Documente Academic
Documente Profesional
Documente Cultură
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 2
1. features of the VIP30 and VIP35
Io> I
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 3
2. use and settings
phase VIP 30
overcurrent sensors:
200/1
S1,S2 to be used
a Is
18 22 28
15 36
12 46
10 56
b 8
80 68
(A) 1.2Is
VAP6
d test plug
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 4
2. use and settings (cont'd)
phase VIP 35
overcurrent sensors:
200/1
S1, S2 to be used
a Is
18 22 28
15 36
12 46
10 56
b 8
80 68
(A) 1.2Is
to>
d
Io> VAP6
25 30 38 test plug
20 48
15 0.3 0.35 0.4 to>
60
12 80 on
0.25
0.2
0.5
0.6
c
10 120 100 off 0.7
0.15
inrush 0.1 1 0.8 Io>
(A) current
earth fault delay (s )
3 4 6 5 7
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 5
2. use and settings (cont'd)
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 6
3. earth fault setting area F When the circuit breaker closes,
All information concerning earth fault energizing of the MV/LV transformer
settings are grouped together in the may generate aperiodic inrush
lower half of the front panel. The currents with a DC component that
section numbers detailed on this momentarily saturates the magnetic
page relate to the numbering on the cores of the VIP35 CT’s. Because of
drawing shown on page 5. this, each CT gives an erroneous
result and the sum of the phase
4. earth fault setting Io> currents (at the CT secondary
The setting is made directly in MV windings) is no longer zero. There is
amperes. false earth fault detection that may
cause tripping of the earth fault
5. earth fault setting time delay protection.
The earth fault protection time delay This is especially critical when the
is set in seconds. setting and time delay settings are
low.
6. inrush current delay
This selector switch starts up the F If the time delay settings are
inrush current delay (1s). The time below the values indicated in the
delay prevents tripping by the earth chart below, start up the inrush
protection when the VIP35 is current delay:
energized during closing of the
circuit breaker. The time delay is only Io> setting to> time delay
active for the earth protection and 0.8 to 0.9 x Ia 0.2 s
has no effect on tripping by the 0.6 to 0.8 x Ia 0.3 s
phase protection. 0.4 to 0.6 x Ia 0.4 s
n in off position: 0.2 to 0.4 x Ia 0.5 s
The inrush current delay is not
activated. The earth fault protection Ia = rated current of the transformer
operates according to the setting of to be protected
the selector switch (5).
n in on: position
The inrush current delay is activated.
In this case:
- when the VIP35 is energized, and
the circuit breaker closes, tripping by
the earth protection is delayed by 1
second.
- when the VIP35 has been supplied
for more than a second, the earth
protection is time-delayed according
to the setting (5).
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 7
2. use and settings (cont'd)
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 8
3. current transformers
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 9
4. connection scheme
14
11
1
0V
2
MITOP -
+ 3
P1 5
S3
CT
L3
S2 6
P1 S1
S3 P2 7
CT L2
S2 8
P1 S1
S3 P2 9
CT L1
S2 10
P2 S1
CSH30 2 12
1 Io
13
14
11
1 0V
MITOP - 2
+
3
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 10
5. assembly and wiring
assembly of CSH30 core balance CT on VIP35 n Mount the CSH30 core balance CT
on the back of the casing using the 2
screws (G) so that the "Merlin Gerin,
F CSH30, 3123973, P2" marking is on
the visible side. Tighten the 2 screws
moderately.
CSH30 core In order to measure the residual
Balance CT current, the wires of the S1
‘A’
secondary windings of the 3 current
transformers are inserted through
the CSH30 core balance CT and
connected to the terminal rail.
n Connect (F) outputs 1 and 2 of the
CSH30 core balance CT to terminals
13 and 12 of the VIP35. The CSH30
core balance CT output is a low level
- view on A signal so the length of the 2 wires
G
should never be more than 15 cm.
Terminal 3 of the CSH30 core
balance CT output connector is not
used.
n the CSH30 and its 2 thermoplastic
(G) ∅3 screws
are supplied with the VIP35.
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 11
5. assembly and wiring (cont'd)
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 12
5. assembly and wiring (cont'd)
Is18 22 28 Is Is18 22 28 Is
55 70 55 70
45 45
15 36 15 36
37 90 37 90
12 46 30 115 12 46 30 115
10 56 25 140 10 56 25 140
8 68 20 170 8 68 20 170
80 200 80 200
(A) (A) (A) (A)
Io>30 Io>
25 38 62 75 95
20 48 50 120
15 60 37 150
12 80 30 200
10 100 25
120 300 250
(A) (A)
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 13
6. technical characteristics
general characteristics
steady thermal resistance 110 A with CT sensor, 8-80A range
270 A with CT sensor, 20-200A range
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 14
6. technical characteristics (cont'd)
0.1
max
typ
0.01 min
0 5 10 15 20 25 30 I/Is
1,2Is
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 15
6. technical characteristics (cont'd)
notes
1. When the VIP30/35 is used with 4. The times are measured for a
Current Transformers, the 8-80A phase-to-phase fault which appears
range, and for I < 20A, the accuracy when the relay is already supplied
is derated in accordance with the (prior presence of a current in the
following characteristics: network that is greater than the
- phase operating setting: minimum operating current). In the
1.2Is -10% +30%. event of closing in the presence of a
The tolerance is mainly due to the fault, the tripping times may be
non-linearity of the CT’s for low increased by 20ms.
currents. The inaccuracy can reach The times indicated do not include
the limit above if the relay is only the mitop response time since it
supplied by one phase. This may be depends on the circuit breaker (the
the case during single-phase no load mitop tripping time is less
injection testing. than 5 ms).
2. Given for the operating setting at 5. The tripping times are measured
1.2 Is for a sinusoidal current.
3. Not applicable to the test plug 6. When the VIP30/35 is used with
Current Transformers, and for I <
30A, the accuracy is derated in
accordance with the following
characteristics:
- earth protection setting:
± 10 % or 0/+6 A
The tolerance is mainly due to the
non-linearity of the CT’s for low
currents. The inaccuracy can reach
the limit above if the relay is only
supplied by one phase. This may be
the case during single-phase
injection testing.
dimensions
22
179 80 *
48
139
127 6
159
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 16
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 17
7. testing of the VIP30/35 and use of the VAP6
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 18
7. testing of the VIP30/35 and use of the VAP6 (cont'd)
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 19
n press the "phase overcurrent"
The test may be carried out with or button to send the phase protection
without the relay energised by the test current.
Ringmaster current transformers, - continue pressing the button
and all the relay settings are throughout the duration of the
effective. During the test, the relay
current.
remains operational and will give a - the VAP6 "test in progress"
tripping order in the event of a fault,
indicator lights up to confirm the
unless the "trip inhibition" button is
sending of the current to the
pressed. VIP30/35 relay.
__________________________________________________________________________________________
- the VAP6 red "trip" indicator lights
n connect the VAP6 to VIP30 / VIP test
the "VAP6 35 protection
up torelays – version
indicate 002 relay
that the / January
has2001 20
plug". The VAP6 batteries are tripped.
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 21
8. Commissioning Ringmaster with VIP 30/35
All Ringmaster panel types are fully Since the system is fully tested it is Testing using secondary injection is
tested before leaving the factory. only necessary to prove the relay on used to test the following parts of the
These tests include the whole site at the service settings, therefore protection system:
protection system including current reducing commissioning time to a n The electronic circuit.
transformers, wiring harness, relay, minimum. n The integrity of the power supply
trip coil and the circuit breaker itself Once the switchgear has been of the VIP 30/35.
using primary injection to energise installed and cabled up, it is n The link to the mitop trip coil and
the system. impractical or sometimes also the circuit breaker mechanical
Tripping tests are carried out using impossible to carry out primary tripping mechanism.
different settings of the IDMT injection tests. It is suggested that n The integrity of the switches on
and DT curves available on the relay. for commissioning and maintenance the front panel to ensure they
The tripping times are measured purposes either of the following two give the correct tripping times for
with a chronometer and its accuracy methods can be used. the curves selected.
is verified against the theoretical 1. Simple trip test using the VAP6
times calculated. test unit (described previously). Caution:
2. Secondary injection using n The ‘MITOP’ trip coil must be used
standard equipment with an output only in conjuction with the VIP relay.
filter.
n Voltage withstand testing of the
auxiliary and control circuits at 2000V
for 1 minute should never be carried
out without disconnecting the MITOP
trip coil or the VIP relay.
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 22
Test set connections:
The injection set is connected to the VIP 30/35 relay without disconnecting the
CT’s.
This is done via the sockets on the terminal rail located in the LV
compartment.
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 23
8. Commissioning Ringmaster with VIP 30/35
89L 52 89R
VIP 30
C11 5 IDMT RELAY
L3
6
C110 7
51
C10 L2
8
C31 9
L1
10
C130
C30
C51
C150
C50
14
11
MITOP COIL 4
K8 K8 1
0v
K11 K11 K11 K11
- 2
K9 K9 K9
+ 3
K9
ITC
K7 K7
89L 52 89R
VIP 35
C11 5 IDMT RELAY
L3
6
C110 7 51/51N
C10 L2
8
C31 9
L1
10
C130
C30
C51
C150
C50 2 12
1 13
C90 14
MITOP COIL 4
K8 K8 1
0v
- 2
K11 K11 K11 K11
+
K9 K9 3
K9 K9
ITC
K7 K7
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 24
8. Commissioning Ringmaster with VIP 30/35
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 25
8. Commissioning Ringmaster with VIP 30/35
Customer Site
Commissioning test
record: Contact Ref. Panel
Note : Ensure CT connections are made for the appropriate ratio and that the
Scale labels are inserted correctly to match the ratio selected.
Indicate on the diagram below actual settings. Carry out tests and record the
results in the table provided.
Is18 22 28 Is Is18 22 28 Is
55 70 55 70
45 45
15 36 15 36
37 90 37 90
12 46 30 115 12 46 30 115
10 56 25 140 10 56 25 140
8 68 20 170 8 68 20 170
80 200 80 200
(A) (A) (A) (A)
Io>30 Io>
25 38 62 75 95
20 48 50 120
15 60 37 150
12 80 30 200
10 100 25
120 300 250
(A) (A)
Is Is
18 22 28 18 22 28
15 36 15 36
12 46 12 46
10 56 10 56
8 8 80 68
80 68
(A) 1.2Is (A) 1.2Is
to>
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 26
8. Commissioning Ringmaster with VIP 30/35
Commissioning test
record:
__________________________________________________________________________________________
VIP30 / VIP 35 protection relays – version 002 / January 2001 27