Sunteți pe pagina 1din 3

DLA Testing

Dielectric loss angle tests, also called dissipation factor, power factor or tan delta tests, determine
the insulation dielectric power loss by measuring the power angle between an applied AC
voltage and the resultant current. In the ideal insulator / dielectric, the power angle would be
90C as it is purely capacitive and non-conducting. However in real insulators, there is some
leakage current and resistive losses through the dielectric.
Relative increases in dielectric power losses are indicative of insulation deterioration and may
further accelerate degradation due to increased heating. Note that dielectric power loss does not
translate to dielectric strength, though there are often common causes for increases in power loss
and decreases in dielectric strength.
Relationship between Power Factor and Dissipation Factor

The cosine of the power angle () is called the power factor. The complement of is called the
loss angle and is denoted by in the diagram above. The power factor can also be approximated
by taking the tangent of (hence the name tan delta). This approximation is called the dissipation
factor (or loss tangent) and is roughly equal to the power factor between values of 0 and 0.08 pu,
which covers the majority of tests (in insulating oils of good condition, the dissipation factor /
power factor is in the order 0.005). Therefore, dissipation factor and power factor can be
considered interchangeable.
The exact relationship between dissipation factor (DF) and power factor (PF) is as follows:

The dissipation factor is essentially the ratio between the resistive and capacitive components of
the insulation and can be measured directly (e.g. with a capacitance bridge circuit - more on this
later). The lower the quality of the insulation condition, the more resistive it will appear and the
more power loss will be dissipated through it (in the form of heat), and thus the dissipation factor
will be higher.
The increase in the dissipation factor values as the test voltage is increased is called the "tip-up"
(dissipation factor or power factor tip-up).
Measurement
Schering Bridge

Schering capacitance bridge circuit
As mentioned earlier, the dissipation factor can be measured directly using a Schering
capacitance bridge circuit (named after Harald Schering). The basic circuit is shown in the figure
right where C
x
is the unknown capacitance under test. Like other bridge circuits (such as the
Wheatstone bridge), the circuit is tuned until the current through the middle of the bridge is zero
and the circuit is balanced. For a capacitance C
n
with low losses, the unknown capacitance and
dissipation factor can be calculated as follows:


The Schering Bridge is typically accurate for measuring dissipation factors down to 0.001 (i.e.
good for liquid insulating materials). For other solid insulating materials such as XLPE and
polypropylene that have dissipation factors <0.001, the Schering bridge may not be able to
provide the accuracy without careful screening and good earthing.

Transformer Ratio-Arm Bridge
TBA
Interpretation of Results
Dissipation factor or power factor is either expressed as a decimal per-unit value (e.g. 0.005) or
as a percentage (e.g. 0.5%).
TBA
The technical literature on this subject has noted that this test is useful for detecting moisture
ingress in bushings and windings. About 90% of bushing failures may be attributed to moisture
ingress evidenced by an increasing power factor from dielectric loss angle testing on a scheduled
basis.

S-ar putea să vă placă și