Documente Academic
Documente Profesional
Documente Cultură
Ltd
DEFINATION
A switchyard is a part of an electrical Generation, Transmission,
and Distribution system. Substations transform voltage from high to
low, or the reverse, or perform any of several other important
functions.
Switchyards generally have Breakers, Isolators , CTs ,PTs , Bus bars,
protection and control equipments, transformers ,grounding wires
and switches, disconnects and metering devices, etc.
132 KV Switchyard
Constructional Overview
Testing
Operation & Maintenance
Protection
Conclusion
Constructional Overview
Two main Bus-1& 2 bars ACSR TWIN MOOSE Conductor.
Both are used to energize any abnormality with Bus-coupler for un
interruption Operation.
Current rating 2000A,Fault Level 40KA for 3 Sec.
Bay Equipment to Equipment Connection-ACSR Moose
Conductor.
CTs are connected in Series , PTs are connected across supply.
STG Generator Transformer Bay
Start-up S.A.T. Bay
-01 No.
-01 No.
-02 No.s
- 01 No.s
-02 No.s
5
TRNSFER BUS
COUPLER BAY
BUS PT
Constructional Overview
GEN BAY
SAT BAY
Line# 1 & 2
BAY
B/C BAY
Bus Bar
Protection Scheme
10
These are used to operate on the fault on line or X-mer depending upon where it is
connected. This isolates the faulty line or equipments from the live portion of the sub
station by opening automatically through protective relays; control cables etc. in
11
definite time.
Make
No of Core
CGL
2
Ratio
132KV/3/110V/3/110V/3
Class
Burden
0.2/3P
100 VA/100 VA
a) Measurement of voltage
b) Provide secondary voltage
protection.
Make
Type
No of Core
Ratio
Class
Burden
CGL
Outdoor
2 Core
400-800/1-1A
0.25/0.25
30 VA
ISF
<= 5
a) Measurement of current
b) Protection current circuits when currents
passed through protective relays like
Distance protection, Backup protection.
for
12
NEXT
Polarity Test :
Battery 9V
P1
P2
S1
S2
Press Back
14
Make
Type
LD DISCHARGE CLASS
Rated Voltage
Rated Frequency
Maximum continuous Operating
Voltage
Nominal Discharge Current
MFD
OBLUM ELECTRICAL
METAL OXIDE
Class-3
60 KV
48-62 HZ
102 KV
10 KA
2010
Make
OBLUM ELECTRICAL
15
Bushing
Make
No of Core
CGL
3
Ratio
132KV/3/110V/3/110V/3/110V
Class
Burden
0.2/3P/3P
100 VA/100 VA/100VA
Make
Type Drive
Rated Voltage
Rated Current
Frequency
Short Time Rating
Lightning Impulse with stand
Across voltage
Motor/Manual,415 v,3
145 kv
1250 A
50 Hz
100 KA for 3 sec
650 kv
16
Spacer
Clamp
Tension
Suspension
17
OPERATIONAL MODES
Normal Operation :
Synchronization
Start Up / Import
Press
Press
Press
18
Move Next
DS-5
DS-5
DS-4
DS-4
CB
CB
DS-3
DS-3
DS-2
<--- GT BAY
DS-2
DS-1
MAIN -1 BUS
DS-1
DS-2
DS-1
DS-2
DS-1
DS-3
DS-2
DS-3
CB
CB
CB
DS-4
DS-4
BUS COUPLER CUM
TRNSFER BREAKER
STN. TRFO
G. TRFO
Gen CB
U.A.TRFO
G GENERATOR
LOAD
19
DS-1
DS-5
DS-5
DS-4
DS-4
CB
CB
DS-3
DS-3
DS-2
<--- GT BAY
DS-2
DS-1
DS-1
MAIN -1 BUS
DS-1
DS-2
DS-1
DS-2
DS-3
DS-1
DS-2
DS-3
CB
CB
CB
DS-4
DS-4
BUS COUPLER CUM
TRNSFER BREAKER
G. TRFO
U.A.TRFO
G GENERATOR
STN. TRFO
LOAD
LOAD
20
Press Back
DS-5
DS-5
DS-4
DS-4
CB
CB
DS-3
DS-3
DS-2
<--- GT BAY
DS-2
DS-1
DS-1
MAIN -1 BUS
DS-1
DS-2
DS-1
DS-2
DS-3
DS-1
DS-2
DS-3
CB
CB
CB
DS-4
DS-4
BUS COUPLER CUM
TRNSFER BREAKER
G. TRFO
U.A.TRFO
G GENERATOR
STN. TRFO
LOAD
LOAD
21
Press Back
MAIN -1 BUS
DS-1
DS-2
DS-2
DS-1
DS-3
CB
CB
Tripping Prt.
DS-4
1. Close DS-3
2. Open DS-3 & DS4
Close DS-3
OUTGOING OHL #1 BAY
22
MAIN -1 BUS
DS-2
DS-1
CB
DS-1
DS-3
Tripping Prt.
DS-2
CB
DS-4
23
Press Back
MAIN -1 BUS
DS-1
DS-2
DS-2
DS-1
DS-3
CB
Protection
Tripping fuse Out
CB
Tripping Prt.
DS-4
1. Open DS-1
2. Close DS-1
24
Press Back
Maintenance
CTs, PTs ,all auxiliaries terminal tightness.
SF6 Breaker Gas pressure monitoring &
maintain.
Stone,metnal layer maintain across the area.
Monitoring & diagnosis using Hotspot detector
or temperature scanner .
Isolator & contact cleaning on scheduled.
25
26
27
Protection
28
29
30
Protection System
A series of devices whose main purpose is to
protect persons and primary electric power
equipment from the effects of faults.
Protective relays
Circuit breakers
Current and voltage transducers
Communications channels
DC supply system
Control cables
CTs
Protected
Equipment
Control
Relay
VTs
Speed
Sensitivity
7080%
1710%
1008%
0302%
INSTANTANEOUS/High Speed
DMT: (Definite Mean Time-I>>/high set)
IDMT: (Inverse Definite Minimum Time)
SI
- Standard Inverse (I>)
VI
- Very Inverse
EI
- Extreme Inverse
LTI
- Long Time Inverse
Example:
If FLC=100A, % setting =105,
Operate time = 10sec Then TMS=?
If CTR =150/1A, In=150, Isec=1A
As per CTR % set= 0.7*In.
Relay Iset= 700mA, Ir=1.05/1.0=1.05
=>TMS will be 0.136
IDMT:SI
IDMT:
For HT Motors:
a.
b.
c.
d.
e.
f.
a.
b.
c. Rotor E/F
d. NPS
e. Backup Impedance
f. Backup O/C & E/F
g. Loss of field
h. Reverse Power (Short Time /Long time)
i. Thermal Overload Alarm
j. Dead Machine
k. Winding temperature
l. O/V & U/V
SUMMARY
Grading margin of 0.3 seconds has been considered between different levels of
protective devices.
In case of a fault on Line, Distance relay will operate instantaneously. If it fails to
Operate than Directional OC relay will operate as backup.
If the fault is still found persisting than GT bay and other line bay relay will give
further backup and will trip their respective breakers to clear the fault.
In case of a fault on Bus, Bus differential relay will operate instantaneously. If this
relay fails to clear the fault , all other feeders including two line bays and GT bay
relays will trip their respective breakers to clear the fault .
In case of a fault in Generator Transformer (GT),Differential protection for GT will
operate instantaneously. And Directional relay looking towards GT will give backup to
it. If the fault is still found persisting than all other feeders including two line bays will
trip their respective breaker to clear the fault.
Forward Path
51
Special Thanks
for Guidance