Sunteți pe pagina 1din 2

The Power behind.

Leaflet_ES48-1800-3 JBA05_en / rev. 1.0 / 06.2006 / Chad Tseng


www.deltaww.com
Power System ES 48/90JBA01
Main features
Up to 5.4 kW installed max. power
User friendly user (LED) operation interface
Wide input voltage range
Module design, front access for simple maintenance
Compact design, saves valuable floor space
Intelligent remote system monitoring and control
Applications
Telecom, wireless, datacom
Small power shelf for telecom power system
Description
Delta ES 48/90JBA01 series power system, consisting
of compact rack enclosures, 1800W rectifier modules
and related power distribution units, is under the control
of Control and Supervisory Unit. User can operate the
system via the user friendly LED interface. Meanwhile,
with the Delta power system management software.
Delta ES 48/90JBA01 series power system is designed
to meet the demands of todays and tomorrows wireless
and wire-line network applications. It combines a
compact, modular design and intelligent power features.
The ES 48/90JBA01 series power module is UL, TUV
approved and manufactured in our modern ISO 9001
and TL 9000 certified facility.
DELTA ELECTRONICS, INC.
3, Tung Yuan Road, Chungli Industral Park,
Taoyuan Hsien 320 Taiwan, R.O.C.
Phone: +886 3 452-6107 Fax: +886 3 452-7314 www.deltaww.com
Power System ES 48/90 JBA01
Technical Specifications
General
Efficiency 91 %
Losses, max. 148.5W (Per rectifiers)
Safety TUV/CE UL/cUL (Per rectifiers)
EMC EN 55022 Class A (Per rectifiers)
Cooling Fan cooled rectifiers
Input
AC connection &
Nominal voltage
L-N + PE : 220 VRMS
Range, full power 175 ... 275 VRMS
Range, reduced power 90 ... 175 VRMS
Frequency range 45 ... 66 Hz
Current nominal L-N + PE: 36 A ARMS @ 5.4kW
Inrush current < 12 Apeak per rectifier
Harmonic distort. THD < 5 %
Main switch AC Breaker
Output
Voltage, nominal Float: 54.0 VDC
Equalize: 56.0 VDC
Voltage range 40 ... 59.5 VDC
Voltage regulation < 0.1 %
Overvoltage protection 59.5 VDC
Ripple + spikes 100 mVp-p
Psophometric noise 2.0 mVRMS (weighted)
Output current 90 ADC @ 54 VDC
90 ADC @ 48 VDC
Power, maximum 5.4 kW
Load distribution
Load
Distribution
Power
Distribution
Unit
1. Main AC Breaker
2. Load Breaker 1x10, 2x20, 2x30A
3. Battery Breaker X 1 (100A Type)
4. Hall Sensor for Load current
measurement
5. The PDU follow Customer request
design
6. D/O eight relays output (From C
Type )
LVBD 100A
Mechanics
Construction Power Shelf
Height, overall 133.4 mm / 5.25 inch
Width, body 482.6 mm / 19 inch
Depth, overall 330.2 mm / 13 inch
Weight, system 22 kg / 48.5 lb (w/o Rectifier)
Weight, rectifiers ESR-48/30D A Type
3.1 kg / 6.83 lb
Environment
Ambient temperature -5 +50C / 23 122F
Relative humidity 95 % max, non cond.
Control and monitoring
Power system controller Delta Smart CSU
Display: LED display
(Show DCV/DCI)
Load Current
AC ON Rectifier
Fail Alarm (RFA)
Current Limit (CL)
Float/Equalize (FL/EQU)
Major Alarm (MAJ)
Minor Alarm (MIN)
High Voltage Alarm (HV)
High Voltage Shutdown (HVSD)
Low Voltage Alarm (LV)
Low Voltage Disconnect Open
(LVDS OPEN)
Fuse Blown (FUSE ALM)
AC Fail (AC FAIL)
Function System monitoring (remote/local)
Parameter setting
Temperature compensation
Boost / Equalize charge
Alarm relay definable
Remote Interface RS-232 Port (Delta RMS
software)
Web Server Function (Optional)
Accessories
Rectifier blank panel
Delta remote management software

S-ar putea să vă placă și