Sunteți pe pagina 1din 8

Te 20

Soft start units


Altistart 46 soft start - soft stop units
Standard duty applications
References
Power indicated on the motor rating plate in kW
Motor Starter
Motor power Factory Rating Starter Weight
230 V 400 V 440 V 500 V set (starter reference (1)
current current limit)
kW kW kW kW A A kg
4 7.5 7.5 9 15.2 17 ATS-46D17N 4.100
5.5 11 11 11 21 22 ATS-46D22N 4.100
7.5 15 15 18.5 28 32 ATS-46D32N 4.400
9 18.5 18.5 22 34 38 ATS-46D38N 4.400
11 22 22 30 42 47 ATS-46D47N 6.900
15 30 30 37 54 62 ATS-46D62N 6.900
18.5 37 37 45 68 75 ATS-46D75N 10.700
22 45 45 55 80 88 ATS-46D88N 10.700
30 55 55 75 98 110 ATS-46C11N 11.900
37 75 75 90 128 140 ATS-46C14N 16.000
45 90 90 110 160 170 ATS-46C17N 44.000
55 110 110 132 190 210 ATS-46C21N 44.000
75 132 132 160 236 250 ATS-46C25N 44.000
90 160 160 220 290 320 ATS-46C32N 45.000
110 220 220 250 367 410 ATS-46C41N 56.000
132 250 250 315 430 480 ATS-46C48N 62.000
160 315 355 400 547 590 ATS-46C59N 62.000
_ 355 400 _ 610 660 ATS-46C66N 62.000
220 400 500 500 725 790 ATS-46C79N 112.000
250 500 630 630 880 1000 ATS-46M10N 124.000
355 630 710 800 1130 1200 ATS-46M12N 124.000
(1) Reference for unit without dialogue option. The option is ordered as a separate item. See page 26.
Presentation, description :
pages 12
Characteristics :
pages 16 to 19
Dimensions :
pages 28 and 29
Schemes :
pages 30 to 35
ATS-46C79N
ATS-46D17N
ATS-46C17N
21
Te
Soft start units
Altistart 46 soft start - soft stop units
Standard duty applications
References
Power indicated on the motor rating plate in HP
Motor Starter
Motor power Factory Rating Starter Weight
208 V 230 V 460 V set (starter reference (1)
current current limit)
HP HP HP A A kg
3 5 10 15.2 17 ATS-46D17N 4.100
5 7.5 15 21 22 ATS-46D22N 4.100
7,5 10 20 28 32 ATS-46D32N 4.400
10 _ 25 34 38 ATS-46D38N 4.400
_ 15 30 42 47 ATS-46D47N 6.900
15 20 40 54 62 ATS-46D62N 6.900
20 25 50 68 75 ATS-46D75N 10.700
25 30 60 80 88 ATS-46D88N 10.700
30 40 75 98 110 ATS-46C11N 11.900
40 50 100 128 140 ATS-46C14N 16.000
50 60 125 160 170 ATS-46C17N 44.000
60 75 150 190 210 ATS-46C21N 44.000
75 100 200 236 250 ATS-46C25N 44.000
100 125 250 290 320 ATS-46C32N 45.000
125 150 300 367 410 ATS-46C41N 56.000
150 _ 350 430 480 ATS-46C48N 62.000
_ 200 400 547 590 ATS-46C59N 62.000
200 250 500 610 660 ATS-46C66N 62.000
250 300 600 725 790 ATS-46C79N 112.000
300 350 800 880 1000 ATS-46M10N 124.000
400 450 900 1130 1200 ATS-46M12N 124.000
(1) Reference for unit without dialogue option. The option is ordered as a separate item. See page 26.
Presentation, description :
pages 12
Characteristics :
pages 16 to 19
Dimensions :
pages 28 and 29
Schemes :
pages 30 to 35
ATS-46D47N
ATS-46C41N
Te 22
Soft start units
Altistart 46 soft start - soft stop units
Severe duty applications
References
Power indicated on the motor rating plate in kW
Motor Starter
Motor power Factory Rating Starter Weight
230 V 400 V 440 V 500 V set (starter reference (1)
current current limit)
kW kW kW kW A A kg
3 5.5 5.5 7.5 11 12 ATS-46D17N 4.100
4 7.5 7.5 9 15.2 17 ATS-46D22N 4.100
5.5 11 11 11 21 22 ATS-46D32N 4.400
7.5 15 15 18.5 28 32 ATS-46D38N 4.400
9 18.5 18.5 22 34 38 ATS-46D47N 6.900
11 22 22 30 42 47 ATS-46D62N 6.900
15 30 30 37 54 62 ATS-46D75N 10.700
18.5 37 37 45 68 75 ATS-46D88N 10.700
22 45 45 55 80 88 ATS-46C11N 11.900
30 55 55 75 98 110 ATS-46C14N 16.000
37 75 75 90 128 140 ATS-46C17N 44.000
45 90 90 110 160 170 ATS-46C21N 44.000
55 110 110 132 190 210 ATS-46C25N 44.000
75 132 132 160 236 250 ATS-46C32N 45.000
90 160 160 220 290 320 ATS-46C41N 56.000
110 220 220 250 367 410 ATS-46C48N 62.000
132 250 250 315 430 480 ATS-46C59N 62.000
160 315 355 400 547 590 ATS-46C66N 62.000
_ 355 400 _ 610 660 ATS-46C79N 112.000
220 400 500 500 725 790 ATS-46M10N 124.000
250 500 630 630 880 1000 ATS-46M12N 124.000
(1) Reference for unit without dialogue option. The option is ordered as a separate item. See page 26.
Presentation, description :
pages 12
Characteristics :
pages 16 to 19
Dimensions :
pages 28 and 29
Schemes :
pages 30 to 35
ATS-46D17N
ATS-46C79N
ATS-46C17N
23
Te
Soft start units
Altistart 46 soft start - soft stop units
Severe duty applications
References
Power indicated on the motor rating plate in HP
Motor Starter
Motor power Factory Rating Starter Weight
208 V 230 V 460 V set (starter reference (1)
current current limit)
HP HP HP A A kg
2 _ 7.5 11 12 ATS-46D17N 4.100
3 5 10 15.2 17 ATS-46D22N 4.100
5 7.5 15 21 22 ATS-46D32N 4.400
7,5 10 20 28 32 ATS-46D38N 4.400
10 _ 25 34 38 ATS-46D47N 6.900
_ 15 30 42 47 ATS-46D62N 6.900
15 20 40 54 62 ATS-46D75N 10.700
20 25 50 68 75 ATS-46D88N 10.700
25 30 60 80 88 ATS-46C11N 11.900
30 40 75 98 110 ATS-46C14N 16.000
40 50 100 128 140 ATS-46C17N 44.000
50 60 125 160 170 ATS-46C21N 44.000
60 75 150 190 210 ATS-46C25N 44.000
75 100 200 236 250 ATS-46C32N 45.000
100 125 250 290 320 ATS-46C41N 56.000
125 150 300 367 410 ATS-46C48N 62.000
150 _ 350 430 480 ATS-46C59N 62.000
_ 200 400 547 590 ATS-46C66N 62.000
200 250 500 610 660 ATS-46C79N 112.000
250 300 600 725 790 ATS-46M10N 124.000
300 350 800 880 1000 ATS-46M12N 124.000
(1) Reference for unit without dialogue option. The option is ordered as a separate item. See page 26.
Presentation, description :
pages 12
Characteristics :
pages 16 to 19
Dimensions :
pages 28 and 29
Schemes :
pages 30 to 35
ATS-46D47N
ATS-46C41N
24
Te
Soft start units
Altistart 46 soft start - soft stop units
Options : dialogue and communication
Description
Description of adjustment-display option
The VW3-G46101 option has four keys, one LED and three 7-segment displays on the front panel. A switch located at
the back is used to select configuration of the dialogue level. There are 3 dialogue levels and one locking level.
Selecting level 1 (for simple applications)
Monitoring parameters (values which can be displayed)
CoS Value of cos (power factor)
Lth Motor thermal state (as a %)
Ltr Load status (as a % of Tn)
Lcr Motor current (in A)
rdY Starter status
LPr Active power
Adjustment and configuration parameters Factory setting
In Motor nominal current (in A) See pages 60514/2 to 60514/5
It Motor limit current (in A) 300 % In
Acc Torque ramp on acceleration (in s) 10
dEc Torque ramp on deceleration (in s) 10
StY Stopping type freewheel
(freewheel, ramp, braking)
Edc Threshold to change to freewheel stopping 20
at the end of the deceleration ramp (% of Tn)
brc Braking torque level (as a %) 50
Selecting level 2 (for additional functions)
At this level, the adjustment and configuration parameters of the following additional functions are accessible :
Adjustment and configuration parameters Factory setting
bSt Voltage boost (as a % of U) oFF
tqo Initial starting torque (as a % of Tn) 10
tLI Maximum torque limit (as a % of Tn) oFF
ULL Underload threshold (as a % of Tn) oFF
tLS Start too long threshold (in s) oFF
thp Motor thermal protection (choice of classes) 10
Presentation, description :
page 12
Characteristics :
pages 16 to 19
References :
pages 20 to 27
Dimensions :
pages 28 and 29
25
Te
Soft start units
Altistart 46 soft start - soft stop units
Options : dialogue and communication
Description
Description of adjustment-display option (continued)
Selecting level 3 (to modify the factory configuration)
This level can be accessed independently of levels 1 and 2. When level 3 is selected, the user does not have access to
the parameters of levels 1 and 2, but can reconfigure the basic product.
Parameters which can be configured Factory setting
ArS Automatic restart oFF
CLp Torque control on
LSc Stator loss compensation (as a %) 50
O-4 Signal type in AO1 0 - 20
LI Assignment of LI LIA
Lo1 Assignment of LO1 tAI
OIL Current tripping threshold (as a % of In) oFF
Phr Phase rotation fault oFF
rI Assignment of relay R1 rIF
rth Reset motor thermal state no
Int Return to factory settings no
SSt Test on low power motor oFF
CSc Cascade starting oFF
tFr Operating time since Reset 0
(in h)
EbA Adjustment of braking (as a %) 20
Ao Assignment of analogue output AO1
ASc Scale A0
EbS Time-delay before restart 2
Assignment of I/O
Assignment of LI:
i Freewheel stopping : LIA (factory setting)
i Not assigned: oFF
i Acknowledgement of an external fault : LIE
i Preheating or braking of the motor to a stop : LIH
i Local override with communication option VW3-G46301 : LIL
i Inhibition of all protection devices : LII (on override function)
i Resetting of motor thermal fault : LIt
i Cascade starting and deceleration : LIC
i Fault reset : LIr
Assignment of LoI :
i Motor thermal fault alarm : tAI (factory setting)
i Not assigned : oFF
i Indication of current in the motor: rnI
Assignment rI (R1) :
i Fault relay : rIF
i Isolation relay : rII
Assignment of Ao (A01) :
i Motor current : Acr
i Not assigned : oFF
i Motor torque : Atr
i Motor thermal state : Ath
i Power factor (cos ) : Aco
i Active power : Aop
Selecting locking level
At this level, only the level 1 and 2 parameters can be read. No parameter can be modified.
Presentation, description :
page 12
Characteristics :
pages 16 to 19
References :
pages 20 to 27
Dimensions :
pages 28 and 29
26
Te
Soft start units
Altistart 46 soft start - soft stop units
Options : dialogue and communication
Description, references
Description of PC connection option
Option VW3-G46104 is used to set up a standard RS 232C point to point link between the Altistart and a PC.
The option comprises:
i an RS 232 interface that plugs into the front of the Altistart,
i 3"1/2 x 1,44 Mb diskettes containing software,
i a connecting cable (length 3 metres) with one 9-pin connector and one 9-pin to 25-pin adaptor.
The user-friendly software has been specially developed to ensure easy installation, maintenance and downloading. It
runs on any PC compatible with 486 processor and 8 Mb of RAM in a Windows 3.1 environment.
It enables:
i display of messages in 5 languages,
i adjustment and configuration without the product being connected,
i saving of setting to diskette or hard disk, and subsequent downloading,
i print-out of settings and access to parameters which cannot be accessed with the dialogue option,
i command, control and monitoring when connected to the soft start unit.
Description of the multidrop communication option
Option VW3-G46301 provides communication on a multidrop bus; it uses the UNI-TELWAY, Modbus RTU/Jbus and
Modbus ASCII protocols and gives access to all the Altistart functions.
The option comprises:
i an RS 485 interface that plugs into the front of the Altistart,
i a connecting cable (length 3 metres) with one 9-pin connector.
The PC software can be used to configure this option. To do this, the RS 485 plug-in interface is connected to the PC
by means of the RS 232 cable (also available under reference VY1-G461510).
Communication options
These options display parameters and modify the factory configuration, either locally via a plug-in option on the starter,
or via a PC link.
Description For starter units Reference Weight
kg
Display-adjustment option (1) ATS-46 all ratings VW3-G46101 0.250
Display-adjustment option (2) ATS-46 all ratings VW3-G46103 0.500
remote mounting kit
PC connection option ATS-46 all ratings VW3-G46104 0.500
for linking to a PC-type
microcomputer (RS 232 C standard)
with cable and PC software
Communication option for ATS-46 all ratings VY1-G461510 0.500
ASCII protocol for PC
PC software comprising 5 sets ATS-46 all ratings VW3-G46105 0.250
of 3" 1/2 diskettes containig the
same software for easy up-dating
Option for communication on multidrop bus
Communication option for ATS-46 all ratings VW3-G46301 0.500
UNI-TELWAY, Modbus RTU/Jbus,
Modbus ASCII protocols
with connecting cable TSX SCA 62
(1) Unit which can be plugged into the front panel of the Altistart 46. It can be flush-mounted remotely on an enclosure
door using the VW3-G46103 kit. From the end of 1998, it will be pre-fitted on the starter unit.
(2) Kit comprising a unit which plugs into the front panel of the Altistart 46, a connection cable (3 metres long) and a flush-
mounting kit.
Presentation, description:
page 12
Characteristics:
pages 16 to 19
References:
pages 20 to 27
Dimensions:
pages 28 and 29
VW3-G46101
VW3-G46301
27
Te
Soft start units
Altistart 46 soft start - soft stop units
Options : line chokes
References
Line chokes
These chokes limit harmonic interference on the mains supply. Their use is especially recommended when installing
several starters on the same supply.
For starter units Characteristics Reference Weight
kg
ATS-46D17N 1.7 mH - 15 A VZ1-L015UM17T 2.100
ATS-46D22N 0.8 mH - 30 A VZ1-L030U800T 4.100
ATS-46D32N and 46D38N 0.6 mH - 40 A VZ1-L040U600T 5.100
ATS-46D47N to 46D62N 0.35 mH - 70 A VZ1-L070U350T 8.000
ATS-46D75N to 46C14N 0.17mH - 150 A VZ1-L150U170T 14.960
ATS-46C17N to 46C25N 0.1 mH - 250 A VZ1-L250U100T 24.300
ATS-46C32N 0.075 mH - 325 A VZ1-L325U075T 28.900
ATS-46C41N to 46C48N 0.045 mH - 530 A VZ1-L530U045T 37.000
ATS-46C59N to 46M10N 0.024 mH - 1025 A VZ1-LM10U024T 66.000
ATS-46M12N 0.016 mH - 1435 A VZ1-LM14U016T 80.000
Presentation, description :
page 12
Characteristics :
pages 16 to 19
References :
pages 20 to 27
Dimensions :
pages 28 and 29