Sunteți pe pagina 1din 1

Technical Information Sheet SF105DIN/A

Novaris Pty Ltd ABN: 33 065 427 232


72 Browns Road, Kingston, TAS. 7050 TEL: +61 3 6229 7233
AUSTRALIA FAX: +61 3 6229 9245
Copyright 2000 Novaris E-mail: sales@novaris.com.au

SURGE FILTERS, LOW CURRENT DINsafe




Product Description

Novaris Technologies DINsafe power line surge filters
are designed for effective protection against induced
transient overvoltages caused by lightning and other
events on AC and DC power supply circuits.

Versions are available for voltage ratings up to 240V
AC and are housed in a rugged metal enclosure with
DIN43880 compliant dimensions.

Operation

Multistage transient protection is utilised in every unit.
Metal oxide varistors, as the first stage, absorb the
majority of the energy. These components are
continuously monitored for integrity with full
protection indicated by a green LED on the top of the
case. A red LED indicates power ON.

The first stage is followed by a low pass LC filter that
further attenuates the let through voltage. The filter
also attenuates low-level noise and harmonics.

The third stage comprises metal oxide varistors. These
provide a final clamping circuit and protect against
impulses generated by the connected load. This is
particularly important when multiple loads are
connected. Do not exceed total filter ratings.

10 amp and 20 amp filters also feature external alarms.
These provide a clean changeover contact that may be
used to remotely monitor the status of the filter or as a
power fail indicator. The relay is normally energised
when power is applied.


Specifications

Description Multistage power surge filter
No phases: 1
Voltage drop: < 2V at full load
Efficiency: 99%
Earth leakage: < 0.75mA
Protection modes: Transverse and common mode
Protection stages: MOV / low pass filter / MOV
Surge withstand: IEEE C62.41 cat, A, B, opt. C
AS1768-1991 cat. A, B, opt. C
Surge rating: 16kA per line for 8/20us pulse
40kA per line for cat. C units
Let through voltage for 6kV 1.2/50us, 3kA 8/20us pulse:
< 680V
Response time: Instantaneous
Frequency response: 3dB point at 800Hz
Indicators: MOV integrity - green LED
Power ON - red LED
Alarm relay: Clean contact with 4kV isolation
from active circuitry.
Dimensions:
SF105DIN-xxx/A: 116H x 80D x 54W
SF110DIN-xxx/A: 116H x 80D x 120W
SF120DIN-xxx/A: 116H x 80D x 120W
Mounting: DIN rail mountable. Panel mount
brackets are available on request.
Terminal capacity:
SF105DIN-xxx/A: 4mm
2

SF110DIN-xxx/A: 16mm
2

SF120DIN-xxx/A: 16mm
2

Location: Final subcircuits to AS1768 location
categories A and B, category C is
optional.
Options
Cat No. Vmax AC Current Rating
SF105DIN-30V/A 30V 5A 2kA
SF105DIN-50V/A 50V 5A 6.5kA
SF105DIN-150V/A 150V 5A 8kA
SF105DIN/A 250V 5A 8kA
SF105DIN-16/A 250V 5A 16kA
SF105DIN-40/A 250V 5A 40kA

SF110DIN-30V/A 30V 10A 4kA
SF110DIN-150V/A 150V 10A 16kA
SF110DIN/A 250V 10A 16kA
SF110DIN-40/A 250V 10A 40kA

SF120DIN/A 250V 20A 16kA
SF120DIN-40/A 250V 20A 40kA

/A indicates LED display for 5A version
/A indicates LED display and external alarm for 10A and 20A
versions.

2Amp and 3Amp versions are also available on request.
Please contact Novaris for details.

S-ar putea să vă placă și