per phase.( Annexure-E)

The impedance is calculated as Z=( R2ac + X2) =
=Z ohm/meter per phase

Vdrop =(3 *I2 *L *Z)/1000= V Volts

The V volts are checked as a percentage of the rated voltage. If the drop is within the limits as
specified in the contract specifications, the busbar size is acceptable. In the absence of
specifications this shall be limited to 1-2% of the rated voltage. (Refer annex. B-2)
12.4 Calculation of the short circuit withstand capacity of bus bars

The short circuit rating of the bus bar will be calculated based on the following method:

A = (Ish X t) / K

Where,

A = Cross sectional area in Sq.mm.
Ish = Fault current in kA
t = Fault clearing time in seconds
K = Constant kA / sq.mm. (K = 0.0799 for Aluminum)

The LV bus ducts will be designed for the LV system fault level of 50kA for 1 second.

RAW MATERIAL HANDLING SYSTEM Page: 19 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



13.0 SMALL POWER PLUG/SOCKETS & WELDING


Single phase switched socket outlets (SSOs) rated 230V, 15A will be provided in plant areas
spaced apart such that all areas can be reached with a 50m extension lead.

The overland conveyor will be provided with a 230V SSO every 100m for portable lighting and
small tools or welding using 50m extension leads.

At least 2 nos. of 230V SSOs will be provided in substation switchrooms and MCC rooms.

Three phase welding sockets rated 415V, 63A will be installed for use with 100m extension
leads.

Socket outlets in plant areas and conveyors will be weatherproof. Those in substations will be
surface mounted, and those in control rooms and offices will be installed in 3-way power skirting.

Socket outlet circuits will be protected by MCCBs and MCBs for welding sockets and SSOs
respectively, all with 30mA earth leakage protection.


14.0 CABLING

14.1 MV Cables

Strip Armoured (GI), XLPE insulated, with stranded aluminum conductors and PVC bedding and
inner / outer sheath.

Voltage ratings: 3.6kV (UE)

Cable ratings, deratings and other data to be used are from cable manufacturer standard
catalogues.


14.2 LV Power and Control Cables

Armoured, 1100V PVC insulated, with stranded copper / aluminum conductors depending up on
the size, and PVC bedding and PVC sheath.
Minimum size for power cables: 4 mm
2

Control cables size: 1,5mm
2

Cables upto 4 sqmm will be of copper conductor and the rest of the sizes will be of aluminum
conductors.

Cable ratings, deratings and other data to be used are from cable manufacturer standard
catalogues.

14.3 Recommended Practice for Cable Sizing

The cables will be selected on the following basis:

1. Power cables: Based on the selection procedure described below.
2. Control cables: Based on customer specifications and general practices followed.
3. Lighting cables: Based on the current carrying requirements considering the voltage drop
RAW MATERIAL HANDLING SYSTEM Page: 20 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



The power cable sizes are selected on the basis of the following:
Current Carrying Capacity:
The cable will carry the full load current of the circuit continuously under the specified ambient
temperature and other conditions of installation.

The current carrying capacity will be worked out on the basis of the following:

Base current rating:

The current ratings for cables shall be referred from the manufacturers cable data sheets.

Correction factors for method of installation:

The cables are mostly laid in metal ladder type GI cable trays in this project.

The base current ratings of cables shall be de-rated for the following conditions:

a) Variations in conditions of installation compared to the standard conditions mentioned above.
b) Group running of cables.

Correction factors for ambient air temperature:

(Based on IS standards & manufacturers catalogue)

The rating factor for variation in ground / air temperature should be taken into consideration. The
ambient to be design ambient considered shall be 50
o
C.

Depth of Laying

The rating factors for variation in depth of laying should be taken from IS/manufacturers catalogue.
Normally standard depth of laying shall be adopted in which case the rating factor will be 1.0. In this
project we are laying the cables above ground and hence will be considering the rating factor as 1.0.

Group De-rating Factor

The de-rating factor for group running of cables laid direct in ground and in ducts shall be taken from
IS/ Manufacturers catalogue. The group de-rating factor for cables laid in air shall be as per IS/
Manufacturers catalogue.

Overall Deration Factor considered based on the duration factors as per manufacturers catalogues:

Deration factor considered for an ambient temperature of 50
o
C 0.82
Deartion factor considered for depth of laying - 1.00
Deration factor considered for grouping of cables
(laid touching each other) - 0.80

Overall derating factor considered (0.82 x 1.0 x 0.80 = 0.66) - 0.66

Short circuit rating

The cable, if protected by circuit breaker, shall be able to withstand the fault current of the circuit for
the desired fault clearing time. For reliable tripping, the instantaneous tripping of breakers shall be
RAW MATERIAL HANDLING SYSTEM Page: 21 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


provided within one cycle ie.0.2 sec. Hence for breaker controlled outgoing feeders, cables shall be
capable of withstanding the system fault level for 0.2secs.

The short circuit withstand capacity of cables shall be calculated as per following formula furnished
in IS:

A = ( Ish X t) / K

Where,

A = Cross sectional area in Sq.mm.
Ish = Fault current in amps (rms)
t = Fault clearing time in seconds
K = Constant amps / mm
2


The value of K for various combinations is as follows:

For copper conductors insulated with PVC K=115
For copper conductors insulated with XLPE, / EPR, K=143
For Aluminum conductors insulated with PVC K=76
For Aluminum conductors insulated with XLPE / EPR, K=94

Fault current (Ish) = The maximum fault current of the system shall be taken.

Fault clearing time (t) = The time t shall be based on the maximum time taken by the breaker of the
circuit to clear the fault on the operation of primary short circuit protection. The recommended value
of t for typical auxiliary system is as mentioned above.

For the breaker controlled outgoing feeders on 3.3 kV side with system fault level of 26.3 kA,
cleared by the breaker within 0.20 secs (from MRSS to incomers of Switchboards at new load
center). Hence the cross section of the aluminum XLPE cables shall be a minimum of:

A = (26.3*1000* 0.20/ 94) = 126 sq. mm.
Hence a cable of 150 sqmm (minimum) is sufficient for the MV incomer cables.


For 415V system, the fault at 1.6 MVA (rating is tentative and for example only) transformer with a
percentage impedance of 5.5% will be calculated as:
1.6 / (3 x 0.415 x 0.055) = 40.5 kA

For the breaker-operated incomers of PMCC on 415 V side with a fault level of ~ 40 kA, the fault
clearing time shall be 0.2 Sec is considered for the selection of cables. Hence the cross section of
the cables shall be a minimum of:

A = (40*1000* 0.2 ) / 94 = 190 sq. mm.
Hence a cable of 240 sqmm (minimum) is sufficient for the PMCC incomers.

Permissible voltage drop

The voltage drop in the cable will be within permissible limits for satisfactory running and starting of
the motor. The allowable voltage drop shall not exceed 3% of the nominal voltage for main
distribution circuits, 5% of the nominal voltage at motor terminals during motor running and 15% of
RAW MATERIAL HANDLING SYSTEM Page: 22 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


the nominal voltage during motor starting. In case of fluid coupling this shall be allowed upto a
maximum of 20%.

For welding receptacles the drop shall be limited to 5%.

The total voltage drops considered will be within 5% between the transformer and the final
consumer during normal running.

The voltage drop is calculated from the following formula:

Vdrop = I
L
x L x (t x R cos + X sin )

Where, I
L
= Load current in amps

L = Length of cable run in metres (one conductor only)
R = Resistance in ohms of one conductor only
t = temperature correction factor
X = Reactance of one conductor
Cos = Power factor (considered as 0.9)
Sin = (1-cos2) =0.44 (as cos = 0.9)

14.4 Cable Installation and cable trays

Cables will be installed on vertical plane ladder trays where horizontal plane formation is
precluded because of the possibility of dust, sand, etc. build-up reducing the heat dissipation
and hence the effective current carrying capacity of cables mounted horizontally. Generally, all
other cables will be installed on horizontal plane trays, except where it is more practical to mount
trays in the vertical plane. The vertical cable trays will be filled by 80% of the area on the tray
and 20% area on the tray will be kept spare for future use. In case of horizontal cables trays at
sub station, the cables will be laid in two layers wherever required.

Cable trays will be made of galvanized mild steel, supported on galvanized mild steel structural
supports. The supports will be site fabricated and all the welded joints will be provided with zinc
rich paint to avoid rusting. The trays shall be generally of 2.0mm thick sheet steel with side
channels and 35x15mm wide rungs at a spacing of every 300mm. The tray width shall be of
150mm, 300mm, 450mm and 600mm and shall be supplied in standard lengths of 3 meters.
Suitable bends shall be fabricated from the standard trays at site.

Instrument cables will be installed on separate trays from power cables with a minimum spacing
between parallel runs of 300mm. In case of vertical trays, the spacing between two trays will be
50mm.

Cables will be tagged at each end only. The cables will be clamped with suitable nylon ties /
aluminum clamps. In case of single core cables these will be laid in trefoil formation and suitable
trefoil clamps will be provided.

The cables will be laid in a maximum of two layers on horizontal trays. However on vertical trays
the cable will be laid always in single layer only. Where ever there are very few no. of cables,
these will be laid with angle iron support or through a suitable diameter MS/GI pipe.


15.0 EARTHING

15.1 Recommended practice for designing the grounding system

RAW MATERIAL HANDLING SYSTEM Page: 23 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


15.1.1 The neutral point of 3.3/0.433KV distribution transformers shall be earthed through NGR on
433 V side.

15.1.2 The transformer neutral shall be earthed by two separate and distinct earth connections. In
case of distribution transformers the two neutral earthing leads shall be taken to two separate
earth electrodes. However finally all the earth pits including the neutral pits and lightning pits
of the plant shall be interconnected rigidly through a buried earth conductor below the ground.

15.1.3 For plant building and indoor substations one main earthing ring shall be provided along the
building periphery connected to required number of earth electrodes. The earthing ring shall
be laid either suitably buried in the floor along building column/wall or laid along the steel
structures in open execution. In case of buried conductor, it will be laid one meter away from
the building.

15.1.4 Main earthing ring shall be further cross-connected so as to form a mesh depending on the
layout and location of the equipment. The cross-connections shall generally run in cable
cellars, cable tunnels, trenches, motor platform or embedded in concrete floor based on the
layout. For buildings having a number of floors separate earthing rings shall be established in
each floor where required. All non-current carrying metallic parts of various electrical
equipment as well as cable armouring, metallic conduit/GI pipe system, cable racks, brackets,
supporting structures etc shall be effectively earthed. Earthing of all equipment (except low
voltage equipment) shall be done by means of two separate earth continuity conductors
connected either directly to earth electrodes or to an earthing ring irrespective of use armored
cable or metallic conduit/GI pipe. Low voltage equipment, 125V and above shall also have two
earthing points. However equipment, 125V & below up to 24V may have single earthing.
Building/technological steel structures, metallic utility pipes shall not be used as earth
continuity conductor.

15.1.5 The earthing system shall be designed to ensure effective operation of protective gears in
case of earth faults. The total earth resistance at any point of the earthing system shall not be
more than one ohm.

15.1.6 For substations and plant buildings, number of electrodes to be provided for the earthing
system shall be calculated based on the soil resistivity to achieve a final total grid resistance
of 1 ohm. After installation, actual earth resistance shall be measured and if required,
bentonite soil can be added to achieve the values indicated above. No earth ring shall have
less than two earth electrodes.

15.1.7 Earth electrodes for earthing stations shall comprise GI pipes of 40mm nominal diameter and
3 meters length in accordance with IEEE-80. Bottom half of the pipe shall have holes drilled at
intervals on its surface. Removable caps shall be provided at the top of pipe to facilitate
pouring of water. Suitable clamps shall be provided with the electrodes for connecting earth
conductors. The top of the electrodes shall be about 100mm below ground level while
connection to the earth conductor shall be made at about 150mm below ground level. The top
portion of electrodes shall be enclosed in 300 x 300 x 300mm M15 concrete housings and
provided with concrete of top cover and marker. Provision shall be kept at each earth station
for testing earth resistance. Each earth station shall be complete with alternate layer of coke
and salt as per general practice.

15.1.8 Galvanised MS flats shall be used for transformer neutral earthing and station earth grid.Earth
conductor shall comprise galvanised MS flat or stranded galvanised steel wire. Generally
main earthing rings and earthing leads shall be directly buried in ground. Additional earthing
rings wherever provided inside plant buildings / substations and earth continuity conductor
shall be taken either exposed on cable racks, structures, walls, ceiling etc. or embedded in
concrete depending on installation. Earth conductor directly buried in ground shall generally
be taken at a depth of 600mm. Earth conductors laid on cable racks shall be placed in
RAW MATERIAL HANDLING SYSTEM Page: 24 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


accessible location keeping adequate clearance to facilitate easy connection. Earth
conductors laid along plant / equipment, structure, wall, ceiling etc. shall maintain symmetry
with other installations and shall be uniformly spaced with cables / utility pipes running along
the same route. MS galvanised saddles shall be used for clamping earth conductors on cable
racks, structure, wall, ceiling etc. The saddles shall be clamped to MS galvanised flat spacers
with tapped holes and supporting the earth conductors. Flats shall be supported at intervals
not exceeding 1,500mm and standard wires at intervals of 750mm. Earthing leads from
transformer neutral shall be so taken as to avoid contact with the transformer body. In case
the contact cannot be avoided, the leads shall be suitably taped with insulation tapes.

15.1.9 As far as possible all earth terminations and connections shall be visible for inspection. Each
earthing system shall be designed to permit testing of individual earth electrodes. Stub-ups
shall be provided at convenient locations near the equipment as well as building columns for
connecting earth continuity conductors leading to the equipment and structures.

15.1.10 Alternate columns of structural building shall be connected to earthing ring. Crane rails,
transfer trolley tracks, railway tracks inside plant building, as well as rails for movable
mechanism shall be earthed at an interval of 100mtrs. In no case the number of earth
connections shall be less than two. Expansion joints of rails shall be bonded by means of
loops of galvanised MS flat.
15.1.11 Earth connections to equipment subjected to movement, vibrations and shocks shall be made
by stranded wires having enough loops. Connection of earthing leads to earth electrodes and
termination of flat earth continuity conductors to equipment shall be made by means of
bolting. Connection of stranded earth wire to flat earth conductor as well as to equipment shall
be made through crimping type lugs and bolting. Jointing and tapping (`T Connection) of flat
earth conductors shall be done by means of welding. Termination of earthing flats to crane
rail, building structures, etc. shall be done by means of welding.

15.1.12 Earth conductors from electrodes or earthing ring when entering basement, cable cellar, cable
tunnel, concrete trench, cable pit etc. shall be generally taken embedded in concrete either
directly or through pipes. Earth conductors crossing roads on rail tracks shall be taken through
concrete pipe.

15.1.13 Cable screens and armours shall be bonded to earthing system. Also, metal pipes and
conduits carrying cables shall be bonded and effectively earthed.

15.1.14 Earthing system shall be kept electrically separate from the metal work of surface by not
connecting to pipes / machinery parts etc. for earth continuity.

15.2 Conductor Sizes:
The various conductor sizes that will be generally used shall be as mentioned below:
i) Buried Earth Grid : 40 mm dia MS rod
ii) Earth Electrode/Pit : 3 M long. 40mm dia. GI pipe
iii) Conv. Gallery / Tunnel : 50 x 6 mm GS Flat
iv) Riser : 50 x 6 mm GS Flat
v) Exposed Main Grid : 50 x 6 mm GS Flat
vi) 415V Switchgears cum MCC, : 50 x 6 mm GS Flat
Transformers, MLDB, AC/DC DB
viii) Cable Tray : 50 x 6 mm GS Flat
ix) Motors Rated upto 5.5 KW : 8 SWG GS Wire
RAW MATERIAL HANDLING SYSTEM Page: 25 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


x) Above 5.5 KW upto 30 KW : 25 x 3 mm GS Flat
xi) Above 30 KW upto 90 KW : 35 x 6 mm GS Flat
xii) Above 90 KW : 50 x 6 mm GS Flat
xiii) Push Button Stations, JBs etc. : 8 SWG GS Wire
xiv) Control Panel, Lighting : 25 x 3 mm GS Flat
Distribution Board, Starter
Panel, Lighting Panel, I/O Rack
Welding Receptacles
xv) Lighting Fixtures : 14 SWG GS Wire
xvi) PLC Panels : Separate treated pits for Electronic Earthing


15.3 Sizing calculations

The following methodology will be followed:

The effective combined grid earth resistance required as per technical specifications is 1 (one) ohm.

Derive the size of earth conductor.

Derive the length and width of the grounding area of the control room. / load center / plant buildings
etc. covering the total plant layout.

Derive the length of conductor buried in soil and number of electrodes.

Calculate the value of resistance of earth grid.

Calculate the value of resistance of earth electrodes.

Calculate the combined value of resistance of earth grid and electrodes.


Data Considered for the Calculations

Soil resistivity : Average soil resistivity is considered as 400 ohm-metre for
design purposes based on soil resistivity report

Size of Earth Electrode selected : 40 mm dia. GI Pipe

Size of buried conductor : 40 mm dia. MS Rod earth conductor

Fault level : Fault level as per specifications 26.3kA

Applicable Standard : IS-3043, IEEE 80 1986, IEC-364



Calculation for sizing of earth conductor

Thermal sizing
RAW MATERIAL HANDLING SYSTEM Page: 26 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



A = (I
f
t ) / K

Where,
A - Area of conductor in sq.mm.
I
f
- Maximum earth fault current in amperes
t - trip time - fault duration in secs.

The factor K is determined from the formula ( Annex A IEC 60364-5-54)

K = [ {Qc (+20
o
C) / 20} ln { 1+ [(f i ) / (+i )] }]

Where,

Qc = Volumetric heat capacity of conductor material ( J /
o
C mm3 ) at 20
o
C
= Reciprocal of temp. coefficient of resistivity at 0
o
C for the conductor
(202
o
C - Table A.54.1 IEC 60364-5-54 )
20 = Electrical resistivity of conductor material at 20
o
C ( mm )
i = Initial temperature of conductor (30
o
C) (table A.54.6)
f = Final temperature of conductor (200
o
C) (table A.54.6)


The value of {Qc (+20
o
C) / 20} is 78 for steel as per, Table A.54.1 of IEC 60364-5-54

Hence K = 78 ln { 1 +[(200 30) / (202 + 30)] } = 57.85

Therefore, the area of conductor for the maximum fault level of 50kA and considering the fault clearing
time is < 0.5 sec. the conductor area is

A = (50000 * 0.5) / 57.85 = 611 sq.mm.

Hence the calculated minimum diameter of the MS Rod = {(611 * 4) / 3.14} = 27.89 mm

Considering 10% corrosion allowance the diameter of the MS rod will be 31 mm. Hence MS rod of 31
mm diameter is sufficient. However we will select a standard size of 40mm MS rod for the main earth
mat below ground as per project specifications.

Resistance of earth conductor

The resistance of earth grid can be calculated by using the formula given below:

Rg =[ (100 * )/(2**L)] * Ln {(2 * L
2
) / (H * 2 * D)} - eq-1

Where
- resistivity of soil in ohm-mtr
L - length of earth conductor in cm.
H - depth of burial of conductor in cm.
D - diameter of earth conductor in cm (or half the width of strip in cm)

Resistance of earth electrode

The resistance of earth electrode is given by

Re (in ohms) = {(100*) / (2 * * l )} * ln (4*l/d) Eq 2 For Round electrodes / pipes

RAW MATERIAL HANDLING SYSTEM Page: 27 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


Where
- resistivity of soil in ohm-mtr
l - length of earth electrode rod/pipe in cm.
d - diameter of earth electrode rod/pipe in cm

Typical Design calculations (example)

Main Substation
Assumptions:
Length of earth grid conductor (L) : 100 mtrs = 10000 cm
Depth of burial of conductor (H) : 0.6 mtrs. = 60 cm
Soil resistivity () : 400 Ohm meter
Diameter of conductor (D) : 40 mm = 4.0 cm
Length of earth electrode (l) : 3 mtr = 300 cm
Diameter of earth electrode (d) : 40 mm = 4.0 cm

The resistance of the earth grid with above data works out to Rg = 8.24 ohms (from eq-1).

The resistance of the earth electrode with above data works out to Re = 12.72 Ohms (from eq-2)

Similarly the earth resistance value for the other areas also will be calculated and all the earth grids will
be connected rigidly below the ground. The no. of earth pits will be added in such a way that the total
effective earth resistance will be maintained less than 1 ohm. The resistivity will be further improved by
adding bentonite soil if required as suggested in IEEE-80 / technical specifications to maintain the value
below 1 ohm. The earth pits will be 40mm galvanized pipe and the pits can be treated at regular interval
by pouring the water.


16.0 LIGHTNING PROTECTION

16.1 Recommended practice for designing the grounding system

16.1.1 The minimum dimensions of the lightning protection conductors have been derived from the
Table of Minimum dimensions of Component parts as mentioned in the IS. The lightning
protection system shall be integrated with the Plant earthing system.

16.1.2 Outdoor Equipment shall be protected against direct lightning stroke by means of overhead
shielding wires or vertical air terminations (masts).The location and height of masts shall be
so selected as to cover all major equipment within a cone of protection not exceeding
45 .

16.1.3 Down conductors from shielding wires/Air terminations shall be as short as possible and shall
follow the most direct path possible between the air termination and earth termination avoiding
sharp bends, upturns and kinks. Joints shall be avoided in down conductors as far as possible.
Each down conductor shall have an independent earth termination which shall be
interconnected with the station earth mat.

16.1.4 All building having concrete roof shall be protected against lightning strike. Structures having
roofing made of CGI sheets and metal chimneys/towers not exceeding 30 meters in height,
RAW MATERIAL HANDLING SYSTEM Page: 28 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


shall not be provided with separate lightning protection system. However, such structures and
installation shall be adequately earthed to ensure free conducting path for lightning stroke.

16.1.5 All buildings/structures irrespective of their type of construction when used for storing explosive,
inflammable gases and fuel oils etc. shall be provided with lightning protection.

16.1.6 The lightning protection system shall comprise air terminations, in the form of horizontal
conductors, down conductors and earth electrodes. Earthing system and lightning protection
system shall be electrically interconnected except for building/structures used in storing,
explosive, inflammable gases and fuel oils.

16.1.7 Unless otherwise specified air terminations shall be of horizontal conductor type. The horizontal
air terminations shall be interconnected such that any part of the roof is not more than 10
meters away from the nearest horizontal conductor. For flat roof, horizontal conductors shall
generally be provided along the outer periphery of the roof.

16.1.8 All metallic projections, chimneys, ducts, ventilation pipes, railing gutters etc. on or above the
main surface of the roof shall be properly bonded to the air termination network.
However, gas pipes shall in no case be bonded with this network.

16.1.9 The number of down conductors from air termination to the earth electrode shall be
selected on the following basis:
Area is <100sq mtrs One down Conductor
Area is >100sq mtrs One down conductor plus one for each additional 300sqmtrs, or one
for each 30Mtr periphery of the Structure.

16.1.10 Conductors of lightning protection will not be connected with the conductors of safety earthing
above ground level. However the pits meant for safety earthing and the lightning will be
interconnected by a conductor below ground. Down conductors will be cleated on the outer side
of the building wall at 1000mm interval or welded to the building columns at 1000mm interval.
Test Link will be provide at 1000mm above ground level between down conductor and Rod
electrode.

16.1.11 Lightning Conductors will not pass through or run in GI conduits. All metallic structures within a
vicinity of 2000mm in air will be bonded to the conductors of lightning system.

16.1.12 The minimum size of horizontal conductor used as air termination shall be 25 x 3mm
galvanised MS flat. Down conductor from air termination to earth shall also be 25 x 3mm
galvanised MS flat. Vertical Air termination Rods will be of 20 mm Dia and 1000mm long GI
Pipes. Rod electrode for earthing will be of 40mm Dia and 3000mm long GS Pipes.
RAW MATERIAL HANDLING SYSTEM Page: 29 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



Calculation Methodology

Air termination conductor:
Specific criteria for provision of Air termination conductors.
1.Vertical conductors(VC): The zone of protection(ZP) is 45Deg


Vertical conductors shall be provided whenever two Levels of elevation exist on roofs.
2. Horizontal conductors(HC) Along the Periphery of the roof building plus along the roof incase
the distance between two parallel conductors exceeds 18 mtrs.




RAW MATERIAL HANDLING SYSTEM Page: 30 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008




Method of clamping horizontal air termination conductors on ridged type roofs.
3. Down conductors (DC) - Down conductors shall be used for connecting vertical air termination and
horizontal conductors to the earth to discharge the lightning stroke. The number of down
conductors is decided by empirical formula applicable for area of building exceeding 100 Sqmtr P/20
( where P is perimeter of roof protected by lightning air termination conductors.)
4. Spike arrestors -These shall be preferable mounted on chimney of the highest elevation if required
with extension of Vertical support for elevation.

17.0 ILLUMINATION

Power for Normal A.C. lighting is derived through a 415/240 V dry type transformer connected to main
lighting distribution board located in each substation.

Normal A.C.Lighting:
a) This is provided by A.C. lighting fixtures distributed throughout the plant and is ON as long as
the A.C. supply is available.
b) A.C. lighting fixtures is fed from respective area lighting panel, which in turn is connected to
main lighting distribution board.

Emergency Lighting:
Emergency lighting will be through DC emergency light fittings. The emergency lights will be provided at
strategic locations and the entry / exit of the electrical rooms / control rooms. These will be standalone
fittings and will be generally under charging when the mains power is available. The battery once fully
charged can operate for 4 hours continuously.

Illumination Levels:
The areas to be illuminated and their respective illumination level are furnished below:-

a) Crusher House, Conv. Tunnel and : 200 Lux
Wagon tippler area, if any
RAW MATERIAL HANDLING SYSTEM Page: 31 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



b) Transfer Point, Pent House, Conv. Gallery : 50 Lux

c) Switchgear Rooms & Pump Houses : 150 Lux

d) Corridors, Walkways (Excluding Conv. Gallery), : 70 Lux
Staircase & Cable Spreader Rooms

e) Control Room : 200 Lux

f) Transformer Room : 50 Lux

g) Storage pile areas : 50 Lux

h) Outdoor yard area : 20 Lux

Factors Considered:
Quantities of lighting fixtures in various area are calculated on the basis of following design data:

a) Maintenance Factor :
Control Room and - 0.75
Switchgear room - 0.65
Dusty Area - 0.55
General Indoor Area - 0.60

b) Utilisation Factor
Dusty areas such as conveyor galleries, tunnels, : 50% ceiling, 30% wall,10% floor
TPs, crusher house etc.

Clean areas such as Switchgear & control room etc : 70% ceiling, 50% wall,10% floor

c) Working Plane : For Conveyors at walkway level
For Buildings at Floor Level

Type of Fixtures :

RAW MATERIAL HANDLING SYSTEM Page: 32 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


a) Conveyor Gallery :Industrial Well Glass Luminaire
with 1 x 70 Watt SON Lamp.

b) Transfer Points, Track hopper :Industrial Well Glass Luminaire with
1 x 70 Watt SON Lamp.
:Industrial Medium Bay Luminaire with
1 x 150 Watt SON Lamp
:Industrial High Bay Luminaire with
1 x 150 Watt SON Lamp.

c) Switchgear Room :Industrial Type Luminaire with
2 x 40 Watt Fluorescent Lamps.

d) Control Room :Decorative Type Luminaire with
2 x 40 Watt SON Lamp.

e) Transformer Room :Industrial Medium Bay Luminaire with 1 x 150
Watt SON Lamp.

f) Open yard :Flood light Luminaire with
2 x 250 / 400 Watt SON Lamp

Methodology

The requirement of number of light fittings and the type of the fittings is decided by the Lumen Method.
This is a method for estimating luminaire quantities and spacing for layouts that is more accurate
because the difference in photometric performance caused by room geometry and system depreciation
are taken into account.

Lamp utilization factor (COU)

for Internal Lights : 0.6
for External lights : 0.2
Lumen out put of lamp (F) : From Mfr. Catalogue
Illuminance or the Lux level (E) : As described above.
Maintenance factor (MF) : As described above.

The Coefficient of utilization factor(COU) is defined as ratio between flux received on working plane from
luminarie to sum of nominal fluxes of all lamps in the luminaire. The COU is calculated based on
room index (K) which is given by formula .

K = (L * W) / [MH * (L + W)]

Where
Length of room is (L)
Width of room (W)
Mounting height (MH)
RAW MATERIAL HANDLING SYSTEM Page: 33 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008



The manufacturers generally specify the COU based on room index and room reflection factors for
ceiling, wall and Floor separately.

COU of 0.6 is considered for internal and COU of 0.2 is considered for external area lighting on average
least value basis for the room indices for the purpose of calculations. (Detailed calculation sheet with
reference to COU table shall be submitted with Detailed engineering for each building taking in to
account of uniformity Factor)

Maintenance factor is taken on the basis of room maintenance over the period of time. The factor mainly
comprises

1. Lamp lumen Depreciation
2. Luminaire Dirt depreciation

Based on general geometry, the Number of lamps (N) required is given by formula (DIN 5035)

N = (1.25 e *A) / (F * COU * MF)

Where 1.25e = E Specified lux level (The factor 1.25 is by which design value should be
chosen to exceed nominal light intensity e.)

MF-Maintenance Factor.
A-Area of Building in sq mtr.
F- Lamp luminance out put

Typical Calculation for Sub-station building:

Substation building tentative dimensions are (Assumed dimensions for example purpose only)

20mtrs. (L) x 16 mtrs.(W) X 6 mtrs.(H)

2 x 40W TL Fixtures (80W) are considered as per specifications.

From manufactures catalogue (CGL) lumen output is 2450 lumens x 2 nos.

MF = 0.65 (considered for sub-station room)
Specified Lux level = 150
COU = 0.6

With substitution of values in above formula, we get,

N= 32 Nos

The similar calculation will be done to decide the no. of light fittings in all the similar type of buildings.


Typical Calculation for Ridge type roofed buildings & conveyor galleries

For transfer towers and Drive house buildings which shall have similar roof structures (Ridge type roofs
with steel structure) the typical calculations will be as follows:

The area of Building : 22 mtr x 12 mtr (the dimensions are for example only)

As per Spec. we shall consider 1 x 150 W Sodium vapor Lamps

RAW MATERIAL HANDLING SYSTEM Page: 34 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


From Manufactures Catalogue (CGL) Lumen out put per lamp is 13500 Lumens.

MF=0.55
Lux level = 150 for Localized internal lighting
COU= 0.6

Substituting above values in the formula, we get,

N = 9 nos.

The similar calculation will be done to decide the no. of light fittings in the other similar type of areas.

Typical Calculation for Outside General Area Lighting:

For typical calculations the area around TP is considered.

Area of TP = 29 mtr (L) x 23 mtr (W) (Area assumed for calculation purpose only)

Maintenance factor considered as 0.55
Lux level as specified in Lafarge specs. is 20
COU is taken as 0.2 For external lighting
Lumen output of lamp for 2 x 250W HPSV lamp is 28000

Now substituting the above values in the formula, we get,

N= 2 Nos

These 2 Nos shall be suitably mounted on the structures to give effective Lighting for the area
Covered.

The similar calculation will be done to decide the no. of light fittings in the other similar type of outside
general areas.

18.0 BATTERY & CHARGER SYSTEM
General
In this project all the DC loads shall be fed from 110V battery. The calculation for sizing of the battery and
its charger are shown below. The battery is to supply the DC power requirements during the following
conditions:
Load on dc system exceeds the maximum output of the battery charger.
Output of the battery charger is interrupted.
AC power is lost

The following factors will be considered while designing the battery system:
Temperature derating factor: The operating temperature affects the available capacity of a cell. The
standard temperature for stating cell capacity is 25 deg C. If the lowest expected electrolyte temperature
is below standard a cell large enough to have the required capacity is selected. The capacity deration
factor for the same is known as temperature factor.
RAW MATERIAL HANDLING SYSTEM Page: 35 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


Design Margin: As a prudent design we are to provide a capacity margin to allow for unforeseen
addition to the DC system.
Aging Factor: The performance of a lead acid battery is relatively stable throughout most of its life, but
begins to decline at the later stage of its life. To ensure that the battery is capable of meeting its design
loads throughout its service life, the batterys rated capacity should be at least 125% of the load
expected at the end of its service life ie an ageing factor of 1.25 is considered.
Design Considerations
The battery sizing is done for a duty cycle of 30 minutes.
The calculated battery size is to be corrected for design margin, aging compensation and
minimum temperature.
The batteries considered are sealed, maintenance free lead acid type with a 10 hour discharge
rate i.e. C10 batteries.
2Volt batteries with an end cell voltage of 1.75volts are considered.
K factors corresponding to 1.75 end cell voltage and temperature correction factor for the lowest
ambient temperature are taken from Exide batteries ltd. (power stack series of VRLA batteries).
This calculation is done for battery nominal voltage of 110V D.C., which is the control supply
voltage.
Design basis
The loads on the battery are mainly pertaining to HT switchboard control supply only.
It is required to be identified which all loads are instantaneous and which all loads are continuous. For
example an 'on' lamp in a breaker feeder is a continuous load, while a tripping relay is an instantaneous
load coming in at the time of a trip.
A design margin of 5% may be allowed for unforeseen additions or future expansion as well as for below
optimum operating conditions.
Battery capacity is referred to at a nominal temperature of 20 deg.celcius. (The factors given by Exide
are at 20deg C). A temperature correction factor for the lowest temperature is considered while
determining the AH capacity of the battery.
The voltage at the load terminals shall never be outside +10% and 15% of the nominal voltage.
Load Details
The individual loads supplied by battery during the duty cycle maybe classified as continuous or non-
continuous. Non-continuous loads lasting for 1 minute or less are designated as momentary loads.
The loads, which are energized through out the duty cycle, are known as continuous loads. These loads
are normally carried by the battery charger and are initiated at the inception of the duty cycle.
RAW MATERIAL HANDLING SYSTEM Page: 36 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


Some of the continuous loads are: Indication lamps, (ON, TCH etc)., continuously energized coils ,
annunciator loads etc.
Momentary loads are non continuous loads which can occur one or more times during the duty cycle but
are of short duration i.e. less than 1 minute. Although the momentary loads may exist for only a fraction
of second, it is common practice to consider that each load will last for one full minute because the
battery voltage drop after several seconds.
Some of the typical momentary loads are: switchgear coil operations (trip and close), etc.
The AH capacity of the battery is calculated as:
AH =AH1* K1 * K2 * K3
Where K1 = Ageing Factor
K2 = Design Margin
K3= Temperature correction factor (For the lowest temperature of 10deg C)
AH1 = max of (Ap A (p-1) )*K
Where p=1 to S (S is the section of the duty cycle being analyzed).
K = Capacity rating Factor which is obtained from the Manufacturer for a given end cell voltage and
discharge capacity.(annexure-A)
The load cycle of the battery is as indicated below.
RAW MATERIAL HANDLING SYSTEM Page: 37 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008





We will consider for this project as,
S1 = 1 minute, S2=28 minutes & S3=1 minute
M1 = S1-0= S1 =1 minute, M2= S2-S1 = 28 minutes & M3=S3-S2 =1 minute
Based on the above calculation methodology, the AH capacity of the battery will be selected.
Float Charger Capacity
I
CC
=Continuous DC load current which is the total continuous current requirement calculated for the
loads
A design margin of 5 % is considered for unforeseen continues loads.
A trickle charging current I
TC
is as recommended by the manufacturer.(Usually 2%)
I
TC
= I
CC
*0.02
The total required capacity of the float charger shall be = I
CC
*1.05 + I
TC

Based on the above calculation float charger capacity will be selected.
RAW MATERIAL HANDLING SYSTEM Page: 38 of 38
DOCUMENT NO: M5006-E670-001 REV: A
ITEM: DESIGN CRITERIA ELECTRICAL Date: 05-09-2008


Boost Charge capacity:
The boost charger shall be equal to maximum allowable battery charging current (generally 14% of the
battery ampereage or the float charger capacity, which ever is higher.

19.0 VVVF DRIVES:
The following factors are considered for determining the drive rating:
1 The type of load (constant torque in case of conveyors, feeders etc)
2 Shaft power of the motor required by the mechanical load
3 Overloading capacity will be considered as 120%
4 Overloading time and cycle O/L for 60 seconds in every 600 seconds.
5 Overload type will be cyclic.
6 Speed range shall be 20% to 100%.
7 The drive will be sized for an ambient of 40 deg C.
All the drives selected for 690V motors (conveyors) shall be in the multidrive configuration,
where the converter will be common and the inverters will be for individual motors. The drives
for VF/belt feeders shall be single drives in this project.
The sizing of the converter module and the inverter modules will be done based on the above parameters
by using the sizing software generally provided by the manufacturers.