Sunteți pe pagina 1din 80

MiCOM P141, P142, P143,

P144, P145

MiCOM P141, P142, P143, P144, P145/EN/TM/A XXXX. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of
ALSTOM. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document is
provided for information only. Neither ALSTOM, its officers or employees accept responsibility for, or should be taken as making any representation or warranty
(whether express or implied), as to the accuracy or completeness of such data or the achievement of any projected performance criteria where these are indicated.
ALSTOM reserves the right to revise or change this data at any time without further notice.
GRID



Technical Data Sheet
Feeder Management Relay
Publication Reference: P14x/EN TDS/Ff7



GRID
X
50/51
67N/67W
/64
50N/
51N
67/
67N
51V 46 49
37P/
37N
27/
59
59N 47 50BF
CTS
VTS 79 25
YN 49SR
Fault records
Disturbance
Record
Measurements
PSL
Local
Communication
2
nd
Remote
comm. port
Remote
comm. port
LEDs
Self monitoring
81U/81O
/81R
X
50/51
67N/67W
/64
50N/
51N
67/
67N
51V 46 49
37P/
37N
27/
59
59N 47 50BF
CTS
VTS 79 25
YN 49SR
Fault records
Disturbance
Record
Measurements
PSL
Local
Communication
2
nd
Remote
comm. port
Remote
comm. port
Feeder management P14x
LEDs
Binary
Input / output
always availabl e
optional
V
ref
V
I
I
E sen
Self monitoring
81U/81O
/81R
Y
IEC
61850
DIFF
I
BIAS
I s2 I
s1 I
K1
K2
Operate
Restrain
K1 0% to 20%
K2 0% to 150%
s1 I 0.08 to 1. 0I n
s2 I 0.10 to 1. 5I n

GRID





P14x Technical Data Sheet 9 P141/2/3/4/5 Software Version 46J
Technical Data
Mechanical Specifications
Design
Modular MiCOM Px40 platform relay,
P141/142/P144-40TE (206mm (8)) case and
P143/P145 (309.6mm (12)) case. Mounting is
front of panel flush mounting, or 19 rack
mounted (ordering options).
Enclosure Protection
Per IEC 60529: 1992
IP 52 Protection (front panel) against dust and
dripping water.
IP 50 Protection for the rear and sides of the
case against dust.
IP 10 Product safety protection for the rear due
to live connections on the terminal block.
Weight
Case 40TE: approx. 7.3 kg
Case 60TE: approx. 9.2 kg
Terminals
AC Current and Voltage Measuring Inputs
Located on heavy duty (black) terminal block:
Threaded M4 terminals, for ring lug
connection.
CT inputs have integral safety shorting, upon
removal of the terminal block.
General Input/Output Terminals
For power supply, opto inputs, output contacts
and COM1 rear communications.
Located on general purpose (grey) blocks:
Threaded M4 terminals, for ring lug
connection.
Case Protective Earth Connection
Two rear stud connections, threaded M4.
Must be earthed (grounded) for safety,
minimum earth wire size 2.5mm
2
.
Front Port Serial PC Interface
EIA(RS)232 DTE, 9 pin D-type female
connector.
Courier protocol for interface to MiCOM S1
software.
Isolation to ELV level.
Maximum cable length 15m.
Front Download/Monitor Port
EIA(RS)232, 25 pin D-type female connector.
For firmware downloads.
Isolation to ELV level.
Rear Communications Port
EIA(RS)485 signal levels, two wire
Connections located on general purpose block,
M4 screw.
For screened twisted pair cable, multi-drop,
1000m max.
For K-Bus, IEC-870-5-103, or DNP3 protocol
(ordering options).
Isolation to SELV level.
Optional Second Rear Communications
Port
EIA(RS)232, 9 pin D-type female connector,
socket SK4.
Courier protocol: K-Bus, EIA(RS)232, or
EIA(RS)485 connection.
Isolation to SELV level.
Optional Rear IRIG-B Interface modulated
or un-modulated
BNC socket
Isolation to SELV level.
50 ohm coaxial cable.
Optional Rear Fiber Connection for
SCADA/DCS
BFOC 2.5 -(ST)-interface for glass fiber, as
per IEC 874-10.
850nm short-haul fibers, one Tx and one Rx.
For Courier, IEC-870-5-103, DNP3 or
MODBUS protocol (ordering options).
Optional Rear Ethernet Connection for IEC
61850 or DNP3.0
Optional redundant Rear Ethernet
Connection (optical)
10BaseT/100BaseTX Communications
Interface in accordance with IEEE802.3 and
IEC 61850
Isolation: 1.5kV
Connector type: RJ45
Cable type: Screened Twisted Pair (STP)
100 Base FX Interface
Interface in accordance with IEEE802.3 and
IEC 61850
Wavelength: 1300nm
Fiber: multi-mode 50/125m or 62.5/125m
Connector style: BFOC 2.5 -(ST)
Ratings
AC Measuring Inputs
Nominal frequency: 50 and 60 Hz (settable)
Operating range: 45 to 65Hz
Phase rotation: ABC





P14x Technical Data Sheet 10 P141/2/3/4/5 Software Version 46J
AC Current
Nominal current (In): 1 and 5 A dual rated.
(1A and 5A inputs use different transformer tap
Connections, check correct terminals are
wired).
Nominal burden per phase: < 0.15 VA at In
Thermal withstand:
continuous 4 In
for 10s: 30 In
for 1s; 100 In
Linear to 64 In (non-offset AC current).
AC Voltage
Nominal voltage (Vn): 100 to 120 V or 380 to
480V phase-phase (min. 196 Vac, max. 560
Vac).
Nominal burden per phase: < 0.02 VA at Vn.
Thermal withstand:
continuous 2 Vn
for 10s: 2.6 Vn
Power Supply
Auxiliary Voltage (Vx)
Three ordering options:
(i) Vx: 24 to 48 Vdc
(ii) Vx: 48 to 110 Vdc, and 40 to
100Vac (rms)
(iii) Vx: 110 to 250 Vdc, and 100 to
240Vac (rms)
Operating Range
(i) 19 to 65V (dc only for this variant)
(ii) 37 to 150V (dc), 32 to 110V (ac)
(iii) 87 to 300V (dc), 80 to 265V (ac)
With a tolerable ac ripple of up to 12% for a dc
supply, per IEC 60255-11: 1979.
Nominal Burden
Quiescent burden: 11W. (Extra 1.25W when
fitted with second rear Courier)
Additions for energized binary inputs/outputs:
Per opto input:
0.09W (24 to 54V),
0.12W (110/125V),
0.19W (220/120V).
Per energized output relay: 0.13W
Power-up Time
Time to power up < 11s.
Power Supply Interruption
Per IEC 60255-11: 1979
The relay will withstand a 20ms interruption
in the DC auxiliary supply, without
de-energizing.
Per IEC 61000-4-11: 1994
The relay will withstand a 20ms interruption
in an AC auxiliary supply, without
de-energizing.
Battery Backup
Front panel mounted
Type AA, 3.6V (SAFT advanced battery
reference LS14250) Battery life (assuming
relay energized for 90% time) >10 years
Field Voltage Output
Regulated 48Vdc
Current limited at 112mA maximum output
Digital ( Opto ) Inputs
Universal opto inputs with programmable
voltage thresholds (24/27, 30/34, 48/54,
110/125, 220/250V). May be energized from
the 48V field voltage, or the external battery
supply.
Rated nominal voltage: 24 to 250Vdc
Operating range: 19 to 265Vdc
Withstand: 300Vdc, 300Vrms.
Peak current of opto input when energized is
3.5mA (0-300V)
Nominal pick-up and reset thresholds:
Nominal battery 24/27: 60 - 80% DO/PU
(logic 0) <16.2 (logic 1) >19.2
Nominal battery 24/27: 50 - 70% DO/PU
(logic 0) <12.0 (logic 1) >16.8
Nominal battery 30/34: 60 - 80% DO/PU
(logic 0) <20.4 (logic 1) >24.0
Nominal battery 30/34: 50 - 70% DO/PU
(logic 0) <15.0 (logic 1) >21.0
Nominal battery 48/54: 60 - 80% DO/PU
(logic 0) <32.4 (logic 1) >38.4
Nominal battery 48/54: 50 - 70% DO/PU
(logic 0) <24.0 (logic 1) >33.6
Nominal battery 110/125: 60 - 80% DO/PU
(logic 0) <75.0 (logic 1) >88.0
Nominal battery 110/125: 50 - 70% DO/PU
(logic 0) <55.0 (logic 1) >77.0
Nominal battery 220/250: 60 - 80% DO/PU
(logic 0) <150.0 (logic 1) >176.0
Nominal battery 220/250: 50 - 70% DO/PU
(logic 0) <110 (logic 1) >154
Recognition time:
<2ms with long filter removed,
<12ms with half cycle ac immunity filter on
Output Contacts
Standard Contacts
General purpose relay outputs for signaling,
tripping and alarming:
Continuous Carry Ratings (Not Switched):
Maximum continuous current: 10A (UL: 8A)
Short duration withstand carry: 30A for 3s
250A for 30ms
Rated voltage: 300 V





P14x Technical Data Sheet 11 P141/2/3/4/5 Software Version 46J
Make & Break Capacity:
DC: 50W resistive
DC: 62.5W inductive (L/R = 50ms)
AC: 2500VA resistive (cos = unity)
AC: 2500VA inductive (cos = 0.7)
Make, Carry:
30A for 3 secs, dc resistive, 10,000
operations (subject to the above limits of
make/break capacity and rated voltage)
Make, Carry & Break:
30A for 200ms, ac resistive, 2,000
operations (subject to the above limits of
make/break capacity & rated voltage) 4A for
1.5 secs, dc resistive, 10,000 operations
(subject to the above limits of make/break
capacity & rated voltage)
0.5A for 1 sec, dc inductive, 10,000
operations (subject to the above limits of
make/break capacity & rated voltage)
10A for 1.5 secs, ac resistive/inductive,
10,000 operations (subject to the above
limits of make/break capacity & rated
voltage)
Durability:
Loaded contact: 10 000 operations
minimum
Unloaded contact: 100 000 operations
minimum
Operate Time
Less than 5ms
Reset Time
Less than 5ms
High Break Contacts (Model D Only)
Continuous Carry Ratings (Not Switched):
Maximum continuous current: 10A
Short duration withstand carry: 30A for 3s
250A for 30ms
Rated voltage: 300 V
Make & Break Capacity:
DC: 7500W resistive
DC: 2500W inductive (L/R = 50ms)
Make, Carry:
30A for 3 secs, dc resistive, 10,000
operations (subject to the above limits of
make/break capacity & rated voltage)
Make, Carry & Break:
30A for 3 secs, dc resistive, 5,000
operations (subject to the above limits of
make/break capacity & rated voltage)
30A for 200 ms, dc resistive, 10,000
operations (subject to the above limits of
make/break capacity & rated voltage)
10A (*), dc inductive, 10,000 operations
(subject to the above limits of make/break
capacity & rated voltage)
*Typical for repetitive shots - 2 minutes idle
for thermal dissipation
Voltage Current L/R
No. of Shots
in 1 sec
65V 10A 40ms 5
150V 10A 40ms 4
250V 10A 40ms 2
250V 10A 20ms 4
MOV protection: Max Voltage 330V dc
Durability:
Loaded contact: 10 000 operations
minimum
Unloaded contact: 100 000 operations
minimum
Operate Time:
Less than 0.2ms
Reset Time:
Less than 8ms
Watchdog Contacts
Non-programmable contacts for relay
healthy/relay fail indication:
Breaking capacity:
DC: 30W resistive
DC: 15W inductive (L/R = 40ms)
AC: 375VA inductive (cos = 0.7)
IRIG-B 12X Interface (Modulated)
External clock synchronization per IRIG
standard 200-98, format B12X.
Input impedance 6k at 1000Hz
Modulation ratio: 3:1 to 6:1
Input signal, peak-peak: 200mV to 20V
IRIG-B 00X Interface (Un-modulated)
External clock synchronization per IRIG
standard 200-98, format B00X.
Input signal TTL level
Input impedance at dc 10k








P14x Technical Data Sheet 12 P141/2/3/4/5 Software Version 46J
Environmental Conditions
Ambient Temperature Range
Per IEC 60255-6: 1988
Operating temperature range:
-25C to +55C (or -13F to +131F).
Storage and transit:
-25C to +70C (or -13F to +158F).
Tested as per
IEC 60068-2-1: 2007
-25C storage (96 hours)
-40C operation (96 hours)
IEC 60068-2-2: 2007
+85C storage (96 hours)
Ambient Humidity Range
Per IEC 60068-2-3: 1969:
56 days at 93% relative humidity and +40C
Per IEC 60068-2-30: 1980:
Damp heat cyclic, six (12 + 12) hour cycles,
93% RH, +25 to +55C
Corrosive Environments
(For relays with harsh environment coating
of PCBs)
Per IEC 60068-2-60: 1995, Part 2, Test Ke,
Method (class) 3
Industrial corrosive environment/poor
environmental control, mixed gas flow test.
21 days at 75% relative humidity and +30
o
C
exposure to elevated concentrations of H2S,
(100 ppb) NO2, (200 ppb) Cl2 (20 ppb).
Per IEC 60068-2-52 Salt mist (7 days)
Per IEC 60068-2-43 for H2S (21 days), 15 ppm
Per IEC 60068-2-42 for SO2 (21 days), 25 ppm
Type Tests
Insulation
Per IEC 60255-27: 2005
Insulation resistance > 100M at 500Vdc
(Using only electronic/brushless insulation
tester).
Creepage Distances and Clearances
Per EN 61010-1: 2001
Pollution degree 2,
Overvoltage category III,
Impulse test voltage 5 kV.
High Voltage (Dielectric) Withstand
EIA(RS)232 ports excepted.
(i) Per IEC 60255-27: 2005, 2 kV rms
AC, 1 minute:
Between all case terminals connected
together, and the case earth.
Also, between all terminals of independent
circuits.
1kV rms AC for 1 minute, across open
watchdog contacts.
1kV rms AC for 1 minute, across open
contacts of changeover output relays.
(ii) Per ANSI/IEEE C37.90-1989 (reaffirmed
1994):
1.5 kV rms AC for 1 minute, across open
contacts of changeover output relays.
Impulse Voltage Withstand Test
Per IEC 60255-27: 2005
Front time: 1.2 s, Time to half-value: 50 s,
Peak value: 5 kV, 0.5J
Between all terminals, and all terminals and
case earth.
Electromagnetic Compatibility
(EMC)
1 MHz Burst High Frequency Disturbance
Test
Per IEC 60255-22-1: 1988, Class III,
Common-mode test voltage: 2.5 kV,
Differential test voltage: 1.0 kV,
Test duration: 2s, Source impedance: 200
EIA(RS)232 ports excepted.
100kHz Damped Oscillatory Test
Per EN61000-4-18: 2007: Level 3
Common mode test voltage: 2.5kV
Differential mode test voltage: 1kV
Immunity to Electrostatic Discharge
Per IEC 60255-22-2: 1996, Class 4,
15kV discharge in air to user interface,
display, and exposed metalwork.
Per IEC 60255-22-2: 1996, Class 3,
8kV discharge in air to all communication
ports.
6kV point contact discharge to any part of
the front of the product.
Electrical Fast Transient or Burst
Requirements
Per IEC 60255-22-4: 2002. Test severity
Class III and IV:
Amplitude: 2 kV, burst frequency 5kHz
(Class III),
Amplitude: 4 kV, burst frequency 2.5kHz
(Class IV).
Applied directly to auxiliary supply, and
applied to all other inputs. EIA(RS)232
ports excepted.
Surge Withstand Capability
IEEE/ANSI C37.90.1:2002:
4kV fast transient and 2.5kV oscillatory applied
common mode and differential mode to opto
inputs (filtered), output relays, CTs, VTs,
power supply, field voltage.
4kV fast transient and 2.5kV oscillatory applied
common mode to communications, IRIG- B.





P14x Technical Data Sheet 13 P141/2/3/4/5 Software Version 46J
Surge Immunity Test
EIA(RS)232 ports excepted.
Per IEC 61000-4-5: 2005 Level 4,
Time to half-value: 1.2/50 s,
Amplitude: 4kV between all groups and case
earth,
Amplitude: 2kV between terminals of each
group.
Immunity to Radiated Electromagnetic
Energy
Per IEC 60255-22-3: 2000, Class III:
Test field strength, frequency band 80 to 1000
MHz:
10 V/m,
Test using AM: 1 kHz / 80%,
Spot tests at 80, 160, 450, 900 MHz
Per IEEE/ANSI C37.90.2: 1995:
25MHz to 1000MHz, zero and 100% square
wave modulated.
Field strength of 35V/m.
Radiated Immunity from Digital
Communications
Per EN61000-4-3: 2002, Level 4:
Test field strength, frequency band 800 to 960
MHz, and 1.4 to 2.0 GHz:
30 V/m,
Test using AM: 1 kHz / 80%.
Radiated Immunity from Digital Radio
Telephones
Per ENV 50204: 1995
10 V/m, 900MHz and 1.89GHz.
Immunity to Conducted Disturbances
Induced by Radio Frequency Fields
Per IEC 61000-4-6: 1996, Level 3,
Disturbing test voltage: 10 V
Power Frequency Magnetic Field Immunity
Per IEC 61000-4-8: 1994, Level 5,
100A/m applied continuously,
1000A/m applied for 3s.
Per IEC 61000-4-9: 1993, Level 5,
1000A/m applied in all planes.
Per IEC 61000-4-10: 1993, Level 5,
100A/m applied in all planes at
100kHz/1MHz with a burst duration of 2s.
Conducted Emissions
Per EN 55022: 1998: Class A:
0.15 - 0.5MHz, 79dBV (quasi peak)
66dBV (average)
0.5 - 30MHz, 73dBV (quasi peak) 60dBV
(average).


Radiated Emissions
Per EN 55022: 1998: Class A:
30 - 230MHz, 40dBV/m at 10m
measurement distance
230 - 1GHz, 47dBV/m at 10m
measurement distance.
EU Directives
EMC Compliance
Per 89/336/EEC:
Compliance to the European Commission
Directive on EMC is claimed via the Technical
Construction File route. Product Specific
Standards were used to establish conformity:
EN50263: 2000
Product Safety
Per 2006/95/EC:
Compliance to the European Commission Low
Voltage Directive. (LVD) is
demonstrated using a Technical File.
A product specific standard was used to
establish conformity.
EN 60255-27: 2005

R&TTE Compliance
Radio and Telecommunications Terminal
Equipment (R&TTE) directive 99/5/EC.
Compliance demonstrated by compliance to
both the EMC directive and the Low voltage
directive, down to zero volts.
Applicable to rear communications ports.
ATEX Compliance
ATEX Potentially Explosive Atmospheres
directive 94/9/EC, for equipment.
The equipment is compliant with Article 1(2) of
European directive 94/9/EC.
It is approved for operation outside an ATEX
hazardous area. It is however approved for
connection to Increased Safety, Ex e, motors
with rated ATEX protection, Equipment
Category 2, to ensure their safe operation in
gas Zones 1 and 2 hazardous areas.

CAUTION - Equipment with this marking is not
itself suitable for operation within a potentially
explosive atmosphere.

Compliance demonstrated by Notified Body
certificates of compliance.

II (2) G






P14x Technical Data Sheet 14 P141/2/3/4/5 Software Version 46J
Mechanical Robustness
Vibration Test
Per IEC 60255-21-1: 1996
Response Class 2
Endurance Class 2
Shock and Bump
Per IEC 60255-21-2: 1995
Shock response Class 2
Shock withstand Class 1
Bump Class 1
Seismic Test
Per IEC 60255-21-3: 1995
Class 2
Transit Packaging Performance
Product testing to simulate protection offered
by primary packaging carton, to ISTA 1C
specification

Vibration and Drop Release Tests:

Vibration tests in 3 orientations, vibratory
movement 7 Hz, amplitude 5.3 mm,
acceleration 1.05g

Drop tests - 10 drops from 61 cm height on
multiple carton faces, edges and corners
P14x Third Party Compliances
Underwriters Laboratory (UL)

File Number: E202519
Issue Date: 21-04-2005
(Complies with Canadian and US
requirements).

Energy Networks Association (ENA)


Certificate Number: 101 Issue 3
Assessment Date: 10-12-2004

Type (s): P141, P142, P143 & P145






P14x Technical Data Sheet 15 P141/2/3/4/5 Software Version 46J
Protection Functions
Three Phase Overcurrent Protection
Accuracy
Additional tolerance X/R ratios:
5% over X/R 190
Overshoot: <30ms
Inverse Time Characteristic
Accuracy
DT Pick-up: Setting 5%
Minimum IDMT trip level:
1.05 x setting 5%
Drop-off: 0.95 x setting 5%
IDMT shape: 5% or 40ms whichever
is greater
IEEE reset: 5% or 50ms whichever
is greater
DT operation: 2% or 50ms, whichever is
greater
DT reset: 5%
Directional boundary (RCA 90%):
2% hysteresis 2o
Characteristic: UK curves
IEC 60255-3 1998
US curves:
IEEEC37.1121996
Earth/Sensitive Fault Protection
Earth Fault 1
DT Pick-up: Setting 5%
Minimum IDMT trip level: 1.05 x Setting 5%
Drop-off: 0.95 x Setting 5%
IDMT shape:
5% or 40ms whichever is greater *
IEEE reset:
5% or 50ms whichever is greater
DT operation:
2% or 50ms whichever is greater
DT reset: 5%
Repeatability: 2.5%
* Reference conditions TMS = 1, TD = 1 and
IN> setting of 1A operating range 2-20In
Earth Fault 2
DT Pick-up: Setting 5%
Minimum IDMT Trip level: 1.05 x Setting 5%
Drop-off: 0.95 x Setting 5%
IDMT shape:
5% or 40ms whichever is greater *
IEEE reset:
10% or 40ms whichever is greater
DT operation:
2% or 50ms whichever is greater

DT reset:
2% or 50ms whichever is greater
Repeatability: 5%
* Reference conditions TMS = 1, TD = 1 and
IN > setting of 1A, operating range 2-20In
SEF
DT Pick-up: Setting 5%
Minimum IDMT Trip level: 1.05 x Setting 5%
Drop-off: 0.95 x Setting 5%
IDMT shape:
5% or 40ms whichever is greater *
IEEE reset:
7.5% or 60ms whichever is greater
DT operation:
2% or 50ms whichever is greater
DT reset: 5%
Repeatability: 5%
* Reference conditions TMS = 1, TD = 1 and
IN > setting of 100mA, operating range 2-0In
REF
Pick-up: Setting formula 5%
Drop-off: 0.80 x setting formula 5%
Operating time: <60ms
High pick up: Setting 5%
High operating time: <30ms
Repeatability: <15%
Wattmetric SEF
Pick-up For P=0W
ISEF> 5% or P> 5%
Drop off: For P>0W
(0.95 x ISEF>) 5% or 0.9 x P> 5%
Boundary accuracy:
5% with 1
o
hysteresis
Repeatability: 5%
SEF Cos(PHI)/
Pick-up: Setting 5% for angles RCA60
o

Drop-off: 0.90 x Setting
IDMT shape:
5% or 50ms whichever is greater *
IEEE reset:
7.5% or 60ms whichever is greater
DT operation:
2% or 50ms whichever is greater
DT reset: 5%
Repeatability:2%
* Reference conditions TMS = 1, TD = 1 and
IN > setting of 100mA, operating range 2-0In
SEF Sin(PHI)
Pick-up: Setting 5% for angles from RCA60
o

to RCA90
o

Drop-off: 0.90 x Setting
IDMT shape:
5% or 50ms whichever is greater *






P14x Technical Data Sheet 16 P141/2/3/4/5 Software Version 46J
IEEE reset:
7.5% or 60ms whichever is greater
DT operation:
2% or 50ms whichever is greater
DT reset: 5%
Repeatability: 2%
Reference conditions TMS = 1, TD = 1 and
IN > setting of 100mA, operating range 2-0In
Zero Polarizing
Operating pick-up: 2%o of RCA 90%
Hysteresis: <3
o

VN > Pick-up: Setting 10%
VN > Drop-off: 0.9 x Setting 10%
Negative Polarizing
Operating Pick-up: 2%o of RCA 90%
Hysteresis: <3
o

VN 2 > Pick-up: Setting 10%
VN 2 > Drop-off: 0.9 x Setting 10%
I2 > Pick up: Setting 10%
I2 > Drop-off: 0.9 x Setting 10%
Negative Sequence Overcurrent
Accuracy
DT Pick-up: Setting 5%
Minimum IDMT trip level: 1.05 x Setting 5%
Drop-off: 0.95 x Setting 5%
IDMT shape: 5% or 40ms whichever
is greater
IEEE reset: 5% or 50ms whichever
is greater
DT operation: 2% or 50ms, whichever is
greater
DT reset: 5%
Directional boundary (RCA 90%):
2% hysteresis 2
o

Characteristic: UK curves
IEC 60255-3 1998
US curves:
IEEEC37.1121996
Reverse/Low Forward/Over Power
Protection
Accuracy
Pick-up: Setting 10%
Reverse/Over Power drop off: 0.95 x Setting
10%
Low forward Power drop off:
1.05xSetting+10%
Angle variation pick-up: Expected pick-up
angle 2 degree
Angle variation drop-off: Expected drop-off
angle 2.5 degree
Operating time: 2% or 50ms whichever
is greater
Repeatability: <5%
Disengagement time: <50ms
tRESET: 5%
Instantaneous operating time: < 50ms
Sensitive Reverse/Low Forward/
Over Power (1 Phase)
Accuracy
Pick-up: Setting 10%
Reverse/Over power Drop-off:
0.9 of setting 10%
Low forward power Drop-off:
1.1 of Setting 10%
Angle variation Pick-up:
Expected pick-up angle 2 degree
Angle variation Drop-off:
Expected drop-off angle 2.5% degree
Operating time: 2% or 50ms whichever is
greater
Repeatability: <5%
Disengagement time: <50ms
tRESET: 5%
Instantaneous operating time: <50ms
Under Voltage Protection
Accuracy
DT Pick-up: Setting 5%
IDMT Pick-up: Setting 5%
Drop-off: 1.02 x Setting 5%
IDMT shape: 2% or 50ms whichever is
greater
DT operation: 2% or 50ms whichever is
greater
Reset: <75ms
Repeatability: <1%
Over Voltage Protection
Accuracy
DT Pick-up: Setting 5%
IDMT Pick-up: Setting 5%
Drop-off: 0.98 x Setting 5%
IDMT shape: 2% or 50ms whichever is
greater
DT operation: 2% or 50ms whichever is
greater
Reset: <75ms
Repeatability: <1%
Rate of Change of Voltage dv/dt
Protection
Accuracy for 110V VT
Tolerance: 1% or 0.07, whichever is greater
Pick-up: Setting tolerance





P14x Technical Data Sheet 17 P141/2/3/4/5 Software Version 46J
Drop-off: (Setting - 0.07) tolerance for
positive direction
Drop-off: (Setting + 0.07) tolerance for
negative direction
Operating time@50Hz: [(Avg.cycle*20)+60]ms
Reset time@50Hz: 40ms
Neutral Displacement/Residual
Voltage
Accuracy
Pick-up: Setting 5% or 1.05 x Setting 5%
Drop-off: 0.95 x Setting 5%
IDMT shape: 5% or 65ms whichever is
greater
DT operation: 2% or 20ms whichever is
greater <55ms
Reset: <35ms
Repeatability: <10%
Under-frequency Protection
Accuracy
Pick-up: Setting 0.025Hz
Drop-off: 1.05 x Setting 0.025Hz
DT operation: 2% or 50ms whichever is
greater *
* The operating time will also include a time
for the relay to frequency track
(20Hz/second)
Over-frequency Protection
Accuracy
Pick-up: Setting 0.025Hz
Drop-off: 0.95 x Setting 0.025Hz
DT operation: 2% or 50ms whichever is
greater *
* The operating will also include a time for
the relay to frequency track (20Hz/ second)
Advanced Over/Under Frequency
f+t Protection [81U/81O]
Accuracy
Pick-up: Setting10mHz
Drop-off:
Setting +20mHz, 10mHz (underfrequency)
Setting -20mHz, 10mHz (overfrequency)
Operating timer:
2% or 50ms whichever is greater
Operating & Reset Time
Operating time* (underfrequency):
<100ms for Fs/Ff ratios less than 2
<160ms for Fs/Ff ratios less than 6
<230ms otherwise
Operating time* (overfrequency):
<125ms for Fs/Ff ratios less than 2
<150ms for Fs/Ff ratios less than 30
<200ms otherwise
Reset time*: <200ms
* Reference conditions: Tested using step
changes in frequency with Freq.Av.Cycles
setting = 0 and no intentional time delay.
Fs/Ff ratios as stated, where:
Fs = start frequency - frequency setting
Ff = frequency setting - end frequency
Advanced Frequency Supervised
Rate of Change of Frequency
f+df/dt Protection [81RF]
Accuracy
Pick-up:
Setting10mHz (frequency threshold)
Setting 3% or 10mHz/s, whichever is
greater (df/dt threshold)
Drop-off (frequency threshold):
Setting +20mHz, 10mHz (underfrequency)
Setting -20mHz, 10mHz (overfrequency)
Drop-off (df/dt threshold, falling frequency):
Setting +0.005Hz/s, 10mHz/s
(for settings between 0.01Hz/s and 0.1Hz/s)
Setting +0.05Hz/s, 5% or 55mHz/s,
whichever is greater
(for settings greater than 0.1Hz/s)
Drop-off (df/dt threshold, rising frequency):
Setting -0.005Hz/s, 10mHz/s
(for settings between 0.01Hz/s and 0.1Hz/s)
Setting -0.05Hz/s, 5% or 55mHz/s,
whichever is greater
(for settings greater than 0.1Hz/s)
Operating & Reset Time
Instantaneous operating time:
<125ms for Freq.Av.Cycles setting = 0
Reset time:
<400ms for df/dt.Av.Cycles setting = 0
Advanced Independent Rate of
Change of Frequency df/dt+t
Protection [81R]
Accuracy
Pick-up:
Setting 3% or 10mHz/s, whichever is
greater
Drop-off (falling frequency):
Setting +0.005Hz/s, 10mHz/s
(for settings between 0.01Hz/s and 0.1Hz/s)
Setting +0.05Hz/s, 5% or 55mHz/s,
whichever is greater
(for settings greater than 0.1Hz/s)
Drop-off (rising frequency):
Setting -0.005Hz/s, 10mHz/s
(for settings between 0.01Hz/s and 0.1Hz/s)





P14x Technical Data Sheet 18 P141/2/3/4/5 Software Version 46J
Setting -0.05Hz/s, 5% or 55mHz/s,
whichever is greater
(for settings greater than 0.1Hz/s)
Operating timer:
2% or 50ms whichever is greater
Operating & Reset Time
Operating time*:
<200ms for ramps 2x setting or greater
<300ms for ramps 1.3x setting or greater
Reset time*: <250ms
* Reference conditions: Tested with
df/dt.Av.Cycles setting = 0, for df/dt
settings greater than 0.1Hz/s (positive or
negative, as relevant) and no intentional
time delay.
Advanced Average Rate of Change
of Frequency f+Df/Dt Protection
[81RAV]
Accuracy
Pick-up:
Setting10mHz (frequency threshold)
Setting 0.1Hz/s (Df/Dt threshold)*
Drop-off:
Setting +20mHz, 10mHz (falling frequency)
Setting -20mHz, 10mHz (rising frequency)
Operating timer:
2% or 30ms whichever is greater
* Reference conditions: To maintain
accuracy the minimum time delay setting,
Dt, should be:
Dt > 0.375 x Df + 0.23 (for Df setting < 1Hz)
Dt > 0.156 x Df + 0.47 (for Df setting 1Hz)
Operating Time
Typically <125ms with Freq.Av.Cycles = 0
Advanced Load Restoration
Accuracy
Pick-up: Setting10mHz
Drop-off: Setting -20mHz, 10mHz
Restoration timer:
2% or 50ms whichever is greater
Holding timer:
2% or 50ms whichever is greater
Broken Conductor Logic
Accuracy
Pick-up: Setting 2.5%
Drop-off: 0.95 x Setting 2.5%
DT operation: 2% or 40ms whichever is
greater

Thermal Overload
Accuracy
Thermal alarm pick-up:
Calculated trip time 10%
Thermal overload pick-up:
Calculated trip time 10%
Cooling time accuracy:
15% of theoretical
Repeatability: <5%
* Operating time measured with applied
current of 20% above thermal setting.
Voltage Dependent Overcurrent
Accuracy
VCO / VRO threshold Pick-up:
Setting 5%
Overcurrent Pick-up:
(K factor x Setting) 5%
VCO / VRO threshold Drop-off:
1.05 x Setting 5%
Overcurrent Drop-off:
0.95 x (K factor x Setting) 5%
Operating time:
5% or 60 ms whichever is greater
Repeatability: <5%
Cold Load Pick-up Setting
Accuracy
I> Pick-up: Setting 1.5%
I> Pick-up: Setting 2.5%
IN> Pick-up: Setting 1.5%
I> Drop-off: 0.95 x Setting 1.5%
I> Drop-off: 0.95 x Setting 2.5%
IN> Drop-off: 0.95 x Setting 1.5%
DT operation:
0.5% or 40ms whichever is greater
Repeatability: <1%
Negative Sequence Overvoltage
Protection
Accuracy
Pick-up: Setting 5%
Drop-off: 0.95 x Setting 5%
DT operation: 2% or 50ms whichever is
greater
Repeatability: <5%








P14x Technical Data Sheet 19 P141/2/3/4/5 Software Version 46J
Admittance, Conductance and
Susceptance
Accuracy
YN, BN and BN measurements:
5%
YN, BN, BN Pick-up: Setting 5%
YN, BN, BN Drop-off:
>0.85 x Setting
Operating time:
Start <100ms Trip Setting 2% or 50 ms
Operating boundary: 2
VN: Setting 5%
Selective Overcurrent Protection
Accuracy
Fast block operation: <25ms
Fast block reset: <30ms
Time delay: Setting 2% or 20ms whichever is
greater
Voltage Transformer Supervision
Accuracy
Fast block operation: <25ms
Fast block reset: <30ms
Time delay: Setting 2% or 20ms whichever is
greater
Current Transformer Supervision
Accuracy
In> Pick-up: Setting 5%
VN< Pick-up: Setting 5%
In> Drop-off: 0.9 x Setting 5%
VN< Drop-off: (1.05 x Setting 5% or 1V
whichever is greater
Time delay operation: Setting 2% or 20ms
whichever is greater
CTS block operation: <1 cycle
CTS reset: <35ms
CB fail

Accuracy
I > Pick-up: Setting 5% or 20 mA whichever is
greater
I > Drop-off: 100% of setting 5% or 20 mA
whichever is greater
Timers: 2% or 50 ms whichever is greater
Reset time: <25 ms without DC offset
<35 ms with DC offset

Programmable Scheme Logic
Accuracy
Output conditioner timer: Setting 2% or 50ms
whichever is greater
Dwell conditioner timer: Setting 2% or 50ms
whichever is greater
Pulse conditioner timer: Setting 2% or 50ms
whichever is greater
Measurements and Recording
Facilities
Measurements
Current: 0.05 3In
Accuracy: 1.0% of reading
Voltage: 0.052Vn
Accuracy: 1.0% of reading
Power (W): 0.22Vn 0.053In
Accuracy: 5.0% of reading at unity power
factor
Reactive Power (Vars):
0.22Vn, 0.053In
Accuracy: 5.0% of reading at zero power
factor
Apparent Power (VA): 0.22Vn 0.053In
Accuracy: 5% of reading
Energy (Wh): 0.22Vn 0.23In
Accuracy: 5% of reading at zero power factor
Energy (Varh): 0.22Vn 0.23In
Accuracy: 5% of reading at zero power factor
Phase accuracy: 036
Accuracy: 0.5%
Frequency: 4565Hz
Accuracy: 0.025Hz
Performance
Year 2000: Compliant
Real time clock accuracy: <2% seconds/day
Modulation ratio: 1/3 or 1/6
Input signal peak-peak amplitude:
200mV20V
Input impedance at 1000Hz:
6000
External clock synchronization:
Conforms to IRIG standard 200-98, format B
IRIG-B and Real Time Clock
Accuracy (for modulated and un-modulated
versions)
Real time clock accuracy: < 2 seconds/day







P14x Technical Data Sheet 20 P141/2/3/4/5 Software Version 46J
Disturbance Records
Accuracy
Magnitude and relative phases:
5% of applied quantities
Duration: 2%
Trigger position: 2% (minimum Trigger
100ms)
Line length: 0.011000kn **
Line impedance (100/110V): 0.1/In250/In
Line impedance (380/480V): 0.4/In1000/In
Line angle: 2085
KZN residual: 07.00
KZN res. angle: -90+90
Plant Supervision
Accuracy
Timers: 2% or 20ms whichever is greater
Broken current accuracy: 5%
Timer Accuracy
Timers: 2% or 40ms whichever is greater
Reset time: <30ms
Undercurrent Accuracy
Pick-up: 10% or 25mA whichever is greater
Operating time: <20ms
Reset: <25ms
IEC 61850 Ethernet Data
100 Base FX Interface
Transmitter Optical Characteristics
(TA = 0C to 70C, VCC = 4.75 V to 5.25 V)

Parameter Sym Min. Typ. Max Unit
Output Optical
Power BOL
62.5/125 m, NA
= 0.275 Fiber EOL
PO
-19
-20
-
16.8
-14
dBm
avg.
Output Optical
Power BOL
50/125 m, NA =
0.20 Fiber EOL
PO
-
22.5
-
23.5
-
20.3
-14
dBm
avg.
Optical Extinction
Ratio

10
-10
% dB
Output Optical
Power at
Logic 0 State
PO
(0)
-45
dBm
avg
BOL - Beginning of life
EOL - End of life



Receiver Optical Characteristics
(TA = 0C to 70C, VCC = 4.75 V to 5.25 V)
Parameter Sym Min. Typ. Max. Unit
Input Optical
Power Minimum
at Window Edge
PIN
Min.
(W)
-33.5 -31
dBm
avg.
Input Optical
Power Minimum
at Eye Center
PIN
Min.
(C)
-34.5 -31.8
Bm
avg.
Input Optical
Power Maximum
PIN
Max.
-14 -11.8
dBm
avg.
Note: The 10BaseFL connection will no
longer be supported as IEC 61850
does not specify this interface





















P14x Technical Data Sheet 21 P141/2/3/4/5 Software Version 46J
Settings, Measurements and
Records List
Settings List
Global Settings (System Data)
Language: English/French/German/Spanish
Frequency: 50/60Hz
Circuit Breaker Control
(CB Control)
CB Control by:
Disabled
Local
Remote
Local+Remote
Opto
Opto+local
Opto+Remote
Opto+Rem+local
Close Pulse Time: 0.1050.00s
Trip Pulse Time: 0.105.00s
Man Close t max: 0.019999.00s
Man Close Delay: 0.01600.00s
CB Healthy Time: 0.019999.00s
Check Sync. Time: 0.019999.00s
Reset Lockout by: User Interface/CB Close
Man Close RstDly: 0.10600.00s
CB Status Input:
None
52A
52B
52A & 52B
Date and Time
IRIG-B Sync: Disabled/Enabled
Battery Alarm: Disabled/Enabled
LocalTime Enable: Disabled/Fixed/Flexible
LocalTime Offset: -720 min720min
DST Enable: Disabled/Enabled
DST Offset: 30min60min
DST Start: First/Second/Third/
Fourth/Last
DST Start Day: Sun/Mon/Tues/Wed/
Thurs/Fri/Sat
DST Start Month: Jan/Feb/Mar/Apr/May/
Jun/Jul/Aug/Sept/Oct/
Nov/Dec DST Start
Mins: 0min1425min
DST End: First/Second/Third/
Fourth/Last
DST End Day: Sun/Mon/Tues/Wed/
Thurs/Fri/Sat
DST End Month: Jan/Feb/Mar/Apr/
May/Jun/Jul/Aug/Sept/
Oct/Nov/Dec
DST End Mins: 0min1425min
RP1 Time Zone: UTC/Local
RP2 Time Zone: UTC/Local
Tunnel Time Zone: UTC/Local
Configuration
Setting Group:
Select via Menu
Select via Opto
Active Settings: Group 1/2/3/4
Setting Group 1: Disabled/Enabled
Setting Group 2: Disabled/Enabled
Setting Group 3: Disabled/Enabled
Setting Group 4: Disabled/Enabled
System Config: Invisible/Visible
Overcurrent: Disabled/Enabled
Negative Sequence O/C: Disabled/Enabled
Broken Conductor: Disabled/Enabled
Earth Fault 1: Disabled/Enabled
Earth Fault 2: Disabled/Enabled
SEF/REF
1
Prot: Disabled/Enabled
Residual O/V NVD: Disabled/Enabled
Thermal Overload: Disabled/Enabled
Neg. Sequence O/V: Disabled/Enabled
Cold Load Pick-up: Disabled/Enabled
Selective Logic: Disabled/Enabled
Admit. Protection: Disabled/Enabled
Power Protection: Disabled/Enabled
Volt Protection: Disabled/Enabled
Freq. Protection: Disabled/Enabled
CB Fail: Disabled/Enabled
Supervision: Disabled/Enabled
Fault Locator: Disabled/Enabled
System Checks
2
: Disabled/Enabled
Auto-Reclose
3
: Disabled/Enabled
Input Labels: Invisible/Visible
Output Labels: Invisible/Visible
Adv. Freq. Protn: Disabled/Enabled
CT & VT Ratios: Invisible/Visible
Record Control: Invisible/Visible
Disturb Recorder: Invisible/Visible
Measuret Setup: Invisible/Visible
Comms Settings: Invisible/Visible
Commission Tests: Invisible/Visible
Setting Values: Primary/Secondary
Control Inputs: Invisible/Visible
Ctrl I/P Config: Invisible/Visible
Ctrl I/P Labels: Invisible/Visible
Direct Access: Disabled/Enabled
InterMiCOM: Disabled/Enabled
Function Key
4
: Invisible/Visible
RP1 Read Only: Disabled/Enabled
RP2 Read Only: Disabled/Enabled
NIC Read Only: Disabled/Enabled
LCD Contrast: (Factory pre-set)








P14x Technical Data Sheet 22 P141/2/3/4/5 Software Version 46J
CT and VT Ratios
Main VT Primary: 100V...1MV
Main VT Sec'y: 80...140V
C/S VT Primary
2
: 100V...1MV
C/S VT Secondary: 80...140V
NVD VT Primary
5
: 100V...1MV
NVD VT Secondary: 80...140V
Phase CT Primary: 1A30kA
Phase CT Sec'y: 1A/5A
E/F CT Primary: 1A30kA
E/F CT Sec'y: 1A/5A
SEF CT Primary: 1A30kA
SEF CT Sec'y: 1A/5A
I Derived Phase
5
:
IA
IB
IC
None
C/S Input
2
:
A-N
B-N
C-N
A-B
B-C
C-A
Main VT Location
2
: Line/Bus
Sequence of Event Recorder
(Record Control)
Alarm Event: Disabled/Enabled
Relay O/P Event: Disabled/Enabled
Opto Input Event: Disabled/Enabled
General Event: Disabled/Enabled
Fault Rec. Event: Disabled/Enabled
Maint. Rec. Event: Disabled/Enabled
Protection Event: Disabled/Enabled
DDB 31 - 0: (up to):
DDB 1279 - 1248:
Binary function link strings, selecting which
DDB signals will be stored as events, and
which will be filtered out
Oscillography (Disturb. Recorder)
Duration: 0.1010.50s
Trigger Position: 0.0100.0%
Trigger Mode: Single/Extended
Analog Channel 1: (up to):
Analog Channel 8:
Disturbance channels selected from:
VA/VB/VC/Vchecksync./IA/IB/IC/IN/IN
Sensitive
Digital Input 1: (up to):
Digital Input 32:
Selected binary channel assignment from
any DDB status point within the relay (opto
input, output contact, alarms, starts, trips,
controls, logic).
Input 1 Trigger: No Trigger/Trigger L/H/Trigger
H/L
(up to):
Input 32 Trigger: No Trigger/Trigger L/H/
Trigger H/L
Measured Operating Data
(Measure't. Setup)
Default Display:
3Ph + N Current
3Ph Voltage
Power
Date and Time
Description
Plant Reference
Frequency
Access Level
Local Values: Primary/Secondary
Remote Values: Primary/Secondary
Measurement Ref: VA/VB/VC/IA/IB/IC
Measurement Mode: 0/1/2/3
Fix Dem. Period: 199mins
Roll Sub Period: 199mins
Num. Sub Periods: 115
Distance Unit: Miles/Kilometers
Fault Location:
Distance
Ohms
% of Line
Remote2 Values: Primary/Secondary
Communications
RP1 Protocol:
Courier
IEC870-5-103
DNP 3.0
RP1 Address: (Courier or IEC870-5-103):
0255
RP1 Address: (DNP3.0):
065519
RP1 InactivTimer: 130mins
RP1 Baud Rate: (IEC870-5-103):
9600/19200 bits/s
RP1 Baud Rate: (DNP3.0):
1200 bits/s
2400 bits/s
4800 bits/s
9600 bits/s
19200 bits/s
38400 bits/s
RP1 Parity:
Odd/Even/None
RP1 Meas Period: 160s
RP1 PhysicalLink:
Copper
Fiber Optic (IEC870-5-103, DNP3.0, Courier,
MODBUS)
K-Bus (Courier only)
RP1 Time Sync: Disabled/Enabled
DNP Need Time: 130m
DNP App Fragment: 1002048
DNP App Timeout: 1120
DNP SBO Timeout: 110
DNP Link Timeout: 0120





P14x Technical Data Sheet 23 P141/2/3/4/5 Software Version 46J
RP1 CS103 Blocking:
Disabled
Monitor Blocking
Command Blocking

RP1 Port Config. (Courier):
K Bus
EIA(RS)485
RP1 Comms. Mode:
IEC60870 FT1.2 Frame 10-Bit No Parity
Optional Additional Second Rear
Communication (Rear Port2 (RP2))
RP2 Protocol: Courier (fixed)
RP2 Port Config:
Courier over EIA(RS)232
Courier over EIA(RS)485
K-Bus
RP2 Comms. Mode:
IEC60870 FT1.2 Frame
10-Bit NoParity
RP2 Address: 0255
RP2 InactivTimer: 130mins
RP2 Baud Rate:
9600 bits/s
19200 bits/s
38400 bits/s
Optional Ethernet Port
NIC Tunl Timeout: 1...30mins
NIC Link Report: Alarm/Event/None
NIC Link Timeout: 0.1...60s
Commission Tests
Monitor Bit 1:
(up to):
Monitor Bit 8:
Binary function link strings, selecting which
DDB signals have their status visible in the
Commissioning menu, for test purposes
Test Mode:
Disabled
Test Mode
Blocked Contacts
Test Pattern:
Configuration of which output contacts are to
be energized when the contact test is
applied.
Static Test Mode: Disabled/Enabled
Circuit Breaker Condition
Monitoring (CB Monitor Setup)
Broken I^: 1.02.0
I^ Maintenance: Alarm Disabled/Enabled
I^ Maintenance: 125000
I^ Lockout: Alarm Disabled/Enabled
I^ Lockout: 125000
No. CB Ops Maint: Alarm Disabled/Enabled
No. CB Ops Maint: 110000
No. CB Ops Lock: Alarm Disabled/Enabled
No. CB Ops Lock: 110000
CB Time Maint: Alarm Disabled/Enabled
CB Time Maint: 0.0050.500s
CB Time Lockout: Alarm Disabled/Enabled
CB Time Lockout: 0.0050.500s
Fault Freq. Lock: Alarm Disabled/Enabled
Fault Freq. Count: 19999
Fault Freq. Time: 09999s
Optocoupled Binary Inputs
(Opto Config.)
Global threshold:
24 - 27V
30 - 34V
48 - 54V
110 - 125V
220 - 250V
Custom
Opto Input 1:
(up to):
Opto Input #. (# = max. opto no. fitted):
Custom options allow independent
thresholds to be set per opto, from the same
range as above.
Filter Control:
Binary function link string, selecting which
optos will have an extra 1/2 cycle noise filter,
and which will not.
Characteristics:
Standard 60% - 80%
50% - 70%
Time stamping accuracy: + 1 msec
Control Inputs into PSL
(Ctrl. I/P Config.)
Hotkey Enabled:
Binary function link string, selecting which of
the control inputs will be driven from
Hotkeys.
Control Input 1: Latched/Pulsed
(up to):
Control Input 32: Latched/Pulsed
Ctrl Command 1:
(up to):
Ctrl Command 32:
ON/OFF
SET/RESET
IN/OUT
ENABLED/DISABLED
EIA(RS)232 Teleprotection
(InterMiCOM Comms.)
Source Address: 110
Received Address: 110
Data Rate:
600 Baud
1200 Baud
2400 Baud
4800 Baud
9600 Baud





P14x Technical Data Sheet 24 P141/2/3/4/5 Software Version 46J
19200 Baud
Loopback Mode:
Disabled/Internal/External

Test Pattern:
Configuration of which InterMiCOM signals
are to be energized when the loopback test
is applied.
InterMiCOM Conf.
IM Msg Alarm Lvl: 0100.0%
IM1 Cmd Type: Disabled/Direct/Blocking
(up to):
IM4 Cmd Type: Disabled/Direct/Blocking
IM5 Cmd Type: Disabled/Permissive/Direct
(up to):
IM8 Cmd Type: Disabled/Permissive/Direct
IM1 FallBackMode: Default/Latched
(up to):
IM8 FallBackMode: Default/Latched
IM1 DefaultValue: 0/1
(up to):
IM8 DefaultValue: 0/1
IM1 FrameSyncTim: 10ms1.50s
(up to):
IM8 FrameSyncTim: 10ms1.50s
Function Keys
4

Fn. Key Status 1:
(up to):
Fn. Key Status 10
Disable
Lock
Unlock/Enable
Fn. Key 1 Mode: Toggled/Normal
(up to):
Fn. Key 10 Mode: Toggled/Normal
Fn. Key 1 Label:
(up to):
Fn. Key 10 Label:
User defined text string to describe the
function of the particular function key
IED CONFIGURATOR
Switch Conf. Bank: No Action/Switch Banks
IEC61850 GOOSE
GoEna: Disabled/Enabled
Test Mode: Disabled/Pass Through/Forced
VOP Test Pattern: 0x00000000...
0xFFFFFFFF
Ignore Test Flag: No/Yes
Control Input User Labels
(Ctrl. I/P Labels)
Control Input 1:
(up to):
Control Input 32:
User defined text string to describe the
function of the particular control input
Settings in Multiple Groups
Note: All settings here onwards apply for
setting groups # = 1 to 4.
Protection Functions
System Config.
Phase Sequence:
Standard ABC
Reverse ACB
2NDHARM BLOCKING:
Disabled
Enabled
2ndHarm Thresh: 570
I>lift 2H: 432
Phase Overcurrent (Overcurrent)
I>1 Function:
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
UK Rectifier
RI
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
Def User Curve 1
Def User Curve 2
Def User Curve 3
Def User Curve 4
I>1 Direction:
Non-Directional
Directional Fwd
Directional Rev
I>1 Current Set: 0.084.00 In
I>1 Time Delay: 0.00100.00s
I>1 TMS: 0.0251.200
I>1 Time Dial: 0.01100.00
I>1 K (RI): 0.1010.00
I>1 DT Adder: 0.00100.00
I>1 Reset Char.: DT/Inverse
I>1 tRESET: 0.00100.00s
I>2 Status
(up to):
I>2 tRESET
All settings and options chosen from the
same ranges as per the first stage
overcurrent, I>1.
I>3 Status:
Disabled
Enabled
I>3 Direction:
Non-Directional
Directional Fwd
Directional Rev






P14x Technical Data Sheet 25 P141/2/3/4/5 Software Version 46J
I>3 Current Set: 0.0832.00 In
I>3 Time Delay: 0.00100.00s
I>4 Status
(up to):
I>4 Time Delay
All settings and options chosen from the
same ranges as per the third stage
overcurrent, I>3.
I> Char Angle: -9595
I>5 Status
(up to):
I>5 tRESET
All settings and options chosen from the
same ranges as per the first stage
overcurrent, I>1.
I>6 Status
(up to):
I>6 Time Delay
All settings and options chosen from the
same ranges as per the third stage
overcurrent, I>3.
I> Blocking:
Binary function link string, selecting which
overcurrent elements (stages 1 to 4) will be
blocked if VTS detection of fuse failure
occurs.
Binary function link string, selecting which
overcurrent elements (stages 1 to 4) will be
blocked if 2
nd
Harmonic Block is enabled with
an option of choosing 1PH block.
Voltage Dependent Overcurrent
V DEPENDANT O/C
V Dep OC Status
VCO Disabled
VCO >1
VCO >2
VCO >1 & >2
VCO >5
VCO >1 & >2 & >5
VCO >1 & >5
VC0 >2 & >5
VRO I>1
VRO I>2
VRO I>5
VRO >1 & >2
VRO >1 & >5
VRO >2 & >5
VRO >1 & >2 & I>5
V Dep OC V<1 Set
10120 V (100/120 V)
40480 V (380/440 V)
V Dep OC V<2 Set
10120 V (100/120 V)
40480 V (380/440 V)


Load Blinder
Blinder Status:
Disabled
Enabled
Blinder Function:
3Ph
1Ph
Blinder Mode:
Both
Forward
Reverse
FWD Z Impedance: 0.1100 ohm
FWD Z Angle: 585 deg
REV Z Impedance: 0.1100 ohm
REV Z Angle: 585 deg
Binder V<Block: 10120 V
Binder I2>Block: 0.84 A
PU cycles: 050
DO cycles: 050
Negative Sequence Overcurrent
I2>1 Function:
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
I2>1 Direction:
Non-Directional
Directional Fwd
Directional Rev
I2>1 Current Set: 0.084.00 In
I2>1 Time Delay: 0.00100.00s
I2>1 TMS: 0.0251.200
I2>1 Time Dial: 0.01100.00
I2>1 DT Adder: 0.00100.00
I2>1 Reset Char.: DT/Inverse
I2>1 tRESET: 0.00100.00s
I2>2 Status
(up to):
I2>2 tRESET
All settings and options chosen from the
same ranges as per the first stage
overcurrent, I2>1.
I2>3 Status:
Disabled
Enabled
I2>3 Direction:
Non-Directional
Directional Fwd
Directional Rev
I2>3 Current Set: 0.0832.00 In
I2>3 Time Delay: 0.00100.00s
I2>4 Status







P14x Technical Data Sheet 26 P141/2/3/4/5 Software Version 46J
(up to):
I2>4 Time Delay
All settings and options chosen from the
same ranges as per the third stage
overcurrent, I2>3.

I2> VTS Blocking:
Binary function link string, selecting which
Neg. Seq. O/C elements (stages 1 to 4) will
be blocked if VTS detection of fuse failure
occurs.

Binary function link string, selecting which
Neg. Seq. O/C elements (stages 1 to 4) will
be blocked if 2
nd
Harmonic Block is enabled.
I2> Char Angle: -9595
I2> V2pol Set:
0.525.0 (100 - 110V):
2100 (380 - 480V):
Broken Conductor
Broken Conductor: Disabled/Enabled
I2/I1 Setting: 0.201.00
I2/I1 Time Delay: 0.0100.0s
Ground Overcurrent
(Earth Fault 1 & 2)
IN1>1 Function
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
RI
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
IDG
Def User Curve 1
Def User Curve 2
Def User Curve 3
Def User Curve 4
IN1>1 Directional
Non-Directional
Directional Fwd
Directional Rev
IN1>1 Current Set: 0.084.00 In
IN1>1 IDG Is: 1.04.0 In
IN1>1 Time Delay: 0.00200.00s
IN1>1 TMS: 0.0251.200
IN1>1 Time Dial: 0.01100.00
IN1>1 K(RI): 0.10..10.00
IN1>1 IDG Time: 1.00..2.00
IN1>1 DT Adder: 0.00100.00
IN1>1 Reset Char.: DT/Inverse
IN1>1 tRESET: 0.00100.00s
IN1>2 Status

(up to):
IN1>2 tRESET
All settings and options chosen from the
same ranges as per the first stage ground
overcurrent, IN>1.
IN1>3 Status:
Disabled
Enabled
IN1>3 Directional:
Non-Directional
Directional Fwd
Directional Rev
IN1>3 Current Set: 0.0832.00 In
IN1>3 Time Delay: 0.00200.00s
IN1>4 Status
(up to):
IN1>4 Time Delay
All settings and options chosen from the
same ranges as per the third stage ground
overcurrent, IN>3.
IN1> Blocking:
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4)
will be blocked if VTS detection of fuse
failure occurs.
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4)
will be blocked if 2
nd
Harmonic Block is
enabled.
IN1> Char Angle: -9595
IN1> Polarization:
Zero Sequence
Neg. Sequence
IN1> VNpol Set:
0.580.0V (100 - 110V)
2320V (380 - 480V)
IN1> V2pol Set:
0.525.0V (100 - 110V)
2100V (380 - 480V)
IN1> I2pol Set: 0.081.00 In
Sensitive Earth Fault Protection/
Restricted Earth Fault Protection
SEF/REF Options:
SEF
SEF cos (PHI)
SEF sin (PHI)
Wattmetric
Hi Z REF
Lo Z REF
Lo Z REF + SEF
Lo Z REF + Wattmetric
ISEF>1 Function:
Disabled
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
RI
IEEE M Inverse





P14x Technical Data Sheet 27 P141/2/3/4/5 Software Version 46J
IEEE V Inverse:
IEEE E Inverse
US Inverse
US ST Inverse
IDG
Def User Curve 1
Def User Curve 2
Def User Curve 3
Def User Curve 4
ISEF>1 Directional:
Non-Directional
Directional Fwd
Directional Rev.
ISEF>1 Current Set: 0.0050.01 In
ISEF>1 IDG Is: 1.04.0 In
ISEF>1 Time Delay: 0.00200.00s
ISEF>1 TMS: 0.0251.200
ISEF>1 Time Dial: 0.5100.0
IN1>1 K(RI): 0.10..10.00
ISEF>1 IDG Time: 1.00..2.00
ISEF>1 DT Adder: 0.00100.00
ISEF>1 Reset Char: DT/Inverse
ISEF>1 tRESET: 0.00100.00s
ISEF>2 Status
(up to):
ISEF>2 tRESET
All settings and options chosen from the
same ranges as per the first stage ground
overcurrent, IN>1.
ISEF>3 Status:
Disabled
Enabled
ISEF>3 Directional:
Non-Directional
Directional Fwd
Directional Rev
ISEF>3 Current Set: 0.005.2.000 In
ISEF>3 Time Delay: 0.00200.00s
ISEF>4 Status
(up to):
ISEF>4 Time Delay
All settings and options chosen from the
same ranges as per the third stage ground
overcurrent, IN>3.
ISEF> Blocking:
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4)
will be blocked if VTS detection of fuse
failure occurs.
Binary function link string, selecting which
ground overcurrent elements (stages 1 to 4)
will be blocked if 2
nd
Harmonic Block is
enabled.
ISEF> Char. Angle: -9595
ISEF> VNpol Set:
0.580.0V (100 - 110V)
2320V (380 - 480V)
WATTMETRIC SEF:
PN> Setting: 020W (1A, 100/120V)
PN> Setting: 0100W (5A, 100/120V)
PN> Setting: 0 80W (1A, 380/440V)
PN> Setting: 0400W (5A, 380/440V)
RESTRICTED EARTH-FAULT
(Low Impedance)
IREF > K1: 0 20%
IREF > K2: 0 150%
IREF > Is1: 0.081.00 In
IREF > Is2: 0.11.50 In
(High Impedance)
IREF > K1: 0.051.00 In
Neutral Voltage Displacement
(Residual O/V NVD)
VN>1 Function:
Disabled
DT
IDMT
VN>1 Voltage Set: 150V
VN>1 Time Delay: 0.00100.00s
VN>1 TMS: 0.5100.0
VN>1 tReset: 0.00100.00s
VN>2 Status: Disabled/Enabled
VN>2 Voltage Set:
180V (100/110V)
4320V (380/440V)
VN>2 Time Delay: 0.00100.00s
Thermal Overload
Characteristic:
Disabled
Single
Dual
Thermal Trip: 0.084.00 In
Thermal Alarm: 50100%
Time Constant 1: 1200mins
Time Constant 2: 1200mins
Negative Sequence Overvoltage
Protection
V2> Status: Disabled/Enabled
V2> Voltage Set:
1V110V (100/120V)
4V - 440V (380/440V)
V2> Time Delay: 0.00100.00s
Cold Load Pick-up Setting
tcold Time Delay: 014 400s
tclp Time Delay: 014 400s
Overcurrent
I>1 Status: Block/Enabled
I>1 Current Set: 0.084.00 In
I>1 Time delay: 0.00100.00s
I>1 TMS: 0.025.2.000
I>1 Time Dial: 0.515.0
I>2 Status
(up to):
I>2 Time Dial
All settings and options chosen from the
same ranges as per the 1st stage.
I>3 Status: Block/Enabled
I>3 Current Set: 0.0832.00 In
3 Time delay: 0.00100.00s





P14x Technical Data Sheet 28 P141/2/3/4/5 Software Version 46J
I>4 Status
(up to):
I>4 Time Delay
All settings and options chosen from the
same ranges as per the 1st stage.
E/F1
IN1>1 Status: Block/Enabled
IN1>1 Current Set: 0.084.00 In
IN1>1 IDG Is: 1.04.0 In
IN1>1 Time Delay: 0.00200.00s
IN1>1 TMS: 0.025.2.000
IN1>1 Time Dial: 0.515.0
IN1>1 K(RI): 0.10..10.00
IN1>2 Status
(up to):
IN2> 1 K(RI)
All settings and options chosen from the
same ranges as per the E/F1 stage.
I>5 Status
(up to):
I>5 Time Dial
All settings and options chosen from the
same ranges as per the 1st stage.
I>6 Status
(up to):
I>6 Time Delay
All settings and options chosen from the
same ranges as per the 3rd stage.
Selective Overcurrent Logic
Overcurrent
I>3 Time Delay: 0.00100.00s
I>4 Time Delay: 0.00100.00s
Earth Fault1
IN1>3 Time Delay: 0.00200.00s
IN1>4 Time Delay: 0.00200.00s
Earth Fault2
IN2>3 Time Delay: 0.00200.00s
IN2>4 Time Delay: 0.00200.00s
Sensitive E/F
ISEF>3 Time Delay: 0.00200.00s
ISEF>4 Time Delay: 0.00200.00s
Overcurrent
I>6 Time Delay: 0.00100.00s
Neutral Admittance Protection
VN Threshold:
140V (100/120V)
4160V (380/440V)
CT Input Type: SEF CT/E/F CT
Correction angle: 3030o
Overadmittance
YN Status: Disabled/Enabled
YN> Set (SEF):
0.110mS (100/110V)
0.0252.5mS (380/440V)
YN> Set (EF):
1100mS (100/110V)
0.2525mS (380/440V)
YN> Time Delay: 0.05s100.00s
YN> tRESET: 0.00100.00s
Over Conductance
GN Status: Disabled/Enabled
GN>Direction
Non-Directional
Directional Fwd
Directional Rev.
GN> Set (SEF):
0.15mS (100/110V)
0.251.25mS (380/440V)
GN> Set (E/F):
150mS (100/110V)
0.2512.5mS (380/440V)
GN> Time Delay: 0.05s100s
GN>tRESET: 0s100s
Over Susceptance
BN Status: Disabled/Enabled
GN>Direction
Non-Directional
Directional Fwd
Directional Rev.
BN> Set (SEF)
0.15mS (100/110V)
0.0251.25mS (380/440V))
BN> Set (E/F):
150mS (100/110V)
0.2512.5mS (380/440V)
BN> Time Delay: 0.05100s
BN> tRESET: 0s100s
Undervoltage Protection
V< Measur't. Mode:
Phase-Phase
Phase-Neutral
V< Operate Mode:
Any Phase
Three Phase
V<1 Function:
Disabled
DT
IDMT
V<1 Voltage Set:
10120V (100/110V)
40480V (380/440V)
V<1 Time Delay: 0.00100.00s
V<1 TMS: 0.5100.0
V<1 Poledead Inh: Disabled/Enabled
V<2 Status: Disabled/Enabled
V<2 Voltage Set:
10120V (100/110V)
40480V (380/440V)
V<2 Time Delay: 0.00100.00s
V<2 Poledead Inh: Disabled/Enabled
Overvoltage Protection
V> Measur't. Mode:
Phase-Phase
Phase-Neutral
V> Operate Mode:
Any Phase
Three Phase
V>1 Function:
Disabled
DT





P14x Technical Data Sheet 29 P141/2/3/4/5 Software Version 46J
IDMT
V>1 Voltage Set:
60185V (100/110V)
240740V (380/440V)
V>1 Time Delay: 0.00100.00s
V>1 TMS: 0.5100.0
V>2 Status: Disabled/Enabled
V>2 Voltage Set:
60185V (100/110V)
240740V (380/440V)
V>2 Time Delay: 0.00100.00s
dv/dt Protection
dv/dt Meas. Mode:
Phase-Phase
Phase-Neutral
dv/dt1 Function:
Disabled
Negative
Positive
Both
dv/dt1 Oper Mode:
Any Phase
Three Phase
dv/dt1 AvgCycles: 550
dv/dt1 Threshold: 0.5200
dv/dt1 TimeDelay: 0100s
dv/dt1 tRESET: 0100s
dv/dt2 Function:
Disabled
Negative
Positive
Both
dv/dt2 Oper Mode:
Any Phase
Three Phase
dv/dt2 AvgCycles: 550
dv/dt2 Threshold: 0.5200
dv/dt2 TimeDelay: 0100s
dv/dt2 tRESET: 0100s
Under-Frequency Protection
F<1 Status: Disabled/Enabled
F<1 Setting: 45.0065.00Hz
F<1 Time Delay: 0.00100.00s
F<2 Status
(up to):
F<4 Time Delay
All settings and options chosen from the
same ranges as per the 1st stage.
F> Blocking:
Binary function link string, selecting which
frequency elements (stages 1 to 4) will be
blocked by the pole-dead logic.
Over-Frequency Protection
F>1 Status: Disabled/Enabled
F>1 Setting: 45.0065.00Hz
F>1 Time Delay: 0.00100.00s
F<2 Status

(up to):
F<2 Time Delay
All settings and options chosen from the
same ranges as per the 1st stage.
Advanced Over/Under Frequency
Protection (f+t [81U/81O])
Stage 1 f+t Status:
Disabled
Enabled
1 (f+t) f: 40.1069.90Hz
1 (f+t) t: 0.00100.00s
Stage 2 f+t Status
(up to):
9 (f+t)t
All settings and options chosen from the
same ranges as per the first stage
over/underfrequency, Stage 1 f+t.
Advanced Frequency Supervised
Rate of Change of Frequency
Protection
(f+df/dt [81RF]
Stage 1 f+df/dt Status:
Disabled
Enabled
1 (f+df/dt) f: 40.1069.90Hz
1 (f+df/dt) df/dt:
0.0110.0Hz/s
Stage 2 f+df/dt Status
(up to):
9 (f+df/dt) df/dt
All settings and options chosen from the
same ranges as per the first stage
frequency supervized rate of change of
frequency, Stage 1 f+df/dt.
Advanced Independent Rate of
Change of Frequency Protection
(df/dt+t [81R])
Stage 1 df/dt+t Status:
Disabled
Negative
Positive
1 (df/dt+t) df/dt: 0.0110.00Hz/s
1 (df/dt+t) t: 0.00100.00 s
Stage 2 df/dt+t Status
(up to):
9 (df/dt+t) t
All settings and options chosen from the
same ranges as per the first stage
independent rate of change of
frequency, Stage 1 df/dt+t.







P14x Technical Data Sheet 30 P141/2/3/4/5 Software Version 46J
Advanced Average Rate of Change
of Frequency Protection
(f+Df/Dt [81RAV])
Stage 1 f+Df/Dt Status:
Disabled
Enabled
1 (f+Df/Dt) f: 40.1069.90Hz
1 (f+Df/Dt) Df: 0.210.0Hz
1 (f+Df/Dt) Dt: 0.022.00 s
Stage 2 f+Df/Dt Status
(up to):
9 (f+Df/Dt) Dt
All settings and options chosen from the
same ranges as per the first stage average
rate of change of frequency, Stage 1 f+Df/Dt.
Advanced Load Restoration
Restore1 Status:
Disabled
Enabled
Restore1 Freq.: 40.1069.90Hz
Restore1 Time: 07200s
Restore2 Status
(up to):
Restore9 Time
All settings and options chosen from the
same ranges as per the first stage load
restoration, Restore1.
Circuit Breaker Fail
CB Fail 1 Status: Disabled/Enabled
CB Fail 1 Timer: 0.0010.00s
CB Fail 2 Status: Disabled/Enabled
CB Fail 2 Timer: 0.0010.00s
Volt Prot. Reset:
I< Only
CB Open & I<
Prot. Reset & I<
Ext Prot. Reset:
I< Only
CB Open & I<
Prot. Reset & I<
Undercurrent
I< Current Set: 0.023.20 In
IN< Current Set: 0.023.20 In
ISEF< Current Set: 0.0010.800 In
BLOCKED O/C
Remove I> Start: Disabled/Enabled
Remove IN> Start: Disabled/Enabled
Fuse Failure (VT Supervision)
VTS Status:
Blocking/Indication
VTS Reset Mode: Manual/Auto
VTS Time Delay: 1.010.0s
VTS I> Inhibit: 0.0832.00 In
VTS I2> Inhibit: 0.050.50 In
CT Supervision
CTS Status: Disabled/Enabled
CTS VN< Inhibit:
0.522.0V (100/110V)
288V (380/440V)
CTS IN> Set: 0.084.00 In
CTS Time Delay: 010s
VTS PickupThresh: 20120V
Fault Locator
Line Length (km): 0.0011000.000km
Line Length (mi): 0.20625.00mi
Line Impedance: 0.10250.00
Line Angle: 2085
KZN Residual: 0.007.00
KZN Res. Angle: -9090
Bus-Line Synchronizm and Voltage
Checks (System Checks)
VOLTAGE MONITORS
Live Voltage:
1.0132.0V (100/110V)
22528V (380/440V)
Dead Voltage:
1.0132.0V (100/110V)
22528V (380/440V)
Synchrocheck (Check Sync.)
CS1 Status: Disabled/Enabled
CS1 Phase Angle: 590 o
CS1 Slip Control:
None
Timer
Frequency
Both
CS1 Slip Freq.: 0.011.00Hz
CS1 Slip Timer: 0.099.0s
CS2 Status
(up to):
CS2 Slip Timer
All settings and options chosen from the
same ranges as per the first stage CS1
element.
CS Undervoltage:
10.0132.0V (100/110V)
40528V (380/440V)
CS Overvoltage:
40.0185.0V (100/110V)
160740V (380/440V)
CS Diff Voltage:
1.0132.0V (100/110V)
4528V (380/440V)
CS Voltage Block:
None
Undervoltage
Overvoltage
Differential
UV & OV
UV & DiffV
OV & DiffV
UV, OV & DiffV





P14x Technical Data Sheet 31 P141/2/3/4/5 Software Version 46J
System Split
SS Status: Disabled/Enabled
SS Phase Angle: 90175
SS Under V Block: Disabled/Enabled
SS Undervoltage:
10.0132.0V (100/110V)
40528V (380/440V)
SS Timer: 0.099.0s
CB Close Time: 0.0000.500s
Auto-reclose
AR Mode Select:
Command Mode
Opto Set Mode
User Set Mode
Pulse Set Mode
Number of Shots: 14
Number of SEF Shots: 04
Sequence Co-ord.: Disabled/Enabled
CS AR Immediate: Disabled/Enabled
Dead Time 1: 0.01300.00s
Dead Time 2: 0.01300.00s
Dead Time 3: 0.019999.00s
Dead Time 4: 0.019999.00s
CB Healthy Time: 0.01s9999.00s
Start Dead on:
Protection Resets/CB Trips
Reclaim Extend:
No Operation/On Prot. Start
Reclaim Time 1: 1.00600.00s
Reclaim Time 2: 1.00600.00s
Reclaim Time 3: 1.00600.00s
Reclaim Time 4: 1.00600.00s
AR Inhibit Time: 0.01600.00s
AR Lockout: No Block/Block Inst. Prot.
EFF Maint. Lock:
No Block/Block Inst. Prot.
AR Deselected:
No Block/Block Inst. Prot.
Manual close:
No Block/Block Inst. Prot.
Trip 1 Main: No Block/Block Inst. Prot.
Trip 2 Main: No Block/Block Inst. Prot.
Trip 3 Main: No Block/Block Inst. Prot.
Trip 4 Main: No Block/Block Inst. Prot.
Trip 5 Main: No Block/Block Inst. Prot.
Trip 1 SEF: No Block/Block Inst. Prot.
Trip 2 SEF: No Block/Block Inst. Prot.
Trip 3 SEF: No Block/Block Inst. Prot.
Trip 4 SEF: No Block/Block Inst. Prot.
Trip 5 SEF: No Block/Block Inst. Prot.
Man. Close on Flt.:
No Lockout/Lockout
Trip AR Inactive:
No Lockout/Lockout
Reset Lockout by:
User Interface/Select Non-Auto
AR on Man. Close: Enabled/Inhibited
Sys. Check Time: 0.019999.00s
AR Skip Shot 1: Enabled/disabled
AR INITIATION
I>1, I>2: No Action/Initiate Main AR
I>3 and I>4:
No Action/Initiate Main AR/Block AR
IN1>1 and IN1>2: No Action/Main AR
IN1>3 and IN1>4:
No Action/Initiate Main AR/Block AR
IN2>1, IN2>2: No Action/Initiate Main AR
IN2>3 and IN2>4:
No Action/Initiate Main AR/Block AR
ISEF>1, ISEF>2, ISEF>3 and ISEF>4:
No Action/Initiate Main AR/Initiate SEF AR/
Block AR
YN/GN/ BN>: No Action/Initiate Main AR
Ext. Prot.: No Action/Initiate Main AR
SYSTEM CHECKS
AR with ChkSync.: Disabled/Enabled
AR with SysSync.: Disabled/ Enabled
Live/Dead Ccts: Disabled/Enabled
No System Checks:
Enabled/Disabled
SysChk on Shot 1: Disabled/ Enabled
I>5: No Action/Initiate Main AR
I>6: No Action/Initiate Main AR/Block AR
Opto Input Labels
Opto Input 1:
(up to):
Opto Input 24:
User defined text string to describe the
function of the particular opto input.
Output Labels
Relay 1:
(up to):
Relay 32:
User defined text string to describe the
function of the particular relay output contact.

















P14x Technical Data Sheet 32 P141/2/3/4/5 Software Version 46J
Measurements List
Measurements 1
I Magnitude
I Phase Angle
Per phase ( = A, B, C) current
measurements
IN Measured Mag.
IN Measured Ang.
IN Derived Mag.
IN Derived Angle
ISEF Magnitude
ISEF Angle
I1 Magnitude
I2 Magnitude
I0 Magnitude
I RMS
Per phase ( = A, B, C) RMS current
measurements
V- Magnitude
V- Phase Angle
V Magnitude
V Phase Angle
All phase-phase and phase-neutral voltages
( = A, B. C)
VN Derived Mag.
VN Derived Ang.
V1 Magnitude.
V2 Magnitude
V0 Magnitude
V RMS
All phase-neutral voltages ( = A, B, C)
Frequency
C/S Voltage Mag.
C/S Voltage Ang.
C/S Bus-line Ang.
Slip Frequency
IM Magnitude
IM Phase Angle
I1 Magnitude
I1 Phase Angle
I2 Magnitude
I2 Phase Angle
I0 Magnitude
I0 Phase Angle
V1 Magnitude
V1 Phase Angle
V2 Magnitude
V2 Phase Angle
V0 Magnitude
V0 Phase Angle
Measurements 2
Phase Watts
Phase VArs
Phase VA
All phase segregated power
measurements, real, reactive and apparent
( = A, B, C)

3 Phase Watts
3 Phase VArs
3 Phase VA
Zero Seq. Power
3Ph Power Factor
Ph Power Factor
Independent power factor measurements
for all three phases ( = A, B, C).
3Ph WHours Fwd
3Ph WHours Rev.
3Ph VArHours Fwd
3Ph VArHours Rev.
3Ph W Fix Demand
3Ph VArs Fix Dem.
I Fixed Demand
Maximum demand currents measured on a
per phase basis ( = A, B, C).
3Ph W Roll Dem.
3Ph VArs Roll Dem.
I Roll Demand
Maximum demand currents measured on a
per phase basis ( = A, B, C).
3Ph W Peak Dem.
3Ph VAr Peak Dem.
I Peak Demand
Maximum demand currents measured on a
per phase basis ( = A, B, C).
Reset Demand: Yes/No
Measurements 3
Highest Phase I
Thermal State
Reset Thermal
IREF Diff.
IREF Bias
Admittance
Conductance
Susceptance
Admittance
Conductance
Susceptance
I2/I1 Ratio
SEF Power
IA 2nd Harmonic
IB 2nd Harmonic
IC 2nd Harmonic
APh Sen Watts
APh Sen Vars
APh Power Angle
Z1 Imp Mag
Z1 Imp Ang
Phase A Imp Mag
Phase A Imp Ang
Phase B Imp Mag
Phase B Imp Ang
Phase C Imp Mag
Phase C Imp Ang







P14x Technical Data Sheet 33 P141/2/3/4/5 Software Version 46J
Stage Statistics (Advanced)
StgX f+t Sta
StgX f+t Trip
StgX f+df/dt Trp
StgX df/dt+t Sta
StgX df/dt+t Trp
StgX f+Df/Dt Sta
StgX f+Df/Dt Trp
StgX Revn Date
(X = 1, 2, 3, 4, 5, 6, 7, 8, 9)
Circuit Breaker Monitoring Statistics
CB Operations
CB Operations
Circuit breaker operation counters on a per
phase basis ( = A, B, C).
Total I Broken
Cumulative breaker interruption duty on a
per phase basis ( = A, B, C).
CB Operate Time
CB CONTROL
Total Re-closures
Fault Record Proforma
The following data is recorded for any
relevant elements that operated during a
fault, and can be viewed in each fault record.
Time & Date
Event Text
Event Value
Select Fault: [0...n]
Started Phase: A/B/C
Tripped Phase: A/B/C
Overcurrent
Start I> 123456
Trip I> 123456
Neg. Seq. O/C
Start I2> 1234
Trip I2> 1234
Broken ConductorTrip
Earth Fault 1
Start IN1> 1234
Trip IN1> 1234
Earth Fault 2
Start IN2> 1234
Trip IN2> 1234
Sensitive E/F
Start ISEF> 1234
Trip ISEF> 1234
Restricted E/F
Trip IREF>
Residual O/V NVD
Start VN> 1 2
Trip VN> 1 2
Thermal Overload: Alarm/Trip
Neg. Seq. O/V
V2> Start Trip
U/Voltage Start
V< 1 2 AB BC CA
U/Voltage Trip
V< 1 2 AB BC CA
O/Voltage Start
V> 1 2 AB BC CA
O/Voltage Trip
V> 1 2 AB BC CA
Underfrequency
Start F< 1234
Trip F< 1234
Overfrequency
Start F> 1 2
Trip F> 1 2
Overadmittance
YN> Start Trip
Overconductance
GN> Start Trip
Oversusceptance
BN> Start Trip
Breaker Fail:
CB Fail 1 2
Supervision
VTS/CTS/VCO/CLP
A/R State: Trip 1/2/3/4/5
Advanced Freq. Protection
Start >123456789
Advanced Freq. Protection
Trip >123456789
Adv. F+df/dt Protection
Trip >123456789
Adv. df/dt Protection
Start >123456789
Adv. df/dt Protection
Trip >123456789
Adv. DelF/DelT Protection
Start >123456789
Adv. DelF/DelT Protection
Trip >123456789
Faulted Phase: A/B/C
Start Elements:
Trip Elements:
Binary data strings for fast polling of which
protection elements started or tripped for the
fault recorded.
Fault Alarms:
Binary data strings for fast polling of alarms
for the fault recorded.
Fault Time:
Active Group: 1/2/3/4
System Frequency: Hz
Fault Duration: s
CB Operate Time: s
Relay Trip Time: s
Fault Location: km/miles//%
The current magnitudes and phase angles
stored before the fault inception.
I
V:
Per phase record of the current and voltage
magnitudes during the fault.
IN Measured
IN Derived
IN Sensitive
IREF Diff.
IREF Bias
VAN





P14x Technical Data Sheet 34 P141/2/3/4/5 Software Version 46J
VBN
VCN
VN Derived
Admittance
Conductance
Susceptance





P14x Technical Data Sheet 35 P141/2/3/4/5 Software Version 46J
P14x CASE DIMENSIONS

Figure 1: P141/P142 Case dimensions





P14x Technical Data Sheet 36 P141/2/3/4/5 Software Version 46J
P1616ENi

Figure 2: P143/P145 Case dimensions

Figure 3: P143 with 32I + 32O Case dimensions





P14x Technical Data Sheet 37 P141/2/3/4/5 Software Version 46J
P14x 2nd Rear Communication Board Connection Diagram
P1727ENb

Figure 4: P14x second rear port connection





P14x Technical Data Sheet 38 P141/2/3/4/5 Software Version 46J
External Connection Diagrams
P2140ena

Figure 5: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
(8 I/P & 7 O/P)





P14x Technical Data Sheet 39 P141/2/3/4/5 Software Version 46J
P2141ena

Figure 6: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with High Impedance Restricted Earth Fault (8 I/P & 7 O/P)





P14x Technical Data Sheet 40 P141/2/3/4/5 Software Version 46J
P2142ena

Figure 7: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Low Impedance Restricted Earth Fault (8 I/P & 7 O/P)





P14x Technical Data Sheet 41 P141/2/3/4/5 Software Version 46J
P2143ena

Figure 8: P141 Feeder Management Relay - Directional and Directional Earth Fault with VEE
Connected VT (8 I/P & 7 O/P)





P14x Technical Data Sheet 42 P141/2/3/4/5 Software Version 46J
P4609ENa

Figure 9: P141 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
(8 I/P & 8 O/P)






P14x Technical Data Sheet 43 P141/2/3/4/5 Software Version 46J
P2144ena

Figure 10: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (8 I/P & 7 O/P)





P14x Technical Data Sheet 44 P141/2/3/4/5 Software Version 46J

Figure 11: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (8 I/P & 11 O/P with 4 High Break Contacts)





P14x Technical Data Sheet 45 P141/2/3/4/5 Software Version 46J
P2145ena

Figure 12: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (12 I/P & 11 O/P)





P14x Technical Data Sheet 46 P141/2/3/4/5 Software Version 46J
P2146ena

Figure 13: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (16 I/P & 7 O/P)





P14x Technical Data Sheet 47 P141/2/3/4/5 Software Version 46J
P2147ena

Figure 14: P142 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose (8 I/P & 15 O/P)





P14x Technical Data Sheet 48 P141/2/3/4/5 Software Version 46J
P2148ena

Figure 15: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 14 O/P)





P14x Technical Data Sheet 49 P141/2/3/4/5 Software Version 46J
P2270ENa

Figure 16: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 18 O/P with 4 High Break
Outputs)





P14x Technical Data Sheet 50 P141/2/3/4/5 Software Version 46J
P2151ena

Figure 17: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 22 O/P)





P14x Technical Data Sheet 51 P141/2/3/4/5 Software Version 46J
P2271ENa

Figure 18: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 22 O/P with 8 High Break
Contacts)





P14x Technical Data Sheet 52 P141/2/3/4/5 Software Version 46J
P2272ENa

Figure 19: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 26 O/P with 4 High Break
Contacts)





P14x Technical Data Sheet 53 P141/2/3/4/5 Software Version 46J
P2154ena

Figure 20: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 30 O/P)





P14x Technical Data Sheet 54 P141/2/3/4/5 Software Version 46J
P2149ena

Figure 21: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 14 O/P)





P14x Technical Data Sheet 55 P141/2/3/4/5 Software Version 46J
P2273ENa

Figure 22: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 22 O/P)






P14x Technical Data Sheet 56 P141/2/3/4/5 Software Version 46J

Figure 23: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-Reclose and Check Synchronizing (32 I/P & 32 O/P)




P14x Technical Data Sheet 57 P141/2/3/4/5 Software Version 46J
P2153ena

Figure 24: P143 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (32 I/P & 14 O/P)





P14x Technical Data Sheet 58 P141/2/3/4/5 Software Version 46J

Figure 25: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (8 I/P & 7 O/P)




P14x Technical Data Sheet 59 P141/2/3/4/5 Software Version 46J

Figure 26: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (8 I/P & 11 O/P with 4 High
Break Contacts)





P14x Technical Data Sheet 60 P141/2/3/4/5 Software Version 46J

Figure 27: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (8 I/P & 15 O/P)




P14x Technical Data Sheet 61 P141/2/3/4/5 Software Version 46J

Figure 28: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (12 I/P & 11 O/P)





P14x Technical Data Sheet 62 P141/2/3/4/5 Software Version 46J

Figure 29: P144 Feeder Management Relay - Directional Phase Overcurrent and Earth Fault
with Auto-reclose and Separate Residual Voltage Input (16 I/P & 7 O/P)




P14x Technical Data Sheet 63 P141/2/3/4/5 Software Version 46J
P1608ENa

E
N
S
U
R
E

C
O
R
R
E
C
T

O
P
E
R
A
T
I
O
N

O
F

T
H
E

P
R
O
T
E
C
T
I
V
E

R
E
L
A
Y
.
5
.


F
O
R

C
O
M
M
S

O
P
T
I
O
N
S

S
E
E

D
R
A
W
I
N
G

1
0
P
x
4
0
0
1
.
4
.


O
P
T
O

I
N
P
U
T
S

1

A
N
D

2

M
U
S
T

B
E

U
S
E
D

F
O
R

S
E
T
T
I
N
G

G
R
O
U
P
C
H
A
N
G
E
S

I
F

T
H
I
S

O
P
T
I
O
N

I
S

S
E
L
E
C
T
E
D

I
N

T
H
E

R
E
L
A
Y

M
E
N
U
.
3
.


T
H
I
S

R
E
L
A
Y

S
H
O
U
L
D

B
E

A
S
S
I
G
N
E
D

T
O

A
N
Y

T
R
I
P

T
O
2
.


C
.
T
.

C
O
N
N
E
C
T
I
O
N
S

A
R
E

S
H
O
W
N

1
A

C
O
N
N
E
C
T
E
D

A
N
D

A
R
E

T
Y
P
I
C
A
L

O
N
L
Y
.
P
I
N

T
E
R
M
I
N
A
L

(
P
.
C
.
B
.

T
Y
P
E
)
N
O
T
E
S

1
.
C
.
T
.

S
H
O
R
T
I
N
G

L
I
N
K
S
(
b
)
(
a
)
N
O
T
E

5
.
A
C

O
R

D
C
A
U
X

S
U
P
P
L
Y
4
8
V

D
C

F
I
E
L
D

V
O
L
T
A
G
E

O
U
T
x
J
2
J
8
J
7
J
9
J
1
0
- - + + +
J
1
S
C
N
J
1
6
J
1
8
J
1
7
K
B
U
S
P
O
R
T
-
+
E
I
A
4
8
5
/
-
*
S
E
E

D
R
A
W
I
N
G
1
0
P
x
4
0
0
1
.
E
A
R
T
H
C
A
S
E
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
C
O
M
M
S
O
P
T
O

1
2
O
P
T
O

1
1
F
8
F
7
F
6
F
5
P
H
A
S
E
R
O
T
A
T
I
O
N
A
C
B
O
P
T
O

1
0
O
P
T
O

9
F
4
F
3
F
2
F
1
R
E
L
A
Y

8
N
C
2
2
C B
C
2
1
C
2
0
D
1
6
D
1
8
D
1
7
D
1
4
D
1
5
D
1
3
D
1
2
N
O
T
E

2
.
S
1
D
I
R
E
C
T
I
O
N

O
F

F
O
R
W
A
R
D

C
U
R
R
E
N
T

F
L
O
W
a
c
b
n N
A
C
B
S
2
S
2
S
1
P
2
P
1
P
2
1
A
5
A
1
A
5
A
C
2
3
C
4
1
A
5
A
1
A
5
A
1
A
5
A
S
E
N
S
I
T
I
V
EA
N
N
C
1
9
C
1
5
C
1
2
C
1
3
C B
C
1
0
C
9
C
6
C
7
D
1
1
D
1
0
D
9
D
8
D
7
D
6
D
5
D
4
D
3
D
2
D
1
C
2
4
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
A
C
3
C
1
P
1
O
P
T
O

6
O
P
T
O

8
C
O
N
N
E
C
T
I
O
N
C
O
M
M
O
N
+
O
P
T
O

7
- + - +
c
a
b
O
P
T
O

5
O
P
T
O

4
- + - +
O
P
T
O

3
O
P
T
O
2
- + +-
N
O
T
E

4
.
O
P
T
O

1
+- -
V

C
H
E
C
K
S
Y
N
C
X
A
X X
A
B
n N C
C B
H
1
4
H
1
6
H
1
8
H
1
7
H
1
5
R
E
L
A
Y

7
R
E
L
A
Y

6
H
1
2
H
1
3
H
1
1
H
1
0
H
9
H
8
H
7
H
6
R
E
L
A
Y

5
R
E
L
A
Y

3


A
N
Y

T
R
I
P
R
E
L
A
Y

4
N
O
T
E

3
.
H
1
H
3
H
5
H
4
H
2
R
E
L
A
Y

2
R
E
L
A
Y

1
R
E
L
A
Y

9
F
1
0
F
1
1
F
1
3
F
1
2
F
1
5
F
1
7
F
1
8
F
1
6
F
1
4
R
E
L
A
Y

1
1
R
E
L
A
Y

1
2
R
E
L
A
Y

1
0
F
9
J
1
3
J
1
4
J
1
2
J
1
1
W
A
T
C
H
D
O
G
W
A
T
C
H
D
O
G
C
O
N
T
A
C
T
C
O
N
T
A
C
T
P
O
W
E
R

S
U
P
P
L
Y

V
E
R
S
I
O
N

2
4
-
4
8
V

(
N
O
M
I
N
A
L
)

D
.
C
.

O
N
L
Y
*

Figure 30: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (12 I/P & 12 O/P)





P14x Technical Data Sheet 64 P141/2/3/4/5 Software Version 46J
P1607ENa

C
O
R
R
E
C
T

O
P
E
R
A
T
I
O
N

O
F

T
H
E

P
R
O
T
E
C
T
I
V
E

R
E
L
A
Y
.
5
.


F
O
R

C
O
M
M
S

O
P
T
I
O
N
S

S
E
E

D
R
A
W
I
N
G

1
0
P
x
4
0
0
1
.
4
.


O
P
T
O

I
N
P
U
T
S

1

A
N
D

2

M
U
S
T

B
E

U
S
E
D

F
O
R

S
E
T
T
I
N
G

G
R
O
U
P
C
H
A
N
G
E
S

I
F

T
H
I
S

O
P
T
I
O
N

I
S

S
E
L
E
C
T
E
D

I
N

T
H
E

R
E
L
A
Y

M
E
N
U
.
3
.


T
H
I
S

R
E
L
A
Y

S
H
O
U
L
D

B
E

A
S
S
I
G
N
E
D

T
O

A
N
Y

T
R
I
P

T
O

E
N
S
U
R
E
2
.


C
.
T
.

C
O
N
N
E
C
T
I
O
N
S

A
R
E

S
H
O
W
N

1
A

C
O
N
N
E
C
T
E
D

A
N
D

A
R
E

T
Y
P
I
C
A
L

O
N
L
Y
.
P
I
N

T
E
R
M
I
N
A
L

(
P
.
C
.
B
.

T
Y
P
E
)
N
O
T
E
S

1
.
C
.
T
.

S
H
O
R
T
I
N
G

L
I
N
K
S
(
b
)
(
a
)
N
C
2
2
C B
C
2
1
C
2
0
D
1
6
D
1
8
D
1
7
D
1
4
D
1
5
D
1
3
D
1
2
N
O
T
E

2
.
S
1
D
I
R
E
C
T
I
O
N

O
F

F
O
R
W
A
R
D

C
U
R
R
E
N
T

F
L
O
W
a
c
b
n N
A
C
B
S
2
S
2
S
1
P
2
P
1
P
2
1
A
5
A
1
A
5
A
C
2
3
C
4
1
A
5
A
1
A
5
A
1
A
5
A
S
E
N
S
I
T
I
V
EA
N
N
C
1
9
C
1
5
C
1
2
C
1
3
C
1
1
C B
C
1
0
C
9
C
8
C
5
C
6
C
7
D
1
1
D
1
0
D
9
D
8
D
7
D
6
D
5
D
4
D
3
D
2
D
1
C
2
4
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
A
C
3
C
2
C
1
P
1
N
O
T
E

5
.
G
4
O
P
T
O

6
A
C

O
R

D
C
A
U
X

S
U
P
P
L
Y
4
8
V

D
C

F
I
E
L
D

V
O
L
T
A
G
E

O
U
T
x
O
P
T
O

8
C
O
N
N
E
C
T
I
O
N
C
O
M
M
O
N
+
O
P
T
O

7
- + - +
J
2
J
8
J
7
J
9
J
1
0
- - + + +
J
1
S
C
N
J
1
6
J
1
8
J
1
7
K
B
U
S
P
O
R
T
-
+
E
I
A
4
8
5
/
-
*
S
E
E

D
R
A
W
I
N
G
1
0
P
x
4
0
0
1
.
G
1
5
G
1
8
G
1
7
G
1
6
E
A
R
T
H
C
A
S
E
R
E
L
A
Y

1
6
G
7
G
6
G
1
0
G
9
G
8
G
5
G
1
3
G
1
2
G
1
1
G
1
4
R
E
L
A
Y

1
5
R
E
L
A
Y

1
2
R
E
L
A
Y

1
1
R
E
L
A
Y

1
0
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
c
a
b
C
O
N
N
E
C
T
I
O
N
C
O
M
M
O
N
O
P
T
O

5
O
P
T
O

4
- + - +
O
P
T
O

3
O
P
T
O

2
- + +-
N
O
T
E

4
.
O
P
T
O

1
+- -
V

C
H
E
C
K
S
Y
N
C
F
1
4
F
1
3
F
1
6
F
1
5
F
1
8
F
1
7
C
O
M
M
S
O
P
T
O

1
6
O
P
T
O

1
5
F
1
0
F
1
1
F
1
2
O
P
T
O

1
4
O
P
T
O

1
3
F
9
O
P
T
O

1
2
O
P
T
O

1
1
F
8
F
7
F
6
F
5
P
H
A
S
E

R
O
T
A
T
I
O
N
A
C
B
X
A
X X
A
B
n N C
C B
O
P
T
O

1
0
O
P
T
O

9
F
4
F
3
F
2
F
1
N
O
T
E

3
.
R
E
L
A
Y

3

A
N
Y

T
R
I
P
H
1
2
H
1
4
H
1
5
H
1
3
H
1
7
H
1
6
G
1
G
2
G
3
H
1
8
R
E
L
A
Y

8
R
E
L
A
Y

9
R
E
L
A
Y

7
H
4
H
3
H
2
H
6
H
5
H
8
H
9
H
1
1
H
1
0
H
7
R
E
L
A
Y

2
R
E
L
A
Y

1
J
1
2
J
1
1
H
1
J
1
4
J
1
3
C
O
N
T
A
C
T
W
A
T
C
H
D
O
G
R
E
L
A
Y

5
R
E
L
A
Y

4
R
E
L
A
Y

6
R
E
L
A
Y

1
3
R
E
L
A
Y

1
4
P
O
W
E
R

S
U
P
P
L
Y

V
E
R
S
I
O
N

2
4
-
4
8
V

(
N
O
M
I
N
A
L
)

D
.
C
.

O
N
L
Y
*
W
A
T
C
H
D
O
G
C
O
N
T
A
C
T

Figure 31: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 16 O/P)




P14x Technical Data Sheet 65 P141/2/3/4/5 Software Version 46J
P2275ENa

Figure 32: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 20 O/P with 4 High Break
Contacts)





P14x Technical Data Sheet 66 P141/2/3/4/5 Software Version 46J
P1611ENa
S
Y
N
C
V

C
H
E
C
K
2
.


C
.
T
.

C
O
N
N
E
C
T
I
O
N
S

A
R
E

S
H
O
W
N

1
A

C
O
N
N
E
C
T
E
D

A
N
D

A
R
E
T
Y
P
I
C
A
L
O
N
L
Y
.
C
H
A
N
G
E
S

I
F

T
H
I
S

O
P
T
I
O
N

I
S

S
E
L
E
C
T
E
D

I
N

T
H
E

R
E
L
A
Y

M
E
N
U
.
4
.


O
P
T
O

I
N
P
U
T
S

1
A
N
D

2

M
U
S
T

B
E

U
S
E
D

F
O
R

S
E
T
T
I
N
G

G
R
O
U
P

E
N
S
U
R
E

C
O
R
R
E
C
T

O
P
E
R
A
T
I
O
N

O
F

T
H
E

P
R
O
T
E
C
T
I
V
E

R
E
L
A
Y
.
+
D
8
1
A
5
A
C
.
T
.

S
H
O
R
T
I
N
G

L
IN
K
S
P
I
N

T
E
R
M
I
N
A
L

(
P
.
C
.
B
.

T
Y
P
E
)
(
b
)
N
O
T
E
S

1
.
(
a
)
3
.


T
H
I
S

R
E
L
A
Y

S
H
O
U
L
D

B
E

A
S
S
I
G
N
E
D

T
O

A
N
Y

T
R
I
P

T
O
5
.


F
O
R

C
O
M
M
S

O
P
T
I
O
N
S

S
E
E

D
R
A
W
I
N
G

1
0
P
x
4
0
0
1
.
C
2
2
C
2
1
N C
C
1
9
C
1
5
C
2
0
B A
D
1
6
D
1
7
D
1
8
+
D
1
2
D
1
3
D
1
4
D
1
5
- + - +
D
9
D
1
0
D
1
1
- + -
N
O
T
E

2
.
D
I
R
E
C
T
I
O
N

O
F

F
O
R
W
A
R
D

C
U
R
R
E
N
T

F
L
O
W
a A
c
b
n N C
B
S
1
S
2
P
2
S
2
P
1
P
2
S
1
A
1
A
5
A
1
A
5
A
1
A
5
A
1
A
5
A
C
1
0
C
1
3
C
1
2
S
E
N
S
IT
IV
E
N
N
C
9
C
C
7
C
6
B
C
4
C
3
+
D
5
D
6
D
7
+- -
D
1
D
2
D
3
D
4
+- -
C
2
4
C
2
3
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
C
1
P
1
N
O
T
E

5
.
O
P
T
O

4
S
E
E
D
R
A
W
I
N
G
J
9

V
O
L
T
A
G
E

O
U
T
E
A
R
T
H
C
A
S
E
- -
J
1
0
O
P
T
O

8
C
O
N
N
E
C
T
I
O
N
C
O
M
M
O
N
O
P
T
O

6
O
P
T
O

7
O
P
T
O

5
+ ++
x
A
C

O
R
D
C
4
8
V

D
C

F
I
E
L
D
-
J
2
J
7
J
8
J
1
*
+
E
I
A
4
8
5
/
P
O
R
T
K
B
U
S
-
S
C
N
J
1
6
J
1
8
1
0
P
x
4
0
0
1
.
J
1
7
R
E
L
A
Y

2
1
R
E
L
A
Y

2
3
R
E
L
A
Y
2
2
R
E
L
A
Y
2
4
E
1
4
E
1
7
E
1
8
E
1
5
E
1
6
E
1
2
E
1
3
E
1
0
E
1
1
R
E
L
A
Y

1
7
R
E
L
A
Y

1
8
R
E
L
A
Y

1
9
R
E
L
A
Y

2
0
R
E
L
A
Y

1
3
R
E
L
A
Y

1
5
R
E
L
A
Y
1
4
R
E
L
A
Y

1
6
G
1
8
E
7
E
8
E
9
E
5
E
6
E
2
E
3
E
4
E
1
G
1
3
G
1
6
G
1
7
G
1
5
G
1
4
G
1
1
G
1
2
G
1
0
G
9
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
F
7
O
P
T
O

3
N
O
T
E
4
.
O
P
T
O

2
O
P
T
O

1
a
c
b
n
F
1
5
C
O
M
M
S
O
P
T
O

1
6
C
O
N
N
E
C
T
I
O
N
C
O
M
M
O
N
F
1
7
F
1
8
F
1
6
O
P
T
O

1
4
O
P
T
O

1
5
O
P
T
O

1
2
O
P
T
O

1
3
F
1
1
F
1
3
F
1
4
F
1
2
F
9
F
1
0
F
8
AC B
X
A
N
B
C
XX
P
H
A
S
E
R
O
T
A
T
I
O
N
A
C
B
O
P
T
O

1
0
O
P
T
O

1
1
O
P
T
O
9
F
6
F
5
F
4
F
3
F
2
F
1
R
E
L
A
Y
4
R
E
L
A
Y

1
1
R
E
L
A
Y

1
0
R
E
L
A
Y

1
2
R
E
L
A
Y

8
H
1
7
G
6
G
7
G
8
G
4
G
5
G
1
G
2
G
3
H
1
8
R
E
L
A
Y

9
H
1
2
H
1
5
H
1
6
H
1
4
H
1
3
R
E
L
A
Y
7
H
1
0
H
1
1
H
9
H
8
R
E
L
A
Y
5
R
E
L
A
Y
6
C
O
N
T
A
C
T
W
A
T
C
H
D
O
G
C
O
N
T
A
C
T
R
E
L
A
Y

3


A
N
Y

T
R
I
P
W
A
T
C
H
D
O
G
J
1
2
H
5
H
6
H
7
H
4
H
3
R
E
L
A
Y

2
J
1
4
H
2
H
1
J
1
3
R
E
L
A
Y
1
J
1
1
N
O
T
E

3
.
P
O
W
E
R

S
U
P
P
L
Y

V
E
R
S
IO
N

2
4
-
4
8
V
(
N
O
M
I
N
A
L
)

D
.C
.

O
N
L
Y
*
A
U
X
S
U
P
P
L
Y

Figure 33: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 24 O/P)




P14x Technical Data Sheet 67 P141/2/3/4/5 Software Version 46J
P2276ENa

Figure 34: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 24 O/P with 8 High Break
Contacts)





P14x Technical Data Sheet 68 P141/2/3/4/5 Software Version 46J
P2277ENa

Figure 35: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 28 O/P with 4 High Break
Contacts)




P14x Technical Data Sheet 69 P141/2/3/4/5 Software Version 46J
P1614ENa
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
1
A
5
A
N
O
T
E
S
:
(
b
)
1
.
(
a
)
S
E
L
E
C
T
E
D

I
N

T
H
E

R
E
L
A
Y

M
E
N
U
.
T
R
I
P

T
O

E
N
S
U
R
E

C
O
R
R
E
C
T

O
P
E
R
A
T
I
O
N

O
F
T
H
E

P
R
O
T
E
C
T
I
V
E

R
E
L
A
Y
.
A
N
D

A
R
E

T
Y
P
I
C
A
L
O
N
L
Y
.
S
E
T
T
I
N
G

G
R
O
U
P

C
H
A
N
G
E
S

I
F

T
H
I
S

O
P
T
I
O
N

I
S
3
.


T
H
I
S

R
E
L
A
Y

S
H
O
U
L
D

B
E

A
S
S
I
G
N
E
D

T
O

A
N
Y
4
.


O
P
T
O

I
N
P
U
T
S

1

A
N
D

2

M
U
S
T

B
E

U
S
E
D

F
O
R
5
.


F
O
R

C
O
M
M
S

O
P
T
I
O
N
S

S
E
E

D
R
A
W
I
N
G

1
0
P
x
4
0
0
1
.
2
.


C
.
T
.

C
O
N
N
E
C
T
I
O
N
S

A
R
E

S
H
O
W
N

1
A

C
O
N
N
E
C
T
E
D
C
.
T
.

S
H
O
R
T
I
N
G

L
I
N
K
S
P
I
N

T
E
R
M
I
N
A
L

(
P
.
C
.
B
.

T
Y
P
E
)
C
2
2
N
C
2
1
C
C
2
0
B
C
1
9
A
C
1
5
Aa
1
A
5
A
C
B
n
c
b
N
N
O
T
E

2
.
1
A
5
A
1
A
5
A
N
S
E
N
S
I
T
I
V
E
C
1
3
C
1
2
C
1
0
N
C
9
1
A
5
A
C
7
C
C
6
C
4
B
C
3
P
1
P
2
P
2
P
1
S
2
S
1
S
2
S
1
D
I
R
E
C
T
I
O
N

O
F

F
O
R
W
A
R
D

C
U
R
R
E
N
T

F
L
O
W
C
1
A
-
D
1
3
S
E
E

D
R
A
W
I
N
G
1
0
P
x
4
0
0
1
.
P
O
W
E
R

S
U
P
P
L
Y

V
E
R
S
I
O
N

2
4
-
4
8
V

(
N
O
M
I
N
A
L
)

D
.
C
.

O
N
L
Y
+
F
1
0
O
P
T
O

1
3
F
1
8
C
O
M
M
O
N
C
O
N
N
E
C
T
I
O
N
+++
F
1
4
F
1
6
F
1
7
F
1
5
-
F
1
2
F
1
3
-
F
1
1
-
O
P
T
O

1
5
O
P
T
O

1
6
O
P
T
O

1
4
*
E
I
A
4
8
5
/
-
S
C
N
P
O
R
T
+
K
B
U
S
J
1
8
J
1
6
N
O
T
E

5
.
C
O
M
M
S
J
1
7
+++ +
F
9
-
F
7
F
8
-
F
5
F
6
-
F
3
F
4
-
O
P
T
O

1
2
O
P
T
O

1
1
O
P
T
O

1
0
++
D
1
7
F
1
F
2
-
D
1
8
D
1
5
D
1
6
-
D
1
4
C
O
N
N
E
C
T
I
O
N
O
P
T
O

9
C
O
M
M
O
N
O
P
T
O

8
O
P
T
O

7
+

V
O
L
T
A
G
E

O
U
T
4
8
V

D
C

F
I
E
L
D
E
A
R
T
H
C
A
S
E
J
1
0
-
J
8
J
9
J
7
- + +
A
U
X

S
U
P
P
L
Y
A
C

O
R

D
C
B
1
3
*
B
1
8
J
2
J
1
-
x
B
1
7
B
1
6
B
1
4
B
1
5
B
1
1
B
1
2
B
1
0
B
9
B
6
B
7
B
8
B
5
B
4
V

C
H
E
C
K
-
D
6
O
P
T
O

3
++++ --
D
1
2
D
1
0
D
1
1
-
D
9
D
8
D
7
O
P
T
O

6
O
P
T
O

5
O
P
T
O

4
++
S
Y
N
C
D
2
D
4
D
5
D
3
-
D
1
-
C
2
4
O
P
T
O

1
N
O
T
E

4
.
O
P
T
O

2
a
c
b
C
2
3
n
N
A
X XX
C
B
C B A
P
H
A
S
E

R
O
T
A
T
I
O
N
A
C
B
E
3
R
E
L
A
Y

1
8
R
E
L
A
Y

2
2
R
E
L
A
Y

2
1
R
E
L
A
Y

2
0
R
E
L
A
Y

2
3
R
E
L
A
Y

2
5
R
E
L
A
Y

2
4
R
E
L
A
Y

1
9
E
1
7
B
1
B
3
B
2
E
1
8
E
1
5
E
1
6
E
1
4
E
1
3
E
8
E
1
0
E
1
1
E
1
2
E
9
E
5
E
7
E
6
E
4
R
E
L
A
Y

1
7
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
E
2
E
1
G
1
3
G
1
8
G
1
6
G
1
7
G
1
5
G
1
4
G
1
1
G
1
2
G
9
G
1
0
G
6
G
8
G
7
G
4
G
5
H
3
H
1
7
G
1
G
2
G
3
H
1
8
H
1
5
H
1
6
H
1
3
H
1
4
H
8
H
1
0
H
1
2
H
1
1
H
9
H
5
H
7
H
6
H
4
J
1
2
H
2
H
1
J
1
4
J
1
3
J
1
1
R
E
L
A
Y

1
0
R
E
L
A
Y

1
6
R
E
L
A
Y

1
5
R
E
L
A
Y

1
4
R
E
L
A
Y

1
3
R
E
L
A
Y

1
1
R
E
L
A
Y

1
2
A
N
Y

T
R
I
P

R
E
L
A
Y

3
R
E
L
A
Y

8
R
E
L
A
Y

9
R
E
L
A
Y

7
R
E
L
A
Y

4
R
E
L
A
Y

5
R
E
L
A
Y

6
R
E
L
A
Y

2
R
E
L
A
Y

1
W
A
T
C
H
D
O
G
W
A
T
C
H
D
O
G
C
O
N
T
A
C
T
C
O
N
T
A
C
T
N
O
T
E

3
.
R
E
L
A
Y

2
6
R
E
L
A
Y

2
7
R
E
L
A
Y

2
8
R
E
L
A
Y

2
9
R
E
L
A
Y

3
0
R
E
L
A
Y

3
1
R
E
L
A
Y

3
2

Figure 36: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (16 I/P & 32 O/P)





P14x Technical Data Sheet 70 P141/2/3/4/5 Software Version 46J
P1610ENa

E
N
S
U
R
E
C
O
R
R
E
C
T
O
P
E
R
A
T
I
O
N

O
F

T
H
E
P
R
O
T
E
C
T
IV
E
R
E
L
A
Y
.
5
.

F
O
R

C
O
M
M
S
O
P
T
IO
N
S
S
E
E
D
R
A
W
I
N
G
1
0
P
x
4
0
0
1
.
4
.

O
P
T
O

IN
P
U
T
S
1

A
N
D

2
M
U
S
T
B
E

U
S
E
D

F
O
R

S
E
T
T
IN
G
G
R
O
U
P
C
H
A
N
G
E
S

IF

T
H
IS

O
P
T
I
O
N

IS

S
E
L
E
C
T
E
D

IN
T
H
E

R
E
L
A
Y

M
E
N
U
.
3
.
T
H
IS

R
E
L
A
Y
S
H
O
U
L
D

B
E
A
S
S
IG
N
E
D
T
O
A
N
Y
T
R
I
P
T
O
2
.
C
.T
.
C
O
N
N
E
C
T
IO
N
S

A
R
E

S
H
O
W
N

1
A
C
O
N
N
E
C
T
E
D
A
N
D
A
R
E

T
Y
P
IC
A
L

O
N
L
Y
.
S
E
N
S
IT
IV
E
1
A
5
A
P
I
N
T
E
R
M
I
N
A
L
(
P
.C
.
B
.
T
Y
P
E
)
C
.
T
. S
H
O
R
T
IN
G
L
IN
K
S
(
b
)
(
a
)
N
O
T
E
S
1
.
N C
C
2
1
C
2
2
B A
C
2
0
C
1
5
C
1
9
C
1
4
D
1
8
D
1
6
D
1
7
D
1
5
D
1
1
D
1
4
D
1
3
D
1
2
D
1
0
D
9
D
8
D
I
R
E
C
T
IO
N
O
F

F
O
R
W
A
R
D
C
U
R
R
E
N
T
F
L
O
W
S
1
N
O
T
E
2
.
B
C
Aa
c
b
n N
P
2
P
1
P
2
S
2
S
2
S
1
C
2
1
A
5
A
1
A
5
A
1
A
5
A
1
A
5
A
N
N
C
1
2
C
1
3
C
1
1
C
1
0
C
9
C
8
C B
C
5
C
7
C
6
C
4
C
3
D
4
D
7
D
6
D
5
D
3
D
2
D
1
C
2
4
C
2
3
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
P
1
A
C
1
+
C
O
M
M
O
N
C
O
N
N
E
C
T
I
O
N
O
P
T
O
8
+ -
O
P
T
O
6
O
P
T
O
7
- + -
O
P
T
O
4
O
P
T
O
5
+ - + -
n
N
O
T
E
4
.
O
P
T
O
2
O
P
T
O
3
+ - +
O
P
T
O
1
- + -
b
V
C
H
E
C
K
S
Y
N
C
a
c
P
H
A
S
E
R
O
T
A
T
IO
N
A
C
B
B
A
XX X
N
B
C
C A
1
0
P
x
4
0
0
1
.
S
E
E

D
R
A
W
IN
G
P
O
W
E
R
S
U
P
P
L
Y
V
E
R
S
IO
N

2
4
-
4
8
V
(
N
O
M
I
N
A
L
)

D
.C
.
O
N
L
Y
N
O
T
E
5
.
P
O
R
T
K
B
U
S
E
IA
4
8
5
/
* S
C
N
J
1
6
+ -
J
1
8
J
1
7
O
P
T
O
2
4
O
P
T
O
2
3
O
P
T
O
2
0
O
P
T
O
2
2
O
P
T
O

2
1
O
P
T
O
1
8
O
P
T
O
1
9
C
O
M
M
S
E
1
7
E
1
8
E
1
6
E
1
5
E
1
4
E
1
3
E
8
E
1
0
E
1
2
E
1
1
E
9
E
4
E
6
E
7
E
5
F
4
O
P
T
O
1
0
O
P
T
O
1
7
O
P
T
O
1
5
O
P
T
O
1
6
O
P
T
O
1
4
O
P
T
O
1
3
O
P
T
O
1
2
O
P
T
O
1
1
F
1
7
E
2
E
3
F
1
8
E
1
F
1
6
F
1
5
F
1
4
F
1
3
F
1
0
F
1
2
F
1
1
F
9
F
8
F
6
F
7
F
5
O
P
T
O
9
F
2
F
3
F
1
V
O
L
T
A
G
E
O
U
T
A
C

O
R
D
C
4
8
V
D
C

F
IE
L
D
+
J
9
J
8
J
1
0
E
A
R
T
H
C
A
S
E
- - +
*
J
1
J
2
J
7
+ -
x
R
E
L
A
Y
1
3
R
E
L
A
Y
1
5
R
E
L
A
Y
1
4
R
E
L
A
Y
1
6
G
1
8
G
1
3
G
1
6
G
1
7
G
1
5
G
1
4
G
1
1
G
1
2
G
1
0
G
9
R
E
L
A
Y
4
R
E
L
A
Y
1
1
R
E
L
A
Y
1
0
R
E
L
A
Y
1
2
R
E
L
A
Y

8
H
1
7
G
6
G
7
G
8
G
4
G
5
G
1
G
2
G
3
H
1
8
R
E
L
A
Y

9
H
1
2
H
1
5
H
1
6
H
1
4
H
1
3
R
E
L
A
Y
7
H
1
0
H
1
1
H
9
H
8
R
E
L
A
Y
5
R
E
L
A
Y
6
C
O
N
T
A
C
T
W
A
T
C
H
D
O
G
C
O
N
T
A
C
T
W
A
T
C
H
D
O
G
J
1
2
H
5
H
6
H
7
H
4
H
3
R
E
L
A
Y
2
J
1
4
H
2
H
1
J
1
3
R
E
L
A
Y

1
J
1
1
R
E
L
A
Y

3

A
N
Y

T
R
IP
N
O
T
E
3
.
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
A
U
X
S
U
P
P
L
Y
C
O
N
N
E
C
T
I
O
N
C
O
M
M
O
N
C
O
N
N
E
C
T
I
O
N
C
O
M
M
O
N

Figure 37: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 16 O/P)




P14x Technical Data Sheet 71 P141/2/3/4/5 Software Version 46J
P2278ENa

Figure 38: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 20 O/P with 4 High Break
Contacts)





P14x Technical Data Sheet 72 P141/2/3/4/5 Software Version 46J
P1612ENa
O
P
T
O

1
O
P
T
O
2
O
P
T
O
3
V

C
H
E
C
K
O
P
T
O
5
O
P
T
O
7
O
P
T
O
6
O
P
T
O
8
C
O
M
M
O
N
C
O
N
N
E
C
T
I
O
N
2
.


C
.
T
.

C
O
N
N
E
C
T
I
O
N
S

A
R
E

S
H
O
W
N

1
A

C
O
N
N
E
C
T
E
D

A
N
D

A
R
E

T
Y
P
I
C
A
L
O
N
L
Y
.
C
H
A
N
G
E
S

I
F

T
H
I
S

O
P
T
I
O
N

I
S

S
E
L
E
C
T
E
D

I
N

T
H
E

R
E
L
A
Y

M
E
N
U
.
4
.


O
P
T
O

I
N
P
U
T
S

1

A
N
D

2

M
U
S
T

B
E

U
S
E
D

F
O
R

S
E
T
T
I
N
G

G
R
O
U
P

E
N
S
U
R
E

C
O
R
R
E
C
T
O
P
E
R
A
T
I
O
N

O
F

T
H
E

P
R
O
T
E
C
T
I
V
E

R
E
L
A
Y
.
O
P
T
O
4
D
8
+
1
A
5
A
C
.T
.

S
H
O
R
T
IN
G

L
IN
K
S
P
I
N

T
E
R
M
I
N
A
L

(
P
.
C
.
B
.

T
Y
P
E
)
(
a
)
(
b
)
N
O
T
E
S

1
.
3
.


T
H
I
S

R
E
L
A
Y

S
H
O
U
L
D

B
E

A
S
S
I
G
N
E
D

T
O

A
N
Y

T
R
I
P

T
O
5
.


F
O
R

C
O
M
M
S

O
P
T
I
O
N
S

S
E
E

D
R
A
W
I
N
G

1
0
P
x
4
0
0
1
.
C
2
1
C
2
2
N C
C
1
5
C
1
9
C
2
0
B A
D
1
5
-
D
1
6
D
1
8
D
1
7
+
D
1
2
D
1
4
D
1
3
+ +-
D
1
0
D
1
1
D
9
+- -
N
O
T
E
2
.
D
I
R
E
C
T
I
O
N
O
F
F
O
R
W
A
R
D
C
U
R
R
E
N
T
F
L
O
W
C
B
Aa
n
c
b
N
P
2
P
1
P
2
S
1
S
2
S
2
S
1
1
A
5
A
1
A
5
A
1
A
5
A
1
A
5
A
C
1
0
C
1
2
C
1
3
S
E
N
S
I
T
I
V
E
N
N
C
9
C
7
C
C
6
C
4
B
C
3
D
1
+
D
7
D
6
D
5
+- -
D
4
D
3
D
2
- + -
S
Y
N
C
C
2
4
C
2
3
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
P
1
C
1
A
n
N
O
T
E

4
.
a
c
b
P
H
A
S
E
R
O
T
A
T
IO
N
A
C
B
B
A
N
XX X
B
C
C A
N
O
T
E

5
.
P
O
W
E
R

S
U
P
P
L
Y

V
E
R
S
I
O
N

2
4
-
4
8
V
(
N
O
M
I
N
A
L
)
D
.C
.
O
N
L
Y
S
E
E
D
R
A
W
IN
G

V
O
L
T
A
G
E
O
U
T
J
9
*
- -
J
1
0
+ +
A
C
O
R

D
C
x
A
U
X

S
U
P
P
L
Y
4
8
V

D
C

F
IE
L
D
+ -
J
2
J
7
J
8
J
1
*
+
E
I
A
4
8
5
/
P
O
R
T
K
B
U
S
-
J
1
6
S
C
N
J
1
8
1
0
P
x
4
0
0
1
.
J
1
7
R
E
L
A
Y

2
4
R
E
L
A
Y

2
2
R
E
L
A
Y

2
3
R
E
L
A
Y

2
1
B
1
4
B
1
7
B
1
8
B
1
6
B
1
5
B
1
2
B
1
3
B
1
1
B
1
0
R
E
L
A
Y

1
6
R
E
L
A
Y

1
4
R
E
L
A
Y

1
5
R
E
L
A
Y

1
3
R
E
L
A
Y

2
0
R
E
L
A
Y

1
9
R
E
L
A
Y

1
8
R
E
L
A
Y

1
7
G
1
8
B
7
B
9
B
8
B
6
B
5
B
2
B
4
B
3
B
1
G
1
3
G
1
6
G
1
7
G
1
4
G
1
5
G
1
1
G
1
2
G
9
G
1
0
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
F
1
5
C
O
M
M
S
C
O
M
M
O
N
C
O
N
N
E
C
T
IO
N
O
P
T
O
1
6
F
1
7
F
1
8
F
1
6
O
P
T
O

1
5
O
P
T
O
1
4
O
P
T
O
1
3
F
1
1
F
1
3
F
1
4
F
1
2
F
9
F
1
0
R
E
L
A
Y
4
R
E
L
A
Y
1
2
R
E
L
A
Y

1
0
R
E
L
A
Y

1
1
H
1
7
R
E
L
A
Y

8
G
6
G
8
G
7
G
5
G
4
G
1
G
3
G
2
H
1
8
R
E
L
A
Y

9
H
1
2
H
1
5
H
1
6
H
1
3
H
1
4
R
E
L
A
Y
7
H
1
0
H
1
1
H
8
H
9
R
E
L
A
Y
5
R
E
L
A
Y
6
W
A
T
C
H
D
O
G
R
E
L
A
Y

3


A
N
Y
T
R
I
P
C
O
N
T
A
C
T
W
A
T
C
H
D
O
G
C
O
N
T
A
C
T
J
1
2
H
5
H
7
H
6
H
3
H
4
R
E
L
A
Y

2
J
1
4
H
1
H
2
J
1
3
R
E
L
A
Y
1
J
1
1
N
O
T
E
3
.
+ - + -+- + -
O
P
T
O

1
2
F
8
O
P
T
O
1
0
O
P
T
O
1
1
O
P
T
O

9
F
5
F
6
F
7
F
4
F
3
F
2
F
1
E
1
3
E
1
6
E
1
8
E
1
7
E
1
5
E
1
4
O
P
T
O
2
4
O
P
T
O
2
3
E
3
E
5
E
4
E
9
E
1
1
E
1
2
E
1
0
E
7
E
8
E
6
O
P
T
O
2
2
O
P
T
O

2
1
O
P
T
O
1
8
O
P
T
O
2
0
O
P
T
O
1
9
E
2
E
1
O
P
T
O
1
7
C
O
N
N
E
C
T
IO
N
C
O
M
M
O
N
E
A
R
T
H
C
A
S
E

Figure 39: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (24 I/P & 24 O/P)




P14x Technical Data Sheet 73 P141/2/3/4/5 Software Version 46J
P1613ENa
S
Y
N
C
V

C
H
E
C
K
+
4
.

O
P
T
O

IN
P
U
T
S

1
A
N
D

2

M
U
S
T
B
E

U
S
E
D
F
O
R
5
.

F
O
R
C
O
M
M
S
O
P
T
IO
N
S

S
E
E

D
R
A
W
I
N
G

1
0
P
x
4
0
0
1
.
3
.

T
H
I
S
R
E
L
A
Y

S
H
O
U
L
D

B
E
A
S
S
IG
N
E
D
T
O

A
N
Y
2
.

C
.
T
.
C
O
N
N
E
C
T
I
O
N
S
A
R
E

S
H
O
W
N

1
A

C
O
N
N
E
C
T
E
D
(
a
)
(
b
)
N
O
T
E
S
:
1
.
P
IN
T
E
R
M
I
N
A
L
(
P
.
C
.
B
.
T
Y
P
E
)
C
.T
.
S
H
O
R
T
I
N
G
L
I
N
K
S
S
E
T
T
IN
G

G
R
O
U
P

C
H
A
N
G
E
S

I
F

T
H
I
S
O
P
T
IO
N
I
S
S
E
L
E
C
T
E
D
I
N

T
H
E

R
E
L
A
Y

M
E
N
U
.
F
1
8
F
1
7
F
1
6
+
T
R
IP

T
O

E
N
S
U
R
E

C
O
R
R
E
C
T

O
P
E
R
A
T
I
O
N

O
F
N
C
2
2
A
N
D

A
R
E

T
Y
P
I
C
A
L
O
N
L
Y
.
T
H
E
P
R
O
T
E
C
T
IV
E

R
E
L
A
Y
.
C B
C
2
1
C
2
0
F
7
F
1
5
F
1
4
+-
F
1
3
F
1
2
+- -
F
1
1
F
1
0
+ -
F
8
F
9
+ -
F
5
F
6
+ -
F
4
F
3
+ -
F
2
F
1
+ -
D
1
8
D
1
7
D
I
R
E
C
T
IO
N
O
F
F
O
R
W
A
R
D
C
U
R
R
E
N
T

F
L
O
W
N
O
T
E
2
.
a
b
c
n N
A
B
C
S
2
S
1
S
2
S
1
P
2
P
2
P
1
1
A
5
A
C
3
1
A
5
A
1
A
5
A
1
A
5
A
1
A
5
A
N
S
E
N
S
I
T
I
V
E
A
N
C
1
9
C
1
5
C
1
3
C
1
2
BC
C
7
C
1
0
C
9
C
6
C
4
D
8
++
D
1
6
D
1
5
-
D
1
4
D
1
3
-
D
1
2
D
1
1
- +
D
9
D
1
0
- +
D
6
D
7
- +
D
5
D
4
- +
D
3
D
2
- +
D
1
-
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
A
C
1
P
1
C
2
4
C
2
3
G
8
B
8
O
P
T
O
2
8
P
O
W
E
R
S
U
P
P
L
Y
V
E
R
S
I
O
N
2
4
-
4
8
V
(
N
O
M
I
N
A
L
)
D
.
C
.
O
N
L
Y
J
1
8
C
O
N
N
E
C
T
IO
N
C
O
M
M
O
N
O
P
T
O
1
6
J
1
6
S
C
N
P
O
R
T
*
+
C
O
M
M
O
N
C
O
N
N
E
C
T
IO
N
O
P
T
O
1
5
O
P
T
O

1
4
O
P
T
O
1
3
O
P
T
O

1
2
O
P
T
O

1
1
O
P
T
O

1
0
C
O
N
N
E
C
T
I
O
N
O
P
T
O

9
C
O
M
M
O
N
B
1
7
B
1
8
J
1
7
N
O
T
E
5
.
E
I
A
4
8
5
/
K
B
U
S
-
C
O
M
M
S
S
E
E

D
R
A
W
IN
G
1
0
P
x
4
0
0
1
.
B
1
1
B
1
2
B
1
0
B
1
3
B
1
4
B
1
5
B
1
6
O
P
T
O
3
1
O
P
T
O
3
2
O
P
T
O
2
9
O
P
T
O
3
0
B
9
C
A
S
E
E
A
R
T
H
A
C
O
R

D
C
A
U
X
S
U
P
P
L
Y
4
8
V
D
C

F
I
E
L
D
V
O
L
T
A
G
E

O
U
T
*
J
7
J
9
J
1
0
- -
J
8
+ +
J
2
+
J
1
-
G
1
6
G
1
7
G
1
8
G
1
4
G
1
5
R
E
L
A
Y
1
4
R
E
L
A
Y
1
3
G
1
3
G
1
2
G
1
1
G
1
0
G
9
R
E
L
A
Y
1
2
R
E
L
A
Y
1
1
x
E
9
C
O
N
N
E
C
T
IO
N
C
O
M
M
O
N
O
P
T
O

4
O
P
T
O

8
O
P
T
O

7
O
P
T
O

6
O
P
T
O

5
O
P
T
O

2
O
P
T
O

3
N
O
T
E
4
.
O
P
T
O

1
E
1
8
O
P
T
O
2
6
O
P
T
O
2
7
B
6
B
7
B
5
B
4
O
P
T
O
2
5
B
3
B
2
B
1
E
1
7
E
1
6
E
1
5
E
1
4
E
1
3
E
1
2
E
1
1
E
1
0
O
P
T
O
2
3
O
P
T
O
2
4
O
P
T
O
2
1
O
P
T
O
2
2
A
X
P
H
A
S
E
R
O
T
A
T
IO
N
A
C
B
BC
a
n
b
c N
X
A
X
B
C
O
P
T
O
1
9
O
P
T
O
2
0
E
7
E
8
E
6
E
5
O
P
T
O
1
8
O
P
T
O
1
7
E
4
E
3
E
2
E
1
N
O
T
E
3
.
R
E
L
A
Y
3

A
N
Y
T
R
IP
G
5
G
7
G
6
G
4
G
3
R
E
L
A
Y

1
0
R
E
L
A
Y
9
H
1
8
G
1
G
2
H
1
6
H
1
7
R
E
L
A
Y
8
H
1
0
H
1
4
H
1
3
H
1
5
H
1
2
H
1
1
R
E
L
A
Y
6
R
E
L
A
Y
5
H
9
H
8
H
6
H
7
H
5
R
E
L
A
Y
4
W
A
T
C
H
D
O
G
W
A
T
C
H
D
O
G
M
i
C
O
M

P
1
4
5

(
P
A
R
T
)
J
1
3
H
2
H
3
H
4
J
1
4
H
1
R
E
L
A
Y
1
R
E
L
A
Y
2
C
O
N
T
A
C
T
J
1
2
J
1
1
C
O
N
T
A
C
T
R
E
L
A
Y
7
R
E
L
A
Y
1
5
R
E
L
A
Y
1
6

Figure 40: P145 Feeder Management Relay - Directional Phase Overcurrent and SEF with
Auto-reclose and Check Synchronizing (32 I/P & 16 O/P)





P14x Technical Data Sheet 74 P141/2/3/4/5 Software Version 46J
Ordering Options
Information Required with Order
Relay Type (Feeder Management Relay) P141/2/3/4
Auxiliary Voltage Rating
24 - 48V dc only
48 - 125V dc (30 - 110V ac)
110 - 250V dc (100 - 240V ac)

1
2
3

Vn rating
100 - 120V ac
380 - 480V ac (Min. 196Vac, Max. 560Vac)

1
2

Hardware options
Nothing
IRIG-B modulated only
Fiber optic converter (ST) only (except IEC 61850)
IRIG-B (modulated) & fiber optic converter (ST)
(except IEC 61850)
Second rear Courier
Second rear Courier port + InterMiCOM
Second rear Courier port + InterMiCOM + IRIG-B (modulated)
IRIG-B (modulated) + second rear comms.
IRIG-B (de-modulated)
Ethernet (100Mbps)
Ethernet (100Mbps) + IRIG-B (modulated)
Ethernet (100Mbps) + IRIG-B (de-modulated)
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports +
Modulated IRIG-B
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports +
Un-modulated IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports + Modulated
IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports +
Un-modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fiber ports +
Modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports +
Un-Modulated IRIG-B

1
2
3
4

7
E
F
8
C
6
A
B
G

H

J

K

L

M

Product Specific
P141 P142/4 P143
No additional hardware
4 inputs + 4 relays
Additional 8 optos
Additional 8 relays
Additional 8 optos and 8 relays
Additional 16 optos
Additional 16 relays
Additional 4 high break relays
Additional 8 inputs + 4 high break relays
Additional 8 relays + 4 high break relays
Additional 8 high break relays
32 inputs and 32 relays configuration (P143 only)
8 inputs and 8 relays configuration (P141 only)

































A
B
C
D
E
F
G
H
J
K
L
M
N

Protocol Options
K-Bus/Courier
MODBUS
IEC 60870-5-103
DNP3.0
DNP3.0 over Ethernet + Courier over RS485
IEC 61850 + Courier over RS485
IEC 61850 + CS103 over RS485

1
2
3
4
8
6
7

Mounting
Panel Mounting M




P14x Technical Data Sheet 75 P141/2/3/4/5 Software Version 46J
Language
Multilingual - English, French, German, Spanish
Multilingual - English, French, German, Russian
Multilingual - English, French, Chinese

0
5
C

Software Version
Unless specified the latest version will be delivered 4 6
Settings File
Default
Customer Specific

0
1

Hardware Suffix
Original J













P14x Technical Data Sheet 76 P141/2/3/4/5 Software Version 46J
Relay Type (Feeder Management Relay) P145
Auxiliary Voltage Rating
24 - 48V dc only
48 - 125V dc (30 - 110V ac)
110 - 250V dc (100 - 240V ac)

1
2
3

Vn rating
100 - 120V ac
380 - 480V ac (Min. 196Vac, Max. 560Vac)

1
2

Hardware options
Nothing
IRIG-B modulated only
Fiber optic converter (ST) only (except IEC 61850)
IRIG-B (modulated) & fiber optic converter (ST)
(except IEC 61850)
Second rear Courier
Second rear Courier port + InterMiCOM
Second rear Courier port + InterMiCOM + IRIG-B (modulated)
IRIG-B (modulated) + second rear comms.
IRIG-B (de-modulated)
Ethernet (100Mbps)
Ethernet (100Mbps) + IRIG-B (modulated)
Ethernet (100Mbps) + IRIG-B (de-modulated)
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports +
Modulated IRIG-B
Redundant Ethernet Self-Healing Ring, 2 multi-mode fiber ports +
Un-modulated IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports + Modulated
IRIG-B
Redundant Ethernet RSTP, 2 multi-mode fiber ports +
Un-Modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fiber ports +
Modulated IRIG-B
Redundant Ethernet Dual-Homing Star, 2 multi-mode fiber ports +
Un-Modulated IRIG-B

1
2
3
4

7
E
F
8
C
6
A
B
G

H

J

K

L

M

Product Specific
Version with 16 output contacts & 16 digital inputs
Version with 12 output contacts & 12 digital inputs
Version with 16 output contacts & 24 digital inputs
Version with 24 output contacts & 16 digital inputs
Version with 24 output contacts & 24 digital inputs
Version with 16 output contacts & 32 digital inputs
Version with 32 output contacts & 16 digital inputs
Additional 4 high break relays
Additional 8 inputs + 4 high break relays
Additional 8 relays + 4 high break relays
Additional 8 high break relays

A
B
C
D
E
F
G
H
J
K
L

Protocol Options
K-Bus/Courier
MODBUS
IEC 60870-5-103
DNP3.0
DNP3.0 over Ethernet + Courier over RS485
IEC 61850 + Courier over RS485
IEC 61850 + CS103 over RS485

1
2
3
4
8
6
7

Mounting
Panel Mounting M
Language
Multilingual - English, French, German, Spanish
Multilingual - English, French, German, Russian
Multilingual - English, French, Chinese

0
5
C

Software Version
Unless specified the latest version will be delivered 4 6





P14x Technical Data Sheet 77 P141/2/3/4/5 Software Version 46J
Settings File
Default
Customer Specific

0
1

Hardware Suffix
Original J

PXXX
Product Description


GRID







Alstom Grid

- ALSTOM 2011. ALSTOM, the ALSTOM
logo and any alternative version thereof are
trademarks and service marks of ALSTOM.
The other names mentioned, registered or
not, are the property of their respective
companies. The technical and other data
contained in this document is provided for
information only. Neither ALSTOM, its officers
or employees accept responsibility for, or
should be taken as making any representation
or warranty (whether express or implied), as
to the accuracy or completeness of such data
or the achievement of any projected
performance criteria where these are
indicated. ALSTOM reserves the right to
revise or change this data at any time without
further notice.
Alstom Grid Worldwide Contact Centre
www.alstom.com/grid/contactcentre/
Tel: +44 (0) 1785 250 070

www.alstom.com

S-ar putea să vă placă și