Contents
1. Handling precautions 1
2. Mounting and wiring
2.1 Panel cutting and mounting 3
2.2 Wiring 3
2.3 Grounding 4
2.4 Wiring of communication line 5
2.5 Terminal assignments 6
2.6 External connection of each model 10
3. Specification
3.1 Model list 11
3.2 Type 11
3.3 Specification 12
3.4 External appearance drawing 16
4. Operation and handling
4.1 Names of controls on front panel and their functions 19
4.2 Operation and selection of the key switch 20
4.3 Operation when setting 21
4.4 Operation in normal state 22
4.5 Reset method of the measurement hysteresis maximum value, the measurement hysteresis minimum value
and the integrated value 22
4.6 Operation at testing time 23
5. Type and functions of external input/output
5.1 Type and functions of external input 24
5.2 Setting method of external input 25
5.3 Types and function of External output 26
5.4 Setting method of external output 27
5.5 Description of ON/OFF/trip output motions 28
6. Measures to be taken when relay motion or equipment failure occurs, and
Reading of code display
6.1 Outline of code display 29
6.2 Reading of code display and measures to be taken 29
6.3 The method of relay test 31
7. Maintenance and inspection
7.1 Inspection item 32
7.2 Design life 32
Appendix Table 1 List of setting and history items 33
Appendix Table 2 List of operation in normal state 41
Appendix Table 3 List of setting items for setting value entry 45
Appendix Table 4 The relay test 49
Appendix Figure 1 Characteristic of an OC-relay 53
Appendix Figure 2 Outside connection diagram collection 59
Chapter 1 handling precautions
1.1 Outline and characteristic of "UM43FG-E5AK type"
The F-MPC60B is a digital multi-functional digital relay for high-voltage distribution facilities. It is a compact unit produced by combining
the function of protection, measurement, control, kWh pulse output and transmission with a transducer (provided only when the relay
incorporates transducer output).
High reliability
By the combination of conventional individual devices, this device realized the following function with difficult realization. The F-
MPC60B improved the function that records the history and fault data.
Improved maintainability
The F-MPC60B reduced the time of the relay test by using the trial output for the test. To prevent operation errors such as a mistaken
disconnect of a circuit the F-MPC60B adopted the fail-safe function and the auto monitoring function.
Flexibility
The F-MPC60B is able to change the circuit conditions, such as VT and CT ratio, by changing the setting value.
The F-MPC60B realizes the standardization of wiring in the distribution facilities, reduces the cost of the wiring and the maintenance.
So, the high economic efficiency is demonstrated in the engineering, production and maintenance division by using F-MPC60B.
The features: the F-MPC60B is able to apply to "the 3-pahse 4-wire system for the high or low voltage facilities" and " the 3-pahse 3-wire
system for the high or low voltage facilities ".
Please carefully read this manual before you use the product in order to use it safely and correctly.
1.2 Handling precautions
The F-MPC60B is used in both 100V AC and 100V DC. Provided when the F-MPC60B is used by AC power, use in combination
with UPS (Power Supply: option) or the F-MPC60 100V AC power supply unit for the F-MPC60B.
The rated CT secondary current is AC 5A. The F-MPC60B detects the current of main circuit: I
A
, I
B
, I
C
and the earth leakage
current: I
0
. By considering the application circuit and the number of CT, use the F-MPC60B correctly.
(1) Precautions for creating a connection diagram, mounting and wiring
Equipment error output is a normally closed contact output (excited in steady state, and if an error occurs, excitation terminates
and contact is closed). Therefore, a lag of around 100ms occurs before the contact opens, since the power was ON (in operation).
Consider the use of a timer, if necessary, when creating the external sequence. (See section 2.6.)
If the trip coil open circuit monitor function will not be used set Trip-coil open circuit monitor function at No in the setting.
Refer the code No 63 in the appendix table 3.
The external connector of the product(which incorporates transducer output)consists of a housing(Type:178289-
7,Manufacturer:AMP)and contacts(Type:175218-2,Manufacturer:AMP). Carry out connection treatment using a dedicated manual
tool(Type:919602-1(standard type),914596-3(economy type ))or 90648-1(economy type , Manufacturer: AMP).
Selective input/output (Eight points each) permits selection of function type by setup. See chapter 5 for types of selectable
functions and see chapter 5 for the setup method.
Each terminal block is the connector type, and it can be mounted and dismounted by lock screws on both sides of the terminal
block, with wires remaining intact. At the time of mounting/dismounting the terminal block, alternately drive/loosen lock screws
on both sides sequentially. If lock screws on one side only are forcibly tightened (or loosened) the terminal block may be broken.
Certainly tear off the upper and dust-proof seal after the wiring. There is the fear in which that the temperature of the inside rises,
when it is used without tearing off, and that it causes the abnormality and product are shorten.
(2) Precautions of setting
The frequency of this unit is the form of selecting 50Hz or 60Hz.
Set correctly at 50Hz or 60Hz to suit the rated-frequency of application.
In respect to setting items, frequency will not become valid unless the power is ON/OFF after setting. When the frequency
setting is changed, turn ON/OFF the control power once.
As the setting value of the code No 73 and No 74 in the setting table, set the sum of the 100ms and the operating time of external
device. The F-MPC60B spends the time for filtering the input signal, so it is necessary to add the time.
(3) Precautions for shipping the panel
Fix the front panel door using adhesive tape so that it will not open up due to excessive vibration or the like during loading or
shipping. (It has been assured that the JEC 2500 has been cleared in regard to vibration resistance.)
(4) Precautions for using the external output relay
Refer to the Table 3.4 "specification for external input/output". The specification of output current of the relay for ON/OFF/trip
is valid for only the closing current. So, do not use the relay of this devise for tripping the CB current. Use the external relay to
trip the CB current.
As the relay except the ON/OFF/trip relay, observe the specification of the section 3.3 (2).
(5) Others
Function of OC relay
In case the external CT used as 2CT,use A-phase and C-phase for the CT, and connect the CT secondary synthesized line
(common line) to the B-phase. 2CT provides the overload protect function for the B-phase even against an unbalanced load to the
3-phase circuit as a result. However, it is possible that the B-phase will also operate when single-phase relay testing of A-phase or
C-phase is conducted in a relay test because of this function. (It depends on the positions of test terminal.)

Active electric energy integrated value
The integrated value is also kept when a power failure occurs. If the setting of the VT ratio and CT ratio was changed, however,
the integrated value is reset to the initial value (0).
2. Mounting and wiring
2.1 Panel cutting and mounting
Cut the relay mounting panel as shown in the panel cut drawing in section 3.4 External appearance drawings. Then mount the unit so that
the top face of the unit become level.
Ventilation holes are provided at the top and bottom of the cases main unit. If these holes are plugged, the internal temperature rises and
errors may occur, or it is possible that the products service life will be shortened. When any equipment is mounted above or below the
cases main unit, provide a space of 100 mm or more from the cases main unit.
2.2 Wiring
Wiring to the F-MPC60B is roughly classified as indicated table 2.1. Be careful that these wires do not come in contact with each other.
Table 2.1 the wiring of F-MPC60B
Classification Name
Communication line,
signal line
Communication (RS-485)cable,
Transducer(4-20mA,kW pulses) output lines
Control line
(classification 1)
Control power lines, VT secondary lines, CT secondary lines, input/output lines(excluding those of
classification 2)
Control line
(classification 2)
CB ON lines, CB OFF lines, CB trip lines
Grounding line Grounding line
1) Communication line, signal line
Use KPEV-SB (0.5sq),CPEV-SB ( 0.9mm) or equivalent for communication cables(RS-485). Lay shielded wire for SD or SG
terminal (No.2 of terminal block A).
Separate route of communication line and signal line from high voltage apparatus or power line.
Separate them from CB control line or high voltage line.
Connect terminal resistor on both ends of communication cables without branching.
If this unit is provided with a communication function (RS-485) and this unit is located at the end (terminal) of a communication line, use
short terminals No.3-5. Terminal resistance of 100 is built-in.
Transmission distance of communication cable is 1,000m or less at RS-485.
Use twisted wires (cables) for transducer output lines.
2) Control line (classification 1)
Wiring of control power line doesnt connect in parallel with such as load that will be source of generating noise.
When the control power lines, input/output and VT/CT secondary lines are located in the same duct, separate VT/CT secondary lines, as
bound together using a tube or the like, from other.
3) Control line (classification 2)
Separate CB ON/OFF/trip lines from other lines.
4) Grounding line
Be sure to ground the earth terminal (FG).
Lay the grounding line (FG terminal) for each unit independently, and separate it from other line.
(See section 2.3)
Figure 2.1 Typical separation of the wiring

5) Terminal block (the interface terminal block)
Disposition of terminal block is indicated figure 2.2.
Figure 2.2 the interface terminal block
6) Other
Arrange the wires as connected on the panel side in such a manner that no stress is applied to the terminal unit before connecting the
wires.
The terminal screw is M3.5. Tighten them to the proper tightening torque. (Recommended value:0.8N m)
Use a tightening torque of 0.8N m or more for fitting the main unit with fixtures.
Use pressure terminal matched size of cable, and check to see if mounting screws are correctly tightened.
In case driving load above contact rating of relay, be sure to use in combination with power relay.
2.3 Grounding
The typical grounding of the panel is indicated below.
Figure 2.3 the typical grounding of panel
Note: Separate grounding should be made if there is any equipment such as an inverter that will be source of generating high-frequency
noise.
2.4 Wiring of communication line
Typical wiring of communication line (RS-485) is indicated below.
Figure 2.4 the wiring of communication line
Note: Wiring of communication line doesnt penetrate room of main-circuit equipment and breakers.
2.5 Terminal assignments
Each terminal block is the connector type, and it can be mounted and dismounted by lock screws on both sides of the terminal
block, with wires remaining intact. At the time of mounting/dismounting the terminal block, alternately drive/loosen lock
screws on both sides sequentially. If lock screws on one side only are forcibly tightened (or loosened) the terminal block may
be broken. Each terminal block units is composed of two terminal blocks, i.e. a 30-pole block (row A) and 30-pole block (row
B).
Pay attention because it becomes the cause that this device is damaged, when mistake the terminal unit of the "block: A" and the "block: B"
and wire. As for the details of wiring, refer to section 2.6.
2.5.1 UM43FG-E5AK type
Figure 2.5 the 30-pole block (A) Figure 2.6 the 30-pole block (B)
Figure 2.7 the connector of transducer output
N.C N.C Output 6- Output 5- Output 4- Output3- Output 2- Output 1-
N.C N.C Output 6+ Output 5+ Output 4+ Output 3+ Output 2+ Output 1+
Pin No.
The minus side of output signal: 4-20mA is common.
Precautions for connection to the row "A": 30-poles terminal block.
(1) The connection position of "Va, Vb, Vc and Vn " differs with "3-phase 3-wire system" and "3-phase 4-wire system".
(2) If this unit is provided with a communication function (RS-485) and this unit is located at the end (terminal) of a communication line,
use short terminals No.3-5. Terminal resistance of 100 is built-in.
(3) Terminal with marks are NC (no connection) terminals. Do not connect wires to these terminals.
7: kWh pulse output (+)
8: kWh pulse output (-)
2.5.2 the wiring of CT and VT the fuse, the test terminal and the ground line are omitted.

The under voltage relay: 27 monitors the line voltage: Vab or Vbc
The over voltage relay: 59 monitors the line voltage: Vab
The under voltage relay: 27 monitors the phase voltage: Van, Vbn, Vcn
The over voltage relay: 59 monitors the phase voltage: Van
Figure 2.10 the wiring of 3-phase 4-wire system with external 3CT
The connection method of CT: Input the inverse synthesis current of Ia, Ib and Ic to the N-phase input.
Note 1: tighten the short circuit bar of No 13-24 with the terminal screw certainly.

The under voltage relay: 27 monitors the phase voltage: Van, Vbn, Vcn
The over voltage relay: 59 monitors the phase voltage: Van
2.5.3 In the case that VT is composed with 3-phase: Va, Vb and Vc
The wiring of the single-phase system shows in Figure 2.11.1, Figure 2.11.2 and Figure 2.11.3.
Figure 2.11.1 the wiring of single-phase system: the load between A and B
Figure 2.11.2 the wiring of single-phase system: the load between B and C
Figure 2.11.3 the wiring of single-phase system: the load between A and C

2.6 External connection: Example of basic connection


UM43FG-E5AK
Figure 2.11
3CT
C B
K
L
A
B
C
RS-485
9 10
8
11
13
14
17
18
21
22
29
30
7
B1 A1 B2 A2 B3 A3 B4 A4 B5 A5 B6 A6
Connector
Wh-pulse output
F-MPC60B
1 2 3
Power
supply
Block
O
N
T
r
ip
-
lo
c
k
L
o
c
k

f
o
r

p
o
w
e
r
s
u
p
p
ly
E
m
e
r
g
e
n
c
y

s
t
o
p
TC CC
TC-coil
Monitor
26 27 30



T
r
ip
29 15 14

C B
A
B
C
T.Tm
a
VT
b c
O
u
t
1
16
O
u
t
2
17
O
u
t
3
18
O
u
t
4
19
O
u
t
5
20
O
u
t
6
21
O
u
t

7
22
O
u
t

8
23
E
r
r
o
r
24 25 5 6 7 8 9 10 11 12 13 4
X1 X2 X3 X4 X5 X6 X7 X8 T
I
N

2
I
N

1
I
N

3
I
N

4
I
N

5
I
N

6
I
N

7
I
N

8
5
2
a
A 100 termination resistor
15
16
19
20
23
24

DC420mA

DC420mA DC420mA DC420mA DC420mA DC420mA


BlockA
BlockB
Counter
Interlock
Input detection circuit
The isolation by the photo-coupler
The current of ON: 4mA at 100V DC
Note: wirethe input-common terminal:
Block B No 4to the "N" at thetime
of use in DC power supply.
Use the Output:1-8 as the failure display or the circuit for trip.
T.Tm
N
n
12
Meter
The transducer output
Meter Meter Meter
Meter
O
F
F
28
1
3
2
5
B
lo
c
k

Note:
(1) Use selective input 1 to 8 and selective output 1 to 8 by selecting the function type by setup.
Refer to chapter 5 for a complete breakdown of the setting.
(2) Outputs of ON, OFF, trip and equipment error are used exclusively. Inputs of "52a: the answer back signal of CB ON" and "the
monitoring of TC coil" are used exclusively.
(3) Equipment error output is a normally closed contact output (excited in steady state, and if an error occurs, excitation terminates and
contact is closed). Therefore, a lag of around 100ms occurs before the contact opens, since the power was ON (in operation). Consider the
use of a timer, if necessary, when creating the external sequence.
(4) In case driving load above contact rating of relay, be sure to use in combination with power relay.
See section 3.3(2).
(5) If this unit is provided with a communication function (RS-485) and this unit is located at the end (terminal) of a communication line,
use short terminals No.3-5. So, the 100 terminal resistor of this unit is connected across the RS-485 bus.
(6) Use twisted wires (cables) as the output cable of transducer.
Chapter 3 Specification
3.1 Model list
Table 3.1 shows the functions of this devise. The functions are generally classified by the combination of protecting elements and
measuring elements. Unnecessary protecting elements may be locked.
Table 3.1 the functions of this device
Protection Measurement Transducer; (4 to 20mA)
M
o
d
e
l
/

b
a
s
i
c

t
y
p
e
5
0
5
1
5
1

D
T
1

D
t
2
5
0
G

5
0
N
5
1
G

5
1
N
2
7
5
9
O
C
A
,
O
C
G
A
A

v
a
r

P
F

W
h

D
A

D
W

H
I
,
A
0

A
0
m
a
x
,
D
A
m
a
x
,
D
W
m
a
x
,
V
.
H
z
,
V
a
r
h
,
V
m
i
n
The kind of the signal is 14.
Line voltage (Vab, Vbc, Vca)
Phase voltage (Van, Vbn, Vcn)
Current (Ia, Ib, Ic)
W, var, power factor, Hz
UM43FG Number of output: 6 quantity
Note 1: See section 3.3(6) for a complete breakdown of transducers output.
Note 2: OCA: Over-current alarm (may be used as a pre-alarm by setting an alarm value.)
Note 4: OCGA: Earth leakage pre-alarm (may be used as the preventive maintenance for the cable deterioration.)
Standing standard
JEC-2500 Protective relays for electric power systems
JEC-2510 (Over-current relays)
JEC-2511 (Voltage relays)
JIS C4602 (Over-current relays for 6.6Kv receiving)
JIS C4609 (Directional ground relay set for 6.6kV consume)
JIS C1102-1 -9(Direct acting analogue electrical instrument and their accessories)
IEC255-3 (1989)
3.2 Type

Represents the series
(Model for 3-phase 4-wire system)
Classification of ground fault protection
50G 51G
Control power supply
100V DC AC common use
CT secondary current
5A
External interface
"4-20mA output" & "RS-485 interface": note 1
Classification of characters on the panel
Except for Japanese
Note 1: Refer to the next manual.
"F-MPC60B (UM4 type) Application manual for RS-485 communication": FH866 that is the same contents as "FIN 75 96 25".
3.3 Specification
(1) General specification
Table 3.2 general specification
Note 1 Operation guaranteed temperature means that operation is guaranteed within two times of the accuracy guaranteed value at JEC
characteristics guaranteed temperature or within the accuracy of influence of JIS temperature.
(2) Specification for external input/output
Table 3.4 specification for external input/output
item Specification
Input circuit
Common to 100V DC(143V DC or less) and 100V AC(132V DC or less)
ON voltage 40V DC to 70V DC ON voltage 40V AC to 70V AC
CB ON/OFF/trip Closing current:15A(110V DC)
allowable continuous conduction current:4A
Output circuit
Other than above Closing current 0.2A (110V DC, inductive load L/R=15ms or less) allowable
continuous conduction current:1A
Item Specification
Control power supply
Common to 100V DC(80-143V
DC) and 100V AC(85-132V AC)
Power consumption Max. 15W
Power consumption of
CT,VT
Max. 1.0VA
Rated current
(CT secondary current)
5A AC
("1A AC" type is the non-standard
correspondence.)
Line
voltage
Select "110V AC" or " 110 3
AC" (VT secondary voltage)
Rated
voltage
Phase
voltage
Select "110V / 3 AC" or "110V
AC" (VT secondary voltage)
Zero-Phase current 5A AC
Insulation resistance 10M or more
between external terminals and
ground
Vibration
16.7Hz, double amplitude 0.4mm
acceleration:1.96m/s
2
10 minutes in each of 3 directions.
Shock 300m/s
2
3 time in each of 3
direction
Withstand voltage
2kV AC 1 minute note 4 (between
external terminal and ground)
However, RS-485 signal line and
transducer output line is excluded.
Item Specification
Noise resistance
JEC2500(conforms to ANSI),
Square wave 1.5kV (1ns/1 s 10
minutes)
Overload
resistance
CT circuit: at ratting 40times,a second, 2
times
VT circuit: at ratting 1.25 times, 10
seconds
Ambient
temperature
-10 60 operation is guaranteed.
Note 1
(0 40 characteristics are
guaranteed.)
Storage
temperature
-20 70
Relative humidity 20% 90% RH(no condensation)
Working
atmosphere
No corrosive gas and no heavy dirt and
dust.
Grounding class Class D grounding
(100-ohm or less)
Mass 1.4kg
Dropout tolerance 20ms
Continues operation, however, display go
out.
Electrostatic
discharge
Contact discharge 8kV
Aerial discharge 15kV
Lightning impulse 5.0kV , between external terminal and
ground
(3) Specification for measurement and display
Table 3.4 specification for measurement and display
Item Effective display range Display range and accuracy Note 2
Current
/Demand current
/Demand maximum current
0, "0.8%" "CT rating" "CT rating 8
times" note 1
1.5% 0 0.8% 100%
5% 100 800%
Zero-phase current
/Zero-phase maximum
current
CT: 0, "2%" "CT rating" "CT rating 8
times"
1.5% 0 "2%" "CT rating"
5% more than CT rating
Effective power
/demand effective power
/reactive power
0.015 1kW at VT secondary circuit
(The value is converted into the VT rated
voltage: 110V AC)
1.5% 0 " 0.015" " 1kW"
(Refer to figure 3.1)
Power factor Lead 0%-100%-Lag 0 5% (Refer to figure 3.1)
Effective electric energy
Reactive electric energy
Note 3
0 99999
multiplying factor 1 10 100 1000
Equivalent to ordinary instrument shown in table 4 of
JIS C 1216(instruments with transformers)
Line voltage 9.5V-260V on VT secondary side
Phase voltage 5.5V-150V on VT secondary side
1.5%
Note: The rating voltage of phase voltage is
equivalent to "the line voltage/ 3".
Frequency
45-55Hz(50Hz) 55-65Hz(60Hz) 0.5%
Demand max. value Same as the above measuring range. Same as the above indication range and the precision.
Harmonics current 3rd,5th,7th,total
Note 1 the accident electric current can be indicated by the electric current value indication to max.2000%
( 5% of the precision)
Note 2 Meaning of 0, A% is 0 is indicated if a range under 0 to A%.
Note 3 There are two indications in the electric power indication that total electric power value (zero clear disable) and period electric
power quantity (zero clear is possible).
Note 4 Here, the mark: "" displays "LEAD/LAG" of the electric power selling, the power purchase or power factor.
The mark: "+" is a blank. The meaning of "mark: " for each item of measuring shows Figure 3.1.
Figure 3.1
(4) Specification for history data
Table 3.5 specification for history data
Item Display range Display
code
Item Display range Display
code
Number of times of the
tripping: 50(INST)
0-9,999 times
Number of times of the
motion: OCA
0-9,999 times
Number of times of the
tripping: 51DT1
0-9,999 times Running times 0-9,999 100(hr)
Number of times of the
tripping: 51(OC)
0-9,999 times Number of times of switching 0-9,999 10
times
Number of times of the
tripping: 51G
0-9,999 times Number of times of the
motion: OCGA
0-9,999 times
Number of times of the
tripping: 50G
0-9,999 times Number of times of the
motion: 51DT2
0-9,999 times
Number of times of the
tripping: 59(OV)
0-9,999 times
--- --- ---
Number of times of the
tripping: 27(UV)
0-9,999 times --- --- ---
Other display
Fault value display: Display of fault value on occurrence of a fault, maximum values in the history of zero-phase current/voltage,
and maximum demand value (A, W), minimum values of instantaneous voltage.
Note 1 Display code in the above table is the code used when displayed on this unit.
Note 2 As for Changing of setting value of history data, see section 4.3.
(5) Specification for protective relays
Table specification for protective relays
Characteristics
Item
Current/voltage operation
value setting range Operation time(timer) setting range
Operation
value
Tripping time
Instant
1-16 times of CT rated
current(0.2 times step) Lock
Fixed 5% 40ms or less
definite time
1-16 times of CT rated
current(0.2 times step) Lock
0-5s
0.05s step
5% Less than 1s 50ms
More than 1s 5%
definite time
20-240% of CT rating current
(2% step) Lock
0-10s
0.1s step
5% Less than 1s 50ms
More than 1s 5%
Inverse time
SI,EI,VI,LT,I t
20 240% of CT rating
current(2% step
Lock
Time multiplication:0.5-20 times
0.1 times step
operation time:150m min.
5%
Setting value 300% 12%
500,1000% 7%
(lower limit 100ms)
(instant, definite time)
0.2-8times of CT rating(0.1
times step) Lock
0.0 10s 180s note 1
(0.1s step)
5% 5%(lower limit 50ms)
SI,EI,VI,LT
2-100% of CT rating(1%
step) Lock
Time multiplication:0.5-20 times 0.1
times step
operation time:150m min. note 1
5%(min
100mA)
Equivalent to that of 51
above.
VT secondary:60-150V
(1V step),Lock
0.0 5.0 60s
(0.5s step) (1s step)
5% 5%(min 50ms)
VT secondary:10-100V
(1V step),Lock
0.0 5.0 60s
(0.5s step) (1s step)
5% 5%(min 35ms)
(Over current pre-
alarm)
10-100% of CT rating
(5% step) Lock
10 200s
(10s step)
10% 5%
(Leakage current pre-
alarm)
50,60,70,80% of the setting
value of "51G operating
current" Lock
10 200s
(10s step)
10%
(min
100mA)
5%
Note 1 With measures for preventing malfunction by exciting rush current (locked when secondary higher harmonics content is about
15% or higher)(this function operates at 15% or higher of basic wave current rating.)
However, Without measures for preventing malfunction by exciting rush current in the case of setting motion time 0s of
"protections 50G".
(6) Specification for transducer output (for product with transducer output)
Table 3.7 specification for transducer output
Item Specification
Transducer output signal
4 to 20mA DC (external load resistance:270 or less
Tolerance
Current (Ia, Ib, Ic For rated 0 to CT,4 to 20mA
Line voltage (Vab,Vbc,Vca
Note 1
For VT secondary
For 0 to 150V, 4 to 20mA.
For 0 to 150V 3, 4 to 20mA.
Phase voltage (Van,Vbn,Vcn
Note 1
For VT secondary
For 0 to 150V/ 3, 4 to 20mA.
For 0 to 150V, 4 to 20mA.
Effective power (W) For 0 to 1kw (CT5A, VT 110V AC conversion), 4 to 20mA.
Reactive power (var) For -1 to 0 to 1kvar (CT5A, VT 110V AC conversion), 4 to 12 to 20mA.
Frequency (Hz) For 45 to 55Hz or 55 to 65Hz, 4 to 20mA.
1.5%









S
i
g
n
a
l

t
y
p
e
Power factor LEAD 0.5 to 1 to 0.5LAG/4 to 12 to 20mA.
5%
* The minus side: "-" of the output signal at the transducer circuit is common.
* For the output signal exceeding upper or lower value, the output signals cause 4mA at lower limit and 20mA at upper limit. The
output signal is limited 4mA at lower value and 20mA at upper value.
Note 1: " " is applied for the line voltage: 100V/110V/120V AC. " " is applied for the line voltage: 100V/110V/120V 3 AC.
Refer to the code No 04 of appendix table 1.
(7) Specification for the "kWh" pulse output
Table 3.8 specification for the "kWh" pulse output
Item Specification
Output Open collector output
Output capacity Maximum 150V DC 100mA.
Pulse width 200 20ms
Output pulse unit
10 kWh per pulse(n -2 4 setting) or 2,000 pulse/k h
(8) Specification for communication
Table 2.9 specification for communication
Item Specification
Standard EIA RS-485
Data exchange method 1:N (polling/selecting system)
Transmission distance Maximum 1000 m
Number of connectable modules Maximum 32 modules (included in master module)
Setting address 00-99
Transmission speed 4800/9600/19200 bps
Start bit 1 bit (fixed)
Data bits 7/8bits (selectable)
Parity bit None/odd/even (selectable)
Data type
Stop bit 1 bit (fixed)
As for communication cable, use "KPEV-SB (0.5mm
2
)", "CPEV-SB ( 0.9mm)"or the equivalent cable.
Connect the shield line to terminal: "SG".
The RS-485 bus must form a single continuous path, and requires termination because of fast transition, high data rates, or long cables. Both
end of the main cable require termination. When this devise is on the end of RS-485 bus, connect the terminal: No 3 and the terminal: No 5
on the terminal: "A" with short circuit bar. This device is including a 100 termination resistor.
The RS-485 cable must separate from the power line, motors, or high-voltage apparatus.
3.4 External appearance drawing
Figure 3.1 external appearance drawing
Angle
180
42.5
B
151
Connector for
transducer output
A
Figure 3.2 Rear view
F-MPC
165
1
9
2
1
7
9
18 85.3 27
m
i
n
.

1
0
0
m
i
n
.

1
0
0
1
8
0
152
+0.5
-0
+
0
.5
-
0
4. Operation and handling
The circuit breaker ON/OFF switch, REMOTE-LOCAL select switch, etc. are protected in dual structure front panel door and switch
protection covers. If the door is open, damage to the door will occur if a worker hits it. The door should be kept closed expect during switch
operation.
4.1 Names of controls on front panel and their functions.
The state in which the front panel door is opened is indicated in Figure 1.
Figure 4.1 front panel

The code table of setting value, history and test is described in the rear of the front panel door.
UM4F(K)
Table 4.1 the name of control of the front panel and their function
Item
POWER At lighting of this LED, it indicates that the control power is ON.
RUN At lighting of this LED, it indicates that running is normal.
ALARM At lighting of this LED, it indicates that the equipment has failed. The details of a failure are
indicated by Code of Chapter 6.
RELAY
RELEASE
This relay flickers when the relay is detected, and it lights up when the relay is actuated.
1)Running status
indicator LEDs
PLURAL
FAULTS
This relay is lit while there are multiple factors for relay motion and for equipment failure.
Explains the contents of the display code of item 6 when relay motion occurs.
2) Relay release failure code chart
Example: When E2 is indicated by E2 OC(A) code, it means that the OC relay was actuated in
the A-phase.
Code
Indicates contents of relay failure, equipment failure and setting item at time of setting. See
section 6 and separate table 1 for details.
3) Indication of
measured value,
setting value or
failure value.
Data Data is displayed.(in 5 digits by 7-segment LEDs)
4)Display item and unit indicator
LEDs
Indicates item and unit of data of item 3. 10 and 100LED indicate display magnification.
(when both 10 100 are lit, this indicates that the display magnification is 1,000 times.)
Example: when R and A are lit, this indicates that the data display is of R-phase current value and
the unit is A(ampere).
5) Sheet switches Used for switching of display item, setting operation, etc.
6) Key switch NORMAL/SET/TEST mode select switch
(insertion/extraction of the key is permitted only in the NORMAL position)
7) Operation indication LED
REMOTE/LOCAL: indicates whether remote running or local running has been selected.
CLOSE/OPEN: indicates whether the CB or the like is ON or OFF.
8)REMOTE/LOCAL,CLOSE,OPE
N operation switch
REMOTE/LOCAL select switch and CLOSE/OPEN operation switch.
(switch with protective cover)
4.2 Operation and selection of the key switch
The key switch has three positions, i.e. setting, normal and test. The motion when each one of three positions is selected is indicated below.
Table 4.2 the operation and selection of the key switch
Item Position of key
switch
Outline of the motion
Setting Select this position any setting value, for checking any setting value or for checking or re-setting
any history data. Even when the key switch selects the SET position, the protective relay function
is continued for conventional setting values.
Normal Select this position for normal running. Insertion and extraction of the key switch can be
performed in this position only. (This front panel door will not be closed unless the key is
extracted.)
Test

Select this position for conducting manual testing such as a system check. This normal running
function of protective relays, etc. is suspended when the TEST position is selected.
4.3 Operation when setting
The key switch selects the SET position.
Key switch
Figure 4.2

Step 1 Step 2 Step 4
Step 3
Operation procedure
Step 1
Confirmation of setting value.
The setting value item number and historical value code is updated each time the sheet switch or is pressed, and the
current setting value is indicated by the 7-segment LED.
(Operation for confirmation is step.1 only.)
Step 2
Change to setting value and historical value.
Press sheet switch SET in the state where a setting change item and historical value is selectively indicated in step 1 above. (The
setting value begins to flicker.) to step 3
Step3
The setting value changes each time the sheet switch or is pressed. Select the data to be set.
(The setting value is flickering, and has not yet been finalized.) to step 4
Step 4
When sheet switch ENT is pressed, the setting value is lit continuously; indicating that setting has terminated.
Repeat step 1 to 4 above to continuously change the setting of multiple items. The selecting lock can delete an unnecessary
relay function item. Confirmation of history data and change to the current value can also be performed in the same manner.
A list of setting items and history data of the feeder unit, the receiving unit and the bus unit are shown in appendix table 1.
Note
In the setup for time of monitoring contact open/close jamming, the set time should not be less than external equipment (sequence) motion
(Ans. signal) time plus 100ms. (This is because the F-MPC60B internal measurement time is from CPU output to finalization after the input
filter time.)
(Locking the setting value)
Change to the setting cannot be performed unless the key switch is located in the SET position.
Therefore, mischievous changes to setting cannot be performed by an unspecified person who does not have the key. In addition, a setting
lock function is provided, and a value which was once set cannot be changed even if the key switch is located in the SET position.
(Method for setup of "setting lock".)
Step 1: Setup of setting lock/cancel can be performed only in any of the display statuses indicated below in the normal mode.
Table 4.3 setting lock
Selection of
display item
Operation
I
A
current display
status
Press sheet switches SET and ENT simultaneously. The lock status has been selected if the display is Lon. Or, the
lock has been canceled if the display is LOFF. The Lon/LOFF display is switched each time the sheet switches
indicated above are pressed simultaneously. Terminate the operation, after confirming the Lon is displayed, to the
setting.
Step 2: Assure that the setting value does not flicker even during work step 2 (change to setting value) of the operating procedure indicated
above is performed.
4.4 Operation in normal state
The key switch selects NORMAL position.
(Operation of keys is unnecessary during normal running.)
As for the display item and display method, see appendix table 2.
Note: " 10" and " 100LED" indicate display magnification in unit indicator LEDs .
when both " 10" " 100" are lit, this indicates that the display magnification is 1,000 times.
Figure 4.3 the operation of normal
Key switch
Normal
The display of measured value can be switched by operating of this switch.
The display of measured value (meter) can be switched during normal running.
The display item is switched sequentially each time the sheet switch or is pressed. Check the display item and unit by reading the
LEDs. The 7-segment LEDs of this unit go out automatically if no switch operation is performed for a continuous 10 minutes, as an
energy conserving measure. However, they light up when any switch operation is performed, any relay is detected or when any equipment
error is detected. (Press one sheet switch to have LEDs to light up again. No change will occur in the running status regardless of which
sheet switch is operated.)
4.5 Rest method of "the measurement hysteresis maximum value", "the measurement hysteresis minimum value" and "the
integrated value".
This appliance has the display function of the hysteresis maximum value, the hysteresis minimum value and integrated value shown at the
bottom table. Please do it by the following in confirmation and the case in which it is reset of period data, etc. And, please similarly reset
field startup test and relay test in the periodic check after the execution on zero-phase current maximum value.
Table 4.4 the list of the measurement hysteresis maximum value and the measurement hysteresis minimum value.
The measurement display item display method in 5 digits by 7-
segment LEDs
Period effective power( ) kWh
Period reactive power( ) kvar
Demand A,B,C-phase current maximum value
Demand effective power maximum value
kW
Minimum value of instantaneous AB,BC,CA-phase voltage
Zero-phase current maximum value
Reset method.
1) By the measured value confirmation operation in the usual time described at 4.4 terms, the correspondence data is displayed. (example:
I
0
LED is the condition that H A was displayed in the lighting in the 7-segment display part in zero-phase current maximum
value.)
2) In the condition that the correspondence data was display, the SET switch is pushed.
the hysteresis maximum value is reset. (It is cleared in the zero.)
Note:
Though period electric power quantity is reset in the superscription operation, the active power quantity is not reset, even if the
superscription operation is carried out.
It is reset only in the case of setting change of the CT, VT ratio the total effective power quantity.
(It is cleared in the zero.)
4.6 Operation at testing time
The key switch selects TEST position. (the function of protection, measurement is all ignored.
The [lamp test (all lamps are lit) status] is produced when the TEST position is selected by the key switch, and switching to [all lamps are
out (code L2 is displayed)] - [input/output testing] - [relay forced motion testing] - [transducer output testing (only with a product with
transducer output)] - [return to lamp test status] each time the sheet switch is pressed thereafter. (Reverse turn occurs when sheet switch
is pressed.)
The contents of input/output testing relay forced motion testing and of transducer output testing are indicated in the Figure 4.5. The test
output is not output even in the test mode, unless the external TEST position input is ON (the CB, etc. have not been pulled out to the TEST
positions). (When the external TEST position is not used, the test output is output in the test mode. Refer to the test position of table 5.2 and
note 3.)
Table 4.5 the operation of the test position
Test item Code display Operation for testing
The state when TEST position input is OFF and actual output is not made is indicated.
The state when test position input is ON and actual output is not made is indicated. CLOSED/OPEN output and
status indication is made by the CLOSE/OPEN operation that corresponds to the REMOTE/LOCAL setup.
Input/output testing
If any equipment error is detected in the input/output testing, the following display is made in the data area.
F4568 A failure detection No. only is displayed. Check the applicable item.
F: Equipment failure
4/5: CB contact open/close is jammed
6: CB trip coil open circuit
8: F-MPC60B internal circuit error
See Chapter 6 for processing when a failure is indicated.
The applicable output is made when sheet switch: SET and ENT are pressed simultaneously in the state when any of the
code displays indicated below are selected. If the product is provided with a communication function, the applicable bit data is also
transmitted.
Code display Testing item and
output
Code display Testing item and
output
Code display Testing item and output
C0 Equipment failure
output
CP E0 50INST CP EF OCGA
C1 Selective output 1 CP E1 50DT1
C2 Selective output 2 CP E2 51(OC)
C3 Selective output 3 CP E3 27(UV)
C4 Selective output 4 CP E4 59(OV)
C5 Selective output 5 CP E8 51G
C6 Selective output 6 CP E9 50G
C7 Selective output 7 CP EC OCA
Relay forced motion
testing transducer
output testing
Note 1
C8 Selective output 8 CP EE 51DT2
Transducer output(DC 4-20mA)
Code display Motion when testing Code display Motion when testing Code display Motion when testing
Ao 4 4mA DC output Ao CH1 V only, 12mA output Ao CH6 CH6 only, 12mA output
Ao 8 8mA DC output Ao CH2 Hz only, 12mA output
Ao 12 12mA DC output Ao CH3 I only, 12mA output
Ao 16 16mA DC output Ao CH4 W only, 12mA output
Transducer output
testing
Note 2
Ao 20 20mA DC output Ao CH5 Var only, 12mA
output
Electric energy pulse output
Code display Motion when testing
P0
Output of one pulse (each time the sheet switch ENT is pressed)
Pulse output testing
P1 Repeated pulse output of one pulse per second when switch ENT is pressed.
The output stops when sheet switch RST is pressed.
* The stopped status is produced if P1 is initially selected.
* Description of C code display is printed on the panel sheet.
Note 1 The protecting elements, which are locked by setting, will not be output.
Testing of CP E* is made to output contact that is set according to section 5.4.
Note 2 the transducer output testing is a test item applicable only to a product with transducer output.
At testing of Ao 4,8,12,16 and 20, outputs of all channels are made simultaneously.
Chapter 5 Type and functions of external input/output
5.1 Type and functions of external input/output
The names and functions of external input/output are indicated in the Table 5.1.
Table 5.1 Types and functions of external input
Name Setting code Remarks
CB52a Circuit breaker (CB) ON answer back signal. (the fixed Input )
Trip coil circuit monitoring The monitoring signal of trip coil (the fixed Input )
Selective input 1 70 Duplexes internal hardware note 1
Selective input 2 71 Duplexes internal hardware note 1
Selective input 3 72 Duplexes internal hardware note 1
Selective input 4 73
Selective input 5 74
Selective input 6 75
Selective input 7 76
Selective input 8 77
Note 1: The circuits of "the selective input 1", "the selective input 2" and "the selective input 3"are duplicated.
In the case that "external OFF", "external trip 1" and "external trip 2" is allocated to "selective input 1, 2 and 3", it is valid for
preventing the miss-trip when the part of this device is failure.
Selective input means input that permits selection of input function (meaning) by setting. Its description is indicated in the Table 5.2. Using
this selection, the application to the various kind circuits becomes easy.
Table 5.2 selective input
Set number Item Function and application Remark
No function
External display select
switch
The function is the same as that of sheet switch on the panel face
(when the key switch is in the NORMAL position).
* Valid at the time of switching of display by external operation such as
operation on the panel face.
External rest switch
The function is the same as that of the sheet switch RST on the panel
face (when the key switch is in the NORMAL position.
* Valid while switching of display by external operation on the panel
face.
Transmission element 1
Transmission element 2
Transmission element 3
Transmission element 4
Transmission element 5
Transmission element 6
General-purpose communication input
* Valid as local remote DI input of the more significant controller
(through communication).
CB52b CB OFF input
* When CB52b is selected, display of CB OFF is made by this input.
Note 2
External OFF External CB OFF signal when remote is selected.
External ON External CB ON signal when remote is selected.
External 43
(selection of external
remote-local)
Remote is selected when ON, and direct is selected when OFF.
* The remote-local select switch on the panel face is invalid when this
function is selected.
Selective of local-central Selection of CB ON/OFF valid signal when remote is selected by
remote-direct selection.
ON: Local (external) operation is valid.
OFF: Central (communication) operation is valid.
* When this function is not selected, ON/OFF operation is valid at both
local and central. (OFF takes precedence if a duplicate operation is
performed.)
Set number Item Function and application Remark
CB ON interlock Circuit breaker ON is interlocked when input is ON (close lock).
CB OFF interlock Circuit breaker OFF is interlocked when input is ON (open lock).
CB ON/OFF interlock Circuit breaker ON/OFF is interlocked when input is ON (open/close
lock).
External trip 1
External trip input(with lockout signal is OFF by pressing RST on the
panel face.
External trip 2 External trip input(without lockout)
External alarm 1
External alarm 2
The input does in on, code display Ed, when the external alarm was
set, while the input signal condition is done in the communication data.
Test position The output test while the key switch is located in the TEST position is
valid when the input is ON.
* Signal for interlocking with circuit breaker draw-out position.
Note 3
Note 1 The internal circuit of each of selective input 1, 2, 3 is duplexes. When External OFF, External trip 1 or External trip 2 is
selectively used, it is effective as a measure for preventing erroneous breaking when a part failure occurs if allocation is made to
selective input 1-3.
Note 2 when this selection is not made, the judgment of the ON/OFF status of the CB is made by CB52a input. ON is displayed
when "52a" is ON, and OFF is displayed when 52a is OFF.
Note 3 When this selection is not made, output testing also becomes valid unconditionally when the key switch selects the TEST
position.
In the case that "test position" is valid at the setting code: No 21, the output of "ON/OFF/trip" relay does not output when the
position of key switch is "normal" or "setting" and when the input signal of "test position" is ON.
Note 4 For selection setup, select setting code of input 1-8 and set a Set number in the state where the key switch is located in the
SET position. See section 4.3 for the operating procedure. (Do not set the same function in duplication for other than Lock. It is
possible that motion will become unstable.)
5.2 Setting method of external input
For selection setup of selective input 1-8, set a Set number by using setting code 70-77. By using appendix table 3 of list of setting items,
decide set number (function) in advance. Setting for example is the following.
Step 1: Selective input 1-8 is set for set number (function) of the diagram below.
Step 2: See section 4.3 for the operating procedure.
For setting selective input 1,select 70 of setting code and set 17 of set Number.
Likewise, select 71-77 of setting code and set an appropriate Set number.
Table 5.3 example of the setting of external input
Setting
Code
Name of Setting function Setting value Remarks
Setting Selective input 1 17 External trip 1
Selective input 1 is set for external trip 1.
Setting Selective input 2 10 External OFF
Selective input 2 is set for external OFF.
Setting Selective input 3 11 External ON
Selective input 3 is set for external ON.
Setting Selective input 4
09 CB52b
Selective input 4 is set for the answer-back signal input of CBs OFF.
Setting Selective input 5 21 Test position
Selective input 5 is set for signal of CB draw-out position when test
position is selected.
Setting Selective input 6 03 Transmission element 1
Selective input 6 is set for transmission element 1. Use as local remote
DI input of the more significant controller.
Setting Selective input 7 04 Transmission element 2
Selective input 7 is set for transmission element 2. Use as local remote
DI input of the more significant controller.
Setting Selective input 8 Lock Selective input 8 is set for the unused.
5.3 Types and function of External output
Table 5.4 the types and function of external output
Name Remarks
Equipment failure Equipment failure signal
CB ON CB ON operation output
CB OFF CB OFF operation output
CB trip CB trip output
Selective output 1 Selective output
Selective output 2 Selective output
Selective output 3 Selective output
Selective output 4 Selective output
Selective output 5 Selective output
Selective output 6 Selective output
Selective output 7 Selective output
Selective output 8 Selective output
functions and motions
1) With or without CB trip output may be set for each protective relay element. If multiple protecting elements are set for with trip
output, the trip output become or output motion.

2) Selective output may be set as an alarm output of each protective relay. If multiple protecting elements are set for the same selective
output, the output becomes or output motion.
3) Setup of selective output permits the following besides item 2) above.
Table 5.5
Name Function Setting code
Failure pickup (batch) Output of ON with pickup of motion value of any protective relay (automatic
rest)
81
Transmission element 1 82
Transmission element 2
General-purpose output
* Valid as local remote DO of more significant controller (through
communication).
83
Output of remote-local
selection status
Refer to "Note 15 " that is described in the page after Appendix table 1. 84
5.4 Setting method of external output
For selection setup of selective output 1-8, use setting codes 11, 14, 18, 1b, 23, 26, 32, 42, 45, 52 and 81-84. Setting for example is the
following.
5.4.1 example setting of external input
1) By using appendix table 3 of list of setting items, decide the output in advance when actuating each protective relay. *CBs trip output
become or output of INST, DT, OG and DG in the diagram below.
Table 5.6 example setting of external With Without
Type of protective
relay element
Setting
code
The presence or
absence of CB's trip
output
The presence or
absence of alarm
output
Number of selective
output for alarm's output
Remarks
Protective INST
(50)
11
Protective DT 14
Protective OC 18
Selective output 1 The alarm output of "50" and
"51" is made for selective output
1 on the block.
Protective DG 32 Selective output 2
Protective OV 42 Selective output 3
Protective UV 45 Selective output 4
Protective OVG 52 Selective output 5
The alarm output of "DG", "OV"
and "OVG" is made for selective
output 2-5 individually.
5.4.2 Setting the output of each Protective relay is indicated below.
Lockout: With: 1 Without: 0
Output contact selection 1-8: contact 1-8: 1-8 No output: 0
CBs trip output: With: 1 Without: 0
Setup for shipping: 000 CBs trip output: without
Output contact selection: No contact output
Lockout: without
If the setting is with lockout, both display and output are continued and the CLOSE signal is invalidated until the sheet switch
RST is pressed, even after the cause of the error was eliminated.
If the setting is without lockout, the output resets automatically (after continuation for at least 1 second) when the cause of the
error was eliminated. But the display is continued until the sheet switch RST is pressed.
When the setting is with lockout in the case of 1) item, setting for example is shown below.
Table 5.7 setting for example
Type of protective relay element Setting code Setting value
Protective INST(50)
Protective
Protective
Protective
Protective
Protective
Protective
5.4.3 See section 4.3 for the operating procedure.
For setting protective INST (50), select 11 of setting code and set 111 of set Number.
5.5 Description of ON/OFF/trip output motions
1) Once the subject input signal is finalized (soft filter about 20ms), the ON/OFF/trip output is continued for one second at minimum even if
the input is gone thereafter. Also CBs trip output permits selection of manual-rest or automatically-reset by setting of the presence or
absence of lockout.
2) When ON/OFF operations are performed simultaneously, the OFF motion takes precedence. Detection of ON signal is made at the
activation (ON) edge. If OFF operation is performed in the state when the ON signal is continuously ON, therefore, OFF output is
made, and the ON output thereafter will not be made until the ON signal is once OFF and is than On again.
Figure 5.1 example of ON/OFF/trip output motions
ON operation signal ON
OFF operation signal
ON output
OFF output
3) The ON signal is not accepted during trip output.
4) At setting code No.65, OFF operation of any becomes also effective regardless of the selection of REMOTE-LOCAL of the
operation place, when the OFF precedence was set at with.
(Supplement)
There is the test position input signal as a signal input that is related to the ON/OFF/trip output action.
The test position input signal determines that the CB (switch) is on "the normal operation position or the extraction position.
In the normal operation, the output action is made to be the case in which the external input setting has made to be test position: 21 in
test position input: OFF. And, the output action is done in the test, if it is made to be test position input: ON.
The output action is done with the setting of the key-switch, if the external input is not set at test position: 21.
Chapter 6 Measures to be taken when relay motion or equipment failure occurs, and reading of code display
The code display (7-segment LED of 2 digits) is out during normal running. If it lights up, take the measures indicate below.
6.1 Outline of code display
If the code display lights up during normal running, it means that a failure occurred in the F-MPC60B main unit or any peripheral
equipment or any relay motion occurred. F represents equipment failure and E represents a relay motion.
6.2 Reading of code display and measures to be taken
1) Equipment failure
When an equipment failure is detected, the ALARM LED is lighted, the output of the equipment failure relay is output, and the code is
displayed. If the code display is other than FE, the running is continued and an equipment failure code and normal operation display
(measured data) are displayed as switched about once every second.
Table 6.1 the code display of the alarm
Code display Description Running of
F-MPC60B
Measure to be taken
Serious failure in F-MPC60B interior(error of
CPU,ROM,RAM or the like)
Stopped Replace the F-MPC60B
Unbalance in 3 phases of PT,CT signal(whether the function
is valid or invalid may be selected)
Continued Check the external wiring.
Jammed CB contact opening Continued
Jammed CB contact closing Continued
Check the CB ON/OFF
wiring and "answer-back"
signal wiring.
Open circuit in CB trip coil Continued Check the trip coil system.
History data error(mismatch of memory check data) Continued Set the history data again.
Error in F-MPC60B constant monitoring internal circuit Continued This device is normal, in the
case that "F8" turned off it by
pushing "the sheet switch;
RST".
Note 1
F
Light-up of
ALARM
LED
Error in setting frequency 50/60Hz Continued ON/OFF the control power
after setting the frequency to
the normal level.
F3 is reset automatically when the cause of failure is eliminated.
F6 is reset automatically when the cause of failure is eliminated. It also goes out when the sheet switch RST is pressed in the state
when the CB is OFF. (If the trip coil open circuit monitor function is not used, set Trip coil open circuit monitoring: None in the
setting.)
F4 and F5 go out when the sheet switch RST is pressed.
Other than the above, execute self-hold when a failure is detected and then goes out when the sheet switch RST is pressed.
Note 1; In the case that the abnormality of the signal is detected in the analogue input circuit, digital input circuit and output relay drive
circuit of this device, the Code display; " F8" is displayed in the 7-segment LED.
There is not abnormality in this device that depends on a temporary factor, in the case that F8 turns off it by pushing the return switch RST.
Therefore, there is not a problem by using this device.
Malfunction has occurred inside this device, in the case that "F8" is displayed even if pushing the switch RST.
2) Relay motion
When any relay motion occurs, lighting of the relay motion LED and output of an alarm (trip) are performed besides the code display.
Check the cause for relay motion. Description of E codes is printed on the front panel sheet.

Table 6.2 the display of the relay motion
Code display Description of relay motion
E0 50(INST)
E1 50DT1
E2 note 1 51(OC)
E3 27(UV)
E4 59(OV)
E5 External trip
E8 51G(OCG)
E9 50G
Ec OCA
Ed External alarm
EE 51DT2
EF OCG pre-alarm
When PLURAL FAULTS LEDs are lit, have a code displayed as switched by pressing sheet switch or .
The relay motion display and T-link data are kept after the cause of the failure was eliminated, and they go out when the sheet switch
RST is pressed. If the control power was gone in the state when the sheet switch RST has not been pressed yet, storage is done
automatically, and the status before the power failure occurred is output and displayed when the control power is recovered.
When the E code display is flickering, it means relay detection in motion. (Operates after elapse of timer time.)
Note 1: When the OC relay is actuated, the fault current value (unit A) and the motion time (unit s) are displayed as switched
approximately once every second.
The tripping time display of 51(OC) relay and 51G(OCG) relay is reference value.
6.3 The method of relay test
Refer to the appendix table 4: "The relay test".
As the relay test is tested at the condition of normal state, the position of the key switch must be the normal.
(When the position of the key switch is the test, the protection function of F-MPC60B does not act at all.)
The note at the test
(1) The Table 6.3 shows the allowable continuous current at input circuit of the phase current. Refer to the Table 6.3 when the operation
time is tested.
Table 6.3 the allowable continuous current (for the F-MPC60B that the secondary rating current is 5A.)
The input current The time of the allowable continuous
current
The input current The time of the allowable continuous
current
0-15A For more than 100 s 40-80A 6.3 s
15-20A 100 s 80-100A 4.0 s
20-40A 25 s --- ---
The overload capacity of the current input circuit is 200A, 1s and 2 times: 60 s as an interval. Refer to Figure 6.1 when the operation time is
tested.
Figure 6.1 the overload capacity of the current input circuit
(2) The F-MPC60B has the band-pass-filter to prevent the wrong action by the harmonic current, and changes the circuit constant of the
band-pass-filter using the setting value of the frequency: 50Hz or 60Hz. So, at the relay test, set up the setting value, and input the signal that
has the same frequency with the setting value.
If the generator is used at the test, keep the accuracy oh frequency: 2.5% or more less.
The current
Chapter 7 Maintenance and inspection
7.1 Inspection item
Perform maintenance and inspection as indicated in the Table 7.1 to use the product in the stable state.
Table 7.1 maintenance and inspection
Inspection period No Inspection item Description of inspection
Daily periodic
ally
Criteria for judgment
Ambient temperature 50 or less(annual average 40 or less
Ambient humidity 90% or less(no condensation on the surface)
Vibration No vibration
1 Ambient
environment
Dust, etc. Excessive contamination or accumulation of dust
should not be observed.
2 Display of error
code
Check visually.
Note 1
F should not be displayed.
Check for looseness and play of
the unit.
Check for abnormal noise, odor
and discoloration.
Check for looseness of screws
of External wiring.
3 Mounting
conditions
Check for damage and
deterioration to external.
Looseness and other abnormality in the external
appearance should not be observed.
4 Indicator LEDs Assure that POWER and RUN
LEDs are lit.
5 Setting values Assure that setting values are
normally displayed. Note 2
6 Relay test
7 Elimination of
foreign matter
Remove dust, etc.
Note 1: the alarm output, the communication and the display on the panel of F-MPC60B output the errors detected by self-diagnosis.
Note 2: the controller is able to check the setting value by using the communication.
The main purpose of the daily check is the check such as the appearance and structure of a relay and also switchboard. As for the daily
check, carry out several months to the rough standard. Also, carry out the inspection promptly, in the case that it corresponds to the next
item.
(1) It is in the case that abnormality admitted the fear that occurs with the daily check and the periodic check.
(2) It is in the case that the abnormality occurred with automatic monitoring (continuous monitoring /automatic inspection) the function.
(3) In the case that the setting value and the sequence circuit of the relay are changed.
As for the periodic check, carry out 1 time to the rough standard in 4 years from 2.
As for the method of the relay test, refer to Section 6.3 ant appendix 4: "The relay test".
7.2 Design life
The exchange part in a periodic check does not exist. The design life value type of F-MPC60B is 15 years at ambient temperature 40 per
a year. If temperature goes up 10 life becomes to about half. The vent (the slit) is opening to the upper part and lower part of the case
main body. There is the fear that the product life becomes short, because the inside temperature goes up when the vent of this device is
closed. Therefore, avoid it to close the vent.
Please understand, because also, the design life is not the guarantee-life. Exchange this device when this device reached life.




2 1 0 2 2 0 3 8 0 4 4 0 4 6 0 3 3 0 0 4 1 6 0 6 6 0 0 1 1 0 0 0 1 3 2 0 0 1 3 8 0 0 1 5 0 0 0 2 2 0 0 0 2 2 9 0 0 3 3 0 0 0 3 5 0 0 0 6 6 0 0 0 7 7 0 0 0
5 n = - 2 4
1 0 n = - 1 ( 1 0 A ) ( 1 0 A )
1 5 ( 1 5 A ) ( 1 5 A ) ( 1 5 A )
2 0
2 5 ( 2 5 A ) ( 2 5 A )
3 0 n = - 2 4 n = - 1 4 ( 3 0 A )
4 0 n = 0 n = 1 ( 4 0 A )
5 0 ( 5 0 A )
6 0 ( 6 0 A )
7 5
8 0 ( 8 0 A ) ( 8 0 A )
1 0 0 n = 0 4
1 2 0 ( 1 2 0 A ) n = 2
1 5 0 ( 1 5 0 A ) ( 1 5 0 A ) ( 1 5 0 A )
2 0 0
2 5 0 ( 2 5 0 A )
3 0 0 ( 3 0 0 A )
4 0 0 ( 4 0 0 A )
5 0 0 ( 5 0 0 A )
6 0 0
6 3 0 ( 6 3 0 A )
7 5 0
8 0 0 ( 8 0 0 A ) n = 1 4 ( 8 0 0 A )
1 0 0 0 n = 3
1 2 0 0
1 2 5 0 ( 1 2 5 0 A )
1 5 0 0 ( 1 5 0 0 A )
1 6 0 0 ( 1 6 0 0 A ) ( 1 6 0 0 A )
2 0 0 0
2 5 0 0 ( 2 5 0 0 A )
3 0 0 0
3 1 5 0 ( 3 1 5 0 A )
4 0 0 0 ( 4 0 0 0 A )
5 0 0 0 ( 5 0 0 0 A ) T h e o u t s i d e o f s e t t i n g
6 0 0 0
7 5 0 0
( 5 A ) ( 5 A )
T h e p r i m a r y r a t e d v o l t a g e o f V T ( V )
( 2 5 0 A )
( 1 2 0 A )
( 2 5 0 0 A )
( 1 2 5 0 A )

The relay test is a test in relay operation value and operation time in the normal operation condition. Therefore, key SW
is an operating state of "NORMAL" position and the relay test is done.
(In "TEST" position, the protective function does not work in key SW.)
The attention of the test
This appliance contains the band-pass filter in order to prevent the unnecessary operation according to the harmonic.
And, the circuit constant of the band-pass filter is being switched by the 50/60Hz selection setting in the main body
inside. Still, please make the output frequency of the generator to be within 2.5% of set rated frequency in the case
of the relay test by the generator.
The method of the test
In proportion to the unit type, characteristic test content and decision value refer to the after next page.
The following are shown in the following: Identification method of the operation value and identification method in
operation time.
Test item The method of test
Operation
value
(note)
The signal is applied to the input terminal, and it gradually changes, and the value in which 7segLED
started the "E" flashing display is the operation value.
However, operation value in case of the short time operation type is any of value that "E"
continued and that it lit, and that it displayed it or the value which output the trip ( alarm ).
Operation
time
The adjustment-finished signal is applied to the input terminal, and the time until a trip (alarm) output
operates is measured.
Note:
The signal value in the pickup relay output action becomes the operation value in trouble pickup output setting (code
of 81) in any of the selective output 1-8.
UM43FG-E5AK 13
Test purpose: It is confirmed that it goes in the characteristic of the relay simple substance abnormal.
Test content
Quality criterion
1.Appearance structural examination: It is confirmed that it goes in the
appearance abnormal.
1. There are no fracture, damage,
stain and corrosion.
2. Withstand voltage test: Between charge division consolidation and ground.
However, transmission lines and transducer output line is excluded.
2. 2kV AC 1 minute
3. Characteristic test: UM43FG type
3. Within the accuracy of the
following
The protection
element name
Test item Testing condition Test input Accuracy
(1)Operation
value
Working current setting
value
AB and C-phasenote 2
ZeroOperation value Setting value 5 Instant over-current
relay.
50INST
(2)Operation
time
Working current setting
value
ZeroBy changing to
200% of the setting value
suddenly, it is applied.
Within 40ms
(1)Operation
value
note 1
Working current setting
value
Time settingMinimum
or use setting values
AB and C-phase
note 2
Zerooperation value Setting value 5 Over-current relay.
51
inverse characteristic
(SI) or
or applying inverse
characteristic(EI or VI
or LT or I
2
t).
Definite time
DT1,DT2
(2)Operation
time
Working current setting
value
Time settingUse
setting values
AB and C-phase
Zero% Input of the
current setting value
300
500
1,000
note 3
Operation timenote 4
300TTheory value12
5001,000 7
The lower limit in operation
time 150ms
(1)Operation
value
Working current setting
value
Time settingMinimum
or use setting values.
ZeroOperation value Setting value 5
min100mA
Ground fault over-
current relay
51G (51N)
inverse
characteristic(SI) or
applying inverse
characteristic(EI or VI
or LT).
(2)Operation
time
Working current setting
value
Time settingUse
setting values
Zero% Input of the
current setting value
300500
1,000note 3
Operation timenote 4
300TTheory value12
5001,000 7
The lower limit in operation
time 150ms
(1)Operation
value
Working current setting
value
ZeroOperation value Setting value 5
min100mA
Instant ground fault
over-current relay
50G (50N) (2)Operation
time
Working current setting
value
ZeroBy changing to
200% of the setting value
suddenly, it is applied.
Within 50ms
Over-voltage relay
(OV)
(1)Operation
value
note 1
Working voltage setting
value
Time setting0s
Voltage Vab
100VThe operation
value as the
voltage gradually
rises. note 5
Setting value 5
Under-voltage
relay (UV)
(2)Operation
time
Working voltage setting
value
Time setting0s
Vab,Vbc (note 6)
Voltage Vab
100V The operation
value as the voltage
gradually down.
Setting value 5
min50ms
UM43FG-E5AK type 23

Note 4: TTheory operation time
Theory operation time at Time magnification10
%INPUT
SI EI I
2
t VI LT
300 6.30s 10.00s 80.00s 6.75s 60.0s
500 4.28s 3.30s 28.80s 3.38s 30.0s
700 3.53s 1.67s 14.69s 2.27s 20.0s
1,000 2.97s 0.81s 7.20s 1.50s 13.3s
Theory operation time formula for computation of the each over-current element
SI
1.0 I
0.14
0.02

10
L
EI
1.0 I
80
2

10
L
I
2
t
2
I
720

10
L
I

t constant
VI
I1
13.5

10
L
LT
I1
120

10
L

Precaution in the test


(1) Allowable conduction time of phase current input circuit. CT secondary current: 5A/1A type
Input current Allowable energization time Input current Allowable energization time
015A It can be energized continuously. 2040A 25s
1520A 100s 4080A 6.3s
80100A 4s
Take the non-energization period over 1 minute, after the current over rated 5A is applied, when the test is resumed.
(I
2
t=(200A)
2
1=40,000) between 40 times 1 second conformed for JEC-2500 is a standard on the overload capacity.
(2) Electric circuit largest applied voltage in the test. (The applied voltage of F-MPC60B body to input circuit.)
Line voltageVab, Vbc, Vca 150V
UM43FG-E5AK 33
Basic test circuit
(1) Instant, definite time and over-current relay test/ Over-voltage relay test/ Under-voltage test
(50INST, 51DT1, 51DT2, 51, OV, UV)
(2) Ground fault over-current relay test
(51G, 51N)
T.Tm F-MPC60B UM43FG-E5AK
Current and voltage
amplifier
Oscillator
A
V
I
V
AC100V
AC100V
Tester or buzzer
(The case in which a selective output was set.)
B1
B2
B29
B30 trip
Selective output
Selective output
Selective output
P
N
A13
A15
A14
A16
A21
A23
A22
A24
A9
A10
A11
Ia
Ic
IbA17A19A18
A20
a
b
c
Hour meter
Tester or buzzer
Current and voltage
amplifier
T.Tm
Oscillator
F-MPC60BUM43FG type
I
V
AC100V
AC100V
A25
A26
B1
B2
B29
B30 trip
Selective output
P
N
Io
Hour meter

100
10
1
0. 15
0. 1
0. 01
100
200 500 1000 2000( )
L=20. 0
15. 0
9. 0
7. 0
5. 0
10. 0
8. 0
6. 0
4. 0
3. 0
2. 0
1. 0
0. 5
ion magnificat time
10

1 I
0.14
t
0.02
=

100
10
1
0. 15
0. 1
0. 01
100
200 500 1000 2000( )
L=20. 0
15. 0
9. 0
7. 0
5. 0
10. 0
8. 0
6. 0
4. 0
3. 0
2. 0 1. 0 0. 5
ion magnificat time
10

I1
13.5
t =
5. 0
L=20. 0
15. 0
9. 0
7. 0
10. 0
8. 0
6. 0
4. 0
3. 0
0. 5
1. 0
2. 0

1000
100
10
0. 1
100
200 500 1000 2000( )
1
ion magnificat time
10

I1
120
t =

100
0. 1
100
200 500 1000 2000( )
1
10
0. 15
L=20. 0
15. 0
10. 0
9. 0
8. 0
0. 5 1. 0 2. 0 3. 0 5. 0 7. 0
6. 0 4. 0
ion magnifucat time
10

1 I
80
t
2
=

1000
0. 1
100
200 500 1000 2000( )
1
100
0. 15
L=20. 0
15. 0
10. 0
9. 0
7. 0
10
8. 0
5. 0
6. 0
4. 0
3. 0
2. 0
1. 0
0. 5
ion magnificat time
10

I
720
t
2
=
Appendix Figure 2 the outside connection diagram collection
Application example 01the circuit diagram is a reference.
By switching "REMOTE/LOCAL" switch in the panel plane of F-MPC60B (UM43FG-E5AK) to "REMOTE",
CLOSE-OPEN control of the circuit breaker is changed from the outside.
24
CC
Inside of CB
TRIP
F-MPC60 UM43FG-E5AK

Trip lock
1 2 3 4
26
1
2
27
TC
5 6 7 8 13
16
30 25
17 18 19 20 21 22 23 4
N
"Off (open)" is set at selective input of 1, and then, the case in, which on (close) is set, is shown in
selection input of 2 in the following.
Selective input of 1 (terminals number 5) is function setting code "70", and "off (open)" function is
"10". Setting code No.70 is set at "10".
Similarly, selective input of 2 (terminals number 6) is function setting code 71, and on (close)
function is 11. Setting code No.71 is set at 11.
Refer to section 5.1 and 5.2.
28 29
Developments
LOCAL
Note 1
In case of the T link communication, it is operable
at 2 places of "the outside" and "communication"
in respect of the "REMOTE/LOCAL" switch, when
"REMOTE" was chosen.
Note 2
It is possible by connecting field-center and
selection switch with selective input circuit of the
F-MPC60B main body, when it is surely made to be
the one place operation.
Application example 03
REMOTE
28 27
Outside
F-MPC60 UM43FG-E5AK
Emergency
stop
Power lock
Close Open
Close
Open
Close
Open
Close
Open Communication
Selective input

Selective output
A
l
a
r
m
Circuit breaker (CB) ON
answer back signal
Close Open
9 10 11 12
Application example 02the circuit diagram is a reference.
It makes "REMOTE/LOCAL" switch of the F-MPC60B (UM43FG-E5AK) panel plane the invalidity, operation place
(43D"REMOTE-LOCAL") is chosen in long way (external input by using selective input), and "CLOSE/OPEN" control
of the circuit breaker is changed.
Off (open)" is set at selective input of 1, and "on" is set at selection input of 2, and then, the case in which
external 43D (the operation site selection) are set is shown in selective input of 3 in the following.
Selective input of 1 (terminals number 5) is function setting code "70", and "off(open)" function is "10".
Setting code No.70 is set at "10".
Similarly, selective input of 2 (terminals number 6) is function setting code 71, and on(close) function is
11. Setting code No.71 is set at 11.
Similarly, selective input of 3(terminal number 7) is function setting code 72, and 43function is 12.
Setting code No.72 is set at 12. Refer to section 5.1 and 5.2.
"ON" in long way (43D).
(It is judged after the setting with "LOCAL",
when "OFF" is done.)
24
CC
TRIP
Power lock
F-MPC60UM43FG-E5AK

A
l
a
r
m

Selective output
Trip lock
1 2 3 4
26
1
2
27
TC
5 6 7 8 13
16
30 25
17 18 19 20 21 22 23 4
N
28 29
LOCAL
Note 1
It is possible by connecting field-center and
selection switch with selective input circuit of
the F-MPC60B main body, when it is surely
made to be the one place operation.
(Application example 03)
REMOTE
28 27
Outside
43D
F-MPC60
UM43FG-E5AK
Emergency
stop
Inside of CB
Developments
Open Close
Open Close
Open Close
Close Open
Communication
Selective input
Close Open
Circuit breaker (CB) ON
answer back signal
9 10 11 12
Application example 03The circuit diagram is a reference.
It makes "REMOTE/LOCAL" switch of the F-MPC60B (UM43FG-E5AK) panel plane the invalidity, operation place
(43D"REMOTE-LOCAL") is chosen in long way (external input), and "CLOSE/OPEN" control of the circuit breaker
is changed. Moreover, equipping operation place priority diverted switch (43C "the field-center) is made to be a
system of operation by "field: External input" or operation by "communication".
Off(open) is set at selective input of 1, and on(close) is set at selective input of 2, and external 43D(Operation site
selection) is set at selective input of 3, and then, the case in which operation place priority diverted switch (43C "the
field-center) are set is shown in selective input of 4 in the following.
Selective input of 1 (terminals number 5) is function setting code "70", and "off(open)" function is "10". Setting
code No.70 is set at "10".
Similarly, selective input of 2 (terminals number 6) is function setting code 71, and on(close) function is 11. Setting code
No.71 is set at 11.
Similarly, selective input of 3(terminal number 7) is function setting code 72, and 43D REMOTE-LOCAL function is 12.
Setting code No.72 is set at 12.
Similarly, selective input of 4(terminal number 8) is function setting code 73, and 43C the field-center function is 13.
Setting code No.73 is set at 13. Refer to section 5.1 and 5.2.
24
CC
Inside of CB
Close Open Trip
Power lock Emergency
Stop

Selective output
Trip lock
1 2 3 4
26
1
2
27
TC
5 6 7 8 13
16
30 25
17 18 19 20 21 22 23 4
N
28 29
ON in the field (43C)
"ON" in long way (43D).
Developments
LOCAL
Note:
After setting each diverted switch, the signal is
switched to other side, when "OFF" is done.
Remote LocalThe fieldThe center
(ON) (OFF) (ON) (OFF)
REMOTE
Communication
28 27
Outside
43D
F-MPC60
UM3FG-E5AK
The field
The center
43C
Open Close
Selective input
Close
Open
Close
Open
Open
Close
A
l
a
r
m
9 10 11 12
Application example 04The case in which definite-time limit characteristic must be set at two steps.
The combination of F-MPC60B instant element (INST) + outside attachment timer and definite-time limit element
(DT).
Figure 4.1 the characteristics of protective INST + outside attachment timer and protective DT
Setting
a) The instant action contact setting (code No.11) is made to be 011.
The meaning of
b) Setting of selective input 1
Setting code No.70 is set at 17(external trip 1).
Figure 4.2 the connection diagram
1.5sec
Definite-time limit operation.
Instantaneous operationTimer
Time
T+40msec
Magnification of the current.
It is not tripped.
Output contact number when actuating each protective relay. Example means selective output 1.
With lockout
Terminal number
16 25 5 6 4
F-MPC60B UM43FG-E5AK
In the transmission, selective input of 2
(setting code No.71) is made to be "03",
when it is notified in the host system.
T
Timer
0-1sec

Selective output 1

Selective input 1

Selective input 2

Application example 05 the circuit breaker is put on by the trip in the external signal
Example: the case in which it was applied to the large-capacity transformer.
Figure 5.1 the configuration
Figure 5.2 the conection


CT
PRT
87T
F-MPC60B ( UM43FG-E5AK
Ratio differential protection
TR
266369

Selective input
5
87T
6 7 8 4 Terminal number
1 2 3 4
F-MPC60B UM43FG-E5AK

26 63 69 (No voltage contact)


9 10 11 12
5 6 7 8