Chvac - Full Commercial HVAC Loads Calculation Program

Design Consortium (Pvt) Ltd


Colombo 08, Sri Lanka, CO 00800

Elite Software Development, Inc.


Page 1

Room Input
Room 1: PS Living And Dining Area (E) (113.52 sq.m) (Zone 1)
Air Handler number:
Room length: (meters)
Lighting Watts:
Number of people in room:
Lighting profile number:
Ceiling height (meters):
Sensible safety factor (%):
Sensible heat per person (Watts):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air L/s:
Minimum supply L/s:
Ceil. exposed to plenum (sq.m):
Cooling loads only are calculated for this room.
Part

1
10.32
50
1
1
5
5
45
0.000
0.300
0.000
0.000
0
0
0

U-Factor

Cool TD

Heat TD

Height

Width

Area

1.93

2.000

2.000

3.00

34.00

102.0

Type

ASHRAE#

U-Factor

Color

Height

Width

Area

Direction

1.930

3.00

10.32

31.0

1
Glass

Room occurrences:
Room width (meters):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Watts):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air L/s:
Latent Watts equipment load:
Exposed floor slab perimeter (m):

Type

3
Wall

1
11.00
1,320
12
1
2.70
5
70
L/s/Pr
AC/Hr
L/s/Pr
AC/Hr
0
0
114

Type

S.U-F.

Shd C.

Height

Width

Occur.

Area

Shade

Tilt

Ref

2.000

0.300

2.50

9.33

23.3

90

Chvac - Full Commercial HVAC Loads Calculation Program


Design Consortium (Pvt) Ltd
Colombo 08, Sri Lanka, CO 00800

Elite Software Development, Inc.


Page 2

Building Summary Loads


Building peaks in June at 10am.

Bldg Load
Descriptions

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

0
8
23
0

0
0
0
0

0.00
0.00
0.00
0.00

0
0
0
0

0
124
6,206
0

0
124
6,206
0

0.00
1.15
57.77
0.00

0.00

6,330

6,330

58.92

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0
0
0
567
0
0
0
0
0
900
0
0
0
0
0
0
0
0
0

1,386
53
0
882
413
0
0
0
0
116
0
96
0
0
0
0
0
0
0

1,386
53
0
1,449
413
0
0
0
0
1,016
0
96
0
0
0
0
0
0
0

12.90
0.49
0.00
13.49
3.85
0.00
0.00
0.00
0.00
9.46
0.00
0.89
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0.00

1,467

9,275

10,743

100.00

Roof
Wall
Glass
Floor Slab
Skin Loads
Lighting
Equipment
Pool Latent
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

1,320
50
0
12
102
0
0
0
0
26
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Room Loads
Plenum Loads
Fan/Duct/Misc Loads

0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00

0
900
0
567
0
0

0
116
0
9,064
0
96

0
1,016
0
9,631
0
96

0.00
9.46
0.00
89.65
0.00
0.89

Building Totals

0.00

1,467

9,275

10,743

100.00

Check Figures
Total Building Supply Air (based on a 11 TD):
Total Building Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

686 L/s
0 L/s
114
6.0439
10.5674
0.0946
0.00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0.00 kW
10.74 kW

37.2 Sq.m/Ton
0.0269 Tons/Sq.m

3.05 Tons