Name of Feeder Incomer-1

Load Current: (IL) 394 Amp


Min Fault Current ( Line-Line): 3500 Amp
Max Fault Current ( Line-Line): 3500 Amp
Relay Type IDMT
Relay Code
Relay No
CT Primary Current 640 Amp
CT Secondary Current 1 Amp
Relay Error (%) 7.5%
CT Error (%) 10.0%
Over shoot 0.05 Sec
C.B Interrupting Time 0.17 Sec
Safety 0.33 Sec
Total Grading Time 0.58 Sec
Expected Operating Time of Relay 0.447 Sec
Low Over Current Setting: (I>)
Over Load Current : 100% X IL
Over Load Current :(In) 394 Amp
Required Over Current Relay Plug Setting 0.615625 0.6 A X In
Actual Plug Setting of Over Current Relay 0.80 0.8 A X In
Time Dial Setting of Over Current Relay (TMS) 0.125 Sec
Curve Selection for Relay Normal Inverse (NI)
Pick Up Setting of Over Current Relay (PMS): (I>) 0.8 Amp
Plug Setting Multiplier (PSM): 6.84
Operation Time of Relay 3.57 Sec
Actual Operating Time of Relay : (tI>) 0.447 Sec
Total Grading Time 0.58 Sec
Operating Time of Previous Up steam Relay 1.03 Sec
High Over Current Setting: (I>>)
Actual Plug Setting of Relay 2.50 2.5 A X In
Time Dial Setting of Over Load Relay (TMS) 0.100 Sec
Curve Selection for Relay Normal Inverse (NI)
Pick UP Setting of Over Load Relay (PMS): (I>>) 2.5 Amp
Plug Setting Multiplier (PSM): 2.19
Time of Operation of Relay 8.87 Sec
Actual Operating Time of Relay : (tI>>) 0.89 Sec
Total Grading Time 0.58 Sec
Operating Time of Previous Up steam Relay 1.46 Sec
Low Over Current Setting: (I>) 0.8 A X In Amp
Actual Operating Time of Relay(tI>) 0.447 Sec
High Over Current Setting: (I>>) 2.5 A X In Amp
Actual Operating Time of Relay(tI>>) 0.89 Sec
5.46875
Summary of Over Current Relay Setting:
Over Current Relay Setting
Calculation of IDMT Over Current Relay Settings:
Name of Feeder
Load Current: (IL) 394 Amp
Min Fault Current ( Line-Ground): 11000 Amp
Max Fault Current ( Line-Ground): 22000 Amp
Relay Type
Relay Code
Relay No
CT Primary Current 600 Amp
CT Secondary Current 1 Amp
Relay Error (%) 7.5%
CT Error (%) 10.0%
Over shoot 0.05 Sec
C.B Interrupting Time 0.17 Sec
Safety 0.33 Sec
Total Grading Time 0.58 Sec
Expected Operating Time of Relay 0.176 Sec
Low Earth Fault Setting: (Ie>)
Earth Fault Current : 20% X In
Earth Fault Current 78.8 Amp
Required Earth Fault Relay Plug Setting 0.1 0.1 A X In
Actual Plug Setting of Earth Fault Relay 0.16 0.2 A X In
Time Dial Setting of Earth Fault Relay (TMS) 0.125 Sec
Curve Selection for Relay Normal Inverse (NI)
Pick Up Setting of Earth Fault Relay (PMS): (Ie>) 0.16 Amp
Plug Setting Multiplier (PSM): 114.58
Operation Time of Relay 1.41 Sec
Actual Operating Time of Relay : (te>) 0.18 Sec
Total Grading Time 0.58 Sec
Operating Time of Previous Up steam Relay 0.76 Sec
High Earth Fault Setting: (Ie>>)
Actual Plug Setting of Relay 2.50 2.5 A X In
Time Dial Setting of Over Load Relay (TMS) 0.100 Sec
Curve Selection for Relay Normal Inverse (NI)
Pick UP Setting of Earth Fault Relay (PMS): (Ie>>) 2.5 Amp
Plug Setting Multiplier (PSM): 7.33
Time of Operation of Relay 3.44 Sec
Actual Operating Time of Relay : (te>>) 0.34 Sec
Total Grading Time 0.58 Sec
Operating Time of Previous Up steam Relay 0.92 Sec
Low Earth Fault Setting: (Ie>) 0.2 A X In Amp
Actual Operating Time of Relay(te>) 0.176 Sec
High Earth Fault Setting: (Ie>>) 2.5 A X In Amp
Actual Operating Time of Relay(te>>) 0.34 Sec
Summary of Earth Fault Relay Setting:
Jignesh.Parmar
www.electricalnotes.wordpress.com
jiguparmar@yahoo.com
Earth Fault Relay Setting
Calculation of IDMT Earth Fault Relay Settings:
Normal Inverse (NI)
Very Inverse (VI)
Exteremely Inverse (EI)
Long Time Inverse
Jignesh.Parmar