Documente Academic
Documente Profesional
Documente Cultură
MIDEA AIRCONDITIONER
DC INVERTER
SPLIT WALL-MOUNTED TYPE
MSG-18HRDN1-QC2(B)
V1.0
April, 2010
CONTENTS
1. Precaution................................................................................................................................................. 1
1.1 Safety Precaution ................................................................................................................................................ 1
1.2 Warning ............................................................................................................................................................... 1
2. Function .................................................................................................................................................... 4
3. Dimension ................................................................................................................................................. 6
3.1 Indoor Unit ........................................................................................................................................................... 6
3.2 Outdoor Unit ........................................................................................................................................................ 7
4. Specification ............................................................................................................................................. 8
5. Refrigerant cycle diagram ....................................................................................................................... 9
6. Wiring diagram ....................................................................................................................................... 10
6.1 Indoor Unit ......................................................................................................................................................... 10
6.2 Outdoor Unit ...................................................................................................................................................... 11
8. Operation characteristics...................................................................................................................... 19
9. Electronic function ................................................................................................................................ 20
9.1 Abbreviation ...................................................................................................................................................... 20
9.2
1. Precaution
1.1
Safety Precaution
installation stand.
must be followed.
1.2
Warning
Installation
Do not use a defective or underrated circuit
circuit.
center.
wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance
near the power cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric
shock.
Do not store or use flammable gas or
combustible near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed
space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas
and open a window for ventilation before turn the
product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
If strange sounds, or small or smoke comes
from product. Turn the breaker off or disconnect
the power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in
storm or hurricane. If possible, remove the
product from the window before the hurricane
1
arrives.
There is risk of property damage, failure of product,
or electric shock.
Do not open the inlet grill of the product
Operational
CAUTION
Always check for gas (refrigerant) leakage
after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is
drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration of water leakage.
Do not install the product where the noise
or hot air from the outdoor unit could damage
the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport
the product.
Avoid personal injury.
Do not install the product where it will be
exposed to sea wind (salt spray) directly.
health hazards
have leaked.
2. Function
Indoor unit
Timer function
Self-diag. function
Auto mode
The mode can be change by the room temperature.
Temp. Compensation
Auto-restart function
When the power supply is
interrupted and then restore, the air
conditioners automatically restore
the previous function setting.
Flexible wiring connection
Outdoor unit
Anti-rust cabinet
Made from electrolytic zinc steel sheet and anti-rust coated components.
3. Dimension
3.1
Indoor Unit
4. Specification
Indoor
Outdoor
MSG-18HRDN1-QC2(B)
MOC-18HDN1-QC2
Power supply
Capacity
Cooling
Heating
Ph-V-Hz
1, 220-240V~, 50Hz
Btu/h
17000(5100~22000)
Input
1550(380~2300)
Rated current
6.9(1.8~10.2)
EER
W/W
3.21
Capacity
Btu/h
17000(5300~23000)
Input
1380(350~2000)
Rated current
6.2(1.6~9.0)
COP
W/W
3.61
Moisture Removal
L/h
1.5
2950
Max. current
13.5
Starting current
10
Model
Compressor
5RS132ZAD21
Type
Rotary
Brand
Panasonic
Capacity
3385
Input
1250
Thermal protector
1NT11L-5270 L115-15
Capacitor
uF
No
Refrigerant oil
ml
370
Model
RPG25
Brand
Indoor fan motor
Welling
Input
55
Capacitor
uF
1.5
Speed(hi/mi/lo)
r/min
1250/1100/950
m3/h
800/700/600
dB(A)
Indoor unit
mm
906*286*235
Packing
mm
1020*381*328
(W*H*D)
Net/Gross weight
Kg
Model
Welling
Input
Capacitor
uF
Speed
r/min
890/540
m3/h
2200
dB(A)
111/96
2.5
56
Dimension(W*H*D)
mm
760*590*285
Packing
mm
887*645*355
Kg
39.5/42
(W*H*D)
Net/Gross weight
Refrigerant type R410A
Refrigerant piping
11.0/15.0
YDK50-6C
Brand
Outdoor fan motor
45/40/34
Dimension (W*H*D)
1100
mm
6.35/12.7
25
10
Operation temp
17 ~ 30
Ambient temp
-15 ~ 50
The above design and specifications are subject to change without prior notice for product improvement.
6. Wiring diagram
6.1
Indoor Unit
MSG-18HRDN1-QC2(B)
10
6.2
Outdoor Unit
MOC-18HDN1-QC2
11
7. Installation details
7.1
7.2
Torque
mm
inch
Kgf.m
6.35
1/4
1.8
12.7
1/2
5.5
7.3
9K
12K
18K
1.5
1.5
2.5
Max.
Additional
Elevation
Length
refrigerant
(m)
B (m)
A (m)
(g/m)
10
25
20
Standard
Pipe size
Capacity
Btu/h
Gas
Liquid
18K
1/2 (12.7)
1/4 (6.35)
length
Caution:
Capacity is based on standard length and maximum allowance length is base of reliability.
Oil trap should be installed per 5-7 meters.
7.4
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the
compressor, reduce the cooling capacity, and could lead to a malfunction of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas
12
Procedure
Caution:
following measures.
valve stem.
13
7.5
Procedure
1. Confirm that both the 2-way and 3-way valves are set to the opened position.
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve.
Connect the charge hose with the push pin to the gas service port.
5. Air purging of the charge hose.
Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
6. Set the 2-way valve to the close position.
7. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
8. Immediately set the 3-way valve to the closed position.
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and amount the 2-way and 3-way valves stem nuts and service port caps.
Use a torque wrench to tighten the service port cap to a torque of 1.8 kgf.m.
Be sure to check for gas leakage.
14
7.6
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3-way valve.
Leave the valve on the charging cylinder closed.
3. Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way
valve approximately 45 for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.
4. Check the gas leakage.
Check the flare connections for gas leakage.
5. Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicates 0.3 to 0.5 Mpa.
6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position.
Be sure to use a hexagonal wrench to operate the valve stems.
7. Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
15
7.7
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valves service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 to
0.1Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than 0.1Mpa,
discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be necessary to
apply a evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be discharged.
16
7.8
Evacuation
Procedure:
1. Connect the vacuum pump to the charge sets centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
17
7.9
Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time
(approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not
sufficient, wait approximately 1 minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valves service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner
before disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
18
8. Operation characteristics
MSG-18HRDN1-QC2(B)
Piping Length Characteristics (Cooling)
Cooling Characteristics
5.2
Cooling Capacity (KW)
5.2
5.1
5.0
4.9
4.8
4.7
5.1
5.0
4.9
4.8
4.7
4.6
4.6
4.5
1.68
1.58
Cooling Power Input (KW)
5.3
1.64
1.60
1.56
1.52
1.48
1.44
25 27 29 31 33
1.56
1.54
1.52
1.50
1.48
1.46
5
35 37 39 41 43
10 11 12 13 14 15
Heating Characteristics
5.4
5.2
Heating Capacity (KW)
5.2
5.0
4.8
4.6
4.4
4.2
5.0
4.8
4.6
4.4
4.2
4.0
1.70
4.0
1.60
1.50
1.40
1.30
1.20
1.10
-7
-5
-3
-1
11
1.45
1.40
1.35
1.30
1.25
1.20
10 11 12 13 14 15
19
9. Electronic function
9.1
Abbreviation
9.2
Display function
AUTO indicator
This indicator illuminates when the air conditioner is in AUTO operation.
TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
DEF. Indicator
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air
control feature is activated in heating mode.
RUN indicator
This indicator illuminates when the air conditioner is running.
9.2.2 LED display control function.
Pressing LED display button on remote controller will turn off all displays on indoor unit, while pressing once
again, all displays will resume.
20
9.3
Protection
If T4(outdoor ambient temperature)3 and the machine connects to power supply newly or if T43
and compressor has stopped for over 3 hours, the compressor heating cable will work.
2)
Preheating mode:
A weak current flows through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
3)
If T45 or user turns on the machine and compressor runs, preheating function will stop.
9.4
Fan-Only Mode
high
T1 24
3.5
3.0
medium
1.5
1.0
low
21
9.5
Cooling Mode
9.5.1 After starting, the operation frequency of compressor submits to following rule.
A
1.5
B
1.0
0.5
-0.5
D
-1.0
When the machine is running and T(=room temp. setting temp.) changes, the frequency of compressor will
rise or descend a grade (7 minutes after starting).
After starting, if T stays in a zone for 3 minutes, the frequency will change as follow:
Zone A : Current frequency rise a grade till the maximum grade F8.
Zone B: Keep the current frequency of compressor.
Zone C: Descend the current frequency of compressor until F1.
Zone D: Compressor stops after running as the minimum frequency F1 for 60 minutes or T is less than -2.
9.5.2 Indoor heat exchanger anti-freezing function.
If T2 is lower than 0, the compressor stops and resumes when T2>5.
9.5.3 Outdoor unit current control in cooling mode(refer to the parameter table)
I3COOL
I2COOL
compressor. pause
I1COOL
running normally
2)
3)
After running for 30 minutes the machine will turn back to previous setting mode.
22
9.5.6
In cooling mode, indoor fan runs all the time and the speed can be selected as high,
2)
9.5.7
high
4.0
3.0
medium
1.5
1.0
low
9.6
9.6.1
Drying mode
Indoor fan speed is fixed at breeze grade and cant be changed. The horizontal angle is the same as in cooling
mode.
9.6.2
9.6.3 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit frequency limit are
valid, and they are the same as that in cooling mode.
9.6.4
9.7
Heating mode
Anti-cold-wind function.
44
Evaporator temp
38
37
low fan
34
33
breeze
24
17
super breeze
fan stop
2)
If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127
seconds with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold wind function is
available.
3)
If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and
anti-cold-wind is disabled.
23
9.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
T=(oom temp) (setting Temp)
9.7.3
2.5
low
2.0
medium
1.5
1.0
high
5.0
4.5
3.5
3.0
2.5
A
When the machine runs, if Th stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate the current frequency one grade, and not stop until the maximum grade.
Zone B: Keep the current frequency.
9.7.4
Zone C:
Zone D:
I3HEAT
I2HEAT
comp. pause
I1HEAT
running normally
9.7.5
9.7.6
Defrosting mode.
1)
Condition 1:
Condition of defrosting.
If T40,
When the units are running, if the following two items are satisfied the units start defrosting:
24
a) The units runs with T33 for 40 minutes and T3 keeps lower than -6 for more than
3 minutes.
b) The units runs with T33 for 80 minutes and T3 keeps lower than -4 for more than
3 minutes.
If T40,
Condition 2:
The program judges according to the condition 1, if the two items are satisfied, then judges if T2 has
descended for more than 5, if it has the machine starts defrosting, or continues to judge T2 and will
not defrost until T2 drops more than 5.
Condition 3:
No matter what value T4 is, if the machine runs with T33 for more than 120 minutes and T3
keeps lower than -2 for more than 3 minutes, the machine will defrost, no matter if T2 drops for more than 5
or not.
2)
If any one of following items is satisfied, defrosting will finish and the machine will turn to normal heating
mode.
a)
b)
c)
on
off
on
4-way valve
outdoor fan
indoor fan
off
on
off
on
off
9.7.8
30s
Set the indoor unit with remote controller as: high fan, 30 in heating mode, then press TURBO
button on controller 6 times or more within 10 seconds(make sure indoor unit receives these signals), the
machine will turn into rating capacity test mode, the buzzer will make a di sound for 2 seconds
continuously. Also, indoor fan will change to rating speed, the frequency of compressor will be fixed as
rating value. Any condition of above is not satisfied, the machine can not be turned into rating capacity test
mode.
2)
The machine will quit from the rating capacity test mode if running for 5 hours or changing fan
9.7.9
Turbo function in heating mode. (press the TURBO button on remote controller)
1)
Elevate current frequency (excluding F8) to a higher grade. If indoor fan is in low speed or pause
caused by defrosting or anti-cold-wind function, frequency of compressor will not be elevated one grade
until these limit has been released.
9.8
2)
3)
After running for 30 minutes the machine will turn back to previous setting mode.
9.8.1 This mode can be chosen with remote controller and the setting temperature can be changed between 17~30.
In auto mode, the machine will choose cooling, heating or fan-only mode according to T(T =T1-Ts).
T=T1-Ts
Running mode
T1
Cooling
-1T1
Fan-only
T-1
Heating
9.9
9.9.1 Forced cooling and auto function can carry out with a touch button. In these two modes, the machine can be
changed by remote controller to any other mode at any moment.
9.9.2 When the machine is off, pressing the touch button will carry the machine to forced auto mode, after this, if
pressing the button once again within 5 seconds, the machine will turn into forced cooling mode. In forced auto,
forced cooling or any other operation mode, pressing touch button will turn off the machine. In forced operaton,
remote control is available.
9.9.3 In forced operation mode, all general protections is available.
9.9.4 In forced cooling mode, after running for 30 minutes. the machine will turn to normal auto mode which setting
temperature is 24.
9.9.5 The action of forced auto mode is the same as normal auto mode which temperature is 24.
9.10
In cooling, drying, fan-only, or turning off mode, 4-way valve is off, while in heating mode 4-way valve is on. If the
machine changes operation mode from heating mode to some other mode, 4-way valve will be delayed off 2
minutes after compressor stop. For defrosting, please refer to the passage defrosting mode.
9.11
9.11.1 Outdoor fan starts at the same time with compressor, but stops 30 seconds later after compressor stop.
9.11.2 Outdoor fan action in heating mode(including heating in auto mode).
26
15
high
Outdoor fan action in heating mode
(including heating in auto mode).
22
high
20
low
low
outdoor temperature
17
outdoor temperature
9.11.3 Outdoor fan action in cooling & drying mode(including cooling in auto & forced mode).
Please refer to the pic. above.
9.12
Timer function
9.13
9.13.1 Operation time in sleep mode is 7 hours. After 7 hours the machine quits this mode and turns off.
9.13.2 In cooling, heating or auto mode sleep function is available.
9.13.3 Operation process in sleep mode is as follow:
1)
After pressing ECONOMIC or SLEEP button on controller, the machine will turn into sleep mode.
2)
When cooling, the setting temperature rises 1(be lower than 30) every one hour, 2 hour later the
When heating, the setting temperature descends 1(be lower than 30) every one hour, 2 hour later
the descending stops and indoor fan is fixed as low speed, and anti-cold-wind is available.
9.13.4 If user uses timer on function in sleep mode, sleep function will pause and not resume until reaches the setting
on time.
9.13.5 When user uses timer off function in sleep mode(or sleep function in timer off mode), if the timing time is less
than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing time is more than 7
hours, the machine will not stop until reaches the setting off time in sleep mode.
9.14
Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In case
of a sudden power failure, the module restores the setting conditions before the power failure. The unit will resume
the previous operation setting (including Mode, Fan speed, Temperature, ON/OFF) automatically after 3 minutes
when power returns.
9.15
85W, rated voltage is 220v-240v. If outdoor temperature is lower than 5, the heating cable begins to work. If
outdoor temperature higher than 15 , the heating cable stops working.
28
10. Troubleshooting
Safety
Because of there are capacitors in PCB and relative circuit in outdoor unit, even shut down the power supply,
electricity power still are kept in capacitors, do not forget to discharge the electricity power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE!
CAUTION!)
Bulb (25-40W)
29
10.1
LED STATUS
E0
E1
E2
E3
E5
E6
P0
P1
P2
P4
Reserved function
30
10.2
10.2.2 E1(indoor / outdoor units communication protection) error diagnosis and solution
Disconnect the power supply, after 1 minute,
connect the power supply, turn on the unit with
remote controller
NO
Check the wiring between
indoor and outdoor unit. Is
the connection of L, N, S and
GND good?
Is the GND connection on
outdoor PCB good?
NO
Yes
Is the LED4 (red) on
outdoor PCB bright and
LED1(yellow) blinking?
Yes
No
The power supply for
outdoor PCB is fail. Check
the wiring on outdoor PCB
comparing with wiring plate.
Is the connection good?
Yes
No
Replace outdoor e-box.
Correct the connection.
NO
YES
Indoor PCB is defective. Replace
the indoor PCB.
31
NO
YES
YES
Is voltage being applied to
the fan motor?
(rang 90v-160v between
mid pin and N on CN1
NO
Replace the indoor fan
motor
10.2.5 E5(Open or short circuit of outdoor temperature sensor) diagnosis and solution.
Is the outdoor temperature
sensor connector and
connection good?
NO
YES
Replace the sensor and
check if E5 display again?
YES
10.2.6 E6(open or short circuit of room or evaporator temperature sensor) diagnosis and solution.
Is the indoor temperature
and evaporator sensor
connector and connection
good?
NO
YES
Replace the sensor and
check if E6 display again?
YES
NO
YES
Replace the outdoor PCB
and then repower on. Is
the failure cleared?
NO
32
10.2.8 P1(over voltage or too low voltage protection) diagnosis and solution.
Is the power supply good?
NO
YES
Replace the outdoor e-box.
Does compressor
operate?
YES
Is the connection
good?
NO
YES
Is refrigerant
circulation
volume normal?
NO
Is protector
normal?
YES
NO
Charge refrigerant
YES
Replace the outdoor PCB.
Is abnormality
the same after
gas charging?
NO
NO
YES
Replace the outdoor E-box.
NO
33
10.3
Position
Resistance Value
Blue - Red
1.417 (20)
Blue - Black
1.392 (20)
Red - Blue
1.435 (20)
Position
Resistance Value
Black - Red
113.5
(20)
Red -Yellow
187.5
(20)
Position
Resistance Value
Black - Red
2708% (20)
White - Black
4758% (20)
34
10
15
20
25
30
40
50
60
26.9
20.7
16.1
12.6
10
5.2
3.5
2.4
90
100
3.7
15
25
35
60
141.6
88
56.1
36.6
13.8
70
80
9.7
6.9
35