VACUTAP VR I II III/VR I HD
Technical Data
2188029/02 EN
Table of contents
Table of contents
1
General ................................................................................................................................ 7
1.1
1.2
1.3
2.1
2.2
2.3
Step capacity diagram VRC, VRE electrical arc furnace operation)* ................................................ 18
2.4
Step capacity diagram VRD, VRF, VRG* (electrical arc furnace operation)** .................................. 18
2.5
2.6
2.7
2.8
2.9
2.10
On-load tap-changer VACUTAP VRC with multiple coarse change-over selector ......................... 24
3.1
3.2
On-load tap-changer combination VACUTAP VRC I/VR II / VRF I/VRF II for delta connection .... 26
3.3
Appendix ........................................................................................................................... 28
4.1
4.2
4.3
VACUTAP VR, basic connection diagrams, designation of tap selector connection contacts according to MR standard (719037) ............................................................................................................ 32
VACUTAP VRF I 1001, VRD/VRF I 1301, VRF I 1001 HD, VRD/VRF I HD 1301, dimensional
drawing (899805) .............................................................................................................................. 34
VACUTAP VRF I 1001/1301 (Um 362 kV), VRF I HD 1001/1301 (Um 362 kV), dimensional drawing (899806) ...................................................................................................................................... 36
VACUTAP VRG I 1001/1301, VRG I HD 1001/1301, dimensional drawing (899810) ................... 38
4.4
4.5
4.6
4.7
4.8
VACUTAP VRG I 1001/1301 (Um 362 kV), VRG I HD 1001/1301 (Um 362 kV), dimensional drawing (899811) ...................................................................................................................................... 40
VACUTAP VRF I 1601, 72.5...300 kV, dimensional drawing (786915) .......................................... 42
4.9
4.10
4.11
4.12
2188029/02 EN
VACUTAP VR I II III/VR I HD
Table of contents
4.13
VACUTAP VRF I 2602 (Um 362 kV), dimensional drawing (727034) ............................................ 52
4.14
4.15
VACUTAP VRG I 2602 (Um 362 kV), dimensional drawing (727036) ........................................... 56
4.16
4.17
4.18
4.19
4.20
4.21
4.22
4.25
VACUTAP VRC I 701/VRC I HD 701 with multiple coarse change-over selector, dimensional drawing (718316) ...................................................................................................................................... 64
VACUTAP VRC I 1001/VRC I HD 1001 with multiple coarse change-over selector, dimensional
drawing (718318) .............................................................................................................................. 65
VACUTAP VRC I 1301/VRC I HD 1301 with multiple coarse change-over selector, dimensional
drawing (718321) .............................................................................................................................. 66
VACUTAP VRF II 1302, dimensional drawing (899814) ................................................................ 67
4.26
VACUTAP VRF II 1302 (Um 362 kV), dimensional drawing (899815) ........................................... 69
4.27
4.28
VACUTAP VRG II 1302 (Um 362 kV), dimensional drawing (899817) .......................................... 73
4.29
4.30
4.31
4.32
4.33
4.34
4.35
VACUTAP VRC III 700 Y with multiple coarse change-over selector, dimensional drawing (718314)
........................................................................................................................................................... 82
VACUTAP VRC III 400/550/700 Y-10191W, detailed connection diagram (ZS030355) ................ 83
4.36
VACUTAP VRE III 700 Y-10193W, detailed connection diagram (ZS030356) .............................. 84
4.37
VACUTAP VRD III 1300 Y-C/D-10191W, detailed connection diagram (ZS030201) .................... 85
4.38
VACUTAP VRG III 1300 Y-E-14271G, detailed connection diagram (ZS030202) ........................ 86
4.39
4.40
4.41
4.42
VACUTAP VRC/VRE, connecting leads 3W, 1G, 3G, dimensional drawing (723590) .................. 90
4.43
4.44
VACUTAP VR, on-load tap-changer head with flange for pressure relief device (899946) ........... 92
4.45
VACUTAP VR, special design for bell-type tank installation (720781) ........................................... 93
4.46
VACUTAP VRC/VRE, arrangement of contacts on tap selector, tap selector division 1022
(899993) ............................................................................................................................................ 94
VACUTAP VRC/VRE I 1001/1301, VRC/VRE I HD 1001/1301, bridges to parallel connection of tap
selector connection contacts (727025) ............................................................................................. 95
4.23
4.24
4.47
VACUTAP VR I II III/VR I HD
2188029/02 EN
Table of contents
4.48
VACUTAP VR, installation position of tap selector connection contacts (727042) ........................ 96
4.49
4.50
VACUTAP VRC III 400/550/700 Y, VRE III 700 Y, arrangement of tap selector (899994) ............ 98
4.51
4.52
VACUTAP VRC I 401/551/701, VRC I HD 401/551/701, VRE I 701, VRE I HD 701, arrangement of
tap selector (899995) ........................................................................................................................ 99
VACUTAP VRC/VRE I 1001, VRC/VRE I HD 1001, arrangement of tap selector (899996) ........ 100
4.53
VACUTAP VRC/VRE I 1301, VRC/VRE I HD 1301, arrangement of tap selector (727043) ........ 101
4.54
4.55
VACUTAP VR, variants of the on-load tap-changer head, gear unit swivel range and drive direction
(721216) .......................................................................................................................................... 102
VACUTAP VR, swivel range of gear unit (728474) ...................................................................... 103
4.56
4.57
VACUTAP VRG, horizontal drive shaft, tap selector size (899959) ............................................. 105
4.58
VACUTAP VRC/VRE III, tie-in resistors with or without potential switch (899972) ...................... 106
4.59
VACUTAP VRC II, tie-in resistors with or without potential switch (899986) ............................... 107
4.60
4.63
VACUTAP VRC/VRE I, VRC/VRE I HD, tie-in resistors with or without potential switch (718447) ....
108
VACUTAP VRC/VRE, tie-in resistor cylinder with potential switch without tie-in resistors (899973)
......................................................................................................................................................... 109
VACUTAP VRD/VRF/VRG, fine tap selector connection contact and change-over selector connection contact (899941) ...................................................................................................................... 110
VACUTAP VRF, bridges to parallel connection of tap selector connection contacts (786919) ... 111
4.64
VACUTAP VRG, bridges to parallel connection of tap selector connection contacts (786920) ... 112
4.65
VACUTAP VRD/VRF, tap selector size C/D, tap selector bottom depiction of the lowest live parts
(899968) .......................................................................................................................................... 113
VACUTAP VRG, tap selector size E, tap selector bottom depiction of the lowest live parts (899969)
......................................................................................................................................................... 114
VACUTAP VRD/VRF, arrangement of potential switches/tie-in resistors (899950) ..................... 115
4.61
4.62
4.66
4.67
4.68
4.69
4.70
4.71
4.72
4.73
4.74
4.75
4.76
4.77
4.78
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder and
potential switch (899951) ................................................................................................................ 116
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder
(899955) .......................................................................................................................................... 117
VACUTAP VRD/VRF III WP, tap selector size C/D, tie-in resistor cylinder and potential switch
(899962) .......................................................................................................................................... 118
VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in resistor cylinder (899964) .................. 119
VACUTAP VRD/VRF I/III WS, VRD/VRF I HD WS, tap selector size C/D, potential switch (899966)
......................................................................................................................................................... 120
VACUTAP VRG I/III WS, VRG I HD WS, tap selector size E, potential switch (899967) ............. 121
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder and
potential switch (899952) ................................................................................................................ 122
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder and
potential switch (899953) ................................................................................................................ 123
VACUTAP VRD/VRF I WP, VRD/VRF I HD WP, tap selector size C/D, tie-in resistor cylinder and
potential switch (899954) ................................................................................................................ 124
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder
(899960) .......................................................................................................................................... 125
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder
(899956) .......................................................................................................................................... 126
2188029/02 EN
VACUTAP VR I II III/VR I HD
Table of contents
4.79
4.82
VACUTAP VRD/VRF I WR, VRD/VRF I HD WR, tap selector size C/D, tie-in resistor cylinder
(899961) ..........................................................................................................................................
VACUTAP VRD/VRF III WP, tap selector size C/D, tie-in resistor cylinder and potential switch
(899963) ..........................................................................................................................................
VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in resistor cylinder and potential switch
(899965) ..........................................................................................................................................
VACUTAP VRF II 1302 WP, tap selector size C/D, tie-in resistor cylinder (728691) ...................
4.83
VACUTAP VRF II 1302 WR, tap selector size C/D, tie-in resistor cylinder (728690) ................... 131
4.84
VACUTAP VRF I 2602 WP, tap selector size C/D, tie-in resistor cylinder (729538) .................... 132
4.85
VACUTAP VRF I 2602 WR, tap selector size C/D, tie-in resistor cylinder (729537) .................... 133
4.80
4.81
VACUTAP VR I II III/VR I HD
2188029/02 EN
127
128
129
130
1 General
1 General
1.1 On-load tap-changer designations
Example: VRF I 1301 Y 245 / C 10 19 1W R
VRF
Type
Number of phases
1301
Ium [A]
1301
Y
245
=
=
Applications
Um [kV]
10
VACUTAP VRC
VACUTAP VRE
VACUTAP VRD
VACUTAP VRF
VACUTAP VRG
1 phase
2 phases
3 phases
VRC
VRC
VRC, VRE
VRC, VRE, VRD, VRF, VRG
VRC, VRE, VRD, VRF, VRG
VRF, VRG
VRF, VRG
1 (3-phase Y)
1 (1-phase)
2 (1-phase)
3 (1-phase)
For use with neutral point only
VRC, VRE, VRD, VRF, VRG
VRC, VRE, VRD, VRF, VRG
VRC, VRE, VRD, VRF, VRG
VRC, VRE, VRD, VRF, VRG
VRC, VRE, VRD, VRF, VRG
VRF, VRG
VRC, VRE
VRC VRE, VRD, VRF
VRC, VRE, VRD, VRF
VRC, VRE
VRG
10
12
14
16
18
2188029/02 EN
VACUTAP VR I II III/VR I HD
VRC
VRE
VRD
VRF
VRG
I
II
III
400
550
700
1000
1300
1600
2600
0
1
2
3
Y
72.5
123
170
245
300
362
B
C
D
DE
E
10
12
14
16
18
1 General
19
1W
Mid-positions
1W
Change-over selector
Tie-in measures
19
23
27
31
35
0 mid-positions (without change-over
selector)
1 mid-position
3 mid-positions
Reversing change-over selector
Coarse tap connection
Tie-in resistor
Potential switch
Potential switch with tie-in resistor
19
23
27
31
35
0
1
3
W
G
R
S
P
VACUTAP VR I II III/VR I HD
2188029/02 EN
1 General
VRC I 401
Number of phases
and application
Maximum rated
through current Ium(in
A)
Rated short-time current (kA)
Rated duration of
short-circuits (s)
Rated peak withstand
current (kA)
Maximum rated step
voltage Vin (V)1)
Step capacity (PStN)
(kVA)
VRC I 551
VRC I 701
VRC I 1001
VRC I 1301
VRD I 1301
1
400
550
700
1000
1300
10
12
15
15
20
25
30
37.5
3300
3300
3300
3300
3300
1320
1500
1500
1500
1500
The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value.
2188029/02 EN
VACUTAP VR I II III/VR I HD
1 General
VACUTAP VRE/VRF/VRG I
On-load tap-changer
Number of phases
and application
Maximum rated
through current Ium(in
A)
Rated short-time current (kA)
Rated duration of
short-circuits (s)
Rated peak withstand
current (kA)
Maximum rated step
voltage Vin (V)2)
Step capacity (PStN)
(kVA)
VRE I 1001
VRE I 1301
VRF I 1601
VRF I 26021)
VRF I 1001
VRF I 1301
VRG I 1601
VRG I 26021)
VRG I 1001
1
VRG I 1301
1
700
1000
1300
1600
2600
10
12
15
19
26
25
30
37.5
47.5
65
4000
4000
4000
4000
4000
2800
3750
3750
3750
6000
VRE I 701
2)
The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value.
10
VACUTAP VR I II III/VR I HD
2188029/02 EN
1 General
VACUTAP VRC/VRF/VRG II
On-load tap-changer
VRC II 402
VRC II 552
VRC II 702
VRF II 1302
2
400
2
550
2
700
VRG II 1302
2
1300
6
3
15
3300
1320
8
3
20
3300
1500
10
3
25
3300
1500
15
3
37.5
4000
3000
The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value.
2188029/02 EN
VACUTAP VR I II III/VR I HD
11
1 General
6
3
15
3300
1320
8
3
20
3300
1500
10
3
25
3300
1500
10
3
25
4000
2800
neutral point
2)
The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value.
12
VACUTAP VR I II III/VR I HD
2188029/02 EN
1 General
1)
1)
1000
1300
1000
1300
12
3
15
3
12
3
15
3
30
37.5
30
37.5
3300
3300
4000
4000
1500
1500
3000
3000
neutral point
2)
The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value.
2188029/02 EN
VACUTAP VR I II III/VR I HD
13
1 General
VACUTAP VRC I HD
On-load tap-changer
Number of phases
and application
Maximum rated
through current Ium(in
A)
Rated short-time current (kA)
Rated duration of
short-circuits (s)
Rated peak withstand
current (kA)
Maximum rated step
voltage Vin (V)1)
Step capacity (PStN)
(kVA)
VRC I HD
401
1
VRC I HD
551
1
VRC I HD
701
1
VRC I HD
1001
1
VRC I HD
1301
1
400
550
700
1000
1300
10
12
15
15
20
25
30
37.5
3300
3300
3300
3300
3300
1320
1500
1500
1500
1500
The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value.
14
VACUTAP VR I II III/VR I HD
2188029/02 EN
1 General
VACUTAP VRE/VRD/VRF/VRG I HD
On-load tap-changer
VRE I HD 701
VRE I HD 1001
VRD I HD 1301
VRE I HD 1301
VRF I HD 1001
VRF I HD 1301
VRG I HD 1001
1
VRG I HD 1301
1
700
1000
1300
1300
10
3
12
3
15
3
15
3
25
30
37.5
37.5
4000
4000
3300
4000
2800
3750
1500
3750
The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if the step capacity is limited to its rated value.
For all on-load tap-changer variants
50...60
without change-over selector: maximum of 181) with change-over selector: maximum of 351)
Pressure-tight up to 0.3 bar permanent differential pressure (test pressure 0.6 bar), head and cover of the on-load tap-changer are vacuumproof
The on-load tap-changer VACUTAP VR can be operated in the rated
load range at oil temperatures of between 25 C and + 105 C and
overload up to + 115 C according to IEC 60214-1.
Weight, displacement volume and oil content of the diverter switch oil
compartment are shown in the relevant dimension drawings.
Oil compartment
Temperature range
Dimensions
2188029/02 EN
VACUTAP VR I II III/VR I HD
15
1 General
On-load tap-changer
72.5 kV362 kV
72.5 kV300 kV
72.5 kV245 kV
140
230
325
850
460
850
460
362
1175
950
510
1)
According to IEC 60214-1, chapter 3.57: highest effective value for phaseto-phase voltage in a three-phase system for which a on-load tap-changer is
designed with respect to its insulation.
16
VACUTAP VR I II III/VR I HD
2188029/02 EN
2 Technical data
2 Technical data
2.1 Step capacity diagram VRC and VRE
Figure 1: Step capacities (rated voltage Vi, rated through current Iu)
Figure 2: Step capacities (rated step voltages Vi, rated through current Iu)
2188029/02 EN
VACUTAP VR I II III/VR I HD
17
2 Technical data
2.3 Step capacity diagram VRC, VRE electrical arc furnace operation)*
* Please contact MR
Figure 3: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),
(rated step voltages Vi, rated through current Iu)
2.4 Step capacity diagram VRD, VRF, VRG* (electrical arc furnace operation)**
* VRG: Versions identical to VRF but with tap selector size "E"
** Please contact MR
Figure 4: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),
(rated step voltages Vi, rated through current Iu)
18
VACUTAP VR I II III/VR I HD
2188029/02 EN
2 Technical data
Figure 5: Step capacities (rated step voltages Vi, rated through current Iu)
Figure 6: Step capacities (rated step voltage Vi, rated through current Iu)
2188029/02 EN
VACUTAP VR I II III/VR I HD
19
2 Technical data
Figure 7: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),
(rated step voltage Vi, rated through current Iu)
Figure 8: Step capacities electrical arc furnace and ladle furnace operation (EAF/LF),
(rated step voltage Vi, rated through current Iu)
20
VACUTAP VR I II III/VR I HD
2188029/02 EN
2 Technical data
1* Notice: Observe maximum rated lightning impulse withstand voltage stress at a0 in mid-position!
a0
a1
2188029/02 EN
VACUTAP VR I II III/VR I HD
21
2 Technical data
= between start and end of a tapped winding and, in version with coarse winding, between start and
end of a coarse winding
Note for coarse tap selector connection (-) position of the change-over selector: When loading with
impulse voltage, note the permissible withstand voltage "a" between the end of a coarse winding
connected with the K fine tap selector contact and the fine tap selector contact at the end of the
tapped winding of the same phase.
b
= between the fine tap selector contacts of different phases and between change-over selector contacts of different phases, which are connected with the beginning/end of a tapped winding or with a
fine tap selector contact
f
= between diverter switch output terminal and ground
Additionally for coarse tap selector connection in (+) position of the change-over selector:
c1
= from one (-) change-over selector contact to take-off lead of the same phase
c2
= between (-) change-over selector contacts of different phases
Insulation distances
a0
Maximum
1502)
150
400
400
550
550
a1
a
b4)
c1
c24)
kV
50 Hz
1 min
20
30
85
100
180
195
kV
50 Hz
1 min
20
30
110
150
210
225
kV
50 Hz
1 min
20
30
180
180
250
280
Table 10: On-load tap-changer VRD, VRF, VRG, rated withstand voltages of the internal on-load tap-changer insulation
1)
2)
Insulation distances
a0
a1
a
22
3)
4)
VACUTAP VR I II III/VR I HD
kV
50 Hz
1 min
20
30
50
kV
50 Hz
1 min
20
30
82
2188029/02 EN
kV
50 Hz
1 min
20
30
105
kV
50 Hz
1 min
20
30
120
2 Technical data
Insulation distances
b2)
c1
c22)
50
143
150
82
178
182
146
208
225
160
230
250
Table 11: On-load tap-changer VRC, VRE, rated withstand voltages of the internal on-load tap-changer insulation
1)
2)
The tap selector size (ID letters B, C, D, DE, E) characterizes the internal insulation of the tap selector, whose rated withstand voltages must be matched to the requirements of the transformer winding.
The admissible maximum operating voltage on the individual tap selector
distances corresponds to half the value of the above mentioned rated shortduration power frequency withstand voltages.
without change-over selector
Tap-change
operation
10050
10060
10070
10080
10090
10100
12110
12120
14130
14140
16150
16160
18170
18180
22190
22200
22210
22220
Tap-change
operation
10071W
10081W
10091W
12101W
12111W
14111W
14121W
14131W
16121W
16131W
16141W
16151W
18151W
18161W
18171W
10191W
12231W
14271W
16311W
18351W
Tap-change
operation
10071G
10081G
10091G
12101G
12111G
14111G
14121G
14131G
16121G
16131G
16141G
16151G
18151G
18161G
18171G
10191G
12231G
14271G
16311G
18351G
2188029/02 EN
VACUTAP VR I II III/VR I HD
23
2 Technical data
a0
a1
a
c1
c2
d1
d2
d3
f
24
VACUTAP VR I II III/VR I HD
2188029/02 EN
2 Technical data
Insulation distances
a0
a1
a
B2)
c1
c22)
d1
d2
d3
Maximum
1501)
150
265
265
455
455
265
350
350
kV
50 Hz
1 min.
20
30
50
50
127
127
50
82
82
kV
50 Hz
1 min.
20
30
82
82
165
165
82
105
105
kV
50 Hz
1 min.
20
30
105
146
210
215
105
105
120
Table 13: On-load tap-changer VACUTAP VRC with multiple coarse change-over selector, rated withstand voltages of
the internal on-load tap-changer insulation
1)
2188029/02 EN
VACUTAP VR I II III/VR I HD
25
3 Special designs
3 Special designs
3.1 Parallel bridges for parallel connections
Current division on the connection contacts of 2 tap selector planes only for
on-load tap-changers VACUTAP VR I 1001 [ 95], VACUTAP VR I
1601 [ 111] and of 3 tap selector planes only for on-load tap-changers
VACUTAP VR I 1301 [ 95].
Parallel bridges on the tap selector connection contacts are then mandatory
if the tap winding has been wound in two or more branches and each of
these branch taps is connected to the contacts of the tap selector.
This measure reliably prevents the following:
26
VACUTAP VR I II III/VR I HD
2188029/02 EN
3 Special designs
Figure 10: On-load tap-changer combination VRC I 401 and VRC II 402 for delta connection
VRC I 401
VRC II 402
2188029/02 EN
VACUTAP VR I II III/VR I HD
27
4 Appendix
4 Appendix
4.1 VACUTAP VRC/VRE type overview (727017)
28
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
29
4 Appendix
30
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
31
4 Appendix
32
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
33
4 Appendix
34
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
35
4 Appendix
36
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
37
4 Appendix
38
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
39
4 Appendix
40
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
41
4 Appendix
42
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
43
4 Appendix
44
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
45
4 Appendix
46
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
47
4 Appendix
48
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
49
4 Appendix
50
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
51
4 Appendix
52
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
53
4 Appendix
54
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
55
4 Appendix
56
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
57
4 Appendix
58
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
59
4 Appendix
60
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
61
4 Appendix
62
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
63
4 Appendix
64
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
65
4 Appendix
66
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
67
4 Appendix
68
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
69
4 Appendix
70
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
71
4 Appendix
72
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
73
4 Appendix
74
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
75
4 Appendix
76
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
77
4 Appendix
78
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
79
4 Appendix
80
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
81
4 Appendix
82
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.35 VACUTAP VRC III 400/550/700 Y-10191W, detailed connection diagram (ZS030355)
2188029/02 EN
VACUTAP VR I II III/VR I HD
83
4 Appendix
4.36 VACUTAP VRE III 700 Y-10193W, detailed connection diagram (ZS030356)
84
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.37 VACUTAP VRD III 1300 Y-C/D-10191W, detailed connection diagram (ZS030201)
2188029/02 EN
VACUTAP VR I II III/VR I HD
85
4 Appendix
86
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
87
4 Appendix
88
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
89
4 Appendix
4.42 VACUTAP VRC/VRE, connecting leads 3W, 1G, 3G, dimensional drawing (723590)
90
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
91
4 Appendix
92
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.45 VACUTAP VR, special design for bell-type tank installation (720781)
2188029/02 EN
VACUTAP VR I II III/VR I HD
93
4 Appendix
4.46 VACUTAP VRC/VRE, arrangement of contacts on tap selector, tap selector division 1022 (899993)
94
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
95
4 Appendix
4.48 VACUTAP VR, installation position of tap selector connection contacts (727042)
96
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
97
4 Appendix
4.50 VACUTAP VRC III 400/550/700 Y, VRE III 700 Y, arrangement of tap selector (899994)
98
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
99
4 Appendix
4.52 VACUTAP VRC/VRE I 1001, VRC/VRE I HD 1001, arrangement of tap selector (899996)
100
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.53 VACUTAP VRC/VRE I 1301, VRC/VRE I HD 1301, arrangement of tap selector (727043)
2188029/02 EN
VACUTAP VR I II III/VR I HD
101
4 Appendix
102
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
103
4 Appendix
104
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
105
4 Appendix
4.58 VACUTAP VRC/VRE III, tie-in resistors with or without potential switch (899972)
106
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
107
4 Appendix
108
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
109
4 Appendix
110
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.63 VACUTAP VRF, bridges to parallel connection of tap selector connection contacts (786919)
2188029/02 EN
VACUTAP VR I II III/VR I HD
111
4 Appendix
4.64 VACUTAP VRG, bridges to parallel connection of tap selector connection contacts (786920)
112
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
113
4 Appendix
114
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
115
4 Appendix
116
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
117
4 Appendix
4.70 VACUTAP VRD/VRF III WP, tap selector size C/D, tie-in resistor cylinder and potential switch (899962)
118
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.71 VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in resistor cylinder (899964)
2188029/02 EN
VACUTAP VR I II III/VR I HD
119
4 Appendix
4.72 VACUTAP VRD/VRF I/III WS, VRD/VRF I HD WS, tap selector size C/D, potential switch (899966)
120
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.73 VACUTAP VRG I/III WS, VRG I HD WS, tap selector size E,
potential switch (899967)
2188029/02 EN
VACUTAP VR I II III/VR I HD
121
4 Appendix
122
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
123
4 Appendix
124
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
125
4 Appendix
126
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
2188029/02 EN
VACUTAP VR I II III/VR I HD
127
4 Appendix
4.80 VACUTAP VRD/VRF III WP, tap selector size C/D, tie-in resistor cylinder and potential switch (899963)
128
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.81 VACUTAP VRD/VRF III WR, tap selector size C/D, tie-in resistor cylinder and potential switch (899965)
2188029/02 EN
VACUTAP VR I II III/VR I HD
129
4 Appendix
4.82 VACUTAP VRF II 1302 WP, tap selector size C/D, tie-in resistor cylinder (728691)
130
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.83 VACUTAP VRF II 1302 WR, tap selector size C/D, tie-in resistor cylinder (728690)
2188029/02 EN
VACUTAP VR I II III/VR I HD
131
4 Appendix
4.84 VACUTAP VRF I 2602 WP, tap selector size C/D, tie-in resistor cylinder (729538)
132
VACUTAP VR I II III/VR I HD
2188029/02 EN
4 Appendix
4.85 VACUTAP VRF I 2602 WR, tap selector size C/D, tie-in resistor cylinder (729537)
2188029/02 EN
VACUTAP VR I II III/VR I HD
133
MR worldwide
Australia
Reinhausen Australia Pty. Ltd.
17/20-22 St Albans Road
Kingsgrove NSW 2208
Phone: +61 2 9502 2202
Fax: +61 2 9502 2224
E-Mail: sales@au.reinhausen.com
Brazil
MR do Brasil Indstria Mecnica Ltda.
Av. Elias Yazbek, 465
CEP: 06803-000
Embu - So Paulo
Phone: +55 11 4785 2150
Fax: +55 11 4785 2185
E-Mail: vendas@reinhausen.com.br
Canada
Reinhausen Canada Inc.
3755, rue Java, Suite 180
Brossard, Qubec J4Y 0E4
Phone: +1 514 370 5377
Fax: +1 450 659 3092
E-Mail: m.foata@ca.reinhausen.com
India
Easun-MR Tap Changers Ltd.
612, CTH Road
Tiruninravur, Chennai 602 024
Phone: +91 44 26300883
Fax: +91 44 26390881
E-Mail: easunmr@vsnl.com
Indonesia
Pt. Reinhausen Indonesia
German Center, Suite 6310,
Jl. Kapt. Subijanto Dj.
BSD City, Tangerang
Phone: +62 21 5315-3183
Fax: +62 21 5315-3184
E-Mail: c.haering@id.reinhausen.com
Iran
Iran Transfo After Sales Services Co.
Zanjan, Industrial Township No. 1 (Aliabad)
Corner of Morad Str.
Postal Code 4533144551
E-Mail: itass@iran-transfo.com
Italy
Reinhausen Italia S.r.l.
Via Alserio, 16
20159 Milano
Phone: +39 02 6943471
Fax: +39 02 69434766
E-Mail: sales@it.reinhausen.com
Japan
MR Japan Corporation
German Industry Park
1-18-2 Hakusan, Midori-ku
Yokohama 226-0006
Phone: +81 45 929 5728
Fax: +81 45 929 5741
Malaysia
Reinhausen Asia-Pacific Sdn. Bhd
Level 11 Chulan Tower
No. 3 Jalan Conlay
50450 Kuala Lumpur
Phone: +60 3 2142 6481
Fax: +60 3 2142 6422
E-Mail: mr_rap@my.reinhausen.com
P.R.C. (China)
MR China Ltd. (MRT)
360
4 E
200120
86 21 61634588
86 21 61634582
mr-sales@cn.reinhausen.com
mr-service@cn.reinhausen.com
Russian Federation
OOO MR
Naberezhnaya Akademika Tupoleva
15, Bld. 2 ("Tupolev Plaza")
105005 Moscow
Phone: +7 495 980 89 67
Fax: +7 495 980 89 67
E-Mail: mrr@reinhausen.ru
South Africa
Reinhausen South Africa (Pty) Ltd.
No. 15, Third Street, Booysens Reserve
Johannesburg
Phone: +27 11 8352077
Fax: +27 11 8353806
E-Mail: support@za.reinhausen.com
South Korea
Reinhausen Korea Ltd.
21st floor, Standard Chartered Bank Bldg.,
47, Chongro, Chongro-gu,
Seoul 110-702
Phone: +82 2 767 4909
Fax: +82 2 736 0049
E-Mail: you-mi.jang@kr.reinhausen.com
U.S.A.
Reinhausen Manufacturing Inc.
2549 North 9th Avenue
Humboldt, TN 38343
Phone: +1 731 784 7681
Fax: +1 731 784 7682
E-Mail: sales@reinhausen.com
United Arab Emirates
Reinhausen Middle East FZE
Dubai Airport Freezone, Building Phase 6
3rd floor, Office No. 6EB, 341 Dubai
Phone: +971 4 2368 451
Fax: +971 4 2368 225
Email: service@ae.reinhausen.com
Luxembourg
Reinhausen Luxembourg S.A.
72, Rue de Prs
L-7333 Steinsel
Phone: +352 27 3347 1
Fax: +352 27 3347 99
E-Mail: sales@lu.reinhausen.com
www.reinhausen.com