Sunteți pe pagina 1din 2

Sl No

DPR Page
number
Clause no. Remark/comment
1 7.1 7.1
Power from this switchyard . . . . . . to Gajwel of APTRANSCO shall be
modified as " Power from this switchyard would be evacuated through
Double Circuit 400 KV line".
2 7.1 7.1
In the Plant Layout (Drawing No.13002-009-DWG-PD-001,Rev 01)
separte 400KV Switchyard with Double Circuit line is shown. Necessary
discription for 400KV Switchyard shall be included in DPR.
3 7.1 7.1 GT voltage shall be chosen as 400 KV/Sqrt 3
4 7.5 7.3
Online Dissolved Gas Analyzer(DGA) is not considered for GT/ST,
whereas the same is considered in similar project of 800MW size.
Hence the same will be added for GT/ST.
5 7-7 and 7-8 7.4
The busduct ratings shall be decided during the detailed engineering.
6 7-7 7.4 11 & 3.3 KV SPBD bus bar material shall be mentioned.
7 7-14 7.7 (b) 87GT shall be added in the protections.
8 7-8 NSPBD
Connections between LT Switchgears/MCCs shall be through cables only.
9 7.9 and 7-10 7.4 and 7.5
Indicate the motor rating as 175KW instead of 200KW
10 7.9 7.4
Delete the 3.3KV/433V, 3 Phase, 50Hz, dry-type LV Auxiliary
transformers.
11 7.9
The sentence "These transformers would receive power from the
11 kV indoor switchgear." shall be modified as These transormers would
receive power from the 11 KV unit/stantion switchgear as per sizing and
requirement.
12 7-10 7.5 (a) Breakers shall be vacuum type only.
13 7.13 7.7 a.
please Include the following protections for Generator
1) Stator winding temp monitoring & Protection
2) VT fuse failure monitoring
3) GCB Pole Discrepancy
4) Busduct earth fault
14 7.14 7.7 b.
please Include the following protections for Generator Transformer
1) Transformer differential
2) Low oil flow
3) 400KV breaker failure
4) 400KV breaker pole discrepency
15 7.15 7.7 c.
please Include the following protections for Unit Transformer
1) LV Phase overcurrent
2) Over fluxing
3) OLTC Surge Protection
Kakatiya Thermal Power Plant (1X 800MW) -Final Detailed Project Report Electrical Comments
Page 1 of 2
16 7.15 7.7 d.
please Include the following protections for station Transformer
1) for point no. iii. Modify as Restricted earth fault for HV/LV instead
of LV-1,LV-2 side
2) HV/LV phase overcurrent(50/51) and earth fault(50/51N) for
400KV
3) OLTC Surge Protection
4) Low oil flow
5) 400KV breaker failure
6) 400KV breaker pole discrepency
7) 400KV CB trip circuit supervision
17 7.15 Please include the station and unit service transformerprotections
18 7.16 d Please include the under voltage(27) for 220V DC system
19 7-19 7.10 Battery shall be Lead acid plante type only
20 General
Welding,normal AC power,illumination loads shall be dervied from
suitable indoor cast resin dry type transformers.
Page 2 of 2