Sunteți pe pagina 1din 48

>

Eltek Valere
Telecom Product Overview
January 2010
Slide 2
15/11/2010
A Full Line of DC Power Systems
Small Medium Large
> Broadest Industry Product Offering
Everything from 5 amps to 10,000 amps
> Highest Performance
High efficiency, high density
Minipack
1U/1,6kW
2U/4,8kW
Compact Systems
2U/7,5kW
FP 2
2U/8kW
6U/8-24kW
FP 2
48-280kW
Scalable
100-1000kW
Micropack
2U/1kW
PP 5,8
54-550kW
Slide 3
15/11/2010
Leading edge Rectifier Modules
Minipack
400 & 800W
FP 2
2000-3000W
V-Series
1000-2500 W
Powerpack
3ph/11000W
> Power from 250W to 11KW per module
> Designed for harsh environments
> Efficiency >96%!
Micropack
250W
Powerpack
3ph/5800W
Small Medium LargeC
Slide 4
15/11/2010
Smartpack More than just a controller
> Scalable controller for systems
based on all new and future
rectifier families
> Configuration and monitoring
Front panel
WEB
Windows SW
> Basic integrated I/O meeting
average system requirements
> Designed for flexibility and future
growth
Smartpack
Smartnode
Battery String Monitor
C
A
N
C
A
N
Rectifiers
Slide 5
15/11/2010
Smartpack More than just a controller
> Full remote control via:
Ethernet using standard WEB Browser or
EltekValere Windows SW and email alert
functionality
Modem using alarm call back and SMS
alert/status report functionality
Ethernet based closed private networks using
Network Management Systems with SNMP
> Comprehensive Battery Management
Thermal compensation
Battery disconnection preventing deep discharge
Multi level load shedding
Charge control, current and voltage
Battery life time prediction
> Hybrid solar features
Generator control (cyclic charging) for reduced fuel
consumption
Reduced charge current limitation when running
gen-sets
Startup delay of rectifiers
Logging of energy produced from PV panel,
genset and other sources
> Efficiency Management
Manages system to target efficiency
Rectifiers disabled based on system load
Rectifiers are shuffled to maximize lifetime
N+1 redundancy kept as default, but can be
removed
> Other features
Multi language menu choice
Major and minor alarm trigger levels on all
monitors
PLC functionality triggering of event trough
Boolean functions
Battery & load fuse monitoring
Mains supervision
Event log (10.000 alarms and events)
Interval data logging of selected monitors
Average and peak values of all monitors
Detailed rectifier inventory with internal monitoring
Adjustable rectifier walk-in
Slide 6
15/11/2010
Smartpack More than just a controller
> Additional functionality by optional CAN nodes
Smartnode RS-232/RS-485
Communication with equipment
with proprietary protocols
Modem call-back and SMS
feature with GSM modems
Battery Monitor
Additional monitoring of
battery fuse, temperature,
block voltage & current
per string
Load Monitor
Additional monitoring of
8 individual load
breakers and currents
I/OMonitor
Additional monitoring of 6
aux. inputs and 6 extra output
relays
2 temperature probe inputs
2 Analogue outputs
2 tacho input readings
Slide 7
15/11/2010
Standard Building blocks
SPD
Battery string
monitoring
Additional I&O
AC distribution kit
Battery shelf kit
Power
modules
Power Cores
Outdoor Enclosures
Indoor Enclosures
Optional kits
Batteries
Slide 8
15/11/2010
CTO Configure To Order
Tailor-made systems combining
standard building blocs
Integrated
Indoor cabinet
Outdoor cabinet
Slide 9
15/11/2010
CTO Configure To Order
ERP BOM
Configurator
Order Office/Logistics
Manufacturing site
Slide 10
15/11/2010
Micropack
Minipack
Flatpack2
Powerpack
Cabinets
Remote Power System

Telecom Product Families


Slide 11
15/11/2010
48V / 250W (241120.100)
24V / 240W (241120.200)
12V / 120W (241120.300)
Main Characteristics
> Convection-cooled (no internal fans)
> Integrated module alarm
> Wide AC range
> CAN Bus communication
150mm
88mm
2U
44mm
1U
Micropack Rectifier
Acronyms
Slide 12
15/11/2010
150 mm
44 mm
134 mm
Micropack Stand-alone
88 mm
Stand-alone Power Core Card
(241120.900)
Main Characteristics
> Single AC feed
> 1 x alarm output
> Bulk feed DC out
> DIN mounted solution
Acronyms
Slide 13
15/11/2010
Compack (241120.400)
Main Characteristics
> CAN Bus communication
> User connects via Ethernet port
> 2 x LVD operation support
> 3 x pot. free alarm contacts
> Supports CAN nodes
110 mm
70 mm
30 mm
Micropack Controller
Acronyms
Slide 14
15/11/2010
Micropack Integrated System
2 or 4 module positions
> Max 500W or 1000W
> Compack controller
> Load distribution modules, each
with 4x plug in breaker positions
> Battery breaker module with
2xBattery MCB, current
measurement and LVBD
> Optional Bulk-feed module
> Optional 19 bracket
Batt. dist. module
241120.910
Load. dist. module
241120.920
Bulk feed module
241120.911
-48V -48V
Slide 15
15/11/2010
Micropack
Minipack
Flatpack2
Powerpack
Cabinets
Remote Power System

Telecom Product Families


Slide 16
15/11/2010
48V / 400W (241117.120)
48V / 800W WIR (241117.130)
Main Characteristics
> Front-to-rear Airflow
> Under-wiring Bus
> Wide AC range
> CAN Bus communication
250mm
88.9mm
2U
42.5mm
1U
Minipack Rectifiers
Acronyms
Slide 17
15/11/2010
Smartpack Extended
(242100.110)
Smartpack RS-232 Front
(242100.111)
Smartpack GB RS-232 Front (Chinese)
(242100.114)
Smartpack WEB/SNMP 6+6
(242100.118)
144 mm
43 mm
1U
109 mm
Smartpack Controller
Main Characteristics
> CAN Bus communication
> LCD screen and keypad
> User connects via USB
> Supports CAN nodes
Acronyms
Slide 18
15/11/2010
Minipack Integrated System 2U
> 48V/3200W
Up to 4 Rectifiers
SmartPack
Max 10 MCB, (2-30A plug-in breakers)
Max 2 x 60A BB
LVBD
Optional LVLD
Bulk-feed options
> 48V/4800W
Up to 6 Rectifiers
SmartPack
Max 8 MCB, (2-30A plug-in breakers)
Max 2 x 100A BB
LVBD
Optional LVLD
Bulk-feed options
Acronyms
Slide 19
15/11/2010
Compack (241120.400)
Main Characteristics
> CAN Bus communication
> User connects via Ethernet port
> 2 x LVD operation support
> 3 x pot. free alarm contacts
> Supports CAN nodes
110 mm
70 mm
30 mm
Minipack 1U Controller
Acronyms
Slide 20
15/11/2010
Minipack Integrated System 1U
> Bulk feed
Pure DC power supply AC in 48V DC out, no
DC distribution
Optional controller, Compack, for remote
monitoring
> DC Distribution
Integrated DC distribution:
- 6 x load fuses, (max. 10A)
- 2 x battery breakers, plug-in type, max 30A
- Low volt disconnection
- Fuse monitoring
Battery management included temp.
compensated charging, automatic or manual
battery testing, low volt disconnection, etc.
Controller (Compack) for full remote
monitoring via WEB and traditional alarm
contacts
Slide 21
15/11/2010
Micropack
Minipack
Flatpack2
Powerpack
Cabinets
Remote Power System

Telecom Product Families


Slide 22
15/11/2010
Main Characteristics
> Fan cooled
> Rear edge-connect
> Wide AC range
3
2
7
m
m
41,5 mm
1U
109 mm
Flatpack2 Rectifiers Standard range
48V / 2000W (241115.100)
48V / 2000W B-F (241115.120)
24V / 2000W WOR (241115.250)
48V / 3000W (241119.100)
Max
Efficiency
Zone
88
90
92
94
0 400 800 1200 1600 2000
Pout(W)
E
f
f
.
(
%
)
Acronyms
Slide 23
15/11/2010
Main Characteristics
> >96% efficiency !!
> Only 1 FAN (less noise)
> 100% plug compatible with standard range
Flatpack2 Rectifiers HE range
48V / 2000W (241115.105)
48V / 3000W (241119.105)
24V / 1800W (241115.205)
96%
95%
Acronyms
Slide 24
15/11/2010
Features
> Maximum Power Point Tracking
> Galvanic isolation
> Supported by current Smartpacks
48V / 1500W (241115.650)
Main Characteristics
> Uses same PR as FP2 rectifier
> Input voltage (tolerance) : 170 265 VDC
Typical input feed is from one string of between 4 to 6 solar
panels
Flatpack2 HE Solar Solar Charger
Slide 25
15/11/2010
Smartpack
Load
Gen set
Solar
Solar
Batteries
Same modular philosophy as for AC/DC
Common Smartpack control system
Galvanic isolation between panels and
telecom equipment improves immunity to
lightning transients
HE technology, 96% efficiency
Maximum Power Point Tracking utilizes
close to 100% of available solar power
CAN bus
I/O* Unit
Fuel tank
~
Mains
Battery
Monitoring*
*optional
Remote
Monitoring*
Flatpack2 Solar Hybrid concept
Slide 26
15/11/2010
Flatpack2 Stand-alone box - DNV
Part number : M20101.000
Suit most Std and HE Flatpack2
rectifiers (see datasheet for details)
Main Characteristics
> DNV Approved
> In-Built alarm monitoring
> Can work in parallel
> CAN Bus communication
Rear view
Acronyms
Slide 27
15/11/2010
Smartpack Extended
(242100.110)
Smartpack RS-232 Front
(242100.111)
Smartpack GB RS-232 Front (Chinese)
(242100.114)
Smartpack WEB/SNMP 6+6
(242100.118)
144 mm
43 mm
1U
109 mm
Smartpack Controller
Main Characteristics
> CAN Bus communication
> LCD screen and keypad
> User connects via USB
> Supports CAN nodes
Acronyms
Slide 28
15/11/2010
> Both PRs are 4 across
> Smartpack can be housed in
left-hand slot
3
7
0

m
m

d
e
e
p
Flatpack2 1U PR building blocks
4
3
1

m
m

d
e
e
p
FP2 2kW
FP2 3kW
Acronyms
Slide 29
15/11/2010
Includes (up to) :
1U Distribution + 1 PR
8000W (166A@48V)
Smartpack
2 x 100A Battery breakers
6 x 260A Load breakers
2 x LVD (150A)
5 k g (ex c l . r ec t i f i er s)
Flatpack2 Small Integrated System
FP2 2kW only
Figure shown is an 8kW system with std 2kW rectifiers
Acronyms
Slide 30
15/11/2010
2kW rectifier : Up to 32kW
3kW rectifier : Up to 24kW
4U Distribution + 1-4 PR
Smartpack
6 x 100A (3 x 200A) BB
21 x 2125A Load breakers*
2 x LVD (up to 600A)
* Check datasheet for other available combinations
Up to 10 kg (excl. rectifiers)
Includes (up to) :
Flatpack2 Medium Integrated System
2kW and 3kW options
Figure shown is a 16kW system with std 2kW rectifiers
Acronyms
Slide 31
15/11/2010
2kW rectifier : Up to 96 kW
3kW rectifier : Up to 108 kW
IFC Cabinet : 2000 x 600 x 600 mm
Input 230V/400V 3-phase
2 x Battery & 6 x Load Fuse options
Secondary 30 x MCB dist. option
Flatpack2 IFC Large Power
2kW and 3Kw options

Acronyms
Slide 32
15/11/2010
Micropack
Minipack
Flatpack2
Powerpack
Cabinets
Remote Power System

Telecom Product Families


Slide 33
15/11/2010
Main Characteristics
> True 3 Phase rectifier
> Up to 5800W output
> CAN Bus communication
> Hot-swappable
> 4 across 23 PR
* Option for IFC Large Power
364 mm
161 mm
Powerpack Rectifiers
Models
48V 5800W 400/480 Vac (241246.500)
* Derates to 3.5kW at 208VAC input
2U
Acronyms
Slide 34
15/11/2010
Main Characteristics
> True 3 Phase rectifier
> Up to 11kW output
> Basic controller built-in
> Models for different AC inputs
> CAN Bus communication
> Not hot-swappable
500 mm
585 mm
Powerpack Rectifiers
Models
11kW 48V 480VAC (241246.000) *
* Derates to 9.6kW with 400VAC input
11kW 48V 208VAC (241246.100)
2U
Acronyms
Slide 35
15/11/2010
Smartpack Extended
(242100.110)
Smartpack RS-232 Front
(242100.111)
Smartpack GB RS-232 Front (Chinese)
(242100.114)
Smartpack WEB/SNMP 6+6
(242100.118)
144 mm
43 mm
1U
109 mm
Smartpack Controller
Main Characteristics
> CAN Bus communication
> LCD screen and keypad
> User connects via USB
> Supports CAN nodes
Acronyms
Slide 36
15/11/2010
Powerpack 5,8kW System Solution
Main Characteristics
> 2000 x 600 x 600 mm
> Up to 20 Rectifiers per cabinet
> Bulk-Feed or integrated distribution
> Top or Bottom Entry
> Maximum 116kW per cabinet
Slide 37
15/11/2010
Powerpack 11kW System solution
Main Characteristics
> 2000 x 600 x 600 mm
> Up to 10 Stacked Rectifiers
> Bulk-Feed or integrated distribution
> Top or Bottom Entry
> Maximum 2300 Amps per bay
Slide 38
15/11/2010
Micropack
Minipack
Flatpack2
Powerpack
Cabinets
Remote Power System

Telecom Product Families


Slide 39
15/11/2010
Main Characteristics
> Cost-effective cabinet
> Steel construction
> 1.2 Tonn weight capacity
> Typically Top Entry
> Some sizes have Flatpacked
option (assemble locally)
Current Range
H x W x D (mm)
700 x 600 x 400
1000 x 600 x 400
1200 x 600 x 600
1500 x 600 x 600 *
1800 x 600 x 400 *
1800 x 600 x 600 *
1800 x 600 x 400
2000 x 600 x 400
2000 x 600 x 600 *
* Available in Silver finish also
Integrated Frame Cabinet (IFC)
Slide 40
15/11/2010
15U Type 2 Fan/filter (237143)
15U Type 2 T20 AC (250661)
Main Characteristics
> Common body with different door
type for Fan/filter or Air Conditioner
> 19 mounting only
> 15U of mounting space *
Lower 3U typically for AC Distribution
> Wall, Floor or Pole mount kits
Type 2 Outdoor cabinet
888 mm
527 mm
586 mm
Slide 41
15/11/2010
Main Characteristics
> Single skin, insulated
> Select door for cooling option
1 Fan/filter
2 Fan /Filter
Air Conditioner
HEX
> Height 1.5 or 1.8m
> Foot print 700 (W) x 760 (D) mm +
Cooling option depth
Type 3 Outdoor cabinet
Figure shown is 2 Fan/Filter option
Slide 42
15/11/2010
Micropack
Minipack
Flatpack2
Powerpack
Cabinets
Remote Power System

Telecom Product Families


Slide 43
15/11/2010
Also known as span power or line power
Typical
distance :
5 to 10 km
RPS Block diagram
RFT-V Type : Remote Feeding Telecommunication Voltage limited
Slide 44
15/11/2010
DC / DC Converter
> Converts -48VDC to 190VDC
> To achieve 380VDC potential, a
positive and negative output
from a pair are connected to
Earth
(Refer to datasheet for specifications)
DC-DC Converter module
Acronyms
Slide 45
15/11/2010
Output Channels
> Provides 380VDC output, limited
to 100W.
> Provides earth leakage, surge
and short circuit protection.
(Refer to datasheet for specifications)
VA Limiter module
Acronyms
Slide 46
15/11/2010
Remote End Converter
> Converts DC input to -48VDC.
> Input voltage and output power
depend on the characteristics of
the twist pair circuit.
Typical
distance :
up to 10 km
(Refer to datasheet for specifications)
Remote End module
Acronyms
Slide 47
15/11/2010
MDF
- 48V
- 48V
+/-190V
System Installation example
MDF = Main Distribution Frame
Slide 48
15/11/2010
Vision
THE GREATEST POWER
IN THE INDUSTRY