MEDIUM VOLTAGE SUBSTATION

1. SESCO MV PANEL
MV switch panel shall be of the indoor type as per WAPDA Standard P44:76 and IEC recommendations (and as per WAPDA single Line
Drawing No. PDW/TE-581).
1- 630 A TP Vacuum/SF-6 circuit Breaker, Manually, operated, rated 11
KV, and Bil 95 KV.
25 KA RC.
1- IDMT Relay, AC operated
5- High Tension Voltage CTs Class 0.5, with metering and Protection
cores/windings single ratio as mentioned in BOQ.
1- Ammeter (144mm x 144mm) scaled 0-15KV, with selector switch.
1-Three pole PT , (Class 0.5) rated 11/110KV.
1- Voltmeter (144mm x 144mm) scaled 0-15KV, with selector switch.
1-KWh meter, class 1.0, with maximum demand indicator to WAPDA
specification P- 42 & P-43.
1- Kvarh meter, class 3.0, to WAPDA specification P- 97.
1- Cable termination pad.
The panel and energy meters shall be as approved by SESCO /WAPDA
as suitable for incoming
and metering purpose.
Consumers MV Panel
MV switch panel shall be of the indoor type floor mounting free
standing of 3mm steel sheet de-rusted,
Degreased, primed with two coats of zinc-chromate and painted with
two coasts of enamel, in a drought
Trolley design. All control wiring and terminals shall be provided with
numbered ferrules.
1-630 amp TP vacuum / SF-6 circuit breaker, manually operated, rated
11kV, 75kV bil, and 20 kA rupturing

Capacity with, series trips (2 x 2.5A, 1 x 0.5A) and /or shunt trip
(110V) with capacity unit.
1- Set of isolating contacts , safety shutters with padlocks , cable
glands for incoming / outgoing cables insulated copper bus bars,
safety interlocks, facility for padlock in the OFF position , 3-phase
mettle oxide surge arrestors etc.
1-

Medium voltage CT, with protection (Class 5), core / winding ,


rates 100/ 5A, with appropriate VA and saturation
Factors short time and dynamic rating.
1- Microprocessor based I.D.M.T. relay, to BS 142 , series or shunt
tripping , with two over- current (2.5 10A) and one earth fault
(.5- 2A) elements , and three high set instantaneous elements
(20-80A) with required auxiliary /dc / control power supply.
1- Bucholz / temp alarm / trip circuit, with alarm hooter (90 dBA)
1- Ammeter (96mm) scaled 0-25/30, with selector switch.

1-

Medium voltage CT, with metering (Class 0.5), and protection


(Class 5), core / windings , rates 100/ 5/5A, with appropriate VA
and saturation factors ,short time and dynamic ratings

1-Double pole PT, (Class 0.5) rated 11/110KV with MV& LIVE control
fuses, appropriate VA (min 180VA).
1- Voltmeter (96mm) scaled 0-15KV, with selector switch.
1- Digital energy analyser for 3-phase measurement of KWhr, Kvarh,
MDI, V, A, PF.
.
1- Set of indicating lamps ON / OFF.
1- Cable box for 95mm2 LOPE Cables (from top).

MEDIUM VOLTAGE SUBSTATION


1. SESCO MV PANEL

MV switch panel shall be of the indoor type as per WAPDA Standard P44:76 and IEC recommendations (and as per WAPDA single Line
Drawing No. PDW/TE-581).
1- 630 A TP Vacuum/SF-6 circuit Breaker, Manually, operated, rated 11
KV, and Bil 95 KV.
25 KA RC.
1- IDMT Relay, AC operated
5- High Tension Voltage CTs Class 0.5, with metering and Protection
cores/windings single ratio as mentioned in BOQ.
1- Ammeter (144mm x 144mm) scaled 0-15KV, with selector switch.
1-Three pole PT, (Class 0.5) rated 11/110KV.
1- Voltmeter (144mm x 144mm) scaled 0-15KV, with selector switch.
1-KWh meter, class 1.0, with maximum demand indicator to WAPDA
specification P- 42 & P-43.
2- Kvarh meter , class 3.0, to WAPDA specification P- 97.
2- Cable termination pad.
The panel and energy meters shall be as approved by SESCO /WAPDA
as suitable for incoming
and metering purpose.
Consumers MV Panel
MV switch panel shall be of the indoor type floor mounting free
standing of 3mm steel sheet de-rusted,
Degreased, primed with two coats of zinc-chromate and painted with
two coasts of enamel, in a drought
Trolley design. All control wiring and terminals shall be provided with
numbered ferrules.
1-630 amp TP vacuum / SF-6 circuit breaker, manually operated, rated
11kV, 75kV bil, and 20 kA rupturing
Capacity with, series trips (2 x 2.5A, 1 x 0.5A) and /or shunt trip
(110V) with capacity unit.
2- Set of isolating contacts , safety shutters with padlocks , cable
glands for incoming / outgoing cables insulated copper bus bars,

safety interlocks, facility for padlock in the OFF position , 3-phase


mettle oxide surge arrestors etc.
2-

Medium voltage CT, with protection (Class 5), core / winding ,


rates 100/ 5A, with appropriate VA and saturation
Factors short time and dynamic rating.
2- Microprocessor based I.D.M.T. relay, to BS 142 , series or shunt
tripping , with two over- current (2.5 10A) and one earth fault
(.5- 2A) elements , and three high set instantaneous elements
(20-80A) with required auxiliary /dc / control power supply.
2- Bucholz / temp alarm / trip circuit, with alarm hooter (90 dBA)
2- Ammeter (96mm) scaled 0-25/30, with selector switch.

3-

Medium voltage CT, with metering (Class 0.5), and protection


(Class 5), core / windings , rates 100/ 5/5A, with appropriate VA
and saturation factors ,short time and dynamic ratings

1-Double pole PT, (Class 0.5) rated 11/110KV with MV& LV control
fuses, appropriate VA (min 180VA).
1- Voltmeter (96mm) scaled 0-15KV, with selector switch.
1- Digital energy analyser for 3-phase measurement of KWhr, Kvarh,
MDI, V, A, PF.
.
1- Set of indicating lamps ON / OFF.
2- Cable box for 95mm2 XLPE Cables (from top).