Air Handling Units

R-134a
Direct expansion
BY Series
BY03 thru BY25
2.5 TR thru 30 TR
9 kW thru 105 kW

Company Business
Zamil Air Conditioners was founded in 1974 as one of the first air conditioning business to be established in Saudi Arabia
and today is a leading international manufacturer of air conditioning systems and is No. 1 in the Middle East.
Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.
The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and
service brands as well as a number of international brands under the OEM sales.
The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.
The four SBUs are:
1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Classic, Cooline, GE and OEM brands for commercial and industrial
customers.
3. Zamil CoolCare providing engineering & project management services, HVAC maintenance, retrofit services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirement of Chillers & Double skin AHUs.
The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare Service direct their business
operations from the corporate headquarters at Dammam, Saudi Arabia.
Geoclima has its engineering & production departments located at Monfalcone, Italy and has a design center in Austria.
All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.
Factories and Productions
Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one speciality production facility
in Italy operated by Geoclima.
The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.
Quality & Product Certificates
The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2000 certification.
Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization)
Certificate for Room Air Conditioners. ZAC's products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent
4. DEMKO
5. ETL
Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed
bin Fahd Al Saud Award for Factory Safety.
Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners
manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the Concealed Units up to 5 tons, the Ducted Splits up to 30 tons, the Packaged Units up to 90 tons, the Single and Double Skin
Air Handling Units up to 70,630 CFM and the Water Chillers up to 660 tons cooling capacity.

INDEX
Contents

Page

Outstanding features ................................................................................................................................ 2


Model decoding ........................................................................................................................................ 3
Blower drive options ................................................................................................................................. 4
Standard specifications ......................................................................................................................... 4-5
Options and accessories ....................................................................................................................... 5-6
Physical data ............................................................................................................................................ 7
Cooling capacities ............................................................................................................................... 8-15
Fan performance data ....................................................................................................................... 16-17
Electrical data .................................................................................................................................... 18-20
Dimensions, indoor units ................................................................................................................... 21-24
Dimensions, heater box .......................................................................................................................... 25
Dimensions, outdoor units ................................................................................................................. 26-30
Typical schematic wiring diagram ...................................................................................................... 31-34
Controls and sequence of operation ....................................................................................................... 35
Installation instructions ........................................................................................................................... 36

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

OUTSTANDING FEATURES
* HIGH EER (ENERGY EFFICIENCY RATIO)
* INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS
* LOW CEILING HEIGHT REQUIREMENTS
* MICROPROCESSOR BASED CONTROLS
* ONE SIDE TOTAL SERVICE ACCESSIBILITY
* SINGLE POINT POWER ENTRY
* UV FLOW LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY)
* NUMBERED CODED WIRES
* INSULATED DRAIN PAN
* FACTORY INSTALLED OPTIONS UPON REQUEST
* SMALL FOOTPRINT
* LIGHT WEIGHT
* PRE-PAINTED CABINETS WITH FIBERGLASS INSULATION
* LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTALLATION
* STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTALLATION
* ALUMINUM OR SYNTHETIC FILTERS
* UL LISTED MAJOR COMPONENTS

NOTES:

AIR
HANDLING
UNIT

BY

1&2
BASIC

V : VERTICAL

F : 460-3-60

M : 380-3-60
(4 WIRE)

H : 208/230-3-60

H : HORIZONTAL C : 208/230-1-60 S : SINGLE

V : VERTICAL

H : HORIZONTAL

5
ARRANGEMENT

F : 460-3-60

M : 380-3-60
(4 WIRE)

D : DUAL

FOR BY18 - BY25

D : DUAL

S : SINGLE

H : 208/230-3-60 FOR BY07 - BY14

7
6
ELECTRICAL REFRIGERATION
CIRCUIT
SUPPLY
(V-Ph-Hz)

Blower motor ON-OFF and trip indication.

25

18

14

10

07

3&4
FACE AREA
(SQ. FT.)

9
BLOWER
MOTOR
10
DRIVE
OPTIONS

C : COOL ONLY

8
MODE

L : 10 HP ODP

J : 7.5 HP ODP

FOR BY25

J : 7.5 HP ODP

G : 5 HP ODP

FOR BY14/18

E : 3 HP ODP

D : 2 HP ODP

FOR BY10

E : 3 HP ODP

D : 2 HP ODP

FOR BY07

9
BLOWER
MOTOR

Y : 1 HP ODP

W : 0.75 HP ODP

K : ALT. II

J : ALT. I

10
DRIVE
OPTIONS

C : COOL ONLY U : 0.5 HP ODP N : DIRECT


DRIVE
W : 0.75 HP ODP

8
MODE
12
EVAPORATOR
COIL

12
EVAPORATOR
COIL

: 5/1
: 6/1
: 7.5 /1
: 10 /2
: 12/2
: 15 /2
: 20 /2
: 25/2
FOR BY18 - BY25
N : NO HEATER
E : 12/2
F : 15 /2
G : 20 /2
H : 25/2
J : 30/2
K : 35/2
L : 40/2

J : 30/2

A
B
C
D
E
F
G
H

F : COPPER FIN

E : COATED
ALUMINUM
FIN

FOR BY07 - BY14 D : ALUMINUM


FIN
N : NO HEATER

11
HEATER
OPTIONS
(kW/STAGE)

N : NO HEATER D : ALUMINUM
FIN
A : 5/1
E : COATED
ALUMINUM
B : 6/1
FIN
C : 7.5 /1**
F : COPPER FIN

11
HEATER
OPTIONS
(kW/STAGE)

MODEL DECODING

* Blower motor ON-OFF and trip indication.


** Heater capacity will be 7kW for single phase power supply.

05

03

3&4
5
7
6
FACE AREA ARRANGEMENT ELECTRICAL REFRIGERATION
(SQ. FT.)
CIRCUIT
SUPPLY
(V-Ph-Hz)

BY07 - BY25

NOTES:

AIR
HANDLING
UNIT

BY

1&2
BASIC

BY03 - BY05

D : 2"SYNTHETIC

B : 2" ALUMINUM

FOR BY25
N : NO FILTER

C : 1" SYNTHETIC
D : 2"SYNTHETIC

N : NO FILTER
A : 1" ALUMINUM
B : 2" ALUMINUM

FOR BY10, 14 & 18

C : 1" SYNTHETIC

FOR BY07
N : NO FILTER
E : 1/2" ALUMINUM
F : 1/2" SYNTHETIC
A : 1" ALUMINUM

13
FILTER

C : 1" SYNTHETIC

A : 1" ALUMINUM

F : 1/2" SYNTHETIC

E : 1/2" ALUMINUM

N : NO FILTER

13
FILTER

V : VOLT FREE
CONTACTS

N : NO OPTION

15
OTHER OPTIONS

N : STD. UNIT
NO ACCESORIES

V : VOLT FREE
CONTACTS

N : NO OPTION

15
14
UNIT ACCESSORIES OTHER OPTIONS

N : STD. UNIT,
NO ACCESORIES

14
UNIT
ACCESSORIES

BLOWER DRIVE OPTIONS


MOTOR
MODEL
NUMBER

BY07
BY10
BY14
BY18
BY25

OPTION
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II

HP

RPM

2
3
2
3
5

1750
1750
1750
1750
1750
1750
1750
1750
1750
1750

7.5
5
7.5
7.5
10

BLOWER
PULLEY
PITCH DIA.
(INCH)
2.7 - 3.7
2.7 - 3.7
3.1 - 4.1
3.1 - 4.1
3.7 - 4.7
4.3 - 5.5
3.7 - 4.7
4.3 - 5.5
4.3 - 5.5
4.3 - 5.5

SPEED RANGE (RPM)


MINIMUM

MAXIMUM

893
964
733
875
809
940
809
875
685
800

1156
1321
970
1157
1028
1203
1028
1120
880
1023

PULLEY
PITCH DIA.
(INCH)
5.6
4.9
7.4
6.2
8.0
8.0
8.0
8.6
11
9.4

APPROX. SPEED
CHANGE PER
PULLEY
TURN (RPM)
62
71
40
47
37
44
37
40
38
44

STANDARD SPECIFICATIONS
A. General
These Zamil Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with
blower motor, DX coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applications.
The unit is ready to operate when piped to a suitable condensing unit, connected to power/controls and air ducts or
plenums.
They should be ordered separately as horizontal air discharge or vertical air discharge units as per application requirements.

B. Unit Enclosure
Casing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1/2" thick fiberglass insulation to prevent condensation from
forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and
errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality conforming
to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. Coils
Coils are of the enhanced louvered fin-and-tube type, constructed of copper tubes, mechanically bonded to aluminum
fins. As an option, corrugated copper or enhanced coated aluminum fins may be provided. End plates and tube support
sheets are 18 gauge galvanized steel, formed to provide structural strength. Each coil is pressure tested in the factory at
not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.

D. Drain Pans
Drain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional
corrosion protection. Drain outlets of 3/4" NPT is provided for field connection.

E. Evaporator Fan
Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor
(except for BY03 & BY05, which have direct drive motors) is mounted on an adjustable base and secured by a locking
device. Fan drive is through adjustable motor pitch pulley and belt-driven. Fan shafts are designed to operate at less than
2/3rds of the first critical speed when the unit comes up to rated revolutions per minute (RPM). Units have sealed,
permanently lubricated ball or sleeve fan bearing and are statically / dynamically balanced in the fan housing during final
assembly. Fan motors are of the open drip-proof type (totally enclosed types are optional) and conform to NEMA MG1 & MG-2. Motor starters are magnetic contactor, across-the-line type.

F. Microprocessor Controller
These air handling units are provided with a microprocessor control board incorporating the following features:
-

BALANCE LOADING OF COMPRESSORS: The units electronic control automatically operates lead/lag sequence
of compressors. This is to load the compressors evenly over long periods of operation. If required however, compressor-1 can also be set to always lead. In this case, compressor-1 always starts first and stops last. (Selectable through
dip switch setting on control board).

PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoids opening and compressor starting to equalize the pressure in the system necessary for compressor to startup. (Selectable through dip switch setting on control board).

COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat due to load demand.

COMPRESSOR LOCK-OUT FUNCTION: If any of the units safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.

FAULT DIAGNOSTICS: In case of system fault, LEDs on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.

DIGITAL I/Os: The units control board is compatible to operate with a DDC controller or any standard 24V a.c.
thermostat commercially available.

SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequential
order: supply fan condenser fan compressor; at a pre-determined timings.

G. Control Panel
A complete factory-wired control panel is provided to ensure safe and proper operation.

OPTIONS AND ACCESSORIES


A. Zone Control
Total comfort zone control systems are available up to 19 zones and can provide a comfortable temperature to each
zone/room (field supplied).

B. Electric Heaters
Electric heaters are of the resistance open coil type and conform to UL requirements. Electrical characteristics, kW
capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switches are provided to
shut-off power to heaters in case of airflow failure.

C. Filters
Filters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminum
type (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units.

D. Discharge Air Plenum & Return Air Grille


As an accessory, discharge air plenum with return air grilles can be provided on vertical units.

E. UV Flow Light Emitters


The damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The
UV flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growth
of these microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow.
To order the UV flow use the kit numbers in the table below:
MODEL NUMBER
KIT PART NUMBER

BY03

BY05

BY07

BY10

BY14

BY18

BY25

700-391-16

700-391-17

700-391-18

700-391-19

700-391-20

700-391-21

700-391-22

F. Electronic Thermostats
General Informations: Single stage or two stage thermostats provide low voltage control of one or two stage heating
and/or cooling applications. The thermostat normally displays room temperature, mode of operation and which system is
currently on.
You may select different heating and cooling setpoints for the systems to maintain (example 700F in heating and 750F in
cooling). Raising or lowering the setpoints in heating or cooling is as simple as pushing a button.
The thermostat also allows you to select continuous fan operation, (useful when using an electronic air cleaner), or have
the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and should
not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers /
diffusers.
The following features are available with the electronic thermostats:
1. Fault Indicator: A 24 volts AC compressor fault signal available as and when required, use thermostat part number
800-645-21.
2. Time Delay Timer: Available on thermostat, Part No. 800-645-21 & 800-645-31. Prevents short cycling of compressor, four minutes delay.
TYPICAL THERMOSTAT
Part No.

Selector Switch Positions

Heating Cooling
Stages Stages

Mode Switch

Fan Switch

800-645-31

OFF-AUTO - HEAT/COOL ON - AUTO

800-645-21*

OFF-AUTO - HEAT/COOL ON - AUTO

800-646-23

OFF-AUTO - HEAT/COOL ON - AUTO

* with built-in compressor fault & clogged filter indication led lights.

TYPICAL THERMOSTAT
(Part Number: 800-645-21/31)

PHYSICAL DATA
MODEL NUMBER

BY03

BY05

BY07

EVAPORATOR BLOWER Type

BY14

BY18

BY25

Centrifugal

Nominal airflow CFM (L/S)

1200 (566) 2000 (944) 2800 (1321) 4600 (2171) 5500 (2596) 7000 (3303) 9000 (4247)

Motor HP (Std/Alt)

0.5/0.75

0.75/1

2/3

3/2

5/7.5

5/7.5

7.5/10

Drive type

Direct

Direct

Belt

Belt

Belt

Belt

Belt

Blower size

10x10

10x10

12x12

15x15

15x15

15x12

18x18

Quantity
EVAPORATOR COIL

BY10

Corrugated Fin & Tube

Type
Tube dia. - Rows - FPI
Face area, Sq. ft. (Sq. m.)

3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 3 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14 3/8 - 4 - 14

3.2 (0.3) 4.6 (0.43)

7 (0.65)

10 (0.93)

14 (1.3) 17.4 (1.62) 25 (2.32)

REFRIGERANT LINES
SINGLE COMPRESSOR

Suction line size O.D. (inch)

7/8

7/8

1-1/8

1-3/8

1-3/8

Liquid line size O.D. (inch)

3/8

3/8

5/8

5/8

5/8

REFRIGERANT LINES
DUAL COMPRESSOR

Suction line size O.D. (inch)

7/8

7/8

1-3/8

1-3/8

1-3/8

Liquid line size O.D. (inch)

1/2

1/2

5/8

5/8

7/8

RETURN AIR FILTER

Size (inch)

SHIPPING WEIGHT

24 x 20 x 1/2 16 x 20 x 1/2 20 x 20 x 1/2 18 x 24 x 1

20 x 24 x 1

20 x 24 x 1 20 x 24 x 2

Quantity

kg. (approx.)

80

120

165

225

300

340

420

COOLING CAPACITIES
(Single compressor units)
BY03 INDOOR UNIT WITH CBX036 OUTDOOR UNIT

BY03 INDOOR UNIT WITH CBX030 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

EVAPORATOR AIRFLOW, CFM/DR


1045/0.117
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
29.78
32.57
35.58
26.55
21.93
17.24
3.28
3.42
3.56
28.23
30.94
33.83
25.87
21.67
16.92
3.43
3.59
3.74
26.32
28.9
31.67
24.29
21.11
16.36
3.67
3.86
4.05
24.63
27.05
29.73
22.81
20.52
15.81
3.83
4.03
4.25
23.04
25.37
27.88
21.3
19.92
15.22
3.99
4.22
4.45

85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

85

95

105

115

125

BY05 INDOOR UNIT WITH CBX060 OUTDOOR UNIT

BY05 INDOOR UNIT WITH CBX048 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR


1230/0.138
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
36.82
40.1
43.53
34.52
28.61
22.57
3.77
3.96
4.14
34.89
38.02
41.41
33.65
27.75
21.8
4.01
4.23
4.44
32.69
35.67
38.91
32.21
26.84
20.93
4.24
4.47
4.72
30.6
33.43
36.53
30.15
26
20.13
4.4
4.65
4.92
28.46
31.19
34.09
28.03
25.18
19.31
4.59
4.87
5.16

CONDENSER
ENTERING AIR
TEMP. (0F)

EVAPORATOR AIRFLOW, CFM/DR


1680/0.130
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
47.07
51.71
56.7
45.16
37.35
29.42
4.65
4.83
4.99
44.73
49.23
54.17
43.45
36.47
28.62
4.86
5.07
5.28
41.73
46.03
50.69
40.7
35.44
27.56
5.11
5.36
5.6
38.94
43.04
47.58
38.01
34.34
26.56
5.34
5.6
5.88
36.38
40.28
44.53
35.51
33.35
25.56
5.54
5.84
6.14

EVAPORATOR AIRFLOW, CFM/DR


2000/0.153
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
57.51
62.79
68.48
56.74
46.94
37.03
6.09
6.36
6.61
54.28
59.4
64.94
53.19
45.75
35.9
6.48
6.8
7.11
50.35
55.22
60.44
49.34
44.02
34.23
6.77
7.11
7.47
47.11
51.74
56.72
46.17
42.62
32.91
7.03
7.41
7.81
44.32
48.7
53.52
43.43
41.59
31.92
7.37
7.79
8.25

CONDENSER
ENTERING AIR
TEMP. (0F)
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

85

95

105

115

125

MULTIPLIERS FOR HIGHER/LOWER CFM


MODEL No.: BY03
% of rated airflow

70%

80%

90%

100%

110%

120%

TC

0.94

0.96

0.98

1.015

1.03

SC

0.82

0.88

0.94

1.05

1.1

kW

0.94

0.96

0.98

1.017

1.035

MODEL No.: BY05


% of rated airflow

80%

90%

100%

110%

120%

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

TC

0.965

0.985

1.015

1.03

SC

0.89

0.945

1.05

1.1

kW

0.975

0.987

1.012

1.025

kW Total unit power input


DR Wet Bulb depression ratio

DBE Dry Bulb Temp. ( F) of Air Entering Coil


WBE Wet Bulb Temp. (0F) of Air Entering Coil
0

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.15 ESP.

COOLING CAPACITIES
(Single compressor units)
BY07 INDOOR UNIT WITH CBX075 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1900/0.102
62
63.83
53.03
7.03
61.35
52.05
7.48
58.53
51.08
7.98
55.72
50.08
8.53
52.74
48.34
9.12

67
69.68
44.32
7.41
67.05
43.38
7.88
64
42.38
8.41
60.95
41.39
9.0
57.66
40.32
9.63

72
75.84
35.4
7.77
73.13
34.54
8.28
69.86
33.55
8.86
66.58
32.57
9.5
63.06
31.54
10.18

EVAPORATOR AIRFLOW, CFM/DR


2400/0.126
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
67.03
73.14
79.76
60.68
49.95
39.12
7.4
7.76
8.13
64.31
70.34
76.76
58.49
49.01
38.2
7.84
8.24
8.65
61.18
67.01
73.34
55.77
47.95
37.23
8.34
8.78
9.25
58.25
63.78
69.83
53.23
46.97
36.23
8.9
9.37
9.91
55.01
60.24
66
50.42
45.86
35.15
9.49
10.02
10.61

2900/0.148
62
69.25
62.93
7.96
66.34
60.33
8.4
63.18
57.6
8.91
60.02
54.85
9.47
56.74
52
10.07

67
75.68
55.17
8.31
72.67
54.17
8.8
69.15
53.08
9.35
65.75
52.08
9.96
62.23
51.1
10.61

72
82.63
42.51
8.7
79.5
41.59
9.24
75.88
40.59
9.86
72.13
39.54
10.51
68.25
38.51
11.24

BY07 INDOOR UNIT WITH CBX090 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2250/0.118
62
72.65
60.97
8.24
69.31
59.8
8.73
64.12
57.21
8.95
59.71
53.72
9.42
55.49
49.95
9.85

67
79.3
50.83
8.68
75.79
49.71
9.2
70.13
47.23
9.44
65.35
45.45
9.94
60.67
43.83
10.4

72
86.41
40.52
9.11
82.63
39.4
9.68
76.62
37.12
9.94
71.38
35.37
10.49
66.34
33.83
10.99

EVAPORATOR AIRFLOW, CFM/DR


2800/0.144
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
75.76
82.79
90.28
68.82
56.74
44.37
8.85
9.28
9.72
72.23
79.02
86.29
65.8
55.6
43.25
9.35
9.81
10.3
66.74
73.08
79.9
60.22
53.04
40.88
9.56
10.05
10.58
62.1
67.98
74.34
55.88
51.17
39.08
10.04
10.56
11.13
57.59
63.12
69.16
51.84
49.57
37.57
10.47
11.03
11.65

3350/0.168
62
78.09
70.93
9.4
74.3
67.68
9.91
68.61
61.91
10.12
63.79
57.39
10.59
59.26
53.35
11.03

67
85.25
62.09
9.83
81.33
60.95
10.37
75.23
58.38
10.61
69.86
56.4
11.13
64.92
54.86
11.6

72
93.14
47.86
10.28
88.95
46.72
10.88
82.31
44.3
11.16
76.67
42.54
11.72
71.19
40.95
12.25

BY10 INDOOR UNIT WITH CBX100 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2800/0.05
62
92.24
86.16
9.96
87.11
84.93
10.61
82.47
80.83
11.07
78.2
76.64
11.55
72.84
71.38
11.83

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
101.6
71.78
10.36
96.26
70.51
11.1
91.28
70.21
11.63
86.67
68.52
12.17
80.84
66.42
12.51

72
111.76
57.18
10.79
106.33
55.93
11.64
101.02
55.36
12.26
95.95
53.64
12.88
89.67
51.6
13.28

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


3400/0.066
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
96.15
106.13
116.95
92.87
80.02
62.61
10.24
10.65
11.11
90.67
100.53
111.23
88.6
78.83
61.42
10.91
11.42
12.01
85.78
95.22
105.52
84.06
78.66
60.88
11.39
11.98
12.66
81.19
90.36
100.24
79.56
76.95
59.18
11.88
12.54
13.3
75.7
84.16
93.65
74.19
74.78
57.11
12.17
12.88
13.72
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

4000/0.076
62
99
95.63
10.66
93.25
91.12
11.35
88.19
86.43
11.84
83.49
81.82
12.34
77.73
76.18
12.64

72
120.86
67.68
11.58
114.83
66.49
12.5
108.97
66.1
13.17
103.45
64.36
13.83
96.55
62.25
14.26

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

67
109.42
87.77
11.08
103.53
86.59
11.87
97.98
86.55
12.44
92.95
84.84
13.01
86.71
82.81
13.37

COOLING CAPACITIES
(Single compressor units)
BY10 INDOOR UNIT WITH CBX120 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

3200/0.059
62
103.74
93.61
11.31
98.16
91.29
11.82
92.58
86.31
12.29
86.73
80.95
12.71
80.59
75.34
13.11

67
114.45
77.99
11.97
108.49
75.83
12.54
102.38
73.76
13.05
96
71.52
13.53
89.34
69.25
13.98

72
125.93
62.07
12.66
119.45
59.94
13.29
112.83
57.88
13.86
105.93
55.7
14.4
98.76
53.49
14.9

EVAPORATOR AIRFLOW, CFM/DR


4000/0.076
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
108.41
119.83
132.07
100.76
88.14
68.71
11.93
12.59
13.31
102.66
113.58
125.17
95.47
86.01
66.53
12.44
13.17
13.96
96.73
106.99
118.28
90.18
83.81
64.51
12.92
13.7
14.56
90.46
100.4
111.03
84.43
81.66
62.33
13.37
14.2
15.11
84.01
93.29
103.28
78.53
79.28
59.98
13.77
14.66
15.64

4800/0.092
62
111.9
104
12.66
105.62
98.23
13.19
99.56
92.81
13.68
93.28
87.07
14.12
86.59
80.94
14.54

67
123.82
97.78
13.34
117.16
95.51
13.93
110.5
93.46
14.47
103.42
91.09
14.97
96.14
88.76
15.44

72
136.55
74.89
14.09
129.31
72.66
14.75
122.07
70.59
15.35
114.62
68.43
15.93
106.55
66.05
16.46

BY10 INDOOR UNIT WITH CBX150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.076
62
122.18
104.58
13.49
116.6
100.41
14.38
110.68
95.4
15.37
104.05
89.67
16.44
97.08
83.66
17.53

67
134.05
86.52
14.12
128.15
84.46
15.11
121.91
82.43
16.21
114.8
80.07
17.38
107.34
77.66
18.58

72
146.9
68.2
14.79
140.86
66.33
15.92
134.31
64.41
17.14
126.55
62.07
18.44
118.45
59.69
19.79

EVAPORATOR AIRFLOW, CFM/DR


4600/0.088
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
125.47
137.6
151.09
108.09
93.22
72.61
14.03
14.66
15.36
119.66
131.62
144.74
103.05
91.23
70.68
14.93
15.68
16.51
113.45
125.24
138
97.79
89.24
68.77
15.94
16.79
17.76
106.63
117.86
130.07
91.89
86.84
66.46
17.02
17.98
19.09
99.42
110.08
121.74
85.68
84.35
64.07
18.11
19.2
20.46

5000/0.095
62
127.23
109.61
14.43
121.35
104.5
15.34
115.03
99.16
16.35
108.06
93.13
17.43
100.87
86.93
18.54

67
139.81
97.68
15.06
133.53
95.56
16.09
127.02
93.57
17.21
119.44
91.1
18.41
111.63
88.67
19.64

72
153.45
75.43
15.78
146.98
73.49
16.94
140.09
71.57
18.2
131.9
69.18
19.55
123.49
66.82
20.93

BY14 INDOOR UNIT WITH CBX150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.050
62
134.73
115.22
14.16
128.1
112.74
15.03
120.78
108.17
15.94
113.46
101.84
16.89
105.1
94.41
17.84

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
147.92
95.97
14.84
141.16
93.7
15.81
133.35
90.79
16.84
125.38
88.19
17.9
116.36
85.13
18.96

72
162.59
76.64
15.59
155.34
74.38
16.71
147.24
71.71
17.88
138.45
69.04
19.07
128.79
66.1
20.28

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


4800/0.062
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
139.92
153.99
169.66
125.25
106.08
83.35
14.78
15.48
16.28
133.02
146.71
162
119.25
103.69
81.06
15.67
16.49
17.46
125.28
138.59
153.31
112.2
100.78
78.26
16.6
17.54
18.65
117.54
130.27
144.21
105.5
98.2
75.64
17.58
18.63
19.89
108.76
120.69
134.07
97.7
95
72.65
18.54
19.72
21.13
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

5800/0.076
62
144.56
129.4
15.76
137.23
123.03
16.68
129.39
115.88
17.63
121.31
108.88
18.62
112.21
100.8
19.6

72
176
91.05
17.35
168
88.75
18.57
159
85.97
19.8
149.5
83.32
21.07
138.75
80.21
22.35

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

10

67
159.67
118.09
16.5
151.87
115.58
17.54
143.58
112.78
18.61
134.77
110.1
19.73
124.72
106.79
20.84

COOLING CAPACITIES
(Dual compressor units)
BY07 INDOOR UNIT WITH CBX075 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1900/0.102
62
67.64
55.74
6.48
64.74
54.62
6.88
60.02
52.79
7.36
56.3
51.37
7.74
52.32
48.92
8.13

67
73.56
46.71
6.82
70.51
45.63
7.24
65.48
43.84
7.77
61.53
42.48
8.18
57.25
40.98
8.61

72
79.85
37.52
7.12
76.66
36.49
7.59
71.41
34.81
8.17
67.16
33.47
8.61
62.49
31.97
9.09

EVAPORATOR AIRFLOW, CFM/DR


2400/0.126
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
71.01
77.2
83.9
63.51
52.45
41.29
6.84
7.15
7.47
67.87
73.98
80.48
62.36
51.38
40.24
7.24
7.59
7.95
62.85
68.67
74.9
58.55
49.59
38.53
7.73
8.13
8.55
58.98
64.51
70.45
55.06
48.24
37.21
8.12
8.54
9.02
54.69
59.93
65.59
51.13
46.68
35.73
8.51
8.98
9.5

2900/0.148
62
73.42
68.12
7.39
70.13
65.19
7.8
64.95
60.51
8.3
60.78
56.74
8.68
56.48
52.81
9.09

67
79.83
57.75
7.7
76.44
56.66
8.15
70.91
54.86
8.7
66.63
53.54
9.12
61.86
51.96
9.57

72
86.75
44.68
8.02
83.25
43.66
8.53
77.5
41.98
9.13
72.75
40.58
9.61
67.75
39.11
10.11

BY07 INDOOR UNIT WITH CBX090 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2250/0.118
62
81.96
70.31
7.5
77.55
68.52
8.06
71.08
65.15
8.31
65.59
62.46
8.73
60.69
59.33
9.19

67
89.84
59.38
7.86
85.16
57.64
8.47
78.13
54.4
8.75
72.18
51.82
9.2
66.82
49.91
9.7

72
98.34
48.27
8.19
93.39
46.59
8.85
85.83
43.52
9.17
79.43
41.08
9.67
73.61
39.19
10.22

EVAPORATOR AIRFLOW, CFM/DR


2800/0.144
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
85.77
94.2
103.19
79.02
65.94
52.58
8.09
8.43
8.75
81.01
89.1
97.88
77.17
64.11
50.87
8.66
9.05
9.43
74.18
81.69
89.91
72.71
60.79
47.75
8.92
9.34
9.76
68.44
75.5
83.16
66.76
58.21
45.26
9.35
9.81
10.28
63.32
69.8
77
61.91
56.24
43.33
9.81
10.32
10.85

3350/0.168
62
88.6
87.06
8.64
83.64
82.64
9.21
76.63
75.12
9.47
70.65
68.91
9.91
65.25
63.79
10.37

67
97.3
71.84
8.96
92.08
70.07
9.59
84.38
66.68
9.89
77.99
64.08
10.37
72.03
62.07
10.88

72
106.85
56.5
9.28
101.37
54.81
9.97
92.99
51.59
10.31
85.92
49.03
10.85
79.56
47.11
11.43

BY10 INDOOR UNIT WITH CBX100 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2800/0.05
62
95.65
88.9
9.48
89.67
86.4
10.15
83.94
82.69
10.69
78.45
77.43
11.18
72.96
72.07
11.28

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
105.73
74.46
9.99
99.54
72.13
10.73
93.35
69.96
11.32
87.4
67.79
11.85
81.45
65.58
11.99

72
116.71
59.78
10.54
110.19
57.54
11.37
103.55
55.4
12.03
97.16
53.28
12.62
90.64
51.06
12.8

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


3400/0.066
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
99.85
110.55
122.37
97.82
82.82
65.38
9.82
10.34
10.93
93.63
104.06
115.48
91.88
80.51
63.12
10.5
11.09
11.77
87.56
97.58
108.45
86.25
78.35
60.94
11.04
11.7
12.46
81.78
91.24
101.71
80.72
76.1
58.79
11.53
12.25
13.08
76
85.05
94.97
75.07
73.9
56.6
11.65
12.39
13.25
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

4000/0.076
62
102.83
100.74
10.26
96.38
94.59
10.96
90.11
88.76
11.51
84.18
83.09
12.01
78.26
77.3
12.12

72
126.72
70.64
11.43
119.48
68.33
12.3
112.07
66.08
12.99
105.17
63.98
13.63
98.1
61.72
13.82

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC= 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

11

67
114.28
90.84
10.8
107.34
88.37
11.57
100.58
86.18
12.19
94.16
84.04
12.75
87.75
81.83
12.89

COOLING CAPACITIES
(Dual compressor units)
BY10 INDOOR UNIT WITH CBX120 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

3200/0.059
62
110.43
96.21
11.71
104.02
93.72
12.39
97.88
91.14
12.95
92.17
86.01
13.44
85.89
80.38
14.03

67
121.39
80.45
12.34
114.59
78.07
13.09
107.79
75.63
13.72
101.55
73.52
14.27
94.75
71.24
14.94

72
133.24
64.43
12.99
125.93
62.09
13.82
118.62
59.73
14.54
111.86
57.63
15.17
104.55
55.41
15.92

EVAPORATOR AIRFLOW, CFM/DR


4000/0.076
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
115.56
127.28
140
107.18
90.66
71.15
12.32
12.95
13.64
108.76
120
132.24
101.09
88.22
68.79
13.02
13.72
14.51
102.31
112.89
124.48
95.26
85.81
66.39
13.6
14.38
15.26
96.21
106.3
117.24
89.78
83.71
64.23
14.09
14.94
15.91
89.59
99.19
109.66
83.84
81.46
62.06
14.7
15.63
16.69

4800/0.092
62
119.22
110.58
13.05
112.1
104.2
13.75
105.41
98.15
14.34
99.14
92.51
14.85
92.24
86.32
15.47

67
131.51
100.22
13.69
124.02
97.85
14.48
116.53
95.36
15.15
109.66
93.25
15.73
102.17
90.9
16.43

72
145.03
77.42
14.41
136.76
74.95
15.3
128.9
72.66
16.07
121.24
70.42
16.74
113.17
68.14
17.55

BY10 INDOOR UNIT WITH CBX150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.076
62
125.84
111.76
15.33
120.44
109.46
16.31
114.68
104.19
17.41
108.93
99.06
18.6
102.83
93.46
19.93

67
137.51
92.46
16.15
131.97
90.5
17.22
125.72
88.22
18.41
119.48
86.14
19.71
112.89
83.78
21.15

72
150.34
73.04
17.05
144.48
71.17
18.23
137.93
69.05
19.54
131.03
66.92
20.97
123.79
64.59
22.56

EVAPORATOR AIRFLOW, CFM/DR


4600/0.088
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
129.08
141.19
154.46
117.28
99.59
77.64
15.9
16.73
17.66
123.47
135.41
148.31
112.22
97.61
75.72
16.89
17.81
18.87
117.46
129.03
141.57
106.71
95.36
73.6
18
19.02
20.21
111.44
122.45
134.43
101.35
93.18
71.46
19.2
20.33
21.66
105.23
115.66
127.09
95.64
90.82
69.18
20.54
21.79
23.27

5000/0.095
62
130.72
118.76
16.32
125.05
113.66
17.31
118.95
108.07
18.41
112.85
102.63
19.63
106.54
96.83
20.97

67
143.28
104.2
17.15
137.21
102.09
18.24
130.71
99.84
19.46
123.99
97.63
20.78
117.27
95.4
22.25

72
156.9
80.64
18.11
150.65
78.73
19.33
143.53
76.48
20.68
136.42
74.41
22.14
128.88
72.08
23.77

BY14 INDOOR UNIT WITH CBX150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.05
62
134.2
118.0
15.56
127.93
115.56
16.54
121.66
111.99
17.63
115.21
106.1
18.83
108.76
100.26
20.16

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
147.05
98.2
16.42
140.29
95.75
17.49
133.53
93.38
18.68
126.76
90.99
20
119.48
88.44
21.44

72
161.03
78.14
17.38
153.97
75.83
18.6
146.72
73.53
19.93
139.31
71.14
21.38
131.55
68.72
22.97

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


4800/0.062
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
139.29
152.95
167.59
127.99
108.57
84.86
16.23
17.12
18.16
132.6
145.66
160.14
121.92
105.98
82.53
17.23
18.22
19.41
125.91
138.59
152.48
115.91
103.62
80.18
18.32
19.43
20.76
119.22
131.31
144.83
109.79
101.07
77.83
19.55
20.77
22.27
112.31
123.82
136.55
103.54
98.58
75.3
20.88
22.24
23.91
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

5800/0.076
62
143.8
132.13
17.26
136.72
125.71
18.27
129.65
119.35
19.37
122.82
113.11
20.61
115.75
106.71
21.97

72
173.75
92.76
19.3
166
90.44
20.59
158
88.08
21.99
149.75
85.57
23.51
141.25
83.09
25.2

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

12

67
158.16
120.69
18.19
150.62
118.14
19.31
143.07
115.65
20.55
135.53
113.11
21.91
127.73
110.62
23.41

COOLING CAPACITIES
(Dual compressor units)
BY14 INDOOR UNIT WITH CBX180 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4400/0.056
62
165.39
140.41
16.81
159.10
137.82
18.22
152.80
135.31
19.85
146.31
132.68
21.67
139.64
130.02
23.66

67
179.74
117.60
17.19
173.10
115.12
18.59
166.26
112.58
20.25
159.62
110.21
22.11
152.22
107.39
24.15

72
195.12
94.42
17.52
187.96
91.97
18.96
180.78
89.57
20.66
173.80
87.29
22.58
166.07
84.66
24.68

EVAPORATOR AIRFLOW, CFM/DR


5500/0.073
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
172.64
187.90
204.27
159.38
131.66
103.55
17.7
18.03
18.4
165.97
180.78
196.73
156.80
129.15
101.12
19.08
19.43
19.84
159.29
173.67
189.18
150.95
126.67
98.73
20.7
21.09
21.55
152.37
166.54
181.63
144.60
124.24
96.37
22.52
22.95
23.48
145.22
158.72
173.61
137.89
121.36
93.79
24.5
24.98
25.59

6600/0.088
62
177.70
167.96
18.95
170.83
161.67
20.33
163.68
155.10
21.94
156.80
148.81
23.75
149.37
141.83
25.73

67
193.60
144.80
19.28
186.19
142.31
20.68
178.79
139.84
22.33
171.39
137.39
24.19
163.42
134.60
26.22

72
210.88
112.04
19.68
202.95
109.58
21.13
195.31
107.30
22.85
187.39
104.88
24.79
178.89
102.21
26.92

BY18 INDOOR UNIT WITH CBX180 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

5050/0.052
62
172.96
154.78
17.9
166.39
151.94
19.54
159.83
149.30
21.01
153.04
145.46
22.88
146.04
138.92
24.94

67
188.21
128.58
18.26
181.24
125.86
19.92
174.26
123.32
21.42
167.30
120.94
23.34
159.68
118.13
25.44

72
204.67
102.06
18.67
197.31
99.47
20.38
190.16
97.16
21.94
182.58
94.74
23.93
174.78
92.22
26.12

EVAPORATOR AIRFLOW, CFM/DR


6300/0.067
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
180.00
196.20
213.99
170.63
144.57
112.52
18.58
18.94
19.41
172.89
188.87
206.15
163.84
141.86
109.90
20.2
20.6
21.13
166.34
181.81
198.59
157.85
139.51
107.57
21.68
22.11
22.72
159.24
174.19
190.76
151.35
136.94
105.22
23.54
24.02
24.73
151.87
166.31
182.38
144.47
134.21
102.58
25.59
26.14
26.94

7550/0.082
62
184.94
175.32
19.49
177.74
168.42
21.11
170.87
162.14
22.58
163.34
155.25
24.44
155.81
148.23
26.49

67
202.24
159.99
19.87
194.43
157.13
21.53
186.94
154.65
23.04
179.12
152.15
24.96
170.98
149.41
27.08

72
220.83
122.38
20.41
212.74
119.77
22.15
204.64
117.30
23.74
196.55
114.97
25.77
187.81
112.30
28.01

BY18 INDOOR UNIT WITH CBX220 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

5050/0.054
62
193.86
161.71
20.98
186.6
158.77
22.77
178.9
155.64
24.77
170.97
152.49
27.0
162.39
149.15
29.48

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
210.17
135.35
21.4
202.51
132.55
23.22
194.19
129.46
25.27
185.65
126.35
27.55
176.46
123.09
30.1

72
227.69
108.63
21.75
219.41
105.87
23.62
210.71
102.98
25.72
201.56
99.96
28.04
191.77
96.8
30.65

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


6300/0.069
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
202.59
219.86
238.69
183.44
151.42
119.18
21.7
22.06
22.45
194.9
211.67
230
180.51
148.57
116.44
23.48
23.88
24.31
186.94
203.2
220.77
174.93
145.7
113.53
25.47
25.92
26.4
178.43
194.19
211.27
167.18
142.59
110.57
27.7
28.19
28.74
169.37
184.36
200.68
158.94
139.22
107.27
30.18
30.73
31.34
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

7550/0.085
62
208.57
194.62
22.58
200.68
187.53
24.36
192.45
180.08
26.35
183.57
171.99
28.58
174.36
163.62
31.05

72
246.35
128.85
23.38
237.56
126.24
25.25
227.8
123.24
27.34
218.04
120.33
29.67
207.3
117.15
32.27

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

13

67
226.83
166.63
22.94
218.32
163.8
24.75
209.48
160.92
26.79
199.99
157.69
29.06
189.84
154.35
31.6

COOLING CAPACITIES
(Dual compressor units)
BY18 INDOOR UNIT WITH CBX240 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

5600/0.061
62
218.88
179.35
23.28
211.56
176.43
25.32
203.75
173.37
27.54
195.21
169.69
29.99
186.67
166.46
32.66

67
237.68
150.65
23.86
229.66
147.67
25.91
221.41
144.75
28.19
212.18
141.14
30.7
202.96
137.91
33.43

72
257.31
121.24
24.3
248.86
118.41
26.38
239.93
115.5
28.71
230.28
112.15
31.29
220.38
108.98
34.1

EVAPORATOR AIRFLOW, CFM/DR


7000/0.078
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
229.06
248.84
269.44
203.28
168.35
132.64
24.22
24.71
25.13
221.13
240.35
260.69
200.31
165.41
129.93
26.23
26.75
27.21
212.9
231.24
251.03
197.33
162.27
126.93
28.45
29.02
29.55
203.75
221.53
240.78
189.62
158.67
123.54
30.89
31.52
32.15
194.6
211.82
230.22
181.44
155.47
120.31
33.56
34.26
34.97

8400/0.094
62
236.44
219.43
25.37
228.03
211.9
27.37
219.24
204.12
29.58
209.73
195.18
32.02
200.21
186.67
34.68

67
256.73
184.91
25.81
247.63
181.83
27.84
238.53
178.97
30.11
228.33
175.28
32.62
218.13
172.03
35.35

72
278.43
143.35
26.25
269.02
140.52
28.33
259.24
137.66
30.69
248.38
134.16
33.3
237.52
131.0
36.14

BY25 INDOOR UNIT WITH CBX240 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

6000/0.041
62
223.53
186.34
22.79
215.69
183.01
24.81
207.06
179.41
27.01
198.43
175.9
29.43
189.54
172.63
32.06

67
242.43
155.42
23.25
234.1
152.23
25.29
225
148.84
27.55
215.9
145.52
30.03
206.27
142.23
32.73

72
262.76
124.18
23.64
253.97
121.16
25.73
244.4
117.97
28.06
234.57
114.71
30.64
224.22
111.48
33.43

EVAPORATOR AIRFLOW, CFM/DR


7500/0.054
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
234.97
255.24
277.05
213.03
175.35
137.31
23.42
23.82
24.27
226.14
246.13
267.67
206.61
172.01
134.27
25.4
25.85
26.36
217.32
236.38
257.33
198.61
168.55
130.98
27.61
28.11
28.71
207.84
226.63
246.66
189.98
165.15
127.57
30.02
30.59
31.3
198.37
216.22
235.67
181.62
161.7
124.3
32.64
33.3
34.12

9000/0.067
62
242.75
221.83
24.23
233.73
213.54
26.21
223.92
204.64
28.41
214.51
196.07
30.82
204.31
187.06
33.45

67
264.15
194.05
24.62
254.39
190.53
26.65
244.25
187.07
28.91
234.1
183.68
31.41
223.18
180.15
34.12

72
287.07
149.38
25.14
276.98
146.19
27.24
266.12
142.84
29.61
255.26
139.55
32.24
243.62
136.17
35.08

BY25 INDOOR UNIT WITH CBX300 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125
`

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

7200/0.052
62
280.16
232.67
29.79
269.8
228.26
32.62
259.14
224.1
35.62
247.22
219.02
38.92
235.29
214.44
42.52

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
303.71
194.92
30.51
292.79
190.74
33.33
281.55
186.71
36.4
269.38
182.14
39.77
256.58
177.56
43.45

72
328.97
156.71
31.13
317.48
152.77
33.97
305.38
148.76
37.12
292.34
144.3
40.58
279.31
140.16
44.37

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


9000/0.067
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
293.33
318.38
345.26
264.24
218.37
172
30.77
31.41
32.06
281.96
306.68
332.84
259.55
214.16
167.97
33.55
34.19
34.87
270.59
294.58
320.04
253.54
210
163.96
36.54
37.25
38.03
258.43
281.71
306.47
242.25
205.4
159.58
39.83
40.62
41.52
245.88
268.44
292.11
230.94
200.98
155.14
43.41
44.3
45.32
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

10800/0.082
62
302.59
282.85
32.09
290.82
272.03
34.85
279.06
261.48
37.83
266.35
249.68
41.11
253.18
237.79
44.69

72
357.05
186.24
33.41
343.55
181.95
36.23
330.52
178.09
39.4
316.09
173.53
42.9
301.66
169.35
46.72

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

14

67
328.68
240.36
32.71
316.04
235.88
35.48
303.87
232.02
38.54
290.29
227.26
41.91
276.71
223
45.58

COOLING CAPACITIES
(Dual compressor units)
BY25 INDOOR UNIT WITH CBX360 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

9000/0.065
62
310.2
260.62
34.57
298.82
255.8
37.49
287.06
251.57
40.71
274.9
246.83
44.33
262.35
236.37
48.3

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
336.33
216.34
35.42
324.23
211.78
38.36
311.36
207.43
41.65
298.48
202.94
45.34
284.83
198.43
49.39

72
363.88
171.35
36.11
351.08
167.06
39.07
337.11
162.74
42.44
323.53
158.5
46.22
309.18
154.25
50.38

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


10500/0.079
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
319.35
346.41
375.19
284.79
234.21
182.99
35.73
36.5
37.18
307.91
333.66
361.62
276.36
229.53
178.56
38.63
39.43
40.13
295.1
320.46
347.13
265.25
225.3
174.24
41.84
42.7
43.5
282.75
307.26
333.1
254.3
220.91
170.02
45.44
46.39
47.29
269.48
293.15
318.17
242.79
216.45
165.74
49.39
50.43
51.46
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

12000/0.092
62
326.8
293.49
37.02
314.77
282.52
39.91
301.7
271.18
43.11
288.63
259.59
46.71
275.56
248.27
50.66

72
383.79
193.84
38.44
369.83
189.41
41.39
355.34
185.3
44.76
340.86
181.06
48.56
324.83
176.43
52.74

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

15

67
354.28
251.26
37.75
341.27
246.67
40.66
327.75
242.5
43.93
313.7
237.77
47.61
299.13
233.26
51.65

FAN PERFORMANCE DATA


DIRECT DRIVE MOTORS
MODEL No.: BY03
BLOWER MOTOR HP

CFM @ External Static Pressure (inch wg.)

BLOWER MOTOR

0.5

0.75

SPEED

0.1

0.2

0.3

0.4

0.5

0.6

HIGH

1350

1290

1220

1160

1070

990
900

MEDIUM

1260

1200

1125

1060

1000

LOW

1070

1020

960

900

830

740

HIGH
MEDIUM

1660
1570

1480
1375

1300
1180

1230
1120

1140
1060

1060
960

LOW

1500

1320

1130

940

870

780

MODEL No.: BY05


BLOWER MOTOR HP

CFM @ External Static Pressure (inch wg.)

BLOWER MOTOR

0.75

1.0

SPEED

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

HIGH

2010

1920

1820

1730

1620

1490

1350

1230

MEDIUM

1830

1740

1660

1570

1470

1360

1240

1100

LOW

1710

1650

1570

1490

1390

1300

1170

975

HIGH

2252

2215

2180

2140

2105

2065

2020

1950

MEDIUM

2021

1990

1950

1920

1880

1840

1795

1700

LOW

1820

1805

1790

1735

1700

1665

1630

1530

NOTE: Values include losses for dry coil, filter & unit casing.

BELT DRIVEN MOTORS


MODEL No.: BY07
Airflow,
CFM (L/S)

0.2

0.4

RPM

BHP

RPM

1800 (849)

820*

0.62*

900

2000 (944)

824*

0.7*

905

2200 (1038)

853

0.81

2400 (1133)

950

External Static Pressure (inch wg.)


0.8
1.0

0.6

1.2

1.4

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

0.71

965

0.82

1020

0.88

1102

1.03

1145

1.14

1220

1.26

0.79

970

0.91

1026

1.0

1107

1.12

1152

1.25

1225

1.35

927

0.91

986

1.02

1041

1.13

1111

1.25

1160

1.36

1237

1.48

0.94

1004

1.05

1059

1.21

1132

1.27

1155

1.38

1244

1.5

1297

1.65

2600 (1227)

968

1.1

1032

1.22

1086

1.33

1150

1.45

1194

1.57

1250

1.69

1305

1.82

2800 (1321)

1054

1.4

1106

1.5

1160

1.61

1216

1.76

1261

1.88

1323

2.02

1380*

2.2*

3000 (1416)

1066

1.55

1133

1.7

1180

1.82

1234

1.94

1276

2.09

1334*

2.23*

1400*

2.3*

3200 (1510)

1091

1.75

1157

1.91

1202

2.02

1255

2.2

1307

2.33

1359*

2.47*

3400 (1605)

1116

1.96

1171

2.1

1228

2.3

1276

2.45

1329

2.6

1368*

2.73*

II

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY10


Airflow,
CFM (L/S)

External Static Pressure (inch wg.)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2800 (1321)
3000 (1416)
3200 (1510)
3400 (1605)
3600 (1699)
3800 (1793)
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2170)

610
625
636
660
675
700
727
772
791
840

0.62
0.69
0.77
0.88
1.0
1.13
1.28
1.41
1.58
1.79

710
720
734
746
760
778
790
843
864
890

0.75
0.80
0.92
1.01
1.16
1.3
1.45
1.62
1.79
1.96

745
760
780
805
820
840
865
880
887
931

4800 (2265)

857

1.95

906

2.17

947

2.4

5000 (2360)

876

2.15

920

2.38

961

2.6

0.87
0.95
1.06
1.18
1.32
1.43
1.62
1.78
1.94
2.2

760
810
820
833
848
868
882
921
934
975

0.95
1.12
1.26
1.34
1.48
1.63
1.8
1.96
2.14
2.38

850
865
870
881
900
913
926
968
979
1017

1.2
1.25
1.38
1.5
1.66
1.8
1.96
2.16
2.34
2.59

988

2.57

1035

2.76

1005

2.76

905
915
925
939
950
966
980
1011
1024
1058

NOTES (For BY07/BY10): 1. Values include losses for filters, unit casing and wet coils.
2. 2 HP motor and alternative drive I to be used for the unshaded portion.
3. 3 HP motor and alternative drive II to be used for the shaded portion.

16

1.32
1.4
1.51
1.67
1.82
2.0
2.18
2.36
2.54
2.77

965
970
978
983
995
1006
1023
1054
1067

1.5
1.6
1.73
1.84
1.98
2.18
2.4
2.56
2.77

1000
1013
1023
1033
1043
1056
1066
1096

1.6
1.75
1.86
2.02
2.21
2.39
2.6
2.76

1054
1065
1073
1083
1090
1100
1108

1.8
2.0
2.1
2.25
2.41
2.58
2.77

II

1100
1115
1122
1128
1131
1143

2.0
2.15
2.28
2.44
2.6
2.78

FAN PERFORMANCE DATA (BELT DRIVEN MOTORS)


MODEL No.: BY14
Airflow,
CFM (L/S)
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2170)
4800 (2265)
5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)

0.2
RPM
694*
705*
719*
735*
748*
761*
778
800
808
826
837
850
879
894

0.4

BHP
1.21*
1.33*
1.43*
1.57*
1.72*
1.87*
2.06
2.31
2.46
2.68
2.90
3.12
3.41
3.76

RPM
743*
761*
774
787
800
812
823
846
858
869
885
900
920
933

0.6

BHP
1.3*
1.45*
1.6
1.75
1.92
2.09
2.27
2.5
2.7
2.9
3.12
3.41
3.70
4.0

RPM
797
811
823
835
846
862
873
894
903
917
927
940
962
973

BHP
1.52
1.67
1.8
1.95
2.09
2.30
2.48
2.72
2.90
3.12
3.37
3.65
3.96
4.24

0.8
RPM
845
857
869
885
897
904
917
934
945
955
965
980
1000
1013

External Static Pressure (inch wg.)


1.0
1.2
1.4

BHP
1.66
1.81
1.97
2.17
2.35
2.52
2.70
2.94
3.12
3.4
3.64
3.92
4.2
4.44

RPM
890
903
918
929
935
948
959
979
987
1000
1009
1021
1040
1050

BHP
1.83
2.0
2.17
2.34
2.52
2.70
2.91
3.15
3.38
3.65
3.9
4.17
4.45
4.68

RPM
937
951
963
971
979
989
1001
1019
1028
1041
1047
1061
1078
1091

BHP
2.03
2.19
2.33
2.55
2.72
2.91
3.11
3.38
3.65
3.9
4.13
4.38
4.69
4.92

RPM
975
992
1006
1013
1023
1032
1038
1056
1063
1078
1088
1100
1114
1125

1.6

BHP
2.25
2.43
2.58
2.75
2.91
3.11
3.34
3.64
3.83
4.13
4.35
4.66
4.92
5.2

RPM
992
1002
1010
1053
1065
1068
1070
1098
1106
1114
1123
1133
1150
1161

1.8

BHP
2.4
2.6
2.78
2.93
3.14
3.37
3.59
3.88
4.14
4.37
4.59
4.85
5.2
5.51

RPM
1075
1080
1093
1100
1107
1113
1119
1133
1139
1150
1157
1167
1183
1194

2.0

BHP
2.64
2.82
2.97
3.17
3.4
3.6
3.85
4.10
4.35
4.6
4.85
5.1
5.45
5.8

RPM
BHP
1102 2.85
1110 3.05
1133
3.2
1138
3.41
1144
3.62
1150
3.86
1159
4.08
1171
4.36
1176
4.57
1186
4.78
1194
5.05
1205
5.4
1218
5.76
1229
6.08

II

MODEL No.: BY18


Airflow,
CFM (L/S)

External Static Pressure (inch wg.)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)
6800 (3209)
7000 (3303)
7200 (3398)
7400 (3492)
7600 (3587)
7800 (3681)
8000 (3775)
8200 (3870)
8400 (3964)

715*
718*
721*
725*
729*
733*
738*
745*
753*
761*
772*
777*
794*
805
820
830
867
890

1.33*
1.42*
1.53*
1.68*
1.81*
1.9*
2.03*
2.15*
2.38*
2.5*
2.69*
2.84*
2.96*
3.18
3.36
3.59
3.77
4.05

NOTES (For BY14/BY18):

731*
737*
750*
756*
762*
775*
788*
795*
800*
810
820
830
845
850
870
880
890
904

1.56*
1.68*
1.81*
1.92*
2.03*
2.14*
2.35*
2.5*
2.64*
2.78
2.92
3.08
3.3
3.5
3.69
3.86
4.1
4.42

787*
793*
802*
807
816
833
839
850
855
863
875
880
890
900
909
922
936
945

1.82*
1.96*
2.07*
2.21
2.35
2.42
2.57
2.71
2.92
3.08
3.33
3.41
3.62
3.83
4.1
4.25
4.5
4.75

850
856
860
866
872
877
888
900
905
910
918
927
936
941
954
963
972
986

2.07
2.26
2.35
2.5
2.64
2.78
2.92
3.08
3.25
3.41
3.58
3.75
3.95
4.2
4.5
4.65
4.9
5.1

902
905
911
916
921
930
935
940
950
960
967
976
985
990
1002
1008
1016
1025

2.4
2.53
2.66
2.79
2.9
3.02
3.24
3.41
3.58
3.75
3.95
4.14
4.4
4.57
4.9
5.05
5.25
5.45

955
961
966
968
970
980
985
990
1000
1004
1012
1017
1021
1026
1041
1046
1054
1066

2.66
2.83
2.96
3.07
3.23
3.4
3.56
3.72
3.88
4.14
4.28
4.47
4.68
4.85
5.14
5.33
5.56
5.85

1005
1010
1012
1015
1020
1025
1030
1036
1045
1050
1054
1059
1065
1069
1083
1087
1100
1107

2.96
3.15
3.23
3.38
3.53
3.69
3.84
4.04
4.23
4.47
4.66
4.85
5.09
5.23
5.47
5.75
6
6.24

1057
1060
1062
1065
1066
1070
1080
1082
1083
1090
1095
1100
1108
1112
1125
1128
1132
1140

II

3.3
3.46
3.57
3.73
3.84
4.0
4.27
4.45
4.6
4.83
5.04
5.19
5.47
5.66
5.9
6.12
6.36
6.72

1104
1107
1109
1110
1113
1118
1120
1126
1127
1134
1135
1141*
1150*
1154*
1158*
1164*
1172*

3.6
3.76
3.88
4.07
4.18
4.4
4.63
4.82
5
5.16
5.39
5.58*
5.8*
6*
6.36*
6.6*
6.84*

1153*
1155*
1157*
1158*
1159*
1162*
1163*
1165*
1170*
1175*
1179*
1183*
1185*
1193*
1200*

3.88*
4.04*
4.27*
4.4*
4.59*
4.72*
4.95*
5.09*
5.3*
5.51*
5.72*
5.95*
6.12*
6.42*
6.78*

1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY25


Airflow,
CFM (L/S)
6000 (2832)
6400 (3020)
6800 (3209)
7200 (3398)
7600 (3587)
8000 (3775)
8400 (3964)
8800 (4152)
9200 (4341)
9600 (4530)
10000 (4719)
10400 (4907)
10800 (5096)
11200 (5286)
11600 (5474)
12000 (5663)

0.4
RPM BHP
700
706
716
722
732
740
751
759
770
779
790
801
809
821
852
870

2.6
2.8
3.05
3.24
3.4
3.6
3.9
4.2
4.5
4.9
5.2
5.55
5.9
6.4
6.8
7.2

0.6
RPM BHP
762
764
766
768
770
772
778
784
790
796
806
813
825
856
872
885

3.12
3.3
3.5
3.7
3.82
4.0
4.35
4.65
5.0
5.35
5.67
6.1
6.5
6.9
7.3
7.8

0.8
RPM BHP

812
813
814
815
816
818
821
824
828
832
838
849
870
876
885
892

3.6
3.78
4.0
4.19
4.35
4.56
4.85
5.16
5.5
5.84
6.15
6.6
7.0
7.4
7.9
8.5

External Static Pressure (inch wg.)


1.0
1.2
1.4
RPM BHP RPM BHP RPM BHP
847
848
849
850
851
852
853
857
862
870
878
890
898
906
914
925

4.0
4.22
4.42
4.64
4.88
5.18
5.5
5.81
6.14
6.45
6.7
7.1
7.5
7.95
8.45
9.0

870
871
872
873
874
875
876
878
880
900
915
920
928
936
944
952

4.5
4.73
4.96
5.2
5.45
5.65
5.97
6.3
6.75
7.1
7.4
7.85
8.3
8.7
9.15
9.6

940
942
944
945
947
948
949
951
953
955
957
965
973
981
989
996

5.0
5.23
5.45
5.68
5.9
6.12
6.48
6.8
7.15
7.6
8.06
8.4
8.8
9.25
9.6
10.1

1.6
RPM BHP

1.8
RPM BHP

2.0
RPM BHP

980
981
982
983
985
986
988
990
992
994
996
1003
1009
1014

1010
1011
1013
1014
1016
1018
1019
1020
1021
1022
1023
1034*

1059*
1060*
1062*
1063*
1064*
1065*
1066*
1067*
1068*
1069*
1070*

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
NOTES: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.

17

5.46
5.71
5.97
6.23
6.5
6.8
7.2
7.6
8.0
8.35
8.71
9.1
9.5
9.9

6.0
6.3
6.6
6.95
7.25
7.5
7.8
8.1
8.45
8.75
9.25
9.7*

II

6.6*
6.92*
7.22*
7.51*
7.78*
8.05*
8.35*
8.65*
9.0*
9.45*
9.8*

ELECTRICAL DATA
MODEL No.: BY03
POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE
MIN.

208/230-1-60

187

MAX.

BLOWER

**

HP

FLA

0.50
(STD.)

1.8

253

0.50
(STD.)
187

0.50
(STD.)
342

0.50
(STD.)
414

4.7

1.8

418
0.75
(ALT.)

460-3-60

1.8

253
0.75
(ALT.)

380-3-60
(4 WIRE)

4.7

4.7

1.0

506
0.75
(ALT.)

2.6

POWER
SUPPLY
(V-Ph-Hz)

ELECTRIC HEATER

MOTOR

0.75
(ALT.)

208/230-3-60

MODEL No.: BY07


MCA
kW

FLA

5
6/7
10*/12*
14*

5
6/7
10*/12*
14*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

21.7
26.1/30.4
43.5/52.2
60.9

21.7
26.1/30.4
43.5/52.2
60.9

12.6
15.1/18.8
25.1/30.1
37.7

12.6
15.1/18.8
25.1/30.1
37.7

7.6
9.1/11.4
15.2/18.2
22.8

7.6
9.1/11.4
15.2/18.2
22.8

6.3
7.5/9.4
12.6/15.1
18.8

6.3
7.5/9.4
12.6/15.1
18.8

MOCP

MIN.
2.3
29.4
34.9/40.3
56.6/67.5
78.4
5.9
33
38.5/43.9
60.3/71.1
82
2.3
18
21.1/25.8
33.6/39.9
49.4
5.9
21.6
24.8/29.4
37.3/43.5
53
2.3
11.8
13.6/16.5
21.3/25
30.8
5.9
15.4
17.3/20.1
24.9/28.6
34.4
1.3
9.1
10.6/13
17/20.1
24.8
3.3
11.1
12.6/15
19/22.1
26.8

15
30
40/45
60/70
80
15
35
40/45
70/80
90
15
20
25/30
35/40
50
15
25
30/35
40/45
60
15
15
15/20
25/30
35
15
20
20/25
30/30
35
15
15
15/20
20/25
30
15
15
15/20
20/25
30

VOLTAGE
RANGE

208/230-3-60

MIN.

208/230-1-60

208/230-3-60

380-3-60
(4 WIRE)

460-3-60

187

187

342

414

MAX.

**

HP

FLA

0.75
(STD.)

4.7

1.0
(ALT.)

8.2

253

0.75
(STD.)

4.7

1.0
(ALT.)

8.2

253

0.75
(STD.)

4.7

1.0
(ALT.)

8.2

0.75
(STD.)

3.0

1.0
(ALT.)

4.4

418

506

187

MCA
kW

FLA

5
6/7
10*/12*
14*

5
6/7
10*/12*
14*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

5
6/7.5
10*/12*
15*

21.7
26.1/30.4
43.5/52.2
60.9

21.7
26.1/30.4
43.5/52.2
60.9

12.6
15.1/18.8
25.1/30.1
37.7

12.6
15.1/18.8
25.1/30.1
37.7

7.6
9.1/11.4
15.2/18.2
22.8

7.6
9.1/11.4
15.2/18.2
22.8

6.3
7.5/9.4
12.6/15.1
18.8

6.3
7.5/9.4
12.6/15.1
18.8

5.9
33
38.5/43.9
60.3/71.1
82
10.3
37.4
42.9/48.3
64.6/75.5
86.4
5.9
21.6
24.8/29.4
37.3/43.5
53
10.3
26
29.1/33.8
41.6/47.9
57.4
5.9
15.4
17.3/20.1
24.9/28.6
34.3
10.3
19.8
21.6/24.5
29.3/33
38.8
3.8
11.6
13.1/15.5
19.5/22.6
27.3
5.5
13.4
14.9/17.3
21.3/24.4
29

6.6

8.8

2
(STD.)

380-3-60
(4 WIRE)

342

418
3
5.14
(ALT.)

2
(STD.)

414

3
(ALT.)

15
40
45/50
70/80
90
15
40
45/50
70/80
90
15
25
25/30
40/45
60
15
30
30/35
45/50
60
15
20
20/25
25/30
35
15
25
25/30
30/35
40
15
15
15/20
20/25
30
15
15
20/20
25/25
30

3.5

506

MOCP

ELECTRIC HEATER
MCA

FLA

253

ELECTRIC HEATER

MOTOR

HP

3
(ALT.)

460-3-60

BLOWER

MAX.

BLOWER
MOTOR

2
(STD.)

MODEL No.: BY05


POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE

4.1

kW

MOCP

FLA

8.3

15

12.6

24

25
30/35

6/7.5

15.1/18.8

27.1/31.8

10*/12*

25.1/30.1

39.6/45.9

40/50

15*/20*

37.7/50.2

55.4/71

60/80

25*/30*

62.8/75.3 86.8/102.4

90/110

11

20

12.6

26.8

30

6/7.5

15.1/18.8

29.9/34.5

35/35

10*/12*

25.1/30.1

42.4/48.6

45/50

15*/20*

37.7/50.2

58.1/73.8

60/80

25*/30*

62.8/75.3 89.5/105.1 90/110

15

7.6

14.5

15

6/7.5

9.1/11.4

16.4/19.3

20/20

10*/12*

15.2/18.2

24/27.8

25/30

15*/20*

22.8/30.4

33.5/43

35/45

25*/30*

38/45.6

52.5/62

60/70

6.4

15

7.6

15.9

20

6/7.5

9.1/11.4

17.8/20.7

20/25

10*/12*

15.2/18.2

25.4/29.2

30/30

15*/20*

22.8/30.4

34.9/44.4

40/45

25*/30*

38/45.6

53.9/63.4

60/70

4.4

15

6.3

12.3

15

6/7.5

7.5/9.4

13.8/16.1

15/20

10*/12*

12.6/15.1

20.1/23.3

25/25

15*/20*

18.8/25.1

27.9/35.8

30/40

25*/30*

31.4/37.7

43.6/51.5

45/60

5.1

15

6.3

13

15

6/7.5

7.5/9.4

14.5/16.9

15/20

10*/12*

12.6/15.1

20.9/24

25/25

15*/20*

18.8/25.1

28.6/36.5

30/40

25*/30*

31.4/37.7

44.4/52.3

45/60

LEGEND
FLA

- Full Load Amps

HP

- Horse Power

MCA

- Minimum Circuit Amps

MOCP - Maximum Over Current Protection

* Combination of 2 heater modules


** Single phase motors
(208/230V-1Ph-60Hz for 208/230V-3Ph-60Hz & 380V-3Ph-60Hz power supply.
460V-1Ph-60Hz for 460V-3Ph-60Hz power supply).

18

ELECTRICAL DATA
MODEL No.: BY10
POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE
MIN.

MAX.

MODEL No.: BY14

BLOWER
MOTOR
HP

208/230-3-60

187

2
(ALT.)

342

6.6

8.8

2
(ALT.)

414

3.5

4.1

FLA

- Full Load Amps

HP

- Horse Power

MCA

- Minimum Circuit Amps

MAX.

BLOWER
MOTOR
HP

FLA

ELECTRIC HEATER
MCA
kW

MOCP

FLA

8.3

15

17.3

30

12.6

24

25

12.6

33

40
45/45

15.1/18.8

27.1/31.8

30/35

25.1/30.1

39.6/45.9

40/50

15*/20*

37.7/50.2

55.4/71

25*/30*

6/7.5

15.1/18.8

36.1/40.8

10*/12*

25.1/30.1

48.6/54.9

50/60

60/80

15*/20*

37.7/50.2

64.4/80

70/90

62.8/75.3 86.8/102.4 90/110

25*/30*

62.8/75.3 95.8/111.4 100/125

11

20

12.6

26.8

30

6/7.5

15.1/18.8

29.9/34.5

35/35

10*/12*

25.1/30.1

42.4/48.6

45/50

15*/20*

37.7/50.2

58.1/73.8

25*/30*

5
13.8
(STD.)

208/230-3-60

187

253

7.5
19.5
(ALT.)

24.4

40

12.6

40.1

50

6/7.5

15.1/18.8

43.3/47.9

50/60

10*/12*

25.1/30.1

55.8/62

60/70

60/80

15*/20*

37.7/50.2

71.5/87.1

80/90

62.8/75.3 89.5/105.1 90/110

25*/30*

62.8/75.3 102.9/118.5 110/125

15

11.3

20

7.6

14.5

15

7.6

20.8

25

6/7.5

9.1/11.4

16.4/19.3

20/20

10*/12*

15.2/18.2

24/27.8

25/30

15*/20*

22.8/30.4

33.5/43

25*/30*

38/45.6

52.5/62

6.4

15

7.6

15.9

20

6/7.5

9.1/11.4

22.6/25.5

25/30

10*/12*

15.2/18.2

30.3/34

35/35

35/45

15*/20*

22.8/30.4

39.8/49.3

45/50

60/70

25*/30*

38/45.6

58.8/68.3

60/70

6/7.5

9.1/11.4

17.8/20.7

20/25

10*/12*

15.2/18.2

25.4/29.2

30/30

15*/20*

22.8/30.4

34.9/44.4

25*/30*

38/45.6

53.9/63.4

5
(STD.)

380-3-60
(4 WIRE)

342

418

7.5
12.5
(ALT.)

15.6

25

7.6

25.1

35

6/7.5

9.1/11.4

27/29.9

35/35

10*/12*

15.2/18.2

34.6/38.4

40/45

40/45

15*/20*

22.8/30.4

44.1/53.6

50/60

60/70

25*/30*

38/45.6

63.1/72.6

70/80

4.4

15

8.6

15

6.3

12.3

15

6.3

16.5

20
20/25

6/7.5

7.5/9.4

13.8/16.1

15/20

10*/12*

12.6/15.1

20.1/23.3

25/25

15*/20*

18.8/25.1

27.9/35.8

25*/30*

31.4/37.7

6/7.5

7.5/9.4

18/20.4

10*/12*

12.6/15.1

24.4/27.5

30/30

30/40

15*/20*

18.8/25.1

32.1/40

35/45

43.6/51.5

45/60

25*/30*

31.4/37.7

47.9/55.8

50/60

5.1

15

6.3

13

15

6/7.5

7.5/9.4

14.5/16.9

15/20

10*/12*

12.6/15.1

20.9/24

25/25

15*/20*

18.8/25.1

28.6/36.5

25*/30*

31.4/37.7

44.4/52.3

5
(STD.)

460-3-60

414

6.9

506

7.5
9.75
(ALT.)

12.2

20

6.3

20.1

25

6/7.5

7.5/9.4

21.6/23.9

25/30

10*/12*

12.6/15.1

27.9/31.1

30/35

30/40

15*/20*

18.8/25.1

35.7/43.6

40/45

45/60

25*/30*

31.4/37.7

51.4/59.3

60/70

LEGEND
FLA

VOLTAGE
RANGE
MIN.

6/7.5

506

3
(STD.)

MOCP

10*/12*

418

3
5.14
(STD.)

460-3-60

kW

253

3
(STD.)

380-3-60
(4 WIRE)

MCA

FLA

2
(ALT.)

POWER
SUPPLY
(V-Ph-Hz)

ELECTRIC HEATER

MOCP - Maximum Over Current Protection

* Combination of 2 heater modules

19

ELECTRICAL DATA
MODEL No.: BY18
POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE
MIN.

MAX.

MODEL No.: BY25

BLOWER
MOTOR
HP

208/230-3-60

187

253

7.5
19.5
(ALT.)

5
(STD.)

380-3-60
(4 WIRE)

342

418

7.5
12.5
(ALT.)

5
(STD.)

460-3-60

414

MCA

FLA

5
13.8
(STD.)

6.9

506

7.5
9.75
(ALT.)

POWER
SUPPLY
(V-Ph-Hz)

ELECTRIC HEATER
kW

MOCP

MIN.

FLA

- Full Load Amps

HP

- Horse Power

MCA

- Minimum Circuit Amps

MAX.

BLOWER
MOTOR
HP

FLA

ELECTRIC HEATER
MCA
kW

MOCP

FLA

17.3

30

25.5

45

12.6

33

40

12.6

41.2

50

6/7.5

15.1/18.8

36.1/40.8

45/45

10*/12*

25.1/30.1

48.6/54.9

50/60

15*/20*

37.7/50.2

64.4/80

70/90

25*/30*

62.8/75.3 95.8/111.4 100/125

35*/40*

87.9/100.4 127.1/142.8 150/150

24.4

40

12.6

40.1

50

6/7.5

15.1/18.8

43.3/47.9

50/60

10*/12*

25.1/30.1

55.8/62

60/70

15*/20*

37.7/50.2

71.5/87.1

80/90

25*/30*

62.8/75.3 102.9/118.5 110/125

35*/40*

87.9/100.4 134.3/149.9 150/175

7.5
20.4
(STD.)

208/230-3-60

187

253

10
26.1
(ALT.)

6/7.5

15.1/18.8

44.3/49

60/60

10*/12*

25.1/30.1

56.9/63.2

70/70

15*/20*

37.7/50.2

72.6/88.3

80/90

25*/30*

62.8/75.3 103.9/119.6 110/125

35*/40*

87.9/100.4 135.3/151 150/175

32.6

50

12.6

48.3

70

6/7.5

15.1/18.8

51.5/56.2

70/70

10*/12*

25.1/30.1

64/70.3

80/80

15*/20*

37.7/50.2

79.7/95.4

90/100

25*/30*

62.8/75.3 111.1/126.8 125/150

35*/40*

87.9/100.4 142.4/158.1 150/175

11.3

20

15.6

25

7.6

20.8

25

7.6

25.1

35

6/7.5

9.1/11.4

22.6/25.5

25/30

10*/12*

15.2/18.2

30.3/34

35/35

15*/20*

22.8/30.4

39.8/49.3

25*/30*

38/45.6

35*/40*

6/7.5

9.1/11.4

27/29.9

35/35

10*/12*

15.2/18.2

34.6/38.4

40/45

45/50

15*/20*

22.8/30.4

44.1/53.6

50/60

58.8/68.3

60/70

25*/30*

38/45.6

63.1/72.6

70/80

53.2/60.8

77.8/87.3

80/90

35*/40*

53.2/60.8

82.1/91.6

90/100

15.6

25

20

35

7.6

25.1

35

7.6

29.5

40

6/7.5

9.1/11.4

27/29.9

35/35

10*/12*

15.2/18.2

34.6/38.4

40/45

15*/20*

22.8/30.4

44.1/53.6

25*/30*

38/45.6

63.1/72.6

35*/40*

53.2/60.8

82.1/91.6

8.6

6.3

7.5
12.5
(STD.)

380-3-60
(4 WIRE)

342

418

6/7.5

9.1/11.4

31.4/34.2

45/45

10*/12*

15.2/18.2

39/42.8

50/50

50/60

15*/20*

22.8/30.4

48.5/58

50/60

70/80

25*/30*

38/45.6

67.5/77

70/80

90/100

35*/40*

53.2/60.8

86.5/96

90/100

15

12.8

20

16.5

20

6.3

20.6

25

6/7.5

7.5/9.4

18/20.4

20/25

10*/12*

12.6/15.1

24.4/27.5

30/30

15*/20*

18.8/25.1

32.1/40

25*/30*

31.4/37.7

35*/40*

10
(ALT.)

16

6/7.5

7.5/9.4

22.2/24.5

30/30

10*/12*

12.6/15.1

28.4/31.6

35/35

35/45

15*/20*

18.8/25.1

36.3/44.1

40/45

47.9/55.8

50/60

25*/30*

31.4/37.7

52/59.8

60/60

43.9/50.2

63.5/71.4

70/80

35*/40*

43.9/50.2

67.7/75.5

70/80

12.2

20

16.3

25

6.3

20.1

25

6.3

24.1

35

6/7.5

7.5/9.4

21.6/23.9

25/30

10*/12*

12.6/15.1

27.9/31.1

30/35

15*/20*

18.8/25.1

35.7/43.6

25*/30*

31.4/37.7

35*/40*

43.9/50.2

7.5
10.2
(STD.)

460-3-60

414

506

10
(ALT.)

6/7.5

7.5/9.4

25.7/28

35/35

10*/12*

12.6/15.1

31.9/35.1

40/40

40/45

15*/20*

18.8/25.1

39.8/47.6

45/50

51.4/59.3

60/70

25*/30*

31.4/37.7

55.5/63.3

60/70

67.1/74.9

70/80

35*/40*

43.9/50.2

71.2/79

80/80

LEGEND
FLA

VOLTAGE
RANGE

MOCP - Maximum Over Current Protection

* Combination of 2 heater modules

20

13

DIMENSIONS
BY03 - BY14 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
BY03
BY05

A
1092(43)
1092(43)

813(32)

600(23.62) 483(19.02) 224(8.82) 406(15.98)

1360(53.5) 1100(43.31) 600(23.62)

BY10

1490(58.7) 1400(55.12) 675(26.57)


1625(64)

648(25.5) 575(22.64) 483(19.02) 143(5.63) 406(15.98)

BY07

BY14

1600(63)

705(27.75)

G
45(1.77)

542(21.34) 524(20.63) 297(11.69) 553(21.77) 151(5.94)

45(1.77)

707(27.83) 550(21.65) 297(11.69) 553(21.77)

813(32)

182(7.16) 406(15.98)

66(2.6)

995(39.17) 550(21.65) 378(14.88) 721(28.38) 123(4.84)

813(32)

332(13.1) 406(15.98)

42(1.65)

1321(52)

187(7.36) 406(15.98)

55(2.16) 1495(58.86) 655(25.8) 471(18.54) 791(31.14) 153(6.02)

1295(51)

625(24.61) 378(14.88) 721(28.38)

21

183(7.2)
198(7.8)

DIMENSIONS
BY03 - BY14 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
BY03
BY05

A
1092(43)
1092(43)

648(25.5) 575(22.64) 483(19.02) 134(5.28) 406(15.98)


813(32)

600(23.62) 483(19.02) 229(9.02) 406(15.98)

32(1.26)

712(28.03) 502(19.76) 300(11.81) 553(21.77) 195(7.68)

1360(53.5) 1100(43.31) 600(23.62)

813(32)

BY10

1490(58.7) 1400(55.12) 675(26.57)

813(32)

365(14.38) 406(15.98)

35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 123(4.84)

1600(63) 705(27.75) 1321(52)

224(8.82) 406(15.98)

49(1.92) 1497(58.95) 607(23.91) 370(14.59) 929(36.56) 110(4.33)

1625(64)

406(15.98)

543(21.38) 502(19.76) 285(11.22) 553(21.77) 154(6.06)

BY07

BY14

213(8.4)

G
35(1.38)
85(3.34)

991(39)

504(19.83) 302(11.87) 697(27.53) 110(4.33)

22

DIMENSIONS
BY18 - BY25 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
BY18
BY25

A
1625(64)

2070(81.5) 705(27.75)

1825(71.85) 2362(93)

840(33.1)

1575(62)

382(15.04) 483(19.02)

35(1.38) 1965(77.36) 655(25.79) 471(18.54) 791(31.14) 153(6.02)

1575(62)

590(23.23) 483(19.02)

50(1.97) 2257(88.86) 790(31.1)

23

503(19.8) 913(35.94) 288(11.34)

DIMENSIONS
BY18 - BY25 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
BY18
BY25

A
1625(64)

2070(81.5) 705(27.75)

1825(71.85) 2362(93)

840(33.1)

1575(62)

422(16.61) 483(19.02)

46(1.81) 1969(77.52) 596(23.46) 354(13.94) 878(34.57) 110(4.33)

1575(62)

625(24.61) 483(19.02)

74(2.91) 2217(87.28) 596(23.46) 704(27.72) 878(34.57) 110(4.33)

24

DIMENSIONS - HEATER BOX


BY03 - BY05
415

(16

.3")

205 (8.1")

(1")
25.4 YP
T

490

(19.3
")

HEATER CONTROLS MTG


PLATE

HEATER CONTROLS MTG


COVER

BY07 - BY14
412

.2")
(16

P
) TY
(1 "

205 (8.1")

4
25.

DIMENSIONS
MODEL

HEATER ACCESS COVER

BY07

818 (32.2)

BY10

818 (32.2)

BY14

1326(52.2)

HEATER CONTROLS MTG


PLATE

HEATER CONTROLS MTG


COVER

BY18 - BY25
.4")
(19
492

T
1")

YP

205 (8.1")

(
25.4

1581 (6
2.3")

HEATER ACCESS COVER


(BOTH SIDES)

HEATER CONTROLS MTG


COVER
HEATER CONTROLS MTG
PLATE

NOTES:

1. All dimensions are in mm (dimensions in brackets are in inches).


2. Heater box is an optional feature.

25

DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CBX030 - CBX060

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812mm) clearance to service end of the
unit, 12" (305mm) on remaining sides and 24"
(610mm) between units for proper airflow.

MODEL NUMBER

CBX030 - CBX036

711

610

708

596

440

175

86

57

CBX048 - CBX060

889

813

806

695

538

216

99

72

26

DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CBX075 - CBX120

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units
for proper airflow.

27

DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CBX150 - CBX220

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

28

DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CBX240 & CBX300

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

29

DIMENSIONS

203
[8.0"]

1550
[61.0"]

MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CBX360

2121
[83.50"]

73
[2.88"]

2197
[86.50"]

943
[37.13"]

943
[37.13"]
2032
[80.0"]

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

30

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with single compressor units)
APPLICABLE FOR BM WITH EXTERNAL OLR

CONNECTION APPLICABLE FOR 1PH BM

REFER TO UNIT
NAMEPLATE FOR
POWER SUPPLY

L3

HVTB OR BMC
L1

L2

L1

TO HVTB

BMC

L2

OLR

70

69

68

L3
LUG
BM

BM

70

69

68

BMC

BMC

LVTB
18 OLR 19
G

ATB
2

BM
TO ATB
SEE CONDENSING
UNIT DIAGRAM

HC2
HC1

AFS
28

NC

NO

230V

BMC
TO CONDENSING UNIT ATB

THERMOSTAT / DDC CONTROLLER


(by others)

LVTB

LOCK2(RED)

Y1

Y1

W1

W1

W2

W2

24Vac

BM CONTROL

STG1 COOLING

Y1

STG1 HEATING

W1

STG2 HEATING

W2

SYSTEM1(YEL)

29

30

SYSTEM2(ORG)
PRI

ECB

LOCK1(RED)

FUSE

TRANS

P3_##

SEC

ON

DIP

TO CONDENSING UNIT ATB

DIP SWITCH
POWER(GRN)
J_PROG

ECB DIP SWITCH SETTINGS & LED INDICATORS


FACTORY SETTINGS OF DIP SWITCHES

DIP SWITCH FUCTIONS


S1

OFF=TEST MODE DISABLE

ON= TEST MODE ENABLE

S2

LOAD BALANCE
OFF= (Comp1&2 Auto Lead Lag)

ON= COMPRESSOR 1 LEAD

S3

OFF= WITHOUT PUMP DOWN

ON= WITH PUMP DOWN OPTION

S4

on-board programming function (always set to on)

DIP SWITCH #
ON
OFF

S1

S2

S3

S4

note:
Set dip switch # 3 according to unit's option
(pump down or no pump down)

LED INDICATORS
power on/off indicator
system lock-out due to system fault
system 1 fault diagnostic
blinking slow - LPS1 ckt fault
Yellow
blinking fast - HPS1 ckt fault
system 2 fault diagnostic
Orange
blinking slow - LPS2 ckt fault
blinking fast - HPS2 ckt fault

Green
Red

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

31

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with single compressor units)
TO HVTB

HC1

28

HC1

29

H1

FL

OHT

H2

OHT
(#1)
H3

FL

FL
OHT
(#2)

FL

OHT
H4

I STG
5 K.W

6 K.W

6 K.W

7.5 K.W

7.5 K.W

10 K.W

5 K.W

5 K.W

12 K.W

6 K.W

6 K.W

15 K.W

7.5 K.W

7.5 K.W

20 K.W

10 K.W

10 K.W

25 K.W

12.5 K.W

12.5 K.W

30 K.W

15 K.W

15 K.W

35 K.W

*
*

7.5+10 K.W

7.5+10 K.W

2*10 K.W

2*10 K.W

40 K.W
FL

FL
FL
OHT

OPT#

STG

F17
F18
F19

71A
72A
73A

74A
75A
76A

F11
F12
F13

F17
F18
F19
HC3

(SEE TABLE)

HEATER2

HEATER1
HC1

T1I
T2I
T3I

T1H
T2H
T3H

T1F
T2F
T3F
28

HEATER3

HEATER4
HC2

30

28

28

(SEE TABLE)

HEATER OPTION-3

OPTIONS

HTR

HC2

1. ANTI ICE OPTION

HEATER DATA TABLE


5 K.W

OHT

HEATER OPTION-2

HEATER DATA TABLE

HEATER TYPES
OHT
FL

28 30

29

(SEE TABLE)

HEATER OPTION-1

OHT

HEATER3

28

HC4

HC2

HC1

HC3

LEGEND

L1 L2 L3

T1H
T2H
T3H

T1F
T2F
T3F
HEATER1

HEATER4
HC3

TO HVTB

L1 L2 L3

74A
75A
76A

74B
75B
76B

HEATER3
30

HC1

HC4
T1I
T2I
T3I

T1H
T2H
T3H

T1G
T2G
T3G

T1F
T2F
T3F

HEATER2

HEATER1
29

HC3

HC2

TO HVTB
L1 L2 L3

71A F11
72A F12
73A F13

F17
F18
F19

71B
72B
73B

74A
75A
76A

F14
F15
F16

F11
F12
F13
71A
72A
73A
HC1

L1 L2 L3

L1 L2 L3

F20
F21
F22

L1 L2 L3

L1 L2 L3

T1G
T2G
T3G

TO HVTB
L1 L2 L3

II STG

NOTES: HTR-35 & 40KW IS APPLICABLE FOR


BY 18 MODEL ONLY.
USE OPTION 1 FOR 230V-3PH UNIT MODEL
USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL

CONNECTION APPLICABLE FOR ANTI ICE

2. VFC OPTION FOR BM ON,OFF &TRIP INDICATION

___

AR4-2B

AR4-2A

AI
AFS
ATB
AR
BM
BMC
CAP
ECB
FL
HC
HVTB
HTR
L1
L2
L3
LVTB
LUG
MOHT
NTB
OHT
OLR
SM
VFC
+

50

49

48

BM OFF

BM ON
AR5-1

AR4-1

51A

NOTES
52

51

*
*

AR4

USE COPPER CONDUCTOR WIRES ONLY.

18

3. IF HEATERS ARE FACTORY INSTALLED, PLEASE READ


BROKEN LINES AS CONTINUOUS LINES.

AR5

*
* FOR UNITS WITH HEATER,CONNECT AR5
ACROSS TERMINAL # 14 & 28

* FOR UNITS WITHOUT HEATER & BM WITH OLR


CONNECT AR5 ACROSS TERMINAL # 19 & 2

* FOR UNITS WITHOUT HEATER & BM WITHOUT


OLR FOLLOW AR5 CONNECTION BELOW:

AFS
C

NC

28B

AR5

BM ON,OFF & TRIP INDICATION OPTION


BMC-1A

BMC-1B
49

BM ON

50
BM OFF

OLR-2
52

51
BM TRIP

32

4. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLE


PROTECTION FOR COMPRESSOR IS AVAILABLE IN
ZAMIL ELECTRONIC THERMOSTAT.
5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY ZAMIL.
6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE
ACROSS TERMINAL # X1, X2 & 2 IS 230VAC.

NO

48

1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.


2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C
OR ITS EQUIVALENT.

BM TRIP/FAIL

14

ANTI ICE THERMOSTAT


AIRFLOW SWITCH
AUXILIARY TERMINAL BLOCK
AUXILIARY RELAY
BLOWER MOTOR
BLOWER MOTOR CONTACTOR
CAPACITOR
ELECTRONIC CONTROL BOARD
FUSE LINK
HEATER CONTACTOR
HIGH VOLTAGE TERMINAL BLOCK
HEATER
LINE 1
LINE 2
LINE 3
LOW VOLTAGE TERMINAL BLOCK
LUG GROUND
MANUAL RESET OHT
NEUTRAL TERMINAL BLOCK
OVERHEAT THERMOSTAT
OVER LOAD RELAY
SYSTEMIZER
VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
FL OR MOHT

7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER


SUPPLY ONLY.

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with dual compressor units)
APPLICABLE FOR 1PH BM

APPLICABLE FOR BM WITH EXTERNAL OLR

L3

L2

L1

TO HVTB

BMC
OLR

69

L3

70

BM

70

68

L2

69

REFER TO UNIT
NAMEPLATE FOR
POWER SUPPLY

BMC

L1

68

HVTB

BM

LUG
LVTB
18 OLR 19
G

BMC

ATB
2

TO ATB
SEE CONDENSING
UNIT DIAGRAM

HC2
HC1

28

NC
NO

BMC
TO CONDENSING UNIT ATB

3A

3B

COMP1

4A
P1

COMP2

P2

4B

14

29

SYSTEM1(YEL)

29

30

THERMOSTAT / DDC CONTROLLER


LVTB

ECB

LOCK1(RED)

SYSTEM2(ORG)
PRI

INFAN

30

LOCK2(RED)

HEATER1

41A
X1

X2

HEATER2

41B

12
OUTFAN1

OUTFAN2

NEUTRAL

LIVE

13

TO CU ATB

FUSE

(HP1)

12v-0-12v

HP2
(HP2)
SEC

TRANS

HP1
240v

DIP SWITCH
POWER(GRN)
J_PROG

21A
27A
21B
27B

9
10
11
12

LP1

22A

(LP1)

23A

LP2

22B

15

(LP2)

23B

16

TO CONDENSING UNIT ATB

13
14

ECB DIP SWITCH SETTINGS & LED INDICATORS


FACTORY SETTINGS OF DIP SWITCHES

DIP SWITCH FUCTIONS


S1

OFF=TEST MODE DISABLE

ON= TEST MODE ENABLE

S2

LOAD BALANCE
OFF= (Comp1&2 Auto Lead Lag)

ON= COMPRESSOR 1 LEAD

S3

OFF= WITHOUT PUMP DOWN

ON= WITH PUMP DOWN OPTION

S4

on-board programming function (always set to on)

DIP SWITCH #
ON
OFF

S1

S2

S3

S4

note:
Set dip switch # 3 according to unit's option
(pump down or no pump down)

LED INDICATORS
power on/off indicator
system lock-out due to system fault
system 1 fault diagnostic
blinking slow - LPS1 ckt fault
Yellow
blinking fast - HPS1 ckt fault
system 2 fault diagnostic
Orange
blinking slow - LPS2 ckt fault
blinking fast - HPS2 ckt fault

Green
Red

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

33

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with dual compressor units)

HC1

29

H1

OHT
FL

OHT

OHT

H2

OHT
(#1)
H3

FL

FL
OHT
(#2)

FL

OHT
H4

FL
FL
OHT

OPT#
2

STG
1

I STG
5 K.W

30

F17
F18
F19

71A
72A
73A

HC3

(SEE TABLE)

HEATER2

HEATER1
HC1

T1I
T2I
T3I

T1H
T2H
T3H

T1F
T2F
T3F
28

HEATER3

HEATER4
HC2

30

28

28

(SEE TABLE)

HEATER OPTION-3

1. ANTI ICE OPTION


II STG

6 K.W

6 K.W

7.5 K.W

7.5 K.W

10 K.W

5 K.W

5 K.W

12 K.W

6 K.W

6 K.W

15 K.W

7.5 K.W

7.5 K.W

20 K.W

10 K.W

10 K.W

25 K.W

12.5 K.W

12.5 K.W

30 K.W

15 K.W

15 K.W

35 K.W

*
*

7.5+10 K.W

7.5+10 K.W

2*10 K.W

2*10 K.W

[ TO COND. UNIT ]

___

ROUTE FPT WIRES TO COND. UNIT.


2. VFC OPTION FOR BM ON,OFF &TRIP INDICATION

ANTI ICE THERMOSTAT


AIRFLOW SWITCH
AUXILIARY TERMINAL BLOCK
AUXILIARY RELAY
BLOWER MOTOR
BLOWER MOTOR CONTACTOR
ELECTRONIC CONTROL BOARD
FUSE LINK
HEATER CONTACTOR
HIGH VOLTAGE TERMINAL BLOCK
HEATER
LINE 1
LINE 2
LINE 3
LOW VOLTAGE TERMINAL BLOCK
LUG GROUND
LEAD LAG SWITCH
MANUAL RESET OHT
NEUTRAL TERMINAL BLOCK
OVERHEAT THERMOSTAT
OVER LOAD RELAY
SYSTEMIZER
VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
FL OR MOHT

AR4-2B

AR4-2A

TERMINAL BLOCK OR TERMINATION POINT


50

49

48

BM OFF

BM ON

NOTES: HTR-35 & 40KW IS APPLICABLE FOR


BY 18 & 25 MODELS ONLY.
USE OPTION 1 FOR 230V-3PH UNIT MODEL
USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL

*
*

HC2

OPTIONS

HEATER DATA TABLE


HTR
5 K.W

74A
75A
76A

F11
F12
F13

F17
F18
F19

HEATER OPTION-2

HEATER DATA TABLE

40 K.W
FL

28

29

(SEE TABLE)

HEATER OPTION-1
HEATER TYPES
OHT
FL

HEATER3

28

HC4

HC2

AI
AFS
ATB
AR
BM
BMC
ECB
FL
HC
HVTB
HTR
L1
L2
L3
LVTB
LUG
LLS
MOHT
NTB
OHT
OLR
SM
VFC

T1H
T2H
T3H

T1F
T2F
T3F
HEATER1

HEATER4
HC3

L1 L2 L3

HC1

HC3

LEGEND

TO HVTB

L1 L2 L3

74A
75A
76A

74B
75B
76B

HEATER3
30

HC1

HC4
T1I
T2I
T3I

T1H
T2H
T3H
28

TO HVTB
L1 L2 L3

71A F11
72A F12
73A F13

F20
F21
F22

F17
F18
F19

71B
72B
73B

T1F
T2F
T3F

T1G
T2G
T3G
HEATER2
HC1

29

HC3

HC2

HEATER1

L1 L2 L3

L1 L2 L3

74A
75A
76A

F14
F15
F16

F11
F12
F13
71A
72A
73A
HC1

TO HVTB

L1 L2 L3

T1G
T2G
T3G

TO HVTB
L1 L2 L3

L1 L2 L3

AR5-1

NOTES

AR4-1

51A

1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.


2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900C
OR ITS EQUIVALENT.

52

51
BM TRIP/FAIL
AR4

USE COPPER CONDUCTOR WIRES ONLY.


2

14

3. IF HEATERS ARE FACTORY INSTALLED, PLEASE READ


BROKEN LINES AS CONTINUOUS LINES.

AR5

4. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT CYCLE


PROTECTION FOR COMPRESSOR IS AVAILABLE IN
ZAMIL ELECTRONIC THERMOSTAT.

FOR UNITS WITH HEATER,CONNECT AR5


ACROSS TERMINAL # 18 & 28
FOR UNITS WITHOUT HEATER & BM WITH OLR
CONNECT AR5 ACROSS TERMINAL # 14 & 2
FOR UNITS WITHOUT HEATER & BM WITHOUT
OLR FOLLOW AR5 CONNECTION BELOW:
AFS
AR5
NC
28B
C
2
14

6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE


ACROSS TERMINAL # X1, X2 & 2 IS 230VAC.

NO

BM ON,OFF & TRIP INDICATION OPTION


BMC-1A
48

BMC-1B
49

BM ON

50
BM OFF

OLR-2
52

51
BM TRIP

34

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER


TO BE PROVIDED BY CONSUMER WITH RATING AS
RECOMMENDED BY ZAMIL.

7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER


SUPPLY ONLY.

CONTROLS & SEQUENCE OF OPERATION


The operation of the air conditioning unit is controlled by a 24VAC electronic control board. All the contactors are operated
by the 24V circuit, including the thermostat.

Mode:
Select the desired mode of operation by continuous pressing of the MODE button:

24 V
(C)

Controls cooling system only (the word COOL will


display for 5 seconds).

24VAC

24 V
R

Controls heating system only (the word HEAT will


display for 5 seconds).

Y2
L
I
G
H
T
S

HEAT/COOL - Controls both systems automatically (the word AUTO will display for 5 seconds).
OFF - Systems will not operate.

Y1
G
W1
W2

Equipment
Relays

Fan Relay
1st stage
Heating
2nd stage
Heating

Cooling:
Select the temperature you want your cooling system to
maintain by pressing and holding the COOLING button
under the
or
symbols until the desired temperature
is displayed. The control setpoint temperature is displayed
for 5 seconds.

LED 1
LED 2
Thermostat
Field Wiring

Line Voltage
Transformer

2nd stage
Cooling
1st stage
Cooling

Clogged Filter

Compressor Fault

* Clogged filter switch not provided

Heating:
Select the temperature you want your heating system to maintain by pressing and holding the HEATING button under
the
or
symbols until the desired temperature is displayed. The control setpoint temperature is displayed for 5
seconds.

Fan:
The fan will be energized automatically when the systems are operating but no indication of this on the display. To select
continuous fan operation, press the FAN button and the display will show
. This is recommended for electronic air
cleaners and continuous ventilation requirements.

Off
When the word OFF is displayed the heating and cooling systems will not operate. Avoid using the OFF mode during
extremely cold weather to prevent damage from freezing.

Auto:
Selecting this mode of operation will control both heating and cooling systems. The thermostat will automatically switch
from one to the other as determined by the selected temperatures in heating and cooling.
NOTE: The thermostat always maintains a minimum 20F (10C) difference or dead band between the heating and cooling
setpoints.

Celsius/Fahrenheit
Simultaneously press

and

to switch between Celsius and Fahrenheit temperature display.

35

INSTALLATION INSTRUCTIONS
A. GENERAL
Blower units are shipped completely wired. Only external power, interconnecting control wiring between outdoor and
indoor units and refrigerant pipe connections are needed to complete the installation. For detailed instructions/informations, please refer to corresponding IOM manual.

B. UNIT LOCATION & ACCESS SPACE


The placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must be kept
on the service access side and return air side.
When making tubing connections, be sure to provide clearance for electrical connections.

C. TUBING INSTALLATION
Do not remove plugs from the compression fittings until tubing has been run and is ready for connection.
a. Make sure the tubing is round, without dent or burrs.
b. Cut tubing to the length required with a tube cutter carefully. Do not use a hacksaw.
c. Remove burr from inside and outside using file or deburring tool.
NOTE: Always use a gear type tube bender when making bends in suction line.
When installing tubing through walls or along side of any structural members, be sure the tubing is isolated from these
members or walls to avoid any transmission of vibration that may occur, while unit is running.

ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
NOTE: Use copper wires of proper rating for all field wiring.
Warning
Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wires
Connect power wires to terminal block per wiring diagram.
Connect ground wire to the ground lug inside the control box.
C) Control wiring between outdoor & indoor unit
Use 16 gauge color-coded wire between the indoor and outdoor units (control wiring).

STEP 2: START-UP
Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging method details.

STEP 3: SEQUENCE OF OPERATION


With power supplied to indoor and outdoor units, the unit starts responding to the thermostat mode requirement.
Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on. The compressor
contactor is energized to start the compressor and condenser fan.
As the conditioned space approaches the thermostat cooling set point, the unit cycles off.
Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor for
electric heater is switched on to energize the heaters. If the room temperature is not satisfied and there are two heaters
installed, the second heater also will be energized.
Once, the conditioned space approaches the desired temperature set point, the heating stages cycles off.
Fan mode: In this mode the indoor unit blower motor is switched on alone.

36

PL-AP-BYB-09-2M-E