Documente Academic
Documente Profesional
Documente Cultură
DC machines (i.e. DC generators or DC motors) can be classified on the basis of their excitation winding. Field
winding may be connected to armature winding (in series or parallel) or it may be separately excited. This
divides DC machines in two main types. You will understand further classification of DC machines from the
diagram below
DC MOTOR
Construction of a DC motor is same as that of a DC generator. A same DC machine can be used interchangeably, as a
motor or generator, at least theoretically.
Above diagram simplifies understanding the working principle of a DC motor. When armature windingsare
connected to supply current sets up in the winding, also field magnets are excited. In this case, current carrying
armature conductors experiences force due to the magnetic field, according to the principle stated above. Thus,
this force causes motor to run.
Back EMF
According to fundamental laws of nature, no energy conversion is possible until there is something to oppose
the conversion. In case of generators this opposition is provided by magnetic drag, but in case of motors there
is back emf. Back emf can be given by the emf equation of DC generator i.e.
When the armature of the motor is rotating, the conductors also are cutting the magnetic
flux lines, and hence according to the Faraday's law of electromagnetic induction, emf
induces in the armature conductors. And the direction of this induced emf is such that it
opposes armature current (Ia). The circuit diagram below illustrates the direction of the
back emf and armature current.
Back emf protect the armature from short circuit during running condition. If there was no back emf
during running condition, the armature will draw a very high current.
ii)
Back emf will help to produce required amount of torque according to increased or decreased external
load torque. If the external load torque on the motor is increased, speed of the motor will decrease.
Therefore, the back emf will also decrease ( Eb is directly proportional N). Hence, the armature
current increases thus producing more torque.
iii) In every energy conversion system, an opposing agent is necessary without which the system will not
be able to convert the energy. In DC motor the back emf plays the role of the opposing agent. Back
emf opposes the applied voltage so that the applied voltage V has to force the current through the
armature against the opposition of back emf. The electric work done in overcoming this opposition is
converted into mechanical energy in the form of mechanical rotation of the armature.
Referring to the diagram beside, we can see, that if E is the supply voltage, E b is the back emf produced and Ia, Ra are
the armature current and armature resistance respectively then thevoltage equation is given by,
But keeping in mind that our purpose is to derive the torque equation of dc motor we multiply both sides of
equation (2) by Ia.
Now Ia2.Ra is the power loss due to heating of the armature coil, and the true effective mechanical power that is
required to produce the desired torque of dc machine is given by,
Where, P is no of poles,
is flux per pole,
Z is no. of conductors,
A is no. of parallel paths,
and N is the speed of the D.C. motor.
The torque we so obtain, is known as the electromagnetic torque of dc motor, and subtracting the mechanical and
rotational losses from it we get the mechanical torque.
Therefore, Tm = Tg mechanical losses.
This is the torque equation of dc motor. It can be further simplified as:
Which is constant for a particular machine and therefore the torque of dc motor varies with only flux and
armature current Ia.
The Torque equation of a dc motor can also be explained considering the figure below.
Current / conductor Ic = Ia / A
Therefore, force per conductor = fc = BLIa/A
Now torque Tc = fc.r = BLIa.r/A
Which is constant for a particular machine and therefore the torque of dc motor varies with only flux and
armature current Ia.
Characteristics Of DC Motors
Generally, three characteristic curves are considered for DC motors which are, (i) Torque vs. armature
current (Ta - Ia), (ii) Speed vs. armature current and (iii) Speed vs. torque. These are explained below for
each type of DC motor. These characteristics are determined by keeping following two relations in mind.
Ta .Ia & N Eb/
hence the torque increases as the square of the armature current. Therefore, the Ta-Ia curve is parabola for
smaller values of Ia. After magnetic saturation of the field winding, flux is independent of armature current Ia.
Therefore, the torque varies proportional to Ia only, T Ia. Therefore, after magnetic saturation, Ta-Ia curve
becomes straight line. The shaft torque (Tsh) is less than armature torque (Ta) due to stray losses. In DC
series motors, (prior to magnetic saturation) torque increases as the square of armature current, these motors
are used where high starting torque is required.
(b) Differential compound motor. Since in differential field motors, series flux opposes shunt flux, the total
flux decreases with increase in load. Due to this, the speed remains almost constant or even it may increase
slightly with increase in load. Differential compound motors are not commonly use, but they find limited
applications in experimental and research work.
Ia = (E - Eb) / Ra
Now, when the motor is at rest, obviously, there is no back emf Eb, hence armature current will be high (20-30
times rated current) at starting. This excessive current will1. Blow out the fuses and may damage the armature winding and/or commutator brush arrangement.
2. Produce very high starting torque (as torque is directly proportional to armature current), and this high
starting toque will produce huge centrifugal force which may throw off the armature windings.
Thus, to avoid the above dangers while starting a DC motor, it is necessary to limit the starting current. For
that purpose, starters are used to start a DC motor. There are various starters like, 3 point starter, 4 point
starter, No load release coil starter, thyristor starter etc.
The concept behind every DC motor starter is, adding external resistance to the
armature winding at starting.
3 Point Starter
The
internal
wiring
of
a3
point
starter is
as
shown
in
the
figure.
When motor is to be started, the lever is turned gradually to the right. When lever
touches point 1, the field winding gets directly connected across the supply, and
the armature winding gets connected with resistances R1 to R5 in series. Hence at
starting full resistance is added in series with armature. Then as the lever is moved
further, the resistance is gradually is cut out from the armature circuit. Now, as the
lever reaches to position 6, all the resistance is cut out from the armature circuit and
armature gets directly connected across the supply. The electromagnet E (no
voltage coil) holds the lever at this position. This electromagnet releases the lever when there is no (or low)
supply voltage. When the motor is overloaded beyond a predefined value, overcurrent release electromagnet D
gets activated, which short circuits electromagnet E, and hence releases the lever and motor is turned off.
Eb = PNZ/60A
(where, P= no. of poles, =flux/pole, N=speed in rpm, Z=no. of armature conductors, A=parallel paths)
thus from above equations
N=
E 60A
/PZ
b
E
b/
thus, it shows speed is directly proportional to back emf and inversely proportional to the flux per pole.
Substitution the value of Eb
(V- IaRa )
= V- IaRa
In this method the, shunt filed is connected to a fixed exciting voltage, and
armature is supplied with different voltages. Voltage across armature is changed with the help of a suitable
switchgear. The speed is approximately proportional to the voltage across the armature.
B) Ward-Leonard System:
This system is used where very sensitive speed control of
motor is required (e.g electric excavators, elevators etc.) The
arrangement of this system is as required in the figure beside.
M2 is
the
motor
whose
speed
control
is
required.
divertor :
veritable
resistance
is
3. Series-Parallel Control
This system is widely used in electric traction, where two or more mechanically coupled series motors are
employed. For low speeds, motors are joined in series, and for higher speeds motors are joined in parallel.
When in series, the motors have the same current passing through them, although voltage across each motor
is divided. When in parallel, voltage across each motor is same although current gets divided.
2. 4 Point Starter:
The main difference between a 3 point starter and a 4 point starter is that the no voltage coil is not
connected in series with field coil. The field gets directly connected to the supply, as the lever moves touching
the brass arc. The no voltage coil (or Hold on coil) is connected with a current limiting resistance Rh. This
arrangement ensures that any change of current in the shunt field does not affect the current through hold on
coil at all. This means that electromagnet pull of the hold-on coil will always be sufficient so that the spring does
not
This
1.
unnecessarily
starter
is
used
restore
where
field
DC
the
current
is
lever
to
be
to
adjusted
series
the
by
means
off
of
motor
position.
field
rheostat.
starter:
Construction of DC series motor starters is very basic as shown in the figure. A start arm is simply
moved towards right to start the motor. Thus at first maximum resistance is connected in series with
the
armature
and
then
gradually
decreased
as
the
start
arm
moves
The no load release coil holds the start arm to the run position and leaves it at no load.
ELECTRICAL BRAKING
towards
right.
A running motor may be brought to rest quickly by either mechanical braking or electrical braking. The
mechanical breaking is applied by means of mechanical break shoes. Hence the smoothness of mechanical
breaking is dependent on the surface and physical condition of brakes. Smooth breaking of a motor can be
achieved
by electric
breaking.
Electric Breaking
The electric breaking of a DC motor is of three types, (i) Rheostatic or dynamic braking, (ii) Plugging or
reverse current braking and (iii) Regenerative breaking.
connected
across
the
armature.
In case of DC series motor, motor is disconnected from the supply and field connections are reversed and a
rheostat is connected in series. The field connections are reversed to make sure that the current through field
winding
(ii)
will
flow
Plugging
in
the
or
same
Reverse
direction
current
as
before.
breaking:
In this method, armature connections are reversed and hence motor tends to run in opposite direction. Due to
reversal of the armature terminals, applied voltage V and back emf Eb starts acting in the same direction and
hence the total armature current exceeds. To limit this armature current a variable resistor is connected across
the
armature.
This
is
similar
for
both
series
and
shunt
wound
methods.
Plugging gives greater breaking torque as compared to rheostatic breaking. This method is generally used in
controlling
(iii)
elevators,
machine
tools,
Regenerative
printing
presses
etc.
breaking:
Regenerative breaking is used where, load on the motor has very high inertia (e.g in electric trains). When
applied voltage to the motor is reduced to less than back emf Eb, obviously armature current Ia will get
reversed, and hence armature torque is reversed. Thus speed falls. As generated emf is greater than applied
voltage (machine is acting as a DC generator), power will be returned to the line, this action is called as
regeneration. Speed keeps falling, back emf Eb also falls until it becomes lower than applied voltage and
direction of armature current again becomes opposite to Eb.