Precise air distribution, maximum use of space

GEA Cassette-Geko
Fan Coil Units | Data & Facts

Now available with


highly efficient EC motors!

GEA Heat Exchangers / HVAC Systems

Table of Contents

GEA Cassette-Geko Fan Coil Unit

Overview of Capacity .....................................................................3


Fan Coil Unit Components ............................................................4
Unit Selection .................................................................................5
Unit Description .............................................................................6
EC Technology: Keyword Energy Efficiency ...............................8
Description of Components ........................................................12
Pressure Drops in Heat Exchanger for
Warm and Chilled Water...............................................................32
Example for Capacity Determination ..........................................33
Acoustics ......................................................................................34
Sound Pressure Level, Sound Power Level .............................. 36
NR and NC Limit Curves .............................................................37
Dimensions/Weight of Basic Units .............................................33
Accessories / Primary Air Supply ..............................................38
Air Distribution .............................................................................43
Control Behaiviour of Valves ......................................................39
Overview of Valves ......................................................................44
Valves (loose) with modulating actuator
(230 V~ and 24 V~)/3-point operation ............................................................. 46
Valves with modulating actuator (230 V~) a. 2 floating auxiliary switches/
3-point operation ............................................................................................. 47
Valves with thermoelectrical Actuators
(230 V~ and 24 V~)/on/off operation ............................................................... 48
Valves with contunuous actuators (24 V~, 0..10 V) ........................................ 49
Shut off valves................................................................................................. 50

Regulation via Thermostat / Miniature Switches/


Regulation by Others....................................................................52
Controls System GEA MATRIX ....................................................54
System Description ......................................................................................... 54
Description of Features ................................................................................... 56
Installing Control Panels ................................................................................. 57
Sensor / Accessories ...................................................................................... 58
Global Modules ............................................................................................... 59
Timer MATRIX.Clock ...................................................................................... 60
Control Panel for All Groups ........................................................................... 61
Service Tools................................................................................................... 62

Unit Type Code..............................................................................63

PR-2010-0107-GB Subject to modifications Status 12/2011

Overview of Capacity

GEA Cassette-Geko Fan Coil Unit

Units without Electrical Heating

Mode
size

Motor CS1)
type

Length x
Width

[mm]

[m3/h]

Heating
Cooling

[kW]
ABCDEFG

2.2-4.7

25-35

330-660

EnEff class 4)

Capacity

Heating duty QH 3)

Cooling duty QK 3)

[dB(A)]

250-460

AC

Sound pressure level2

Air flow rate

1.5-2.5

ABCDEFG

2.8-7.6

26-43

ABCDEFG

1.9-4.2

ABCDEFG

575 x 575

Single

480-850

EC

250-850

ABCDEFG

2.6-5.0

ABCDEFG

2.2-9.2

25-49

530-1000

3.7-9.2

35-49

ABCDEFG

1.5-5.0

ABCDEFG
ABCDEFG

4.7-12.4

30-47

3.2-6.8

ABCDEFG

AC
2

Double

EC

840-1400

1175 x 575

530-1400

6.7-16.0

40-54

ABCDEFG

4.6-8.8

ABCDEFG
ABCDEFG

4.7-16.0

30-54

3.2-8.8
1

620-1200

ABCDEFG
ABCDEFG

5.3-14.6

24-42

3.5-8.2

ABCDEFG

AC
Big
Single

EC

822 x 822

770-1700

620-1530

ABCDEFG

6.3-18.6

29-51

4.3-10.5

ABCDEFG
ABCDEFG

5.3-17.5

24-49

3.5-9.8

ABCDEFG

1)

CS = capacity stage

2)

Ambient conditions refer to page 34 "Acoustics".

3)

Capacity data only apply to units without electrical heating. Input parameters: PWW 70/50C, tL1 = +20C; PCW 6/12C, tL1 = 27C/46%r.h.

4)

EnEff class = Energy Efficiency Class according to EUROVENT refer to page 10.
Correction factors 5)

Correction factors fK for

cooling capacity QK
The correction factors listed below
can be used to calculate the
capacity data in accordance with
EUROVENT classification
conditions:
Cooling (2+4-pipe system):1.01

Correction factors fH for

heating capacity QH

Chilled
water
temp.

Air intake: tL1 [C], 1 [% r.h.]

[C]

32/40 30/40 27/46 26/50 24/50

6/12

1.41

1.19

1.00

0.96

Warm
water
temp.

2-pipe system
air intake: tL1 [C]

4-pipe system
air intake: tL1 [C]

[C]

+10

+15

+20

+10

+15

+20

0.74

80/60

1.53

1.40

1.27

1.60

1.45

1.31

7/13

1.31

1.09

0.90

0.87

0.65

70/55

1.33

1.21

1.08

1.40

1.26

1.12

Heating (2-pipe system): 0.68

8/12

1.37

1.15

0.97

0.94

0.73

70/50

1.26

1.13

1.00

1.29

1.14

1.00

8/14

1.22

1.00

0.81

0.76

0.56

60/50

1.14

1.01

0.89

1.22

1.08

0.93

Heating (4-pipe system): 1.23

10/15

1.09

0.89

0.70

0.66

0.49

60/40

0.98

0.85

0.71

0.98

0.82

0.67

Sound power level 6)+3 dB

12/16

0.97

0.77

0.60

0.56

0.43

50/40

0.88

0.75

0.62

0.91

0.78

0.63

12/18

0.82

0.65

0.49

0.43

0.33

40/30

0.61

0.47

0.33

0.62

0.47

0.31

14/18

0.77

0.64

0.48

0.43

0.33

5)

All indicated correction factors are arithmetically calculated for different unit configurations and are meant for approximate calculations of
capacity data using other parameters. Exact data and other parameters can be obtained from our staff.

6)

Maximum indication due to EUROVENT zero tolerance.

PR-2010-0107-GB Subject to modifications Status 12/2011

Components of Fan Coil Units

GEA Cassette-Geko Fan Coil Unit

Unit Components

11
10

12

13
4

Fig. 1:

Pos. 1:
Pos. 2:
Pos. 3:
Pos. 4:
Pos. 5:
Pos. 6:
Pos. 7:

Unit components (depending on unit model)

Intake grille
Filter fleece
Design panel with air deflection vanes
Main condensate tray
Fan with casing
Heat exchanger (inc. optional electric heater)
Basic casing

Pos. 8:
Pos. 9:
Pos. 10:
Pos. 11:
Pos. 12:
Pos. 13:

Metal sheet electrical control box


with control electronics
Lateral condensate tray
Suspension brackets
Primary air connection
Opening for external air outlet
Condensate pump

GEA is a participant in the EUROVENT certification programme.


The certified products are listed in the corresponding EUROVENT lists.

PR-2010-0107-GB Subject to modifications Status 12/2011

Unit Selection

GEA Cassette-Geko Fan Coil Unit

Recirculating
air

Unit Description

EC Technology
Keyword Energy Efficiency [Energy Label]

4-Pipe Chilled and Warm Water

12

2-Pipe Chilled Water and Electrical Heating

16

2-Pipe Chilled or Warm Water

20

Heating

2-Pipe Warm Water *

24

Cooling

2-Pipe Chilled Water

28

Cooling and
heating

Cooling or
heating

* Cassette-Geko for only-heating operation can not be subsequently converted for cooling operation

Druckverluste im Wrmetauscher

4 Rohrreihen Khlen, 2-Leiter-System


1

25

20
6

DruckverlustDp [kPa]

15

10
9,0
8,0
7,0
6,0
5,0
4,5
4,0
3,5
3,0

30

2,5
2,0
1,5

1500

600
700
800
900
1000

Technical Data, Dimensions


and Description of Accessories

32

Valves

45

GEA MATRIX Control System/Thermostat Switches

52

2000

250
300
350
400
450
500

200

50
60
70
80
90
100

0,5

150

1,0
0,9
0,8
0,7
0,6

Wasservolumenstrom VW [l/h]
Abb. 25.3
GEA Top-Geko nderungen vorbehalten Stand 08/00 (D)

25

PR-2010-0107-GB Subject to modifications Status 12/2011

Unit Description

Single basic unit 2-pipe system

GEA Cassette-Geko Fan Coil Unit

Basic unit with valve equipment and


lateral drain pan (installation by others)

Single/Double/Big Single
Cassette unit
Heating/cooling/filtering
2/4-pipe system,
ceiling installation.
Unit made of galvanized metal
sheet, flocked on the outside,
with polyethylene sound
insulation and thermal insulation
on the inside (electrical and valve
equipment depends on functions
and requirements)

Fig. 2
Valve equipment
2 and 3-way valves with
actuators for

Valves

2-point 230/24 V~ 50/60 Hz,


3-point 230/24 V~ 50/60 Hz
continuous 24 V~,
control signal 0-10 V

Fig. 3
Electric equipment
Terminal box
Steel sheet electrical control box
(depending on unit model,
function and requirements)

Electric equipment

Fig. 4
Speed and thermostat switches

MATRIX control system

Controls and
regulation systems
according to
unit model, valves,
internal and external
electronic components

Fig. 5

PR-2010-0107-GB Subject to modifications Status 12/2011

Unit Description

GEA Cassette-Geko Fan Coil Unit

Heat exchanger Single


for warm and chilled water

Heat exchanger Big Single


for warm and chilled water

Heat exchanger:
Copper pipes with attached
aluminium fins, connection "
or " internal thread
(" connection on double and
Big Single 2-pipe units and in
cooling circuit on Double and
Big Single 4-pipe units), air vent/
drain valves.
Inlet temperature
Heating: max. 80 C
Cooling: min. 6 C
Max. operating pressure: 16 bar

Centrifugal fan

Lateral drain pan


for collecting condensate from
valve pipework and transporting
it to the main drain pan.

Fig. 6
Lateral drain pan

Centrifugal fan
with selectable AC or high
efficiency EC motors with
backward curved blades, single
inlet, with low-noise and
maintenance-free ball bearings,
IP44 protection type,
building material class B

Fig. 7

Main drain pan Single

Main drain pan Big Single

Main drain pan


made of foamed polystyrene with
integrated air intake nozzle for
fan, fire protection type B1

Design panel Double

Synthetic washable filter


medium, easy to change, filter
classification G1 (EN 779)

Fig. 8
Filter

Fig. 9
Design panel Single

Design panel Big Single

Design panel
Panel with attractive and
elegant design, consisting of:

Plastic frame and


air intake grille

Air vanes, individually


adjustable, optionally flocked

Wide range of colours

Fig. 10
PR-2010-0107-GB Subject to modifications Status 12/2011

EC-Technology: Keyword Energy Efficiency

GEA Cassette-Geko Fan Coil Unit

What are EC motors?


Regulation

Regulation

South

North pole

In such a way the motor operates at optimal conditions, resulting in maximum torque and minimum losses. The efficiency rate of the EC motors used by GEA is twice as high
as the comparable AC motors. The application of this technology in GEA fan coil units makes it possible to achieve
high efficiency rates for fan motors - especially in part-load
mode.

Coil

South pole

Coil

North pole

EC-motors (= electronically commutated motors) are DC


motors, where the rotor is not performed as a coil, like in
usual AC motors, but consists of a permanent magnet.
Electronic control of the motor enables continuous operation, where the integrated electronics ensures alternating
magnetic field which adjusts itself to the relevant speed
(refer to Fig. 11). As compared to mechanical commutating (brushes), there are no moving regulation components
that generate additional losses.

Current flow

Current flow

Fig. 11: Functional description of an EC motor


(electronical commutation)

This results in the reduction of electrical power consumption of an EC fan by up to 75%.


Comparison AC/EC fan - Single Cassette
100

Electrical power consumption [W]

90

80

70
-46%
60

AC fan CS1

50

AC fan CS2
AC fan CS3

40

47%

EC fan

-75%
30
-67%
20

-72%
-74%

10

0
200

300

400

500

600

700

800

900

Air volume flow [m/h]

Fig. 12: Comparison - electrical power consumption EC/AC fan

PR-2010-0107-GB Subject to modifications Status 12/2011

EC-Technology: Keyword Energy Efficiency

GEA Cassette-Geko Fan Coil Unit

Further aspects:

Continuous operation
Low generation of heat
Established and usual high motor quality
Same design for 50 and 60 Hz

Continuous GEA MATRIX controls


EC fans featuring continuous operation mode offer a few of benefits:
Room temperature control is performed with a higher accuracy, because occurring
temperature differences can be addressed with the accordingly adjusted fan speed.
This effect is assisted by using 3-point regulation valves (hydraulic method).
Variable fan speed control can compensate for fluctuating conditions of heating and
cooling medium. Example: season-related different inlet temperature of heat generator or fluctuating volume flow rates (hydraulics)
With standard AC fans the fan speed, which is optimal for room temperature control,
must be adapted to the available fan speed stages which often leads to rapid
increase of motor RPM and thus electrical power consumption.
With continuous speed regulation - "hard" fan speed changes are eliminated, which
provides additional acoustical comfort.
The GEA MATRIX controls uses these features by making the following functions
available, the customer can select between automatic and manual operation:

Automatic mode:

Room temperature control with continuous regulation (1.5-10 V) of a stepless EC fan.


The fan continuously operates within the minimum and maximum air volumes.
Using the display control panel OP50/51 a speed limitation can be activated (mute
function) in order to prevent an acoustic overshoot in automatic mode. This upper RPM
limit can be separately set for each control panel.
As an additional measure to avoid possible on site acoustical resonance occurrences,
up to three speed ranges can be hidden using MATRIX.PC software.

Manual mode:

OP 50/51 (control panel with display): continuous fan setting using rotary switch
between minimum and maximum air volume flow rate.
OP30/31 and OP44: (speed-stage control panel): 5-speed fan setting with speed
1 = minimum air volume flow rate and speed 5 = maximum air volume flow rate.
Percentage values (regarding maximum air volume flow rate) for speeds 2-4 are
pre-configured by the factory (default values) and can be changed on site by others
using MATRIX.PC.

PR-2010-0107-GB Subject to modifications Status 12/2011

EC-Technology: Keyword Energy Efficiency

GEA Cassette-Geko Fan Coil Unit

EUROVENT Energy Label


Within the framework of EU regulations (Eco-Design Directive) clear limits will be set
in the future with respect to the energy efficiency of available technological standards.
EUROVENT, as the European Association of Manufacturers of HVAC equipment,
anticipates this development by having published Energy Label for fan coil units to
include 7 energy efficiency classes (A to G) in January 2011.
In this case the energy efficiency is composed of time-weighted relationship between
cooling or heating output and consumed electrical power of the fan.
Fan coil units that are equipped with an energy-efficient temperature regulation system
(GEA MATRIX) and, depending on situation-related heating or cooling demand, react
with adjusted fan speed must consider the time share of the corresponding speed
stages for the evaluation of energy efficiency. For the description of time-connected
relationships EUROVENT uses coefficient A (maximum), B (medium) and C (minimum
speed). These indicators vary, depending on heating or cooling operation mode.
Fan stage

Coefficient

High (maximum)

Time percentage
Cooling

Heating

5%

5%

Medium

30 %

25 %

Low (minimum)

65 %

70 %

The energy efficiency relationship is composed of time-weighted shares and is


presented in the examples using the following formulas:
Cooling (FCEER):

A Q KHighSpeed + B Q KMediumSpeed + C Q KLowSpeed


FCEER = ----------------------------------------------------------------------------------------------------------------------------------------------A Pe HighSpeed + B Pe MediumSpeed + C QPe LowSpeed

Fan Coil Energy Efficiency Ratio - total cooling capacity


(= Energy efficiency relationship)

Heating (FCCOP):

A Q HHighSpeed + B Q HMediumSpeed + C Q HLowSpeed


FCCOP = ----------------------------------------------------------------------------------------------------------------------------------------------A PeHighSpeed + B Pe MediumSpeed + C Pe LowSpeed

Fan Coil Coefficient Of Performance


(= Performance coefficient of fan coil unit)

with QK = Total cooling capacity

mit QH = Heating capacity


mit Pe = Electrical power consumption of fan

Higher numerical value of these indicators stands for especially outstanding energy
efficiency.

10

PR-2010-0107-GB Subject to modifications Status 12/2011

EC-Technology: Keyword Energy Efficiency

GEA Cassette-Geko Fan Coil Unit

For the corresponding energy label the EUROVENT performs the following
classification:

Example:

FCEER (Total)

FCCOP

Class
A

Value
185

Class
A

Value
265

120

160

80

100

55

70

E
F

=
=

40
30

50

40

GEA-Single Cassette-Geko GSC1.UWW.SE5


[unit type code for a 4-pipe unit with an EC fan]
Cooling (FCEER)*:
5% 3, 21 + 30% 2, 61 + 65% 1, 99
FCEER = ----------------------------------------------------------------------------------------------------------- = 209 185
5% 0, 026 + 30% 0, 014 + 65% 0, 008

Label

CLASS A

Heating (FCCOP)*:
5% 5, 63 + 25% 4, 54 + 70% 3, 44 = 367 265
FCEER = ----------------------------------------------------------------------------------------------------------5% 0, 026 + 25% 0, 014 + 70% 0, 008

Label

CLASS A

*) Cooling, heating and electrical output in [kW] under EUROVENT conditions:


Cooling: air intake 27C / 47% r.h., chilled water 7 / 12C
Heating: air intake 20C, warm water 70 / 60C

Data for unit types as defined by the EUROVENT classification can be calculated using
our AiD@ layout software or provided by our sales representatives.

PR-2010-0107-GB Subject to modifications Status 12/2011

11

Chilled water
6/12 C
tL1 = +27 C
1 = 46 % r.h.

Sizes Single, Double and Big Single

Pressure drop

Cooling capacity

Pressure drop

Heating capacity

Pressure drop

Cooling capacity

Pressure drop

Heating capacity

QH
kW

pH
kPa

QK
kW

pK
kPa

QH
kW

pH
kPa

QK
kW

pK
kPa

[m /h]

pK
kPa

QH
kW

pH
kPa

250
310
460
330
480
660
480
710
850
250
330
480
660
850
530
740
1000
840
1220
1400
530
740
1000
1220
1400
620
920
1200
770
1150
1700
620
770
920
1150
1530

1.5
1.8
2.5
-

1.9
2.7
4.6
-

2.2
2.7
3.6
-

0.8
1.2
2.0
-

1.9
2.6
3.2
1.5
1.9
2.6
3.2
3.7
3.2
4.2
5.3
3.2
4.2
5.3
6.0
6.6
3.5
4.9
5.9
3.5
4.3
4.9
5.8
6.9

2.9
4.9
7.3
1.9
2.9
4.9
7.3
9.6
2.1
3.5
5.2
2.1
3.5
5.2
6.6
7.9
1.8
3.3
4.7
1.8
2.6
3.3
4.5
6.2

2.8
3.7
4.5
2.2
2.8
3.7
4.5
5.4
4.7
6.1
7.6
4.7
6.1
7.6
8.7
9.4
5.3
7.2
8.7
5.3
6.3
7.2
8.4
10.1

1.3
2.1
3.1
0.8
1.3
2.1
3.1
4.3
0.9
1.5
2.2
0.9
1.5
2.2
2.9
3.4
1.1
2.0
2.8
1.1
1.6
2.0
2.7
3.7

2.6
3.3
3.7
4.6
6.0
6.6
4.3
5.8
7.4
-

4.9
8.0
9.6
4.1
6.6
7.9
2.6
4.5
7.0
-

3.7
4.8
5.4
6.7
8.7
9.4
6.3
8.4
10.8
-

2.1
3.4
4.3
1.8
2.9
3.4
1.6
2.7
4.2
-

EC

AC
D
EC

AC
B
EC

1
Capacity stage

Terminal box
(select metal sheet electrical
switch box for GEA MATRIX)
(only for Single and Double)

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
7035 (light grey)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 7035 (light grey)

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
9003 (signal white)

Colour shade of choice


(design panel and unflocked
air vanes only)

Speed combination

123

min...max

Integrated TC

External TC

EC motor

12

. U

W .

25
26
35
26
34
43
35
45
49
19
26
35
43
49
30
39
47
40
50
54
29
37
45
50
53
23
35
42
29
41
51
23
29
34
40
48

Colour

3-speed motor

34
35
44
35
43
52
44
54
58
28
35
44
52
58
38
47
56
48
59
62
38
46
53
58
62
32
43
50
38
49
59
32
38
43
49
56

Motor thermal contact

dB(A) dB(A)

Metal sheet electric control box


with terminal strip or
for integrated control

Speed combination
123

Pressure drop

Heating capacity

Cooling capacity

Pressure drop

AC

Capacity stage 2

QK
kW

1
2
3
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max

Capacity stage 1

GEA Cassette-Geko Fan Coil Unit

Air ?ow rate

Speeds

Motor type

Model size

Capacity stage 0

Warm water
70/50 C
tL1 = +20 C

Sound pressure*

4-Pipe Chilled and Warm Water

Sound power

Recirculating Air Unit Cooling and Heating

Order code

For ambient conditions refer to page 34 "Acoustics"

PR-2010-0107-GB Subject to modifications Status 12/2011

Accessories/Valves

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling and Heating


4-Pipe Chilled and Warm Water, Sizes Single, Double and Big Single

Accessories
Spare filter
(Single and Big Single = 4 pieces, Double = 8 pieces)

Mounting bracket set

Model sizes S, D, B, 0 *

Order code

* 0 - if regardless of model size

Valves

MATRIX 500

MATRIX 2000

MATRIX 3000

Terminal box

Heating circuit

Actuator
2-point open/
close

Cooling/Heating

Operating voltage/circuit
230 V AC

1.60

24 V AC *

2.50

0.25

0.40

0.63

230 V AC
3-point open/
stop/close

kvs-values

Cooling circuit

continuous

24 V AC *

230 V AC with auxiliary switch

0/2...10 V = 24 V AC *

230 V AC Heating circuit 3-P


230 V AC Cooling circuit 2-P

24 V AC Heating circuit 3-P *


24 V AC Cooling circuit 2-P *

with shut off valve

1
0

1.00

1.60

2.50

4.00

kvs-values indicated above


for open/close actuators
(T,Q) only kvs 1.6 and 2.5

mixed

without shut off valve

Cooling

Heating

Sizes
Single

Double

Big Single

Order code
*

24 V transformer to be provided by others

PR-2010-0107-GB Subject to modifications Status 12/2011

13

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling and Heating


4-Pipe Chilled and Warm Water, Sizes Single, Double and Big Single

GEA MATRIX 500/2000 (not for EC motor)


System features:

Temperature assignment.: 10..30 C


Manual assignment of speed stage
Limitable setting range
Change-over between normal/economy mode on control panel
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2-point)
Temperature control via fan on/off and valve(s)
Status messages using LED
Group control
Group switch-off switch-off in case of fault
Temperature monitoring of motor
(TC required)

Additional features MATRIX 2000:

MATRIX OP5C
Control panel for MATRIX 500
Pure white casing, protection type IP20
Setpoint temperature setting
Speed stage selection switch 0-A (continuous)-1-2-3
Economy mode button
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

MATRIX OP21C
Control panel for MATRIX 2000, like control panel
OP5C, but with additional:
Speed stage selection switch 0-A (Auto)-1-2-3

MATRIX OP30C

System features MATRIX 3000

Control panel for MATRIX 3000


Pure white casing, protection type IP20
Setpoint temperature setting
Speed-stage selection switch 0-A(Auto)-1-2-3-4-5
(Stages 4 and 5 only in connection with EC motor)
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

Extended temperature assignment.: 7...40 C (default 10..30 C)


Temperature control via fan speed change and valve(s)
Network capability

GEA MATRIX 3000

Temperature assignment: 7 ... 40 C (default 10 ... 30 C)


Speed (stage) assignment
Limitable setting range
Change-over between normal/economy mode on control panel
Input for change-over between normal/economy mode or unit OFF
with frost protection
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2x2 or 2x3 point)
Temperature control via fan and/or valve(s)
Room frost protection
Status messages using LED
Status and fault signals using floating change-over contacts
Unit individual and group control
Isolation of individual units in case of fault
Temperature monitoring of motor
(with speed stage motors TC required)
Network capability

MATRIX OP31C
Like control panel OP30C, but with additional:
Normal/economy mode buttons

MATRIX OP44C
Like control panel OP31C, but with additional button for:
Change-over recirculating / mixed air mode
Change-over heating/cooling/automatic mode

MATRIX OP50C
Control panel for MATRIX 3000
Pure white casing, protection type IP20
Menu-guided controls using rotation navigator
LCD clear text display
Status messages using pictograms
Integrated indoor temperature sensor
Continuous speed assignment (only in connection
with EC motor)

MATRIX OP51C
Like control panel OP50C, but with additional:
Integrated weekly clock timer with a holiday and special days programme

MATRIX.IR
Infrared remote control for control system MATRIX
3000/4000
Black casing, RAL 9004
LCD display approx. 45x30 mm
Functions as in OP44C (without status, fault and
external control signals, no integrated indoor
temperature sensor, only 0-A-1-2-3 speed selection)
Maximum range 20 m

14

off

on
func

send

PR-2010-0107-GB Subject to modifications Status 12/2011

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling and Heating


4-Pipe Chilled and Warm Water, Sizes Single, Double and Big Single

Master
unit

Slave units
1-15

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM


230 V~
50 Hz

3x1.5 mm2 NYM

without return air sensor *

with return air sensor *

Cooling/heat.medium

Order code MATRIX 500

0 . 5

1 . T

0 . 5

1 . Z

Order code MATRIX 2000

2 . 2

1 . A

2 . 2

1 . Z

Master
unit

Slave units
1-15
With controller type:
D2 = 4x2x0.8 J-Y(ST)Y
D3/4 = e.g. 1x2x0.5 Helukabel

e.g. 2x2x0.5 Helukabel

3x1.5 mm2 NYM

Cooling/heat.medium

3x1.5 mm2 NYM

up to 3
speeds
continuous

Supply air temperature


limitation

Economy mode
contact input

Input unit OFF with


indoor frost protection

up to
3 speed

Unit group control with


operation and error
messaging

Stand alone unit


control with operating
and error messaging

Speed (stages)

230 V~
50 Hz

without return air sensor *

with return air sensor *

1
1
1

3 . 2

control panel

Order code
*

Alternative room temperature sensor (see page 53)

PR-2010-0107-GB Subject to modifications Status 12/2011

.
Master unit

. 2

. Z

Slave unit(s)

15

Chilled water
6/12 C
tL1 = +27 C
1 = 46 % r.h.

Recirculating Air Unit Cooling and Heating


2-Pipe Chilled and Electric Heating

Heating
capacity

Pressure
drop

Sound
power

Sound
pressure *

EC

Pressure
drop

Cooling
capacity

AC

Pressure
drop

EC

Heating
capacity

Pressure
drop

AC

Cooling
capacity

EC

Pressure
drop

250
310
460
330
480
660
480
710
850
250
330
480
660
850
480
570
660
710
850
530
740
1000
840
1220
1400
530
740
1000
1220
1400
840
1000
1110
1220
1400
620
920
1200
770
1150
1700
620
770
920
1150
1530
770
920
1150
1340
1530

Capacity stage 2

Heating
capacity

AC

1
2
3
1
2
3
1
2
3
min
2
3
4
max
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max
min
2
3
4
max

Capacity stage 1

Pressure
drop

[m3/h]

Capacity stage 0
Cooling
capacity

Air volume
flow

Speed

Motor type

Model size

Sizes Single, Double and Big Single

GEA Cassette-Geko Fan Coil Unit


Electric heating
230V~N/P/E
50Hz

QK
kW
1.5
1.8
2.5
-

pK
kPa
1.9
2.7
4.6
-

QH
kW
1.0
1.0
1.0
-

pH
kPa
-

QK
kW
2.4
3.3
4.2
1.9
2.4
3.3
4.2
5.0
4.0
5.3
6.8
4.0
5.3
6.8
8.0
8.8
4.8
6.7
8.2
4.8
5.8
6.7
7.9
9.7
-

pK
kPa
3.4
5.9
9.4
2.1
3.4
5.9
9.4
12.8
2.4
4.1
6.3
2.4
4.1
6.3
8.5
10.1
4.8
8.6
12.3
4.8
6.6
8.6
11.6
17.0
-

QH
kW
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
-

pH
kPa
-

QK
kW
3.3
4.4
5.0
3.3
3.8
4.2
4.4
5.0
5.9
8.0
8.8
5.9
6.8
7.4
8.0
8.8
5.8
7.9
10.4
5.8
6.7
7.9
8.9
9.7

pK
kPa
5.9
10.3
12.8
5.9
7.8
9.4
10.3
12.8
4.9
8.5
10.1
4.9
6.3
7.4
8.5
10.1
6.6
11.6
19.4
6.6
8.6
11.6
14.4
17.0

QH
kW
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

pH
kPa
-

dB(A)
34
35
44
35
43
52
44
54
58
28
35
44
52
58
44
48
52
54
58
38
47
56
48
59
62
38
46
53
58
62
49
53
56
58
62
32
43
50
38
49
59
32
38
43
49
56
38
43
49
53
56

dB(A)
25
26
35
26
34
43
35
45
49
19
26
35
43
49
35
39
43
45
49
30
39
47
40
50
54
29
37
45
50
53
40
45
47
50
53
23
35
42
29
41
51
23
29
34
40
48
29
34
40
44
48

Capacity stage
Colour

Motor thermal contact


Integrated TC

External TC

3-speed motor

EC motor

G
16

. U

E . K

Order code

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
6034 (pastel turquoise)
Design panel similar to RAL
9003 (signal white),
Air vanes flocked, similar to
RAL 6034 (pastel turquoise)
Design panel similar to RAL
9003 (signal white),
Air vanes similar to RAL
7035 (light grey)
Design panel similar to RAL
9003 (signal white),
Air vanes flocked, similar to
RAL 7035 (light grey)
Design panel similar to RAL
9003 (signal white),
Air vanes similar to RAL
9003 (signal white)
Colour shade of choice
(design panel and unflocked
air vanes only)

For ambient conditions refer to page 34 "Acoustics"

PR-2010-0107-GB Subject to modifications Status 12/2011

Accessories/Valves

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling and Heating


2-Pipe Chilled Water and E-Heating, Sizes Single, Double and Big Single

Accessories
Spare filter
(Single and Big Single = 4 pieces, Double = 8 pieces)

Mounting bracket set

Model sizes S, D, B, 0 *

Order code

* 0 - if regardless of model size

Terminal box

MATRIX 3000

MATRIX 2000

MATRIX 500

Valves

Actuator

Operating voltage/circuit

2-point open/
close

230 V AC

1.60

24 V AC *

2.50

230 V AC

0.25

0.40

0.63

1.00

1.60

2.50

4.00

3-point open/
stop/close

kvs-values

Cooling circuit

continuous

24 V AC *

Cooling

230 V AC with auxiliary switch

0/2...10 V = 24 V AC *

kvs-values as indicated
above for open/close
actuators (T,Q)
only kvs 1.6 and 2.5 possible

with shut off valve

without shut off valve

Sizes
Single

Double

Big Single

Order code
*

24 V transformer to be provided by others

PR-2010-0107-GB Subject to modifications Status 12/2011

17

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling and Heating


2-Pipe Chilled Water and E-Heating, Sizes Single, Double and Big Single

GEA MATRIX 500/2000 (not for EC motor)


System features:

Temperature assignment.: 10..30 C


Manual assignment of speed stage
Limitable setting range
Change-over between normal/economy mode on control panel
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2-point)
Temperature control via fan on/off and valve(s)
Status messages using LED
Group control
Group switch-off switch-off in case of fault
Temperature monitoring of motor
(TC required)

Additional features MATRIX 2000:

MATRIX OP5C
Control panel for MATRIX 500
Pure white casing, protection type IP20
Setpoint temperature setting
Speed stage selection switch 0-A (continuous)-1-2-3
Economy mode button
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

MATRIX OP21C
Control panel for MATRIX 2000, like control panel
OP5C, but with additional:
Speed stage selection switch 0-A (Auto)-1-2-3

MATRIX OP30C

System features MATRIX 3000

Control panel for MATRIX 3000


Pure white casing, protection type IP20
Setpoint temperature setting
Speed-stage selection switch 0-A(Auto)-1-2-3-4-5
(Stages 4 and 5 only in connection with EC motor)
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

Extended temperature assignment.: 7...40 C (default 10..30 C)


Temperature control via fan speed change and valve(s)
Network capability

GEA MATRIX 3000

Temperature assignment: 7 ... 40 C (default 10 ... 30 C)


Speed (stage) assignment
Limitable setting range
Change-over between normal/economy mode on control panel
Input for change-over between normal/economy mode or unit OFF
with frost protection
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2x2 or 2x3 point)
Temperature control via fan and/or valve(s)
Room frost protection
Status messages using LED
Status and fault signals using floating change-over contacts
Unit individual and group control
Isolation of individual units in case of fault
Temperature monitoring of motor
(with speed stage motors TC required)
Network capability

MATRIX OP31C
Like control panel OP30C, but with additional:
Normal/economy mode buttons

MATRIX OP44C
Like control panel OP31C, but with additional button for:
Change-over recirculating / mixed air mode
Change-over heating/cooling/automatic mode

MATRIX OP50C
Control panel for MATRIX 3000
Pure white casing, protection type IP20
Menu-guided controls using rotation navigator
LCD clear text display
Status messages using pictograms
Integrated indoor temperature sensor
Continuous speed assignment (only in connection
with EC motor)

MATRIX OP51C
Like control panel OP50C, but with additional:
Integrated weekly clock timer with a holiday and
special days programme

MATRIX.IR
Infrared remote control for control system MATRIX
3000/4000
Black casing, RAL 9004
LCD display approx. 45x30 mm
Functions as in OP44C (without status, fault and
external control signals, no integrated indoor temperature sensor, only 0-A-1-2-3 speed selection)
Maximum range 20 m

18

off

on
func

send

PR-2010-0107-GB Subject to modifications Status 12/2011

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling and Heating


2-Pipe Chilled Water and E-Heating, Sizes Single, Double and Big Single

Master
unit

230 V~
50 Hz

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

Slave units
1-15
With controller type:
D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM

3x2.5 mm2 NYM

3x1.5 mm2 NYM

3x2.5 mm2 NYM

230 V~
50 Hz

230 V~
50 Hz

with return air sensor *

Order code MATRIX 500


Order code MATRIX 2000

0 . 5

2 . T

0 . 5

2 . Z

2 . 2

1 . A

2 . 2

1 . Z

Master
unit

Slave units
1-15

230 V~
50 Hz

3x1.5 mm2 NYM

3x2.5 mm2 NYM

3x1.5 mm2 NYM

3x2.5 mm2 NYM

230 V~
50 Hz

Supply air temperature


limitation

Input unit OFF with


indoor frost protection

up to
3 speed

Cooling medium

230 V~
50 Hz

Economy mode contact


input

Unit group control with


operation and error
messaging

230 V~
50 Hz

Stand alone unit control


with operating and
error messaging

230 V~
50 Hz

With controller type:


D2 = 4x2x0.8 J-Y(ST)Y
D3/4 = e.g. 1x2x0.5 Helukabel

e.g. 2x2x0.5 Helukabel

Speed (stages)

Cooling medium

230 V~
50 Hz

without return air sensor *

up to 3
speeds
continuous

230 V~
50 Hz

without return air sensor *

with return air sensor *

1
1

3 . 2

control panel

Order code
*

Alternative room temperature sensor (see page 53)

PR-2010-0107-GB Subject to modifications Status 12/2011

.
Master unit

. 2

. Z

Slave unit(s)

19

Chilled water
6/12 C
tL1 = +27 C
1 = 46 % r.h.

Sizes Single, Double and Big Single

Pressure drop

Heating capacity

Pressure drop

Air fow rate

Cooling capacity

EC

Pressure drop

Heating capacity

AC

Pressure drop

EC

Cooling capacity

Pressure drop

AC

Heating capacity

EC

Capacity stage 2

Pressure drop

1
2
3
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max

[m3/h]
250
310
460
330
480
660
480
710
850
250
330
480
660
850
530
740
1000
840
1220
1400
530
740
1000
1220
1400
620
920
1200
770
1150
1700
620
770
920
1150
1530

Capacity stage 1

Cooling capacity

AC

Speeds

Model size

Motor type

Capacity stage 0

GEA Cassette-Geko Fan Coil Unit

QK

pK

QH

pH

QK

pK

QH

pH

QK

pK

QH

pH

kW
1.5
1.8
2.5
-

kPa
1.9
2.7
4.6
-

kW
2.9
3.5
4.7
-

kPa
0.6
0.8
1.4
-

kW
2.4
3.3
4.2
1.9
2.4
3.3
4.2
5.0
4.0
5.3
6.8
4.0
5.3
6.8
8.0
8.8
4.9
6.7
8.2
4.9
5.9
6.7
7.9
9.8

kPa
3.4
5.9
9.4
2.1
3.4
5.9
9.4
12.8
2.4
4.1
6.3
2.4
4.1
6.3
8.5
10.1
5.2
9.2
13.2
5.2
7.2
9.2
12.4
18.2

kW
4.4
6.0
7.6
3.5
4.4
6.0
7.6
9.2
7.3
9.7
12.4
7.3
9.7
12.4
14.4
16.0
8.6
11.8
14.6
8.6
10.2
11.8
14.2
17.5

kPa
0.9
1.7
2.6
0.6
0.9
1.7
2.6
3.7
0.7
1.1
1.8
0.7
1.1
1.8
2.4
2.8
1.4
2.4
3.6
1.4
1.8
2.4
3.4
4.9

kW
3.3
4.4
5.0
5.9
8.0
8.8
5.9
7.9
10.5
-

kPa
5.9
10.3
12.8
4.9
8.5
10.1
7.2
12.4
20.8
-

kW
6.0
8.1
9.2
10.8
14.4
16.0
10.2
14.2
18.9
-

kPa
1.7
2.9
3.7
1.4
2.4
2.8
1.8
3.4
5.7
-

1
Capacity stage

Terminal box
(select metal sheet electrical
switch box for GEA MATRIX)
(only for Single and Double)

Colour

Speed combination

123

min...max

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
7035 (light grey)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 7035 (light grey)

Integrated TC

External TC

1
5

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
9003 (signal white)

Colour shade of choice


(design panel and unflocked
air vanes only)

3-speed motor
EC motor

20

. U

C .

dB(A)
25
26
35
26
34
43
35
45
49
19
26
35
43
49
30
39
47
40
50
54
29
37
45
50
53
23
35
42
29
41
51
23
29
34
40
48

Motor thermal contact

dB(A)
34
35
44
35
43
52
44
54
58
28
35
44
52
58
38
47
56
48
59
62
38
46
53
58
62
32
43
50
38
49
59
32
38
43
49
56

Metal sheet electric control box


with terminal strip or
for integrated control

Speed combination
123

Sound pressure*

2-Pipe Chilled or Warm Water

Warm water
70/50 C
tL1 = +20 C

Sound power

Recirculating Air Unit Cooling or Heating

Order code

For ambient conditions refer to page 34 "Acoustics"

PR-2010-0107-GB Subject to modifications Status 12/2011

Accessories/Valves

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling or Heating


2-Pipe Chilled or Warm Water, Sizes Single, Double and Big Single

Accessories
Spare filter
(Single and Big Single = 4 pieces, Double = 8 pieces)

Mounting bracket set

Model sizes S, D, B, 0 *

Order code

* 0 - if regardless of model size

Terminal box

MATRIX 3000

MATRIX 2000

MATRIX 500

Valves

kvs-values

Heating circuit/cooling circuit


Actuator

Operating voltage/circuit

2-point open/
close

230 V AC

1.60

24 V AC *

2.50

230 V AC

0.25

0.40

0.63

1.00

1.60

2.50

4.00

3-point open/
stop/close

continuous

Cooling/Heating

24 V AC *

230 V AC with auxiliary switch

0/2...10 V = 24 V AC *

kvs-values as indicated
above for open/close
actuators (T,Q)
only kvs 1.6 and 2.5 possible

with shut off valve

without shut off valve

Sizes
Single

Double

Big Single

Order code
*

24 V transformer to be provided by others

PR-2010-0107-GB Subject to modifications Status 12/2011

21

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling or Heating


2-Pipe Chilled or Warm Water, Sizes Single, Double and Big Single

GEA MATRIX 500/2000 (not for EC motor)


System features:

Temperature assignment.: 10..30 C


Manual assignment of speed stage
Limitable setting range
Change-over between normal/economy mode on control panel
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2-point)
Temperature control via fan on/off and valve(s)
Status messages using LED
Group control
Group switch-off switch-off in case of fault
Temperature monitoring of motor
(TC required)

Additional features MATRIX 2000:

MATRIX OP5C
Control panel for MATRIX 500
Pure white casing, protection type IP20
Setpoint temperature setting
Speed stage selection switch 0-A (continuous)-1-2-3
Economy mode button
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

MATRIX OP21C
Control panel for MATRIX 2000, like control panel
OP5C, but with additional:
Speed stage selection switch 0-A (Auto)-1-2-3

MATRIX OP30C

System features MATRIX 3000

Control panel for MATRIX 3000


Pure white casing, protection type IP20
Setpoint temperature setting
Speed-stage selection switch 0-A(Auto)-1-2-3-4-5
(Stages 4 and 5 only in connection with EC motor)
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

Extended temperature assignment.: 7...40 C (default 10..30 C)


Temperature control via fan speed change and valve(s)
Network capability

GEA MATRIX 3000

Temperature assignment: 7 ... 40 C (default 10 ... 30 C)


Speed (stage) assignment
Limitable setting range
Change-over between normal/economy mode on control panel
Input for change-over between normal/economy mode or unit OFF
with frost protection
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2x2 or 2x3 point)
Temperature control via fan and/or valve(s)
Room frost protection
Status messages using LED
Status and fault signals using floating change-over contacts
Unit individual and group control
Isolation of individual units in case of fault
Temperature monitoring of motor
(with speed stage motors TC required)
Network capability

MATRIX OP31C
Like control panel OP30C, but with additional:
Normal/economy mode buttons

MATRIX OP44C
Like control panel OP31C, but with additional button for:
Change-over recirculating / mixed air mode
Change-over heating/cooling/automatic mode

MATRIX OP50C
Control panel for MATRIX 3000
Pure white casing, protection type IP20
Menu-guided controls using rotation navigator
LCD clear text display
Status messages using pictograms
Integrated indoor temperature sensor
Continuous speed assignment
(only in connection with EC motor)

MATRIX OP51C
Like control panel OP50C, but with additional:
Integrated weekly clock timer with a holiday and special days programme

MATRIX.IR
Infrared remote control for control system MATRIX
3000/4000
Black casing, RAL 9004
LCD display approx. 45x30 mm
Functions as in OP44C (without status, fault and
external control signals, no integrated indoor temperature sensor, only 0-A-1-2-3 speed selection)
Maximum range 20 m

22

off

on
func

send

PR-2010-0107-GB Subject to modifications Status 12/2011

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling or Heating


2-Pipe Chilled or Warm Water, Sizes Single, Double and Big Single

Master
unit

Slave units
1-15

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM

3x1.5 mm2 NYM


2x2x0.8 J-Y(ST)Y
230 V~
50 Hz

Cooling/heat.medium

flow sensor

Only MATRIX 500


without return air sensor *

with return air sensor *

Order code MATRIX 500

0 . 5

Order code MATRIX 2000

2 . 1

1 . T

0 . 5

1 . Z

1 . A

2 . 1

1 . Z

Master
unit

Slave units
1-15
With controller type:
D2 = 4x2x0.8 J-Y(ST)Y
D3/4 = e.g. 1x2x0.5 Helukabel

e.g. 2x2x0.5 Helukabel

3x1.5 mm2 NYM

3x1.5 mm2 NYM


2x2x0.8 J-Y(ST)Y

Cooling/heat.medium

Flow sensor

up to 3
speeds
continuous

Supply air temperature


limitation

Input unit OFF with


indoor frost protection

up to
3 speed

Economy mode
contact input

Unit group control with


status and fault signals

Stand alone unit control


with operating and
error messaging

Speed (stages)

230 V~
50 Hz

without return air sensor *

with return air sensor *

1
1
1

3 . 1

control panel

Order code
*

Alternative room temperature sensor (see page 53)

PR-2010-0107-GB Subject to modifications Status 12/2011

.
Master unit

. 1

. Z

Slave unit(s)

23

Recirculating Air Unit Heating

GEA Cassette-Geko Fan Coil Unit


Warm water
70/50 C
tL1 = +20 C

Pressure drop

Heating capacity

Pressure drop

Air ?ow rate

Cooling capacity

EC

Pressure drop

Heating capacity

AC

Pressure drop

EC

Cooling capacity

Pressure drop

AC

Heating capacity

EC

Capacity stage 2

Pressure drop

1
2
3
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max

[m3/h]
250
310
460
330
480
660
480
710
850
250
330
480
660
850
530
740
1000
840
1220
1400
530
740
1000
1220
1400
620
920
1200
770
1150
1700
620
770
920
1150
1530

Capacity stage 1

Cooling capacity

AC

Speeds

Motor type

Model size

Capacity stage 0

QK

pK

QH

pH

QK

pK

QH

pH

QK

pK

QH

pH

kW
-

kPa
-

kW
2.9
3.5
4.7
-

kPa
0.6
0.8
1.4
-

kW
-

kPa
-

kW
4.4
6.0
7.6
3.5
4.4
6.0
7.6
9.2
7.3
9.7
12.4
7.3
9.7
12.4
14.4
16.0
8.6
11.8
14.6
8.6
10.2
11.8
14.2
17.5

kPa
0.9
1.7
2.6
0.6
0.9
1.7
2.6
3.7
0.7
1.1
1.8
0.7
1.1
1.8
2.4
2.8
1.4
2.4
3.6
1.4
1.8
2.4
3.4
4.9

kW
-

kPa
-

kW
6.0
8.1
9.2
10.8
14.4
16.0
10.2
14.2
18.9
-

kPa
1.7
2.9
3.7
1.4
2.4
2.8
1.8
3.4
5.7
-

1
Capacity stage

Terminal box
(select metal sheet electrical
switch box for GEA MATRIX)
(only for Single and Double)

Colour

Speed combination

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
7035 (light grey)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 7035 (light grey)

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
9003 (signal white)

Colour shade of choice


(design panel and unflocked
air vanes only)

A
123

min...max

Integrated TC

External TC

3-speed motor

24

. U

W .

dB(A)
25
26
35
26
34
43
35
45
49
19
26
35
43
49
30
39
47
40
50
54
29
37
45
50
53
23
35
42
29
41
51
23
29
34
40
48

Motor thermal contact

dB(A)
34
35
44
35
43
52
44
54
58
28
35
44
52
58
38
47
56
48
59
62
38
46
53
58
62
32
43
50
38
49
59
32
38
43
49
56

Metal sheet electric control box


with terminal strip or
for integrated control

Speed combination
123

Sound pressure*

Sizes Single, Double and Big Single

Sound power

2-Pipe Warm Water

Order code

For ambient conditions refer to page 34 "Acoustics"

PR-2010-0107-GB Subject to modifications Status 12/2011

Accessories/Valves

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Heating


2-Pipe Warm Water, Sizes Single, Double and Big Single

Accessories
Spare filter
(Single and Big Single = 4 pieces, Double = 8 pieces)

Mounting bracket set

Model sizes S, D, B, 0 *

Order code

* 0 - if regardless of model size

Terminal box

MATRIX 3000

MATRIX 2000

MATRIX 500

Valves

Actuator

Operating voltage/circuit

2-point open/
close

230 V AC

1.60

24 V AC *

2.50

0.25

0.40

0.63

1.00

1.60

2.50

4.00

230 V AC
3-point open/
stop/close

kvs-values

Heating circuit

continuous

Heating

24 V AC *

230 V AC with auxiliary switch

0/2...10 V = 24 V AC *

kvs-values as indicated
above for open/close
actuators (T,Q)
only kvs 1.6 and 2.5 possible

with shut off valve

without shut off valve

Sizes
Single

Double

Big Single

Order code
*

24 V transformer to be provided by others

PR-2010-0107-GB Subject to modifications Status 12/2011

25

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Heating


2-Pipe Warm Water, Sizes Single, Double and Big Single

GEA MATRIX 500/2000 (not for EC motor)


System features:

Temperature assignment.: 10..30 C


Manual assignment of speed stage
Limitable setting range
Change-over between normal/economy mode on control panel
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2-point)
Temperature control via fan on/off and valve(s)
Status messages using LED
Group control
Group switch-off switch-off in case of fault
Temperature monitoring of motor
(TC required)

Additional features MATRIX 2000:

MATRIX OP5C
Control panel for MATRIX 500
Pure white casing, protection type IP20
Setpoint temperature setting
Speed stage selection switch 0-A (continuous)-1-2-3
Economy mode button
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

MATRIX OP21C
Control panel for MATRIX 2000, like control panel
OP5C, but with additional:
Speed stage selection switch 0-A (Auto)-1-2-3

MATRIX OP30C

System features MATRIX 3000

Control panel for MATRIX 3000


Pure white casing, protection type IP20
Setpoint temperature setting
Speed-stage selection switch 0-A(Auto)-1-2-3-4-5
(Stages 4 and 5 only in connection with EC motor)
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

Extended temperature assignment.: 7...40 C (default 10..30 C)


Temperature control via fan speed change and valve(s)
Network capability

GEA MATRIX 3000

Temperature assignment: 7 ... 40 C (default 10 ... 30 C)


Speed (stage) assignment
Limitable setting range
Change-over between normal/economy mode on control panel
Input for change-over between normal/economy mode or unit OFF
with frost protection
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2x2 or 2x3 point)
Temperature control via fan and/or valve(s)
Room frost protection
Status messages using LED
Status and fault signals using floating change-over contacts
Unit individual and group control
Isolation of individual units in case of fault
Temperature monitoring of motor
(with speed stage motors TC required)
Network capability

MATRIX OP31C
Like control panel OP30C, but with additional:
Normal/economy mode buttons

MATRIX OP44C
Like control panel OP31C, but with additional button for:
Change-over recirculating / mixed air mode
Change-over heating/cooling/automatic mode

MATRIX OP50C
Control panel for MATRIX 3000
Pure white casing, protection type IP20
Menu-guided controls using rotation navigator
LCD clear text display
Status messages using pictograms
Integrated indoor temperature sensor
Continuous speed assignment (only in connection
with EC motor)

MATRIX OP51C
Like control panel OP50C, but with additional:
Integrated weekly clock timer with a holiday and
special days programme

MATRIX.IR
Infrared remote control for control system MATRIX
3000/4000
Black casing, RAL 9004
LCD display approx. 45x30 mm
Functions as in OP44C (without status, fault and
external control signals, no integrated indoor temperature sensor, only 0-A-1-2-3 speed selection)
Maximum range 20 m

26

off

on
func

send

PR-2010-0107-GB Subject to modifications Status 12/2011

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Heating


2-Pipe Warm Water, Sizes Single, Double and Big Single

Master
unit

Slave units
1-15

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

230 V~
50 Hz

Heating medium

3x1.5 mm2 NYM

3x1.5 mm2 NYM

without return air sensor *

with return air sensor *

Order code MATRIX 500

0 . 5

1 . T

0 . 5

1 . Z

Order code MATRIX 2000

2 . 0

1 . A

2 . 0

1 . Z

Master
unit

Slave units
1-15
With controller type:
D2 = 4x2x0.8 J-Y(ST)Y
D3/4 = e.g. 1x2x0.5 Helukabel

e.g. 2x2x0.5 Helukabel

3x1.5 mm2 NYM

Heating medium

3x1.5 mm2 NYM

up to 3
speeds
continuous

Supply air temperature


limitation

Input unit OFF with


indoor frost protection

up to
3 speed

Economy mode contact


input

Unit group control with


status and fault signals

Stand alone unit control


with operating and
error messaging

Speed (stages)

230 V~
50 Hz

without return air sensor *

with return air sensor *

1
2

3 . 0

control panel

Order code

.
Master unit

PR-2010-0107-GB Subject to modifications Status 12/2011

. 0

. Z

Slave unit(s)

27

Chilled water
6/12 C
tL1 = +27 C
1 = 46 % r.h.

Sizes Single, Double and Big Single

Pressure drop

Heating capacity

Pressure drop

Air ?ow rate

Cooling capacity

EC

Pressure drop

Heating capacity

AC

Pressure drop

EC

Cooling capacity

Pressure drop

AC

Heating capacity

EC

Capacity stage 2

Pressure drop

1
2
3
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max
1
2
3
1
2
3
min
2
3
4
max

[m3/h]
250
310
460
330
480
660
480
710
850
250
330
480
660
850
530
740
1000
840
1220
1400
530
740
1000
1220
1400
620
920
1200
770
1150
1700
620
770
920
1150
1530

Capacity stage 1

Cooling capacity

AC

Speeds

Model size

Motor type

Capacity stage 0

GEA Cassette-Geko Fan Coil Unit

QK

pK

QH

pH

QK

pK

QH

pH

QK

pK

QH

pH

kW
1.5
1.8
2.5
-

kPa
1.9
2.7
4.6
-

kW
-

kPa
-

kW
2.4
3.3
4.2
1.9
2.4
3.3
4.2
5.0
4.0
5.3
6.8
4.0
5.3
6.8
8.0
8.8
4.9
6.7
8.2
4.9
5.9
6.7
7.9
9.8

kPa
3.4
5.9
9.4
2.1
3.4
5.9
9.4
12.8
2.4
4.1
6.3
2.4
4.1
6.3
8.5
10.1
5.2
9.2
13.2
5.2
7.2
9.2
12.4
18.2

kW
-

kPa
-

kW
3.3
4.4
5.0
5.9
8.0
8.8
5.9
7.9
10.5
-

kPa
5.9
10.3
12.8
4.9
8.5
10.1
7.2
12.4
20.8
-

kW
-

kPa
-

1
Capacity stage

Terminal box
(select metal sheet electrical
switch box for GEA MATRIX)
(only for Single and Double)

Colour

Speed combination

123

min...max

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 6034 (pastel turquoise)

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
7035 (light grey)

Design panel similar to RAL


9003 (signal white),
Air vanes flocked, similar to
RAL 7035 (light grey)

Integrated TC

Design panel similar to RAL


9003 (signal white),
Air vanes similar to RAL
9003 (signal white)

Colour shade of choice


(design panel and unflocked
air vanes only)

3-speed motor
External TC
EC motor

28

. U

0 .

dB(A)
25
26
35
26
34
43
35
45
49
19
26
35
43
49
30
39
47
40
50
54
29
37
45
50
53
23
35
42
29
41
51
23
29
34
40
48

Motor thermal contact

dB(A)
34
35
44
35
43
52
44
54
58
28
35
44
52
58
38
47
56
48
59
62
38
46
53
58
62
32
43
50
38
49
59
32
38
43
49
56

Metal sheet electric control box


with terminal strip or
for integrated control

Speed combination
123

Sound pressure*

2-Pipe Chilled Water

Sound power

Recirculating Air Unit Cooling

Order code

1
E

For ambient conditions refer to page 34 "Acoustics"

PR-2010-0107-GB Subject to modifications Status 12/2011

Accessories/Valves

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling


2-Pipe Chilled Water, Sizes Single, Double and Big Single

Accessories
Spare filter
(Single and Big Single = 4 pieces, Double = 8 pieces)

Mounting bracket set

Model sizes S, D, B, 0 *

Order code

* 0 - if regardless of model size

Terminal box

MATRIX 3000

MATRIX 2000

MATRIX 500

Valves

kvs-values

Cooling circuit

Cooling

Actuator

Operating voltage/circuit

2-point open/
close

230 V AC

1.60

24 V AC *

2.50

230 V AC

0.25

0.40

0.63

1.00

1.60

2.50

4.00

3-point open/
stop/close

continuous

24 V AC *

230 V AC with auxiliary switch

0/2...10 V = 24 V AC *

kvs-values as indicated
above for open/close
actuators (T,Q)
only kvs 1.6 and 2.5 possible

with shut off valve

without shut off valve

Sizes
Single

Double

Big Single

Order code
*

24 V transformer to be provided by others

PR-2010-0107-GB Subject to modifications Status 12/2011

29

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling


2-Pipe Chilled Water, Sizes Single, Double and Big Single

GEA MATRIX 500/2000 (not for EC motor)


System features:

Temperature assignment.: 10..30 C


Manual assignment of speed stage
Limitable setting range
Change-over between normal/economy mode on control panel
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2-point)
Temperature control via fan on/off and valve(s)
Status messages using LED
Group control
Group switch-off switch-off in case of fault
Temperature monitoring of motor
(TC required)

Additional features MATRIX 2000:

MATRIX OP5C
Control panel for MATRIX 500
Pure white casing, protection type IP20
Setpoint temperature setting
Speed stage selection switch 0-A (continuous)-1-2-3
Economy mode button
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

MATRIX OP21C
Control panel for MATRIX 2000, like control panel
OP5C, but with additional:
Speed stage selection switch 0-A (Auto)-1-2-3

MATRIX OP30C

System features MATRIX 3000

Control panel for MATRIX 3000


Pure white casing, protection type IP20
Setpoint temperature setting
Speed-stage selection switch 0-A(Auto)-1-2-3-4-5
(Stages 4 and 5 only in connection with EC motor)
LEDs for operation/fault/ext.control
Integrated indoor temperature sensor

Extended temperature assignment.: 7...40 C (default 10..30 C)


Temperature control via fan speed change and valve(s)
Network capability

GEA MATRIX 3000

Temperature assignment: 7 ... 40 C (default 10 ... 30 C)


Speed (stage) assignment
Limitable setting range
Change-over between normal/economy mode on control panel
Input for change-over between normal/economy mode or unit OFF
with frost protection
Indoor temperature measurement using control panel
External indoor temperature sensor can be connected
Valve control (2x2 or 2x3 point)
Temperature control via fan and/or valve(s)
Room frost protection
Status messages using LED
Status and fault signals using floating change-over contacts
Unit individual and group control
Isolation of individual units in case of fault
Temperature monitoring of motor
(with speed stage motors TC required)
Network capability

MATRIX OP31C
Like control panel OP30C, but with additional:
Normal/economy mode buttons

MATRIX OP44C
Like control panel OP31C, but with additional button for:
Change-over recirculating / mixed air mode
Change-over heating/cooling/automatic mode

MATRIX OP50C
Control panel for MATRIX 3000
Pure white casing, protection type IP20
Menu-guided controls using rotation navigator
LCD clear text display
Status messages using pictograms
Integrated indoor temperature sensor
Continuous speed assignment (only in connection
with EC motor)

MATRIX OP51C
Like control panel OP50C, but with additional:
Integrated weekly clock timer with a holiday and
special days programme

MATRIX.IR
Infrared remote control for control system MATRIX
3000/4000
Black casing, RAL 9004
LCD display approx. 45x30 mm
Functions as in OP44C (without status, fault and
external control signals, no integrated indoor temperature sensor, only 0-A-1-2-3 speed selection)
Maximum range 20 m

30

off

on
func

send

PR-2010-0107-GB Subject to modifications Status 12/2011

Control Components

GEA Cassette-Geko Fan Coil Unit

Recirculating Air Unit Cooling


2-Pipe Chilled Water, Sizes Single, Double and Big Single

Master
unit

Slave units
1-15

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

With controller type:


D0 = 7x2x0.8
D2 = 4x2x0.8 J-Y(ST)Y

3x1.5 mm2 NYM

3x1.5 mm2 NYM

230 V~
50 Hz

without return air sensor *

with return air sensor *

Cooling medium

Order code MATRIX 500

0 . 5

1 . T

0 . 5

1 . Z

Order code MATRIX 2000

2 . 0

1 . A

Master
unit

. 0

. Z

Slave units
1-15
With controller type:
D2 = 4x2x0.8 J-Y(ST)Y
D3/4 = e.g. 1x2x0.5 Helukabel

e.g. 2x2x0.5 Helukabel

3x1.5 mm2 NYM

Cooling medium

3x1.5 mm2 NYM

up to 3
speeds
continuous

Supply air temperature


limitation

Input unit OFF with


indoor frost protection

up to
3 speed

Economy mode
contact input

Unit group control with


status and fault signals

Stand alone unit control


with operating and
error messaging

Speed (stages)

230 V~
50 Hz

without return air sensor *

with return air sensor *

1
2

3 . 0

control panel

Regulation of external heating valve on request

Order code
*

Alternative room temperature sensor (see page 53)

PR-2010-0107-GB Subject to modifications Status 12/2011

.
Master unit

. 0

. Z

Slave unit(s)

31

Pressure Drops in Heat Exchanger

GEA Cassette-Geko Fan Coil Unit

for Warm and Chilled Water

Cooling, 2-pipe system

Cooling, 4-pipe system


25

25

20

S/0
S/1,2

6,0

5,0
4,5
4,0
3,5
3,0

5,0
4,5
4,0
3,5
3,0

700
800
900
1000

1500

2000

1500

2000

Water volume flow Vw [l/h]

600

50

2000

1500

700
800
900
1000

600

350
400
450
500

0,5

300

0,5
250

1,0
0,9
0,8
0,7
0,6

200

1,0
0,9
0,8
0,7
0,6
150

1,5

70
80
90
100

1,5

700
800
900
1000

2,0

350
400
450
500

2,0

2,5

300

2,5

250

Pressure loss [kPa]

6,0

B/1,2

200

D/1,2

60

D/1,2

10
9,0
8,0
7,0

B/1,2

50

Pressure loss [kPa]

10
9,0
8,0
7,0

15

150

15

S/0,1,2

SZ/CS*

70
80
90
100

SZ/CS*

60

20

Water volume flow Vw [l/h]

Heating, 2-pipe system

Heating, 4-pipe system

25

25

20

S/0

SZ/CS*

S/0,1,2

SZ/CS*

20
S/1,2

15

15

10
9,0
8,0
7,0
6,0

5,0
4,5
4,0
3,5
3,0

5,0
4,5
4,0
3,5
3,0

2,0

Water volume flow Vw [l/h]

600

350
400
450
500

2000

1500

700
800
900
1000

600

350
400
450
500

300

250

200

0,5
150

0,5
70
80
90
100

1,0
0,9
0,8
0,7
0,6
60

1,0
0,9
0,8
0,7
0,6

300

1,5

250

1,5

2,5

200

2,0

150

2,5

70
80
90
100

Pressure loss [kPa]

6,0

D/1,2
B/1,2

60

D/1,2

50

B/1,2

50

Pressure loss [kPa]

10
9,0
8,0
7,0

Water volume flow Vw [l/h]

* SZ = Size, CS = Capacity stage

Fig. 13: Pressure drop in heat exchanger for warm and chilled water

32

PR-2010-0107-GB Subject to modifications Status 12/2011

Example for Capacity Determination

GEA Cassette-Geko Fan Coil Unit

The tables on pages 6 to 25 specify heating capacity for pumped warm water 70/50 C and air intake temperature tL1= +20 C
as well as cooling capacity for chilled water 6/12 C and air intake condition tL1=+27 C/46 % r.h.
Capacity for other operating canditions can be determined using the correction factors on fold-out page 1.2
Selected unit type:
GC1S.UWW.K##
Sample calculation for Cassette-Geko FCU for cooling and heating
with 4-pipe system with a heating capacity of min. 4.5 kW for warm
See page 6
water 70/50/+15 C and cooling capacity of at least 2.0 kW for chilled
Sample speed 3 = 660 m3/h
water 8/12 (24 C/50 % r.h.)

Heating duty PWW* 70/50 C and tL1 = + 15 C

QH (70/50/+15)
fH (70/50/+15)

QH (70/50/+20)

=
=
=

new heating capacity


1.13 (see page 1.2)
4.5 (see page 6)

QH (70/50/+15) = fH (70/50/+15) QH (70/50/+20)

QH (70/50/+15) = 1.13 4.5 kW = 5.1 kW

Cooling duty PCW* 8/12 C and tL1= +24C/50% r.F.

QK (8/12/+24/50%)
=
fK (8/12/+24/50%) =

QK (6/12/+27/46%)
=

new cooling capacity


0.73 (see page 1.2)
3.2 (see page 6)

QK (8/12/+24/50%) = fK (8/12/+24/50%) QK (6/12/+27/46%)

QK (8/12/+24/50%) = 0.73 3.2 kW = 2.3 kW

* PWW = Pumped Warm Water; PCW = Pumped Chilled Water

Power and current consumption (units with AC motors)


Model size

3-speed motor
Power consumption [W]
Current consumption [A]
CS0
CS1
CS2
CS0
CS1
CS2
25

0.12

Speed

Air flow rate


[m3/h]

250

310

29

0.14

460

40

0.18

330

30

0.14

480

38

0.17

660

50

0.22

480

57

0.28

710

74

0.34

850

88

0.39

530

59

0.30

740

74

0.35

1000

100

0.44

840

111

0.54

1220

147

0.67

1400

176

0.78

620

42

0.37

920

74

0.49

1200

103

0.58

770

56

0.43

1150

98

0.57

1700

159

0.68

Single

Double

Big Single

Power and current consumption (units with EC motors)


140

1,0

Current consumption [A]

Power consumption [W]

120
100
80
60

D
B

40
20

0,8

0,6

0,4

0,2
S

0
0

500

1000

1500

Air flow rate [m/h]

PR-2010-0107-GB Subject to modifications Status 12/2011

500

1000

1500

Air flow rate [m/h]

33

Acoustical Data for Units with AC Motors

GEA Cassette-Geko Fan Coil Unit

Single

Double

Big Single

*)

Air flow
rate

Speed

Capacity
stage

Model

Sound power level (dB)

Sound pressure level *)

Octave centre frequency [Hz]

unrated

unrated

unrated

rated according to

[m3/
h]

63

125

250

500

1000

2000

4000

8000

[dB]

dB(A)

[dB]

dB(A)

NR

NC

250

27

43

33

31

30

23

<20

<20

44

34

35

25

22

20

310

27

41

37

33

31

23

<20

<20

44

35

36

26

22

20

460

33

48

46

42

38

30

<20

<20

51

44

42

35

30

28

330

22

42

39

33

26

<20

<20

<20

44

35

35

26

20

18

480

35

48

48

42

35

29

<20

<20

52

43

43

34

29

27

660

43

56

55

50

45

40

30

21

60

52

51

43

38

37

480

37

47

47

44

38

31

<20

<20

51

44

42

35

31

29

710

44

57

56

53

49

44

34

<20

61

54

52

45

40

39

850

47

62

59

57

53

49

41

28

65

58

56

49

44

43

530

30

44

43

37

29

<20

<20

24

47

38

39

30

24

22

740

38

52

52

46

40

32

23

27

55

47

47

39

34

32

1000

46

59

59

55

49

45

35

27

63

56

54

47

42

41

840

40

54

53

47

41

34

24

<20

57

48

49

40

35

33

1220

49

63

62

57

52

49

40

29

66

59

57

50

45

44

1400

53

67

65

60

56

53

45

35

70

62

62

54

48

48

620

<20

<20

39

33

<20

<20

<20

<20

40

32

31

23

20

17

920

36

43

45

42

40

29

<20

<20

49

43

41

35

31

29

1200

49

50

51

48

47

41

30

<20

56

50

48

42

38

36

770

30

43

41

38

31

<20

<20

<20

46

38

37

29

26

23

1150

47

49

50

47

47

40

31

<20

55

49

47

41

37

36

1700

63

63

59

55

56

51

43

34

68

59

60

51

47

46

Sound pressure level relates to a reverberation field of a 100 m3 room and reverberation time of 0.5 s
=for values extracted for the sample calculation, see page 29/30.

34

PR-2010-0107-GB Subject to modifications Status 12/2011

Acoustical Data for Units with EC Motors

min

Single

no

yes

Double

no

yes

Big Single

no

yes

Air flow
rate

Sound power level (dB)


Speed

Capacity
stage

Unit with
el. heating

Model

GEA Cassette-Geko Fan Coil Unit

Sound pressure level *)

Octave centre frequency [Hz]

unrated

unrated

unrated

rated according to

[m3/h]

63

125

250

500

1000

2000

4000

8000

[dB]

dB(A)

[dB]

dB(A)

NR

NC

250

21

36

33

28

23

<20

<20

<20

39

28

30

19

13

10

330

28

41

39

34

29

<20

<20

<20

44

35

35

26

20

18

480

36

49

48

43

39

32

24

<20

52

44

43

35

30

28

660

44

55

55

51

47

42

33

<20

60

52

51

43

38

37

max

850

50

61

61

58

54

50

40

26

66

58

57

49

44

43

min

250

21

36

33

28

23

<20

<20

<20

39

28

30

19

13

10

330

28

41

39

34

29

<20

<20

<20

44

35

35

26

20

18

480

36

49

48

43

39

32

24

<20

52

44

43

35

30

28

660

44

55

55

51

47

42

33

<20

60

52

51

43

38

37

max

850

50

61

61

58

54

50

40

26

66

58

57

49

44

43

min

480

36

49

48

43

39

32

24

<20

52

44

43

35

30

28

570

40

52

52

48

43

37

28

<20

56

48

47

39

34

33

660

44

55

55

51

47

42

33

<20

60

52

51

43

38

37

710

46

57

57

53

49

44

35

<20

61

54

52

45

40

39

max

850

50

61

61

58

54

50

40

26

66

58

57

49

44

43

min

530

28

42

40

34

29

<20

<20

<20

44

38

36

29

23

21

740

36

49

47

43

38

30

23

<20

52

46

43

37

32

30

1000

43

55

55

50

46

40

31

<20

59

53

51

45

40

38

1220

48

59

59

55

51

46

37

<20

64

58

56

50

45

44

max

1400

51

62

63

59

55

51

41

26

67

62

58

53

48

47

min

530

28

42

40

34

29

<20

<20

<20

44

38

36

29

23

21

740

36

49

47

43

38

30

23

<20

52

46

43

37

32

30

1000

43

55

55

50

46

40

31

<20

59

53

51

45

40

38

1220

48

59

59

55

51

46

37

<20

64

58

56

50

45

44

max

1400

51

62

63

59

55

51

41

26

67

62

58

53

48

47

min

840

39

51

50

46

41

34

26

<20

55

49

46

40

35

34

1000

43

55

55

50

46

40

31

<20

59

53

51

45

40

38

1110

46

57

57

53

49

43

34

<20

61

56

52

47

42

41

1220

48

59

59

55

51

46

37

<20

64

58

56

50

45

44

max

1400

51

62

63

59

55

51

41

26

67

62

58

53

48

47

min

620

<20

<20

38

32

<20

<20

<20

<20

39

32

30

23

19

16

770

30

43

41

38

31

<20

<20

<20

46

38

37

29

24

22

920

36

43

45

42

40

29

<20

<20

49

43

40

34

29

27

1150

47

49

49

46

46

40

31

<20

55

49

46

40

36

34

max

1530

50

54

55

53

53

48

37

27

61

56

53

48

44

43

min

620

<20

<20

38

32

<20

<20

<20

<20

39

32

30

23

19

16

770

30

43

41

38

31

<20

<20

<20

46

38

37

29

24

22

920

36

43

45

42

40

29

<20

<20

49

43

40

34

29

27

1150

47

49

49

46

46

40

31

<20

55

49

46

40

36

34

max

1530

50

54

55

53

53

48

37

27

61

56

53

48

44

43

min

770

30

43

41

38

31

<20

<20

<20

46

38

37

29

24

22

920

36

43

45

42

40

29

<20

<20

49

43

40

34

29

27

1150

47

49

49

46

46

40

31

<20

55

49

46

40

36

34

1340

47

51

52

49

49

44

33

24

57

53

48

44

40

39

max

1530

50

54

55

53

53

48

37

27

61

56

53

48

44

43

PR-2010-0107-GB Subject to modifications Status 12/2011

35

GEA Cassette-Geko Fan Coil Unit

The sound pressure specifications in the tables


on pages 6-25 and 28 apply to the reverberant
sound field of a room with a volume of 100 m3
and a reverberation time of 0.5 s.

Increase in sound level (dB)

LPges. = LP + 4.5 dB = 31 dB(A) + 4.5 dB


= 35.5 dB(A)
The value which is the minimum requirement,
according to Tab. 1, is therefore fulfilled.

To determine the anticipated sound pressure


level at the installation location, refer to the
A-rated sound power level in conjunction with
the conversion diagram in Fig. 16.

Table A-sound pressure level LP 1) guide


values from VDI 2081

Example:

Room type

Three Cassette Gekos of type GCS1 are to be


installed in a conference room with dimensions
(20 x 10 x 4m). They are to be operated at
stage 2, i.e. the sound power level should be
43 dB(A), see p. 28.

A-sound level
dB(A)

Home
*
(Hotel room) at night
35/30
Living space (daytime)
35
Auditoriums
TV studio
30
Concert hall
30
Opera house
30
Theatre
35
Cinema
40
Lecture theatre
40
Reading room
40
Seminar room
40
School classroom
40
Offices
Conference room
40
Restroom
40
Break room
40
Small office
40
Open-plan office
50
Church
35
Museum
40
Ticket office
45
Computer room
55
Laboratory
45
Restaurant
40
Kitchen
45

Determining the sound pressure level


1. Based on the room volume (800 m3),
absorption surface of approx. 100 m2 Sabin
is estimated in accordance with the diagram in
Fig. 16 Homes, offices, hotel rooms,
conference rooms.
2. The mean distance to the Cassette Gekos is
assumed to be approx. 3 m and the direction
coefficient to be 2, Fig. 15. The intersection of
the dotted sample lines in the diagram in
Fig. 12 produces the sound level difference:
L~12 dB
3. The anticipated A-rated sound pressure
level LP for a unit is thus:
LP = LW L = 43 dB(A) 12 dB = 31 dB(A)

to
to

0,5
0,5

25
25
25
30
30
35
35
35
35

1,5
2,0
1,5
1,0
1,0
1,0
1,0
1,0
1,0

35
35
35
35
45
25
35
40
40
40
552)
602)

1,0
0,5
0,5
0,5
0,5
3,0
1,5
1,5
1,5
2,0
1,0
1,5

5 6

8 10

Number of units

Mean reverberati
on time
(s)

**
30/25
30

10
9
8
7
6
5
4,5
4
3
2
1

Increase in sound level dB

The anticipated sound pressure level in the


room is thus:

Sound pressure level dB(A)

Fig. 14
Direction coefficients

Fig. 15
Direction coefficient 2
(hemispherical radiation):
Unit is mounted freely in the middle of a
surface
Direction coefficient 4
(quarter-spherical radiation):
Unit borders on two room surfaces
Direction coefficient 8
(eight-spherical radiation):
Unit borders on three room surfaces

Tab. 1

According to Fig. 14, appr. 4.5 dB.

* = minimum requirements
** = increased requirements
1)
Also see applicable building regulations, DIN standards
and VDI guidelines (e.g. DIN 4109, DIN 1946, VDI 2058);
2) Depending on use

Conversion of sound power level to sound pressure level

10
12
15

5
10
=
=

3
0,0
5

=
0,1
=
=
=

20

20

0,0

0,1

50
HoK
srapni
kta

0,2

0,4

30

800 m

25

8
4

Unitgrenzt
bordersanonzwei
two Raumflchen
room surfaces
Gert

Unit is mounted at any point in the middle of a surface

Gert ist frei in der Mitte einer Flche

4 5 6

8 10

15 20

Distance
from
source
Abstand
von the
der sound
Schallquelle
[ m[m]
]

30 40

60 70

50
Direction
factor
Richtungsfaktor

35

100
200
500
1000
2000
5000

ldd
ffie

Gert
grenzt on
an three
drei Raumflchen
Unit borders
room surfaces

0,5

Lar

groe
ceh
enl zw
Kuirrcc
imam
rdes
hhee
ns
Co
r ,, sk
nKfoen
m
leina
rfeerne
ell Kc
irhcuhr
cne
zrro
ecnh
u
m
o
es
De
em, T
sh, et
par
hateear
tme
tres
Kanut
fhsto
usree
rs
Mu
Msuic
sikrzo
imom
mes
r

2 Sabin]
2 Sabin
Absorption surface
Absorbtionsflche
[ m[m
]

Fac
Fatobrie
rik-s a
u.nSd
cshw
wim
imm
min
hagll p
enools
HW
C
om
lacsh
S
ohen
bat
surlro
sr,uom
hs
o
u
fefi,cB
m
mes
e
sr,o
R
Leesa
s
h
,oHto
ed
sinleg
etlerlz
oim
, Freoo
om
mes
rnm
ses
r
hs, tT
udVios
s t ud
ios
RRau
dnido
fusnt
kusd
tuido
io
ss

re. i
FFr

Sound level differenceL=LW


L=LW
- LP
[dB]
Schallpegelgifferenz
- LP
[dB]

100

200

500

1000 2000

5000 10000

30000

Room
volume[ [m
Raumvolumen
m 33]]
Absorption factor
A wall surface that absorbs all sound waves that hit it has an absorption
factor of = 1. The above m values represent the relationship between
the actual and ideal absorption performance of a wall. They represent
mean values.
Absorption surface m2 (Sabin)
This is the surface that completely absorbs all sound waves that hit it.
It is not identical to the entire room surface.

Fig. 16

36

PR-2010-0107-GB Subject to modifications Status 12/2011

NR and NC Limiting Curves

GEA Cassette-Geko Fan Coil Unit

Limiting curves

Although various noise-rating curves exist, NR (Noise Rating)


curves as per Fig. 30-2 have become accepted internationally.
NC curves (Noise Criteria) are now only used for noise rating in
the USA as per Fig. 30-3.
If the observance of a particular NR or NC limiting curve is
required for a room, the measured sound pressure must not
exceed this limiting curve in any octave.
The sum level across all eight octaves as per DIN is always
around 7 to 10 dB higher than the limiting curve value. In the case
of air treatment units, the difference of the sound pressure level
in the medium is 5 dB(A) because the spectrum of these sounds
does not always reach the same limiting curve in all octaves.

ISO
evaluation curves
ISO NR
NR-Bewertungskurven
90

80
NR 80

Sound
pressure in
level
Schalldruckpegel
dB in dB

If narrower frequency components or outstanding single tones


with high intensity peaks occur in a broad frequency range (e.g.
on a fan), the dB(A) specification (sum level) is not sufficient as it
does not sufficiently address the annoying nature of the noise.
Thus, for the purposes of noise evaluation, so-called limiting
curves (curves which produce the same level of inconvenience)
are added that also take the combination of frequencies in the
noise into account.

70
70
60
60
50
50

40

40
30
30
NR28

20

20

10

0
63

125

250

500

1000

2000

4000

8000 Hz

Octave
band/medium frequency
Oktavband/Mittenfrequenz
Example
The requirement of NR 28 or NC 26 must be observed.
The basis is the tabulated data from page 28. In order to identify
the sound pressure level in the individual octaves, the sound
power values should be entered for Single, capacity stage 1 and
speed 2 in a table, see Table 2.

Fig. 17

NC
evaluation curves
NC-Bewertungskur
ven

In order to obtain the sound pressure levels in the individual


octaves, the value of 12 dB calculated on page 36 must be
subtracted from the sound power specifications entered in
Table 2. The new values attained can be entered in the
nomograms Fig. 17 (NR) or Fig. 18 (NC).

90

The highest point in the NR evaluation is NR 26 (1000 Hz) and


NC 24 (1000 Hz) in the NC evaluation.

70

Octave medium frequency for Single type,


capacity stage 1 and speed 2
1000 2000 4000 8000

Sound
pressure in
level
Schalldruckpegel
dB in dB

The requirement of NR 28 (NR 26 is below NR 28) or NC 26


(NC 24 is below NC 26), is thus maintained.

80

NC 70

60
60
50
50
40
40
30
30
NC 26

20

63

125

250

500

35

48

48

42

35

29

<20

<20

[dB]

12

12

12

12

12

12

12

12

[dB]

23

36

36

30

23

17

<8

<8

[dB]

20
NR 21

[Hz]
10

0
63

125

250

500

1000

2000

4000

8000 Hz

OctaveOktavband/Mittenfrequenz
band/medium frequency

Tab. 2
Fig. 18

PR-2010-0107-GB Subject to modifications Status 12/2011

37

Dimensions/Weight of Basic Units

GEA Cassette-Geko Fan Coil Unit

Single

575
600

207

370

120
289

65

341
660

1)

25
273

150

ca. 65

196

41 - 45 3)

263
340

230

2)

143

2)

100

ca.116

> 55 1)

575

660
2)
3)

Size limitation applies only to closed intermediate ceilings

Size of electrical switch box depends on unit configuration


Ceiling gap for design panel depends on the mounting type

Fig. 19

Double

575
1200

370

65

> 55 1)

1175

207
120

ca.116

2)

25
273
ca. 65

263
341

41 - 45 3)

340
797

230

196

2)

660

1260
883

100

289

150

150

1) Size limitation applies only to closed intermediate ceilings


2) Size of electrical switch box depends on unit configuration
3)
Ceiling gap for design panel depends on the mounting typ

Fig. 20

Big Single
822

822

714

714
120

411

207

> 75 1)

470

905

1)

Size limitation applies only to closed intermediate ceilings

30

150

42 - 46 2)

22

300

236

~ 181

100

340

905

2)

Ceiling gap for design panel depends on the mounting type

Fig. 21
38

PR-2010-0107-GB Subject to modifications Status 12/2011

Dimensions/Weight of Basic Units

GEA Cassette-Geko Fan Coil Unit

Mounting sizes for installation without mounting brackets

Pos. 1:

Outline of design panel

Pos. 2:

Outline of basic unit

Pos. 3:

Mounting drill holes

Fig. 22
Mounting sizes for installation with mounting brackets (accessory items ZGC0112)

Pos. 1:

Outline of design panel

Pos. 2:

Outline of basic unit

Pos. 3:

Mounting drill holes

Fig. 23
PR-2010-0107-GB Subject to modifications Status 12/2011

39

Dimensions/Weight of Basic Units

GEA Cassette-Geko Fan Coil Unit

Necessary clear opening in the intermediate ceiling


Depending on the selected section in the intermediate ceiling - the installation of the design panel requires a shadow
gap of around 4 mm running around the entire perimeter (for variant 1 - see Fig. 24), that can optionally be filled with a
standard enclosed sealing strip (for variant 2, see Fig. 24), or the design panel directly contacts the ceiling
(for variant 3, see Fig. 25).
Variant 1 and 2

Variant 3

L1(2), max

L3, max
L3, min

L1(2), min
b

b
1

4 mm

Fig. 24

Pos. 1:
Pos. 2:
Pos. 3:

Fig. 25

Ceiling panel
Design panel
Sealing strip (optional)

Pos. 1:
Pos. 2:

Clear opening
Variant 1 + 2

Variant 3

Ceiling panel
Design panel

Unit type Single

Unit type Double

Unit type Big Single

L1, min

[mm]

577 x 577

1177 x 577

824 x 824

L1, max

[mm]

600 x 600

1200 x 600

850 x 850

[mm]

575 x 575

1175 x 575

822 x 822

[mm]

660 x 660

1260 x 660

905 x 905

L3, min

[mm]

615 x 615

1215 x 615

862 x 862

L3, max

[mm]

640 x 640

1240 x 640

885 x 885

[mm]

575 x 575

1175 x 575

822 x 822

[mm]

660 x 660

1260 x 660

905 x 905

Weight
Unit Type

Single

Double

Big Single
1)

CS 1)

2-pipe [kg]

4-pipe [kg]

27

28

27

28

27

28

53

54

53

54

44

46

44

46

CS = capacity stage

The specified weight data apply to empty heat exchangers including a design panel

40

PR-2010-0107-GB Subject to modifications Status 12/2011

Dimensions/Weight of Basic Units

GEA Cassette-Geko Fan Coil Unit

Coil connections internal screw thread (warm/chilled water) 2-pipe Coil connections internal screw thread (warm/chilled water) 4-pipe
system (position of connections identical on single and double
system (position of connections identical on single and double
models)
models)

1 Opening for condensate hose 4 Size and position of electrical


switch box depend on unit configuration

1 Opening for condensate hose 2 Cooling 3 Heating 4 Size and


position of electrical switch box depend on unit configuration

Fig. 27

Fig. 26

Coil connections internal screw thread (warm/chilled water) 2-pipe Coil connections internal screw thread (warm/chilled water) 4-pipe
system on Big Single model
system on Big Single model

1 Opening for condensate hose

1 Opening for condensate hose 2 Cooling 3 Heating

Fig. 28

Fig. 29

Inlet line
[R]

Outlet line
[R]

Inlet line
[R]

Outlet line
[R]

Single

Double

Big Single

Outlet line [R]

Single

Double

Big Single

CS1)

Single

Double
Big Single

Water charge [l]


2-pipe system

1.5

2.1

2.1

4.2

2
4.62)

4.33)

4.62)

4.33)

1)

CS = capacity stage

2)

without e-heating

3)

with e-heating

Specified dimensions
are approximate
values. The total of
tolerances may result
in deviations of up to 10
mm (or more in some
cases).

4.2

Heating connection

Unit Type

Inlet line [R]

Unit Type

Cooling connection

Heating or cooling connections

Unit Type

PR-2010-0107-GB Subject to modifications Status 12/2011

Unit
type

Single

Double
Big
Single
1)

Water charge [l]


CS1)

4-pipe system
Heating

Cooling

0.8

1.5

0.8

1.5

0.8

1.5

1.6

3.0

1.6

3.0

1.6

3.1

1.6

3.1

Specified dimensions
are approximate
values. The total of
tolerances may result
in deviations of up to
10 mm (or more in
some cases).

CS = capacity stage

41

Air Distribution via External Air Outlets

GEA Cassette-Geko Fan Coil Unit

Spare filter set (1 set = 4 pieces) (1 set: with Single and Big Single = 4 units, with Double = 8
units) / Plastic filter with frame, quality class G1 (EN 779), regenerative filter medium
Order number

Single
ZGCS111

Double
ZGCD111

Big Single
ZGCB111

Fig. 30
Mounting bracket set, galvanized steel, rubber
2

3
4

Fig. 31

1 set comprises:
Mounting bracket with anti-vibration function (4 pieces, pos. 1)
M8 nuts with lock washers (8 pices, pos. 2)
Washers (8 pieces, pos. 3)
M8 nuts (8 pieces, pos. 4)
Order number ZGC0112

Supply of conditioned air


Both Single and Double units are
equipped with connections laterally at
the corners of the unit for primary air
that is supplied to the air suction inside
the unit.
The primary air openings enable to
insert a standard rectangular duct with
the dimensions of 110 x 55 mm.

Single
and
Double
Fig. 32

Big
Single
Fig. 33

Single
Big
Single

4
Fig. 34

Fig. 35

Double

There is a slight low pressure at the


primary air openings which can be
disregarded when planning the primary
air supply.
The maximum primary air volume flow
may not exceed 20 % of the unit air volume flow at medium speed. No more
than 100 m3/h may be supplied by each
primary air opening.
In Single unit type with electrical heater,
this type of primary air connection is
possible at one corner
(Fig. 29, Pos. 1).
In Single unit type without electrical
heater, this type of primary air connection is possible at two corners (Fig. 29,
Pos. 1 + Pos. 2).
In Big Single unit type, primary air connection is possible at three corners
(Fig. 29, Pos. 4).
In Double unit type, primary air connection is possible at three corners
(Fig. 31, Pos. 3).
Installation is quick and easy. The
opening in the unit for a standard
rectangular duct is prepared by
removing the pre-punched sheet-metal
part and the insulation on the inner face
of the unit. The duct can be easily and
permanently secured using the sheetmetal part removed previously as a
mounting bracket.
Note:
Primary air is conditioned air i.e.
filtered and temperature controlled to
cover the base load.

3
Fig. 36
42

PR-2010-0107-GB Subject to modifications Status 12/2011

Accessories / Primary Air Supply

GEA Cassette-Geko Fan Coil Unit

The GEA Cassette Gekos each have 2 air distribution openings in the
unit side walls (See Fig. 32 and Fig. 33 for size and position).
These make it possible to install ducts by others (e.g. DN150 flexible
pipe) in order to be able to transfer supply air to distant parts of the
room, or even neighbouring rooms.
In this case, the unit's own air vanes can remain opened or be closed.

Single

However, note that the number of air outlets used will


affect the air volume flow and pressure at each air outlet.
Refer to the graphs below for the resulting air volume
flows through these air outlets, which are dependent on
the pressure differences in the duct system provided by
others.
The graphs apply to the maximum speed of the units.
Layout:

Ext. pressure [Pa]

With regard to the air-flow layout of the units, it should be


assumed that the use of air outlets does not affect the total air volume flow of the units. This means that the total
air volume flow through the air vanes and the external air
outlets corresponds to the data on pages 6 to 25.
Pos. 1:
Pos. 2:
Pos. 3:
Pos. 4:
Pos. 5:
Pos. 6:

CS0 - 1 discharge used


CS0 - 2 discharges used
CS1 - 1 discharge used
CS1 - 2 discharges used
CS2 - 1 discharge used
CS2 - 2 discharges used

Fig. 37

Air volume flow [m/h]

Double

Note:
All air ducts leading from the unit must be thermally insulated. If not, condensate may form on the outer face of
the ducts.

Ext. pressure [Pa]

Pos. 1:
Pos. 2:
Pos. 3:
Pos. 4:

CS0 - 1 discharge used


CS0 - 2 discharges used
CS1 - 1 discharge used
CS1 - 2 discharges used

Fig. 38

Air volume flow [m/h]

Big Single

Note:
All air ducts leading from the unit must be thermally insulated. If not, condensate may form on the outer face of
the ducts.

Ext. pressure [Pa]

Pos. 1:
Pos. 2:
Pos. 3:
Pos. 4:

Air volume flow [m/h]

PR-2010-0107-GB Subject to modifications Status 12/2011

CS0 - 1 discharge used


CS0 - 2 discharges used
CS1 - 1 discharge used
CS1 - 2 discharges used

Fig. 39

43

GEA Cassette-Geko Fan Coil Unit

Control Behaviour of Valves


On/off control mode

On/Off control mode


3-way valve

warmer

Temperature which is obtained


in room with on/off control
mode.

setpoint
colder

warmer
setpoint

Temperature which is obtained


in medium with on/off control
mode at air outlet

M
R

AB
B

colder

Fig. 40: (On/off control mode)

2-way valve

The valve is either open or


closed.

Set command for valve.


+ = valve open
0 = valve closed

0
M
R

Performance viewed over time

Fig. 41: (On/off control mode)

Modulating operation

Modulating control mode


3-way valve

warmer

Temperature which is obtained


in room with modulating control
mode.

setpoint
colder

warmer
setpoint

Temperature which is obtained


in medium with modulating
control mode at air outlet.

M
R

AB
B

colder

Fig. 42: (Modulating mode)

2-way valve

The valve setting corresponds


in percent to the mass flow
(0 . . .100 %).

+
0

Set command for valve.


+ = valve direction open
- = valve direction closed

R
V

Performance viewed over time

Fig. 43: (Modulating mode)

44

PR-2010-0107-GB Subject to modifications Status 12/2011

GEA Cassette-Geko Fan Coil Unit

Overview of Valves / Selection Table


The following selection table presents all available valve equipment variants with the main features and compatible standard
equipment.
The following symbols are used:
9 = Valve type compatible with the corresponding control panel
or electrical equipment.
= Valve type not compatible with the corresponding control panel or electrical equipment.
Valve type

Function
type

Control type

modulating

Voltage

230 V~

Compatible standard equipment

Control
system by
others

MATRIX
500

MATRIX
2000

MATRIX
3000

Thermostat
switch

(only
2-pipe system;
transfor. necessary by others)

(transfor.
necessary
by others)

AB
B

(only
2-pipe system)
N

modulating

24 V~

AB
B

230 V~

(2 potential free
floating auxiliary
switches)

AB

modulating

(only
2-pipe
system)

On/Off

230 V~

On/Off

24 V~

(transfor. necessary by others)

(transfor.
necessary
by others)

AB
B

AB
B

S
A

AB
B

continuous

24 V~
(analogue
signal
0..10 V)

PR-2010-0107-GB Subject to modifications Status 12/2011

45

Overview of Valves

GEA Cassette-Geko Fan Coil Unit

Valves (enclosed) with Modulating Actuator (230 V~ and 24 V~)/Modulating Mode

(82**)

(88**)

3-way valve

2 and 3-way valves with modulating actuator for water


side control (modulating control mode). Plastic
connection cable and motor casing, brass
(G 1/2"A) / red brass (G 3/4"A) valve body, stainless
steel spindle and cone.
Technical data

230 V~

16 bar

Max. allowed ambient


temperature

60 C

Max. water inlet


temperature

110 C

Operating voltage

0,7 VA
IP 43

120 s at 50 Hz
100 s at 60 Hz

Running time

24 V~/50/60 Hz

7 VA

Protection type

AB

230 V~/50/60 Hz

Power consumption

24 V~

Nominal pressure

150 s at 50 Hz
125 s at 60 Hz

Water with maximum 50 % glycol permissible.


Do not fit actuator upside down!

* Size for G 3/4" in brackets


** Size for 24 V in brackets

Connection values of valves

Fig. 44

kvs-value
[m3/h]

pmax1)
[kPa]

Valve
outer thread

0,25

1600/8002)

G 1/2" A

0,40

1600/8002)

G 1/2" A

0,63

1600/8002)

G 1/2" A

1,0

1200/2502)

G 1/2" A

1,6

1200/2502)

G 1/2" A

2,5

400/1002)

G 3/4" A

4,0

400/1002)

G 3/4" A

(82**)

(88**)

2-way valve

1)

Max. permissible pressure difference at which the valve


still shuts against the pressure (for 2-way valves)

2)

For 3-way valves

M
R

The control valves can be supplied loose either with or


without pipework.

Order Nr.

* Size for G 3/4" in brackets


** Size for 24 V in brackets

kvsvalue

2-way

Fig. 45



   
   
   
   
   

   

Pressure
loss p
[kPa]






2-way

3-way




Water volume
flow V [l/h]
 
!

 "#

















0,25

935.421

935.411

VR203.0#

0,40

935.422

935.412

VR204.0#

VR303.0#
VR304.0#

0,63

935.423

935.413

VR206.0#

VR306.0#

1,00

935.424

935.414

VR210.0#

VR310.0#

1,60

935.425

935.415

VR216.0#

VR316.0#

2,50

935.426

935.416

VR225.0#

VR325.0#

4,00

935.427

935.417

VR240.0#

VR340.0#

0,25

935.441

935.431

VN203.0#

0,40

935.442

935.432

VN204.0#

VN304.0#

0,63

935.443

935.433

VN206.0#

VN306.0#

Operating voltage 24 V~







46

3-way

Loose valves
with piping

Operating voltage 230 V~

   

Fig. 46

Loose valves

VN303.0#

1,00

935.444

935.434

VN210.0#

VN310.0#

1,60

935.445

935.435

VN216.0#

VN316.0#

2,50

935.446

935.436

VN225.0#

VN325.0#

4,00

935.447

935.437

VN240.0#

VN340.0#

With loose valves with pipework for a 4-pipe system, the order no. needs
to be supplemented by the reference number for the kvs value of the
heating valve, e.g. VC31610.0# (compare Unit type code on p. 55). The
# symbol is a place holder for the single (S), double (D) or "Big
Single" (B) sizes.
Note:
The maximum pressure loss in the heat exchanger with a fully opened
valve should not exceed 25 kPa in cooling mode and 20 kPa in heating
mode!

PR-2010-0107-GB Subject to modifications Status 12/2011

Overview of Valves

GEA Cassette-Geko Fan Coil Unit

Valves with Modulating Actuator (230 V~) and 2 Floating Auxiliary Switches/Modulating Mode

109

3-way valve

2 and 3-way valves with modulating actuator for


upstream control (modulating control mode).
Plastic connection cable and motor casing, brass
(G 1/2"A) / red brass (G 3/4"A) valve body, stainless
steel spindle and cone.

~ 116,5

Potential-free auxiliary switches:

AB

Switch S1

(signals valve 100 % open),

Switch S2

(signals valve position


0..100 % adjustable)

Technical data

40

M
R

AB
B

56 (66)

Nominal pressure

16 bar

Max. allowed ambient


temperature

60 C

Max. water inlet


temperature

110 C

Operating voltage

Size for G 3/4" in brackets


Fig. 47

230 V~/50/60 Hz

Power consumption

7 VA

Protection type

IP 43

Running time

150 s at 50 Hz (125 s at 60 Hz)


max. 5(1) A/250 V
max.100 mA/24 V

Load capacity of auxiliary


switches

109

2-way valve

Water with maximum 50 % glycol permissible.


Do not fit actuator upside down!

~ 116,5

Connection values of valves


kvs-value
[m3/h]

pmax
[kPa]

Valve
outer thread

0,25

16001)/8002)

G 1/2"A

0,40

16001)/8002)

G 1/2"A

0,63

16001)/8002)

G 1/2"A

1,00

12001)/2502)

G 1/2"A

1,60

12001)/2502)

G 1/2"A

2,50

4001)/1002)

G 3/4"A

4,00

4001)/1002)

G 3/4"A

M
R
56 (66)

Size for G 3/4" in brackets

1)

Max. permissible pressure difference at which the valve


still shuts against the pressure (for 2-way valves)

2)

For 3-way valves

Fig. 48
   


   
   
   
   
   

   

Pressure
loss p
[kPa]






The control valves can be supplied loose either with or


without pipework.
Order Nr.
kvsvalue







0,25

Loose valves

Loose valves
with piping

2-way

3-way

2-way

3-way

935.491

935.481

VC203.0#

VC303.0#

0,40

935.492

935.482

VC204.0#

VC304.0#

0,63

935.493

935.483

VC206.0#

VC306.0#

1,00

935.494

935.484

VC210.0#

VC310.0#

1,60

935.495

935.485

VC216.0#

VC316.0#

2,50

935.496

935.486

VC225.0#

VC325.0#

4,00

935.497

935.487

VC240.0#

VC340.0#

















Water volume
flow V [l/h]
 
!

 "#

Fig. 49

PR-2010-0107-GB Subject to modifications Status 12/2011

With loose valves with pipework for a 4-pipe system, the order no. needs
to be supplemented by the reference number for the kvs value of the
heating valve, e.g. VC31610.0# (compare Unit type code on p. 55). The
# symbol is a place holder for the single (S), double (D) or "Big
Single" (B) sizes.
Note:
The maximum pressure loss in the heat exchanger with a fully opened
valve should not exceed 25 kPa in cooling mode and 20 kPa in heating
mode!.

47

Overview of Valves

GEA Cassette-Geko Fan Coil Unit

Valves with Thermoelectrical Actuators (230 V~ and 24 V~)/On/Off Control Mode

3-way valve

42

2 and 3-way valves with thermoelectrical actuator for


water side control (on/off control mode).
Plastic connection cable and motor casing, brass valve
body, stainless steel spindle and cone.

~ 92

Technical data

AB

Max. allowed ambient


temperature

50 C

Max. water inlet


temperature

110 C
230 V~/50/60 Hz

Starting current

AB

Operating current

0,6 A

0,013 A

0,09 A
3 VA

3 VA

Protection type
56 (66)

Size for G 3/4" in brackets


Fig. 50

24 V~/50/60 Hz

0,3 A

Power consumption

24 V~

16 bar

Operating voltage

40

230 V~

Nominal pressure

IP 43

Running time

approx. 3 min

Water with maximum 50 % glycol permissible.


Do not fit actuator upside down!

Connection values of valves

2-way valve

~ 92

42

kvs-value
[m3/h]

pmax
[kPa]

Valve
outer thread.

1,60

2001)/1502)

G 1/2"A

2,50

2001)/ 502)

G 3/4"A

1)

Max. permissible pressure difference at which the valve


still shuts against the pressure (for 2-way valves)

2)

For 3-way valves

The control valves can be supplied loose either with or


without pipework.

Order Nr.

56 (66)

Size for G 3/4" in brackets

kvsvalue

Fig. 51

Loose valves
2-way

3-way

Loose valves
with piping
2-way

3-way

Operating voltage 230 V~

k vs= 1,6

30

k vs= 2,5

1,60

935.463

935.353

VT216.0#

VT316.0#

2,50

935.464

935.354

VT225.0#

VT325.0#

1,60

935.383

935.373

VQ216.0#

VQ316.0#

2,50

935.384

935.374

VQ225.0#

VQ325.0#

Operating voltage 24 V~

10
8
6
5
4
3

With loose valves with pipework for a 4-pipe system, the order no. needs
to be supplemented by the reference number for the kvs value of the
heating valve, e.g. VT32516.0# (compare Unit type code on p. 55). The
# symbol is a place holder for the single (S), double (D) or "Big
Single" (B) sizes.

Note:
The maximum pressure loss in the heat exchanger with a fully opened
valve should not exceed 25 kPa in cooling mode and 20 kPa in heating
mode!.

2000

1000

800

500
600

400

300

200

1
0,8
0,6
0,5
0,4
0,3
100

Pressure loss p
[kPa]
Druckverlust
p [kPa]

20

Water
volume flow VW V
[l/h](l/h)
Wasservolumenstrom

Fig. 52

48

PR-2010-0107-GB Subject to modifications Status 12/2011

Overview of Valves

GEA Cassette-Geko Fan Coil Unit

Valves with Continuous Actuator (24 V~, 0..10 V)

100

3-way valve

2 and 3-way valves with continuous actuator for water


side control (modulating control mode).

~ 92

Plastic connection cable and motor casing, brass


(G 1/2"A) / red brass (G 3/4"A) valve body, stainless
steel spindle and cone.
Technical data

AB
40

M
A

AB

16 bar

Max. allowed ambient


temperature

55 C

Max. water inlet


temperature

110 C

Operating voltage

24 V~/50/60 Hz

Analogue control signal

0..10 (2..10) V
1,4 VA

Power consumption

56 (66)

Nominal pressure

Protection type

Size for G 3/4" in brackets

IP 40

Running time

150 s at 50 Hz (125 s at 60 Hz)

Water with a maximum 50 % glycol permissible.


Do not fit actuator upside down!

Fig. 53

Connection values of valves


100

pmax1)
[kPa]

Valve
outer thread

0,25

16001)/8002)

G 1/2" A

0,40

16001)/8002)

G 1/2" A

0,63

16001)/8002)

G 1/2" A

1,00

12001)/2502)

G 1/2" A

1,60

12001)/2502)

G 1/2" A

2,50

4001)/1002)

G 3/4" A

4,00

4001)/1002)

G 3/4" A

~ 92

2-way valve

kvs-value
[m3/h]

M
R
V

56 (66)

1)

Max. permissible pressure difference at which the valve


still shuts against the pressure (for 2-way valves)

2)

For 3-way valves

Size for G 3/4" in brackets


Fig. 54

   


The control valves can be supplied loose either with or


without pipework.

   
   
   
   
   

   

Pressure
loss p
[kPa]






Order Nr.
kvsvalue

0,25








Loose valves

Loose valves
with piping

2-way

3-way

2-way

3-way

935.611

935.601

VS203.0#

VS303.0#

0,40

935.612

935.602

VS204.0#

VS304.0#

0,63

935.613

935.603

VS206.0#

VS306.0#

1,00

935.614

935.604

VS210.0#

VS310.0#

1,60

935.615

935.605

VS216.0#

VS316.0#

2,50

935.616

935.606

VS225.0#

VS325.0#

4,00

935.617

935.607

VS240.0#

VS340.0#

















Water volume
flow V [l/h]
 
!

 "#

Fig. 55

PR-2010-0107-GB Subject to modifications Status 12/2011

With loose valves with pipework for a 4-pipe system, the order no. needs
to be supplemented by the reference number for the kvs value of the
heating valve, e.g. VS31610.0# (compare Unit type code on p. 55). The
# symbol is a place holder for the single (S), double (D) or "Big
Single" (B) sizes.
Note:
The maximum pressure loss in the heat exchanger with a fully opened
valve should not exceed 25 kPa in cooling mode and 20 kPa in heating
mode!

49

Overview of Valves

GEA Cassette-Geko Fan Coil Unit

Shut off Valves


All GEA valve equipment is optionally available with flow
and water outlet shut-off valves.

kvs-value 1,45

SW19

These shut off the cooling or heating medium and also


regulate and balance the medium flow.

32

Depending on the nominal size of the control valve,


shut off valves with a kvs value of 1.45 or 2.20 are used.

3/4"

MNG

3/4"

Technical data:
Nominal pressure:
Max. inlet temperature:
pH value:

10 bar
130 C
8-9.5

Water with max. 50 % glycol is allowed as a medium.

51

The shut off valves are supplied as standard with cap


nuts and flat sealing inserts (solder fitting):

kvs-value 2,20
SW24

Control valve
Connection
thread

kvs values

Connection
thread

0.25-1.60

G 1/2" A

1.45

G 3/4" A

2.50-4.00

G 3/4" A

2.20

G 3/4" A

Solder
fitting for
Cu pipe

15
15

3/4"

3/4"

33

kvs values

Shut off valve

66

15

3/4"

Connection

18

Fig. 56
The required medium volume flow is set in accordance with the depicted flow diagrams.
The pre-setting corresponds to the number of turns to the left of the setting screw from the right stop position (valve closed).

50

PR-2010-0107-GB Subject to modifications Status 12/2011

Overview of Valves

GEA Cassette-Geko Fan Coil Unit

Shut off Valves

Pre-setting

kvs-value 1,45
 

 

  

  


Pressure drop p [kPa]















Water volume flow mW [kg/h]

Pre-setting

1/4

1/2

1 1/2

kv-values

0,07

0,13

0,22

0,32

0,43

0,65

0,85

1,10

1,25

1,40

1,45

kvs-value 2,20

Pre-setting
 

 

 

 

Pressure drop p [kPa]

















Water volume flow mW [kg/h]

Pre-setting

1/2

1 1/2

2 1/2

kv-values

0,2

0,4

0,6

1,0

1,5

1,7

2,0

2,2

Fig. 57

PR-2010-0107-GB Subject to modifications Status 12/2011

51

Regulation with Thermostat/Speed Switches, Controls by Others

GEA Cassette-Geko Fan Coil Unit

Terminal box with connections for Geko components.


Order code basic unit
Terminal box

Components such as fan(s) and valve(s) are wired in a terminal box in order to connect
them to a controller.
Depending on the unit application and the valve equipment that have been chosen, the
terminal box is in the form of a metal sheet hood or a metal sheet electrical switch box.
As shown in the adjacent illustration, selection takes place using the equipment type
code.

GCxx.xxx.Axx

Metal sheet electric switch box

NOTE!
Regulation system is not suitable for continuous (EC) motors!

GCxx.xxx.Kxx

Using thermostat and speed switches of series C easy control is provided for fan coil units
Fan

The switches can be used with:

Switch type
CMT (= 983 861)

4-pipe system
chilled and warm water
Cooling and
Heating

Return air
sensor

Order
symbol

without
with

0
5

without
with

0
5

without
with

0
5

without
with

0
5

CMS (= 983 860)

CMT

0
5

1 .

CET (= MCR2000)
CMT

2-pipe system
chilled water and
electric heating

CET
CMT with flow thermostat (Flow

Cooling or
Heating

thermostat is to be ordered under


separate order number 902 035 )

2-pipe system
chilled or warm water

CET with flow sensor


(Flow sensor included in package)

CMT
Heating

2-pipe system
warm water

CET

Cooling

2-pipe system
chilled water

without
with

CET

CMS

Alternatively to a return air sensor, a room temperature sensor can be connected to a CET type switch.
If a return air sensor is used, the fan must be operating in a continuous mode.

Please note:
In connection with thermostat and speed switches only 2-point valve actuators (T) can be
used.

Relay kit
is necessary if up to four fan coil unit are
switched in parellel. The mixing of different
Cassette-Geko types and sizes is allowed.

With kit

Without
kit

Order code

0 .

NOTE!
The following maximum number of units can be connected without a relay kit:
2 units of Double type or
2 units of Big-Single type or
4 units of Single type.
It is NOT allowed to mix unit types. The capacity range
of the commonly operated units has to be identical as well.

52

PR-2010-0107-GB Subject to modifications Status 12/2011

Regulation
with Thermostat/Miniature
Switches
GEA Cassette-Geko
Fan Coil Unit
Field-Provided Regulation by Others
Functions of thermostat switch / miniature switch:
Switch type

Functions

CMS

On / off switch
Fan speed selection switch 1-2-3

CMT

On / off switch
Fan speed selection switch 1-2-3
Setpoint setting for room temperature 5..35 C (mechanical limitation of setting
range)
Thermostat with neutral zone

CET

On / off switch
Fan speed selection switch 1-2-3
On / off switch for electrical heater
Setpoint setting for room temperature 5..35 C (mechanical limitation of setting
range)
Thermostat with neutral zone
Input for enabling via potential free contact by others
Room frost protection function
Connection possibilities for external room or return air sensor and flow sensor
Integrated room temperature sensor

Sensors

Functions

Room temperature
sensor
903 414

Thermistor sensor for on-wall installation


NTC sensor element; resistance coefficient at 25 C = 10 k
Plastic casing; white; similar to RAL 9010
Protection type IP 20; dimensions in mm (W x H x D): 84 x 84 x 22

Flow sensor
903 434

Thermistor sensor for installation at inlet with tightening strap


NTC sensor element; resistance coefficient at 25 C = 10 k
Max. ambient temperature 100 C
Protection class 2; cable length 2 m

Return air sensor


903 474

Thermistor sensor for installation in unit


NTC sensor element; resistance coefficient at 25 C = 10 k
Protection type IP 43; casing dimensions (D x L): 6 x 100 mm; cable length 1,5 m
Maximum ambient temperature 100 C

Flow thermostat for change-over between heating or cooling mode.


Capillary length 1000 mm
Switching points 19 C / 25 C 1K
Operating voltage 250 V AC 50/60 Hz
Dimensions in mm (W x H x D): 85 x 53 x 65
Flow thermostat in closed casing for wall mounting.
The measuring capillaries are mounted on the water inlet.
Additional sensors which are supplied loose and wired on-site by others should be ordered optionally (not in connection with the above-mentioned
switch types CMT and CMS).
Flow thermostat
902 035

NOTE!
Flow and return air sensors are integrated in the relevant controls packages and do
not have to be selected separately if ordered using the package number.

PR-2010-0107-GB Subject to modifications Status 12/2011

53

Controls System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

System Description
Overview

Vavle actuator type


2-point

MATRIX 500
The MATRIX 500 control system supports all basic functions (heating/ cooling) of the
recirculating air Cassette-Geko. The controller can be integrated into the following
system types:

2-pipe heating only systems


2-pipe cooling only systems
2-pipe heating or cooling systems (change over)
4-pipe heating and cooling systems

The speed can be set manually and the unit switched off via the control panel. Valves
with on/off or modulating control behaviour and a supply voltage of 230 V AC can be
activated to control the heating and/or cooling capacity.
Additionally, the MATRIX 500 enables monitoring of the fan motor via thermal
contacts with external leads as well as the condensate water level for cooling units
with a condensate pump. The connected sensors are monitored as well.

Norm/economy
switch
Fan speeds
selection switch

LEDs for
operation/
fault/
ext. control
Setpoint
temperature

The OP5 control panel enables the setpoint values to be set quickly and easily without
extensive prior experience. Mechanical limit stops can be used to limit the setting
range for the setpoint temperature and speed stage. Room temperature is measured
via a sensor integrated in the control panel. If the control panel is positioned in an
unfavourable location (such as by the door), an external temperature sensor or return
air sensor can be connected (not possible on changeover systems). System faults are
signalled centrally via the red malfunction LED. If economy mode is activated, it is
displayed via the yellow LED integrated into the button.
In addition to protection type IP20 (OP5 C), an IP54 control panel model (OP5 I) is
available for moist areas.
The connection in the unit is made via plug-in cage clamps. Electronics, fans and
valves (230V) are fused separately via two microfuses on the power supply. A prefuse of B 10A type must be supplied to provide the necessary circuit protection.
The MATRIX 500 can be used for controlling individual recirculating air units and also
recirculating air unit groups.

54

PR-2010-0107-GB Subject to modifications Status 12/2011

Controls System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

System Description
MATRIX 2000
Valve actuator
2-point

3-point

The Matrix 2000 control system is based on features incorporated in the MATRIX 500
system but also provides additional functions that can be summarized as follows:
Along with manual speed selection the fan control can be also carried out in a 3
speed mode based on the deviation of actual temperature from the setpoint.
With 2-pipe units modulating valve actuators can be controlled as well.
Besides, the control of valve actuators using 24V AC supply voltage is also
possible (transformer by others).
The direct connection of an external room temperature sensor is not possible with
change over units, but can be performed via a Global Module.
A fault message can also be received using a Global Module. Direct tapping is not
possible.
The OP5 control panel enables the setpoint values to be set quickly and easily without
extensive prior experience. Mechanical limit stops can be used to limit the setting
range for the setpoint temperature and speed stage. Room temperature is measured
via a sensor integrated in the control panel. If the control panel is positioned in an
unfavourable location (such as by the door), an external temperature sensor or return
air sensor can be connected (not possible on changeover systems). System faults are
signalled centrally via the red malfunction LED. If economy mode is activated, this is
displayed via the yellow LED integrated into the button.
In addition to protection type IP20 (OP5 C), an IP54 control panel model (OP5 I) is
available for moist areas.
The connection in the unit is made via plug-in cage clamps. Electronics, fans and
valves (230V) are fused separately via two microfuses on the power supply. A pre-fuse
of B 10A must be supplied to provide the necessary circuit protection.
The MATRIX 2000 can be used for controlling individual recirculation air units and also
recirculation air unit groups. The integrated MATRIX.Net bus system enables integration of up to 16 several groups to one network. The combination with MATRIX 3000
controllers and connection of Global Modules and communication intefaces is also
possible.
MATRIX 3000

Valve actuator

The Matrix 3000 control system is based on the MATRIX 2000 system and provides
additional functions. The main functions are as follows:

2-point

3-point

Operation and error messages are output via two change-over contacts on the unit.
The maximum load on the contacts at 230 V AC is 4 A ohmic / 2 A inductive.

The supply air temperature can be limited for heating and cooling demand. Fixed and
sliding limits can be defined.

Valves with modulating control behaviour can be applied on 4-pipe systems. Mixed
operation is also possible (on/off cooling valve / modulating heating valve or
modulating cooling valve / on/off heating valve).

An external temperature sensor or recirculation air sensor can be connected to all


system types.
An additional control input enables the following operating modes to be defined
externally:

Normal / economy mode

or

Unit OFF with frost protection

Various types of control panels are available. The spectrum ranges from a simple
variant with setpoint temperature and fan operating mode selection using infrared
remote control to a control panel with display. The display unit can also be supplied
with an integrated weekly timer.

PR-2010-0107-GB Subject to modifications Status 12/2011

55

Controls System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

Description of Features

Description of features
Unit type

Fan

MATRIX 500

MATRIX 2000

Matrix 3000

2-pipe systeme: only heating, only cooling; heating or cooling

4-pipe system: heating and cooling

up to 3 speeds

up to 5 speeds

9
9

Continuous (stepless EC motors)

Valve control

Temperature related fan miniature switching

Minimal speed 1

9
9

Motor monitoring with external thermal contacts

2- and 4-pipe system: On/Off actuators

2-pipe system: modulating actuator

4-pipe system: modulating actuators


External heating valve with cooling units with fan switch off
Electrical heating

9
9

1 speed

9
9

2 speed
Frost protection

Room frost protection

Summer / winter compensation


Supply air temperature limitation

9*

9*
9

Min. / max. limitation heating

Min. limitation cooling


Control inputs

Economy mode
Economy mode or gate or window contact

9*

Economy mode and gate or window contact and unit OFF and free operation mode

9*

9*

Outside temperature measurement

Via GEA MATRIX.AI

Inlet temperature measurement

Via local sensor connection

Return air temperature


measurement

Via local sensor connection

9**

Supply air temperature


measurement

Via local sensor connection

Messages

Alarm condensate level too high with unit switch off

9
9

Heating or cooling demand

Chiller control

up to 2 speeds via MATRIX.RF module

Control types

Room temperature control

9
9*

9*

9*

Operation message via change-over contact


Fault message via change-over contact

9
9*

Bus system GEA MATRIX.Net


Extendible with:

9
9

Supply air temperature control

GEA MATRIX.DI

GEA MATRIX.AI

GEA MATRIX.DO

9
9

GEA MATRIX.RF

GEA MATRIX.EM
GEA MATRIX.LON

Service tools

GEA MATRIX.PC

Control panels

GEA MATRIX OP5x


GEA MATRIX OP21x

*
**

56

9
9

GEA MATRIX OP30x

GEA MATRIX OP31x

GEA MATRIX OP44x

GEA MATRIX OP50x/51x

with additional module only


not with heating or cooling units

PR-2010-0107-GB Subject to modifications Status 12/2011

Controls System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

Installing Control Panels


As the control panel is split into two units, the the control panel cover only
needs to be snapped on the mounting plate during commissioning. This
provides optimum protection against dirt and damage for the control panels
during the construction phase.

The cable connection is made via cage clamps. This enables quick and easy
use of solid and flexible cores.

To mount the control panel over a standard in-wall socket, corresponding drill
holes need to be provided in the mounting plate.

The control panel can also be fitted directly onto the wall (cable laid under
plaster or in cavity wall).

IP54 control panels for moisture proof applications are available on request.

To prevent dirt accumulation or accidental operation, control panel covers


are available as accessories (See Fig. 54 page 58).

PR-2010-0107-GB Subject to modifications Status 12/2011

57

Controls System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

Sensor / Accessories
Room sensor, order no. 903.414
Thermistor sensor for on-wall mounting

NTC sensor element


Plastic casing: white, similar to RAL 9010
Resistance coefficient at 25 C = 10 k
IP 20 protection type
Dimensions in mm (W x H x D): 84 x 84 x 22

The 903.414 room sensor replaces the room sensor in


the MATRIX OP XXC control panels. The additional
sensor must be fitted if the control panel is integrated in
the Geko or mounted in a location that is unsuitable for
accurate temperature measurement.
Fig. 58

Control panel cover


White

order no. OPD.C

(for OP21C / OP30C / OP31C / OP44C)


Light grey

order no. OPD.C

(for OP21I / OP30I / OP31I / OP44I)


For covering the operating elements of the control panel.
The control panel cover is hung into the guide slots of the
control panel and protects the control panel from dirt
accumulation and accidental operation.
Fig. 59

58

PR-2010-0107-GB Subject to modifications Status 12/2011

Control System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

Global Modules
The global modules of the MATRIX control system are designated for input and output
of MATRIX system signals. The global modules enable the transmission of messages
and operation statuses to external units as well as control via these external units. The
modules can be integrated at any location within the MATRIX network. The network
may contain and simultaneously operate a maximum of 2 MATRIX modules of the
same type (DI,DO,AI) or 16 modules (LON).
The modules are supplied with the default factory configuration. Configurations with
other settings can be adjusted using the MATRIX.PC software.
.

Technical data:
Power supply
Protection type
Operation temperature
Fusing
Mounting
MATRIX.DI max. current consumption
MATRIX.DI dimensions
MATRIX.DO max. current consumption
MATRIX.DO contact assignment
MATRIX.DO dimensions
MATRIX.AI nominal current consumption
MATRIX.AI dimensions
MATRIX.LON nominal current
consumption
MATRIX.LON dimensions

24 V DC 15 %
IP 20
0 up to +45 C
10 A T
Mounting rail
0,1 A
106 mm x 90 mm x 58 mm
0,14 A
250 V/5 A (ohmic); 2 A (inductive)
160 mm x 90 mm x 58 mm
0,03 A
160 mm x 90 mm x 58 mm
0,045 A
106 mm x 90 mm x 58 mm

Digital input module MATRIX.DI


The digital input module MATRIX.DI is used to receive 8 independent digital control
signals.
Factory configuration:
Input

valid for

Kontakt geschlossen bewirkt

1
2
3
4
5
6
7
8

all groups
all groups
all groups
all groups
Group 0
Group 0
Group 0
Group 0

HVAC Mode Heating


HVAC Mode Cooling
Normal mode
Economy mode
Fan in speed 3
Secondary air damper close
Secondary air damper open
Mixed air operation 100 %

Digital output module MATRIX.DO


The module has 8 digital outputs with potential free change over contacts.
Factory configuration:
Output

valid for

Energized relay signals

1
2
3
4
5
6
7
8

all groups
Group 0
Group 0
Group 1
Group 1
Group 2
Group 2
all groups

Operation
Fault message
Frost message
Fault message
Frost message
Fault message
Frost message
Fault message

PR-2010-0107-GB Subject to modifications Status 12/2011

59

Control System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

Analogue input module MATRIX.AI


The module has 8 analogue inputs that are controlled using 010 V/2..10 V signals or
can be supplied with NTC sensors (10 k Ohm/25 C).
Factory configuration:
Input

valid for

Parameter

Type

Filter
value

Measurement
range

all groups

NTC

2
3
4
5
6
7
8

all groups
Group 0
Group 1
Group 2
Group 1
Group 2
Group 3

Outside
temperature
Inlet temperature
Room setpoint
Room setpoint
Room setpoint
Outside air ratio
Outside air ratio
Outside air ratio

NTC
0 ... 10 V
0 ... 10 V
0 ... 10 V
0 ... 10 V
0 ... 10 V
0 ... 10 V

0
0
0
0
0
0
0

10 30 C
10 30 C
10 30 C
0 ... 100 %
0 ... 100 %
0 ... 100 %

MATRIX.LON module
The MATRIX.LON communication module is part of the global modules of the GEA
MATRIX control system and is used for connecting the MATRIX control system to a
network structure in accordance with the LON WORKS standard. It enables the connection of air treatment components to a building management system or other facility
management systems. It also enables external systems such as dampers or lighting
systems to be controlled via the MATRIX OP50/51 control panel. The module can be
integrated into the MATRIX network at any point.
Group 2

Group 3

60

Group 4

Group 16

Group 1

PR-2010-0107-GB Subject to modifications Status 12/2011

Control System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

MATRIX.OP71 control panel for all groups


The MATRIX.OP71 control panel is designed to be operated from one central point. It
can integrated at any location within the MATRIX network and can simultaneously
serve up to 16 groups.
Up to 16 unit groups can be assigned to one cluster:
One unit group per each cluster
Each cluster with up to 16 unit groups.
Clear text menus and "push&turn" function enable easy handling during operation or
configuration. A maximum of 16 unit groups can be induvidually grouped to clusters.
Using the control panel the wanted setpoints for temperature, fan speed, etc. can be
assigned for each cluster. Thanks to the control unit features comprising all groups, the
necessary room or return air sensors are located in the respective groups (group
locations).
Local control panels (OP2xx, OP3xx, OP4xx, OP5x) can be additionally integrated in
individual groups. Their functional scope can be defined and adjusted using the control
panel for all groups. Thus, a relative daily setpoint can be entered via a local control
panel, whereas the OP71C setpoint is assigned as standard.
The integrated clock timer enables to assign 8 weekly programmes to clusters at any
sequence. Each weekly programme enables to enter four switching times per day
(2 x On/2 x Off), that can also be set to be valid for the whole day. Besides, it is possible
to set 8 special switching days with up to four switching times (2 x On/2 x Off) per
special switching day. Holidays / bank holidays can be set using the calendar annual
programme.
During holidays the unit can be set to operate in "unit off" or economy mode.
The summer / winter time switch over is performed automatically.
The control unit is currently supplied with 7 selectable languages:
German
English
French
Polish
Czech and
Hungarian.
Two different variants are available:

MATRIX.OP71C with IP 20 protection type; colour white (similar to RAL 9016)


MATRIXOP71I with IP 54 protection type; colour light grey (similar to RAL 7035).

PR-2010-0107-GB Subject to modifications Status 12/2011

61

Control System GEA MATRIX

GEA Cassette-Geko Fan Coil Unit

MATRIX.PC service software


Based on the functions of the MATRIX.PDA service tool, the MATRIX.PC service
software provides further comprehensive functions in the field of parameterization,
commissioning and data recording of the GEA MATRIX controller system.
The service software can be connected via the service interface that is integrated into
all control panels, controllers, global modules, the timer and the communication
modules. A USB interface is required on the PC. The enclosed adaptor establishes the
necessary connection between the PC and the service interface.
In addition to the functions of the MATRIX.PDA, the following main functions are also
available:

Online display of module, status and network data


Recording and saving of temperature developments and switching states of the
actuators with adjustable sample rate
Offline parameterization
Programming of the inputs and outputs provided for this purpose
(controllers, global modules)
Output of messages and network data
Parameterization of controller and control panel functions
Input of sensor correction factors

PC system requirements:

PC with 233 MHz clock speed or higher


20 MB of free hard drive space
Minimum screen resolution of 800x600 pixels
USB interface for CAN adaptor

The software can be run on the following operating systems:


Windows 98 Second Edition; Windows 2000; Windows XP
In addition to the program CD, the installation instructions and interface module for
connection to the USB port of the PC are also provided.

62

PR-2010-0107-GB Subject to modifications Status 12/2011

Unit Type Code

GEA Cassette-Geko Fan Coil Unit

Unit type code


G

1 . U

W. K

Controls package
0

3 . 0

1 . B

Valve code

Size

Controller type

Function type

S = Single
D = Double
B = Big Single

0 = Terminal box
/Matrix 500
2 = MATRIX 2000
3 = MATRIX 3000

2-pipe/4-pipe
T = Thermoelectric (230 V, on/off type)
Q = Thermoelectric (24 V, on/off type)
R = Modulating actuator
(230 V, modulating control)
N = Modulating actuator
(24 V, modulating control)
S = Continuous actuator
(24 V, analogue signal 0 - 10 V)
C = Modulating actuator
(230 V, modulating) + 2 contacts
Combinations (4-pipe)
1 = cooling = Thermoelectric
(230 V, on/off)
heating = Modulating actuator
(230 V, modulating)
2 = cooling = Modulating actuator
(230 V, modulating)
heating = Thermoelectric
(230 V, on/off)
3 = cooling = Thermoelectric
(24 V, on/off)
heating = Modulating actuator
(24 V, modulating)
4 = cooling = Modulating actuator
(24 V, modulating)
heating = Thermoelectric
(24 V, on/off)
5 = cooling = Modulating actuator
with 2 auxiliary switches
(230 V, modulating)
heating = Modulating actuator
(230 V, modulating)

Capacity stage

0 = Capacity stage 0
1 = Capacity stage 1
2 = Capacity stage 2

Controls package Nr.

Air flow function

A
B
C
D
E
F
N
P
Q
R
S
T
U
Z

Control panel

U = Recirculating air unit


Medium flow function
Only heating
0W
= Pumped Warm Water (PWW)
Cooling only
W0
= Pumped Chilled Water (PCW)
Cooling or heating
WC = Pumped chilled - warm water
Cooling and heating
WE = PCW - electric heating

WW

PCW - PWW

Fan speeds
Terminal box with terminal strip
A = Fan speed 1, 2, 3
Metal sheet electric switch box with
terminal strip or for integrated control
K = Fan speed 1, 2, 3

=
=
=
=
=
=
=
=
=
=
=
=
=
=

MATRIX OP21C
MATRIX OP30C
MATRIX OP31C
MATRIX OP44C
MATRIX OP50C
MATRIX OP51C
MATRIX.IR
CMS = 983 860
CMT = 983 861
CET = MCR 2000
MATRIX OP44C
MATRIX OP5C
MATRIX OP20C
without control panel

Unit type
Master unit, control panel
A = Single/master unit,
control panel supplied
C = Slave unit
without control panel
D = Slave unit
without control panel

Motor/thermal contacts

0 = Standard motor with integrated thermal contacts


1 = Standard motor with external thermal contacts

0 . 1

Water side connection

2
3
8
9

=
=
=
=

2-way (cooling), 2-way (heating)


3-way (cooling), 3-way (heating)
2-way (cooling), 3-way (heating)
3-way (cooling), 2-way (heating)

Colour

1 = Design panel similar to RAL 9003 (signal white)


Air vanes similar to RAL 6034 (pastel turqoise)
2 = Design panel similar to RAL 9003 (signal white)
Air vanes flocked, similar to RAL 6034 (pastel turqoise)
3 = Design panel similar to RAL 9003 (signal white)
Air vanes similar to RAL 7035 (light grey)
4 = Design panel similar to RAL 9003 (signal white)
Air vanes flocked, similar to RAL 7035 (light grey)
5 = Design panel similar to RAL 9003 (signal white)
Air vanes similar to RAL 9003 (signal white)
9 = other colour (only design panel and unflocked air vanes)

Circuit 1 (2-pipe cooling/heating, 4-pipe cooling)

03
04
06
10
16
25
40

=
=
=
=
=
=
=

Kvs-value 0.25
Kvs-value 0.40
Kvs-value 0.63
Kvs-value 1.0
Kvs-value 1.6
Kvs-value 2.5
Kvs-value 4.0

(R, N, S, C)
(R, N, S, C)
(R, N, S, C)
(R, N, S, C)
(R, N, S, C, T, Q)
(R, N, S, C, T, Q)
(R, N, S, C)

Circuit 2 (4-pipe heating)

03
04
06
10
16
25
40

=
=
=
=
=
=
=

Kvs-value 0.25
Kvs-value 0.40
Kvs-value 0.63
Kvs-value 1.0
Kvs-value 1.6
Kvs-value 2.5
Kvs-value 4.0

(R, N, S, C)
(R, N, S, C)
(R, N, S, C)
(R, N, S, C)
(R, N, S, C, T, Q)
(R, N, S, C, T, Q)
(R, N, S, C)

Shut off valves inlet and outlet

0
1

= without shut off valves


= with shut off valves

Size

S = Single
D = Double
B = Big Single

PR-2010-0107-GB Subject to modifications Status 12/2011

63

w w w.gea -air treatment .com