Documente Academic
Documente Profesional
Documente Cultură
I. INTRODUCTION
This paper investigates and discusses the arc-flash hazard
in a Wind Power Plant (WPP) collector system. It will define
an arc-flash calculation methodology for multiple sources and
provide two examples of the methodology.
The approach this paper will be as follows: Section II discusses the arc-flash hazard in general the causes of arcs, the
available models to calculate incident energy levels and certain concerns, which are specific to wind power plants. Section III describes the possible mitigation strategies defining
an arc-flash protection boundary, the types of personal protective equipment (PPE) available, and possible means of reducing incident energy levels through various technologies. Section IV presents a detailed, structured method to calculate arcflash incident energy levels in a WPP. Section V concludes
the paper with two examples.
II. ARC-FLASH HAZARD
A. General Description of Arc-flash Hazard
An electric arc is the result of the electrical breakdown of
an insulator (typically air) resulting in current flowing through
the insulator. An arc-flash fault is often caused by:
Human mistake (e.g., dropping a tool, accidental contact with live parts)
Environment (e.g., contamination, water vapor)
Equipment failure (e.g., insufficient insulation, deteriorated insulation, corrosion)
Overvoltage conditions
A combination of the above.
In power systems the path of the arc can be between two
phases, multiple phases, single phase and ground, and multiple
phases and ground. The arc flash is surrounded by a conductive plasma cloud and often vaporized conductive material,
which increases the likelihood of a single-phase fault making
contact with nearby phases and escalating into a three-phase
fault. This is more likely to happen on systems with low insulation level and at locations with small clearance between
conductors, such as low-voltage systems and switchgear
equipment. For these cases a single-phase fault often escalates
into a three-phase fault within a few milliseconds (Schau and
Stade, 1995).
A large amount of energy is released during an arc flash,
primarily in the form of heat. The burn hazard during an arc
flash is the main concern for worker safety (e.g. Lee, 1982).
Additionally, the energy released in the form of pressure is of
concern for worker safety since the pressure wave can directly
injure the worker or can destroy objects resulting in shrapnel
that can injure the worker (Lee, 1987). The part of the arc
flash that is associated with the release of a pressure wave is
commonly referred to as the arc blast (Dugan, 2007).
The arc-flash fault current is generally smaller than the
bolted fault current of the system due to the impedance of the
arc. The incident energy is the energy impressed on a surface
at a certain distance from the arc and is used as a measure to
quantify the burn hazard from an arc-flash.
Arc-flash energy is transferred to the surroundings by conduction, convection, and radiation energies (Wilkins et al.,
2004). For enclosed equipment, a substantial part of the
arc-flash energy is also converted to pressure. Figure 1 illustrates the energy dissipation for open-space and enclosedspace configuration. For arcs in open spaces, the geometry of
the energy emission is spherical and consequently the fraction
of the total arc energy that is emitted as radiant energy is proportional to 1/D2. On the other hand, there is a focusing effect
for the enclosed-space configuration, which increases the
energy emitted in the direction of the opening. Consequently,
the radiation emitted from the box is less divergent than for
the spherical geometry resulting in a distance relationship of
1/Dx with the distance exponential x being smaller than 2.
B. Arc-Flash Models
Arc-flash models estimate the incident heat energies a person near an arc fault is exposed to. The incident energy levels
calculated in an arc-flash hazard analysis determines arc-flash
hazard categories, which in turn guide the decision regarding
the appropriate Personal Protective Equipment (PPE) for a
person that works near energized equipment. The calculated
incident energies are vastly model dependent (e.g., Ammerman et al., 2008) and there is currently no consensus on which
model to employ in an arc-flash hazard analysis.
Models that are based on empirical data include the IEEE
1584 model for system voltages below 15 kV, the Doughty
model, sometimes referred to the NFPA 70E model, (Doughty
et al., 2000), and the Wilkins model (Wilkins et al., 2005).
The IEEE 1584 and Doughty models are purely empirical
while the Wilkins model is based both on empirical data and
circuit theory making it a semi-empirical or behavioral model.
In general, empirical and semi-empirical models are fitted to
test data and consequently are only applicable for the tested
range of the relevant parameters and for conditions that resemble the test conditions.
Models that are based on theory include the Duke Power
model, which is available in the public domain, the commercially available ARCPRO model, and models that are based on
theory published by Lee (1982). The Duke Power model and
the ARCPRO models are the models integrated into the Heat
Flux calculator software and the ARCPRO software, respectively. The models were developed for single-phase arc faults
in open air. The single-phase, open-air incident energies can
be converted to incident energies during three-phase faults and
Category
Energy
Level
(cal/cm2)
<1.2
1.2-4
4-8
8-25
25-40
Protective Clothing/PPE
Long-sleeve shirt and long pants
composed of non-melting or untreated natural fiber, safety glasses
FR long-sleeve shirt, FR pants, hard
hat, safety glasses
Category 1 protection + arc-rated
face shield, hearing protection,
leather gloves, leather work shoes
Category 2 protection + FR coverall, FR hard hat liner, flash suit
hood
Category 3 protection + flash suit
jacket, flash suit pants
1) Protection Devices
Protection devices, such as Overcurrent Protection Devices
(OCPDs) are used for fault clearing. OCPDs and other protection devices are:
Fuses: Fuses are reliable OCPDs which do not require periodic maintenance. A Fuse clears a permanent fault by removing the faulted segment from the circuit. The fusible element is heated and melted by the overcurrent. The behavior of
the fuse is characterized by a time-current plot, which shows
two curves (1) the minimum melting curve and (2) the total
clearing curve. The minimum melting curve gives the melting
time of the fusible element for any given current. After the
fusible element melts, the circuit is not immediately interrupted due to arcing between the fuse terminals. The sum of
maximum melting time and the duration the fuse arc is sus-
tained (i.e., the fuse arcing time) represents the total clearing
time. The fuse clearing time increases with decreasing current
magnitude and consequently arc flashes during low-current
faults may have larger energies than arc flashes during highcurrent faults.
Figure 2: Person wearing an arc-flash hazard suit during the installation of power quality equipment at an energized wind turbine
(photograph by Gene Porter).
Circuit Breakers: Circuit breakers are mechanically- driven interrupting devices which are capable of breaking and
possibly reclosing on a faulted and non-faulted circuit. The
primary task of the circuit breaker is to extinguish the arc that
develops when the breaker contacts separate. Depending on
the type of breaker, the arc is extinguished in air, oil, vacuum,
or SF6 gas. Reclosers are circuit breakers with a mechanism
that automatically closes the breaker after it has opened due to
a fault to avoid unnecessary system outages caused by temporary faults. However, in wind power plants there are no locations where any reclosing operations are to be used. It is dangerous and damaging to equipment to reclose, since synchronization will be lost during the interruption between the source
and the multiple generation sites and synchronization is lost
when any break in connection occurs. Normal restart procedures must then be followed to bring back affected WTGs and
circuits.
Protective Relays: A relay calculates the operating conditions on an electrical circuit and trips the circuit breaker when
a fault is detected. During a fault the primary relay operates
first. If available a backup relay will operate if the primary
relay fails to operate as desired.
Protective relays may be either overcurrent or differential.
Overcurrent relays trip if they sense that the current levels are
too high.
Differential relays work in a group and calculate the difference between the input and output currents. By Kirchoffs
Current Law, both the sum of input currents and the sum of
output currents must be equal. A difference would imply that
a fault has occurred within the differential relay groups zone
of protection, causing all of them to respond instantaneously.
On the substation bus of the WPP, the differentials relays will
provide the fastest clearing of an arc fault and thus the smallest arc-flash duration and incident energy.
A. Introduction
This section will present a structured method for performing an arc-flash hazard study in a WPPs collector system.
IEEE 1584-2002/2004a is referenced in this section and the
reader is encouraged to study the IEEE 1584 standard for
greater understanding of arc-flash incident energy calculations.
Many different equipment setups exist in WTGs. Equipment locations may play a significant role in the overall harm
of the arc-flash incident. Some common layouts of wind turbines are shown in Figure 3. For instance, if an arc occurs
while a worker is at a piece of equipment outside the wind
turbine, he will be able to quickly escape and limit his exposure to an arc and its harmful products. On the other hand, if a
worker is at the same type of equipment inside the tower or
nacelle, which has a confining workspace the harm will likely
be greater. See Section IIC.
For this paper, the WTG equipment setup on the extreme
left in Figure 3 and shown as a block diagram in Figure 4 will
be the one exemplified here. In this setup, the wind turbine
tower base contains the low-voltage power system control
equipment and the step-up transformer is located just outside
the tower. The scope of this paper will range from the
low-voltage circuit breaker (LVCB) to the medium-voltage
circuit breaker (MVCB) at the substation.
Figure 3: Various wind turbine generic layouts with possible fault locations.
Generator
Low-Voltage
Circuit Breaker
Step Up
Transformer
Medium Voltage
Circuit Breaker
(MVCB)
Low Voltage
(LV) equipment located
in or near the
wind turbine
tower
The dynamics of the generators behavior creates asynchronous fault values and how that impacts quantification of
an arc-flash energy and on the response of the LVCB and its
trip logic is beyond the scope of this paper, which is focusing
on the collector system. Instead, a constant conservative fault
current from the WTG is assumed for the examples in Section
V.
B. Short-Circuit Study
1) Collect the system and installation data
It is imperative that the component data used for the
short-circuit study be accurate. The study must consider all
sources (e.g. utilities, generators, and motors) as well as the
impedances of the connecting system, transformers, and
cables. A single-line diagram is essential in finding the available fault currents at each WTG site and the WPP substation
bus.
2) Calculate arcing fault currents
Bolted fault currents can be calculated using any commercially available power engineering software that is capable of performing a short-circuit analysis. The reader must consider all
possible scenarios during operation and then utilize the component data, along with the single-line diagram to obtain the
bolted fault current at each piece of equipment. Also all three
initial short-circuit conditions must be calculated, which are
commonly called: momentary, interrupting, and time-delayed
(or steady-state). For the example below the momentary will
be estimated at five time steady-state and interrupting will be
estimated at three times the steady-state.
2) Determine and/or establish the parameters and assumptions at each location, such as open air or cabinet situation,
likely working distance and arc gap distance. Use actual values for the distances or typical values from IEEE 1584.
The next three steps will be iterated at each selected fault
location based on how the multiple sources of fault current
contribute to the total fault current at that location through
time. The only step that may be skipped may be step 3, which
is the need to rerun the fault calculation after each device
clears. Engineering judgment regarding the impact on values
after each loop may be small enough to allow working only
with each of the separate fault flows that would be contributing to the event. The initial fault calculation run may be adequate.
3) Perform a short circuit fault calculation run on a particular location to obtain its fault flows for the momentary, interrupting, and steady-state conditions from all sources and determine how much is flowing through the protecting devices to
the fault location.
4) Determine the total clearing times for all the protecting
devices that are allowing fault flow to the fault location, such
as:
a) At the collector feeder breaker relay use the TCC curve
and find the respective time for the fault flow passing through
it (taking into account a faster trip of the breaker due to a
higher momentary current) from the substation and external
power system, or
b) In the LV secondary cabinet of a wind turbine step-up
transformer use the transformer fuses, the LVCB TCC, or the
control logic to the LVCB to estimate the time depending on
the fault flow direction use either the transformer fuses or
the control logic to trip and clear the LVCB to estimate the
time.
5) Determine the amount of incident energy occurring at
this location by using an arc-flash model (such as the IEEE
1584 model, the ARCPRO model, or another model) with all
the respective contributing fault current sources (step 3) and
the clearing time of the next fastest clearing device (step 4).
For instance:
a) At a 34.5kV substation collector feeder exit - use
ARCPRO with the parameters from step 2, such as the openair three-phase case at 15-inch working distance and a 6-inch
arc gap (NESC Table 410-1), or
b) in a 600V secondary cabinet of a step-up transformer
use IEEE 1584 with the parameters from step 2, such as the
under-1000V and in-a-box options that will provide a 24-inch
working distance and an 1.25-inch arc gap (IEEE 1584 Tables
2 and 3).
6) Loop steps 3 though 5 for each successively slower protecting device as it removes its respective amount of contributing fault flow from this location from the quickest device to
slowest device, until all the fault flow is eliminated.
7) Sum the arc-flash incident energy from each of the successively passes for this location. This sum will be the total
incident energy for this location.
8) Finally, repeat the steps 3 through 7 for all selected locations.
V. EXAMPLES
Example 1 A fault and arc-flash occur at a 34.5kV
MVCB breaker exit on the collector-side of a collector feeder
with two turbines generating at an LV of 600V. Each WTG is
rated 2 MW, uses a 2500 kVA step-up transformer, and has a
rated current of about 33A at 34.5 kV. See Figure 5.
SYSTEM
Wind Turbine 1
Wind Turbine 2
HV
Collector
Sub
Crow Bar
WT Tower
Top
Crow Bar
WT Tower
Top
Sub Transf
WT Tower
Middle
Flow 1
LV CB
MV CB
WT Tower
Middle
WT Tower
Base
LVCB
LV
WT Tower
Base
LV
MV
WT Transf
Flow 2
C.L. Fuse
Outside
Tower
Step-up
Transformer
Tank
WT Transf
C.L. Fuse
Exp. Fuse
Outside
Tower
Step-up
Transformer
Tank
Exp. Fuse
MV
Fault
Current
at the
Site of
the Arcflash
Event
Since the fault currents are much higher on the 600 V side, the
arc-flash values are certain to be larger as well.
Assuming the MVCB feeder relay, the transformer fuses
and the LVCB are all coordinated, then the sequence of clearing can be determined from the TCC plot that was used in
their coordination. That coordination would have the transformer fuses clearing before the feeder breaker to keep the
feeder energized while the generator is taken off-line. Therefore the clearing sequence for this location will be between the
LVCB and the fuses, with the fuses generally taking the longer
time and the LVCB tripping first to clear the local generator.
The LVCBs clearing time will be defined the same way here
as it was in the first example by the LVRT with a total time of
0.35 seconds. The clearing time will be shorter if the overcurrent mechanism responds before the LVRT trip.
0.10 sec
5kA
7.8 cal/cm
0.25 sec
0.6 cal/cm
0.21kA
0.0
0.10
0.35
Time Duration of Arc-flash (sec)
Example 2 Using the same WPP setup, the fault and arcflash now occurs in the LV (600 V) cabinet of the first wind
turbine step-up transformer. See Figure 7.
At this location there are also three sources, but two fault
flows. One flow is from the generator associated with this
transformer (Flow 3), and the other is from the collector feeder
(Flow 4), which represents the contributions from the other
turbine, the substation and the external power system. Since
this location is in a cabinet (a.k.a. in-a-box) and is on the lowvoltage side, the assumptions and equations from IEEE 1584
empirically will be the best choice and will provide a good
baseline. Therefore, the working distance, gap size, and default values will come from their respective tables in the IEEE
1584 document. Because this fault is at 600 V, the Ampere
level of the fault flows (Flows 3 and 4) will be much higher
compared to a similar power level on the 34.5-kV system.
8
[8]
[9]
2
45kA
Fault
Current
at the
Site of
the Arcflash
Event
35kA
0.20 sec
[11]
[12]
23.6 cal/cm
[10]
10.6 cal/cm
[13]
[14]
0.0
0.35
0.55
VI. CONCLUSION
This paper has investigated and discussed the arc-flash hazard on a WPP collector system. A brief discussion of the arcflash hazard and its causes were presented along with a methodology and two examples for tallying the total incident
energy from multiple sources.
The use of the various conditions of fault current in the methodology, are presented as a conservative measure for estimating the arc-flash incident energy, but it must be understood
that the real behavior of the fault current from the WTG is
very unpredictable and situation dependent. From these two
brief examples it can be seen that one of the highest levels of
the arc-flash hazard in a WPP collector system can be on the
LV cable and inclusive cabinets between the LVCB and the
step-up transformer. However, these results could be very
different if another arc-flash calculator were used, such as the
IEEE 1584 theoretical model, which has a dependence on voltage.
VII. REFERENCES
[1]
[2]
[3]
[4]
[5]
[6]
[7]
Lee, R.H., The Other Electrical Hazard: Electric Arc Blast Burns,
IEEE Transactions on Industry Applications, Vol. 1A-18, No.3,
May/June 1982.
Lee, R.H., Pressures Developed by Arcs, IEEE Transactions on Industry Applications, Vol. 1A-23, No.4, July/August 1987.
Martin, L., J. Beattie, Arc Protection Recommendations for SaskPower
Transmission and Distribution,, TS&R Report Number 05-345, 2005.
Schau, H. and D. Stade, Requirements to be met by protection and
switching devices from the arcing protection point of view, 5th International Conference on Electric Fuses and their Application, September
1995.
Reilly, J.P., H. Antoni, M.A. Chilbert, Applied Biolectricity, ISBN
0387984070, Springer, 1998.
Wallace, K., L. Garrett, and S. Patel, Protective Grounding Methods
and Requirements on Distribution Line Wood Pole Construction, Proceedings of the 11th International Conference on Transmission & Distribution Construction, 15-19 October 2006.
Wilkins, R., M. Allison, and M. Lang, Improved Method for Arc-flash
Hazard Analysis, IEEE Industrial and Commercial Power Systems
Technical Conference, pp. 55-62, 2-6 May 2004.