Copyright 2010 AIA

MasterSpec Full Length


02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
This Product MasterSpec Section is licensed by ARCOM to ThyssenKrupp Elevator ("Licensee").
This Product MasterSpec Section modifies the original MasterSpec text.
Revisions made to the original MasterSpec text are made solely by the Licensee and are not endorsed by,
or representative of the opinions of, ARCOM or The American Institute of Architects (AIA). Neither AIA
nor ARCOM are liable in any way for such revisions or for the use of this Product MasterSpec Section by
any end user. A qualified design professional should review and edit the document to suit project
requirements.
For more information, contact ThyssenKrupp Elevator North American Sales and Service, ThyssenKrupp
Elevator, 2591 Dallas Parkway, Suite 600, Frisco, TX 75034; Phone: (800) 230-0303; Website:
www.thyssenkrupp.com; Email: sales@thyssenkrupp.com.
For information about MasterSpec contact ARCOM at (800) 424-5080 or visit www.MasterSpec.com.
SECTION 142400 - HYDRAULIC ELEVATORS
PART 1 - GENERAL
SCHEDULE 0 - RELATED DOCUMENTS
PRODUCT DATA SHEET 0 - Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
SCHEDULE 1 - SUMMARY
PRODUCT DATA SHEET 0 - Section includes hydraulic [passenger] [and] [service] elevators.
PRODUCT DATA SHEET 1 - Related Requirements:
1.1
1.2
1.3
1.4

Section 015000 "Temporary Facilities and Controls" for temporary use of elevators for
construction purposes.
Section 033000 "Cast-in-Place Concrete" for setting sleeves, inserts, and anchoring
devices in concrete.
Section 042000 "Unit Masonry" for setting sleeves, inserts, and anchoring devices in
masonry and for grouting elevator entrance frames installed in masonry walls.
Section 051200 "Structural Steel Framing" for the following:
A.
B.
C.
D.

1.5

Attachment plates, angle brackets, and other preparation of structural steel for
fastening guide-rail brackets.
Divider beams.
Hoist beams.
Structural-steel shapes for subsills that are part of steel frame.

Section 055000 "Metal Fabrications" for the following:

HYDRAULIC ELEVATORS

142400 - 1

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
A.
B.
C.
D.
E.
F.
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15

1.16

Attachment plates and angle brackets for supporting guide-rail brackets.


Divider beams.
Hoist beams.
Structural-steel shapes for subsills.
Pit ladders.
Cants in hoistways made from steel sheet.

Section 055213 "Pipe and Tube Railings" for railings between adjacent elevator pits.
Section 057000 "Decorative Metal" for combination hall push-button stations.
<Insert Section number>-<Insert Section title> for finish flooring in elevator cars.
Section 099113 "Exterior Painting" for field painting of hoistway entrance doors and
frames.
Section 099123 "Interior Painting" for field painting of hoistway entrance doors and
frames.
Section 102213 "Wire Mesh Partitions" for guards between adjacent elevator pits.
Section 142413 "Hydraulic Freight Elevators" for hydraulic elevators used primarily for
carrying freight and inaccessible to the general public.
Section 221429 "Sump Pumps" for sump pumps, sumps, and sump covers in elevator
pits.
Section 271500 "Communications Horizontal Cabling" for telephone service for
elevators.
[Section 283111 "Digital, Addressable Fire-Alarm System"] [Section 283112 "Zoned
(DC Loop) Fire-Alarm System"] for smoke detectors in elevator lobbies to initiate
emergency recall operation[ and heat detectors in shafts and machine rooms to
disconnect power from elevator equipment before sprinkler activation] and for
connection to elevator controllers.
Section 31200 "Earth Moving" for excavating well hole to accommodate cylinder
assembly.

SCHEDULE 2 - ALLOWANCES
PRODUCT DATA SHEET 0 - Elevator Car Allowances: Provide finished passenger[ and service]
elevator cars under the Elevator Car Allowance specified in Section 012100 "Allowances."
Allowance includes furnishing and installing the following:
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8

Car wall finishes including trim.


Car floor finishes.
Car ceiling finishes.
Car[ and hoistway] door finishes.
Car door sills.
Car light fixtures.
Handrails.
Cutouts and other provisions for installing elevator signal equipment in cars.

SCHEDULE 3 - UNIT PRICES


PRODUCT DATA SHEET 0 - Unit Prices: Rock excavation for cylinder well holes is paid for under
the unit price indicated in the Contract and as specified in Section 012200 "Unit Prices."

HYDRAULIC ELEVATORS

142400 - 2

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
SCHEDULE 4 - DEFINITIONS
PRODUCT DATA SHEET 0 - Definitions in ASME A17.1/CSA B44 apply to work of this Section.
PRODUCT DATA SHEET 1 - Service Elevator: A passenger elevator that is also used to carry freight.
SCHEDULE 5 - ACTION SUBMITTALS
PRODUCT DATA SHEET 0 - Product Data: Include capacities, sizes, performances, operations,
safety features, finishes, and similar information. Include product data for car enclosures,
hoistway entrances, and operation, control, and signal systems.
PRODUCT DATA SHEET 1 - Shop Drawings:
1.1
1.2
1.3

Include plans, elevations, sections, and large-scale details indicating service at each
landing, machine room layout, coordination with building structure, relationships with
other construction, and locations of equipment.
Include large-scale layout of car-control station[ and standby power operation control
panel].
Indicate maximum dynamic and static loads imposed on building structure at points of
support, and maximum and average power demands.

PRODUCT DATA SHEET 2 - Samples for Initial Selection: For finishes involving color selection.
PRODUCT DATA SHEET 3 - Samples for Verification: For exposed car, hoistway door and frame,
and signal equipment finishes; 3-inch- (75-mm-) square Samples of sheet materials; and trim.
SCHEDULE 6 - INFORMATIONAL SUBMITTALS
PRODUCT DATA SHEET 0 - Qualification Data: For Installer.
PRODUCT DATA SHEET 1 - Seismic Qualification Certificates:
accessories, and components, from manufacturer.
1.1
1.2
1.3

For

elevator

equipment,

Basis for Certification: Indicate whether withstand certification is based on actual test of
assembled components or on calculation.
Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate
and describe mounting and anchorage provisions.
Detailed description of equipment anchorage devices on which the certification is based
and their installation requirements.

PRODUCT DATA SHEET 2 - Manufacturer Certificates: Signed by elevator manufacturer certifying


that hoistway, pit, and machine room layout and dimensions, as shown on Drawings, and
electrical service[ including standby power generator], as shown and specified, are adequate
for elevator system being provided.
PRODUCT DATA SHEET 3 - Sample Warranty: For special warranty.

HYDRAULIC ELEVATORS

142400 - 3

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
SCHEDULE 7 - CLOSEOUT SUBMITTALS
PRODUCT DATA SHEET 0 - Operation and Maintenance Data:
emergency, operation, and maintenance manuals.
0.1

For elevators to include in

In addition to items specified in Section 017823 "Operation and Maintenance Data,"


include diagnostic and repair information available to manufacturer's and Installer's
maintenance personnel.

PRODUCT DATA SHEET 1 - Inspection and Acceptance Certificates and Operating Permits:
required by authorities having jurisdiction for normal, unrestricted elevator use.

As

PRODUCT DATA SHEET 2 - Continuing Maintenance Proposal: Submit a continuing maintenance


proposal from Installer to Owner, in the form of a standard [one-year] [two-year] [five-year]
<Insert agreement period> maintenance agreement, starting on date initial maintenance
service is concluded. State services, obligations, conditions, and terms for agreement period
and for future renewal options.
PRODUCT DATA SHEET 3 - Continuing Maintenance Proposal: Submit a continuing maintenance
proposal from Installer to Owner with terms, conditions, and obligations as set forth in, and in
same form as, "Draft of Elevator Maintenance Agreement" at end of this Section, starting on
date initial maintenance service is concluded.
SCHEDULE 8 - QUALITY ASSURANCE
PRODUCT DATA SHEET 0 - Installer Qualifications: Elevator manufacturer[ or an authorized
representative who is trained and approved by manufacturer].
SCHEDULE 9 - DELIVERY, STORAGE, AND HANDLING
PRODUCT DATA SHEET 0 - Deliver, store, and handle materials, components and equipment in
manufacturer's protective packaging. Store materials, components, and equipment off of
ground, under cover, and in a dry location.
SCHEDULE 10 - COORDINATION
PRODUCT DATA SHEET 0 - Coordinate installation of sleeves, block outs, elevator equipment with
integral anchors, and other items that are embedded in concrete or masonry for elevator
equipment. Furnish templates, sleeves, elevator equipment with integral anchors, and
installation instructions and deliver to Project site in time for installation.
PRODUCT DATA SHEET 1 - Furnish well casing and coordinate delivery with related excavation
work.
PRODUCT DATA SHEET 2 - Coordinate locations and dimensions of other work relating to hydraulic
elevators including pit ladders; sumps and floor drains in pits; entrance subsills; electrical
service; and electrical outlets, lights, and switches in hoistways, pits, and machine rooms.

HYDRAULIC ELEVATORS

142400 - 4

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
SCHEDULE 11 - WARRANTY
PRODUCT DATA SHEET 0 - Manufacturer's Special Warranty: Manufacturer agrees to repair,
restore, or replace elevator work that fails in materials or workmanship within specified
warranty period.
0.1

0.2

Failures include, but are not limited to, operation or control system failure, including
excessive malfunctions; performances below specified ratings; excessive wear; unusual
deterioration or aging of materials or finishes; unsafe conditions; need for excessive
maintenance; abnormal noise or vibration; and similar unusual, unexpected, and
unsatisfactory conditions.
Warranty Period: <Insert number> year(s) from date of Substantial Completion.

PART 2 - PRODUCTS
SCHEDULE 0 - MANUFACTURERS
PRODUCT DATA SHEET 0 - Basis-of-Design Product: Subject to compliance with requirements,
provide ThyssenKrupp Elevator or comparable product by one of the following:
0.1

<Insert manufacturer's name>.

0.2

Major elevator components, including pump-and-tank units, plunger-cylinder assemblies,


controllers, signal fixtures, door operators, car frames, cars, and entrances, shall be
manufactured by single manufacturer.

SCHEDULE 1 - PERFORMANCE REQUIREMENTS


PRODUCT DATA SHEET 0 - Regulatory Requirements: Comply with ASME A17.1/CSA B44.
PRODUCT DATA SHEET 1 - Accessibility Requirements: Comply with Section 407 in the U.S.
Architectural & Transportation Barriers Compliance Board's ADA-ABA Accessibility
Guidelines and with ICC A117.1.
PRODUCT DATA SHEET 2 - Seismic Performance: Elevator system shall withstand the effects of
earthquake motions determined according to [ASCE/SEI 7] <Insert requirement> and shall
comply with elevator safety requirements for seismic risk Zone 2 or greater in
ASME A17.1/CSA B44.
2.1
2.2
2.3
2.4

The term "withstand" means "the system will remain in place without separation of any
parts when subjected to the seismic forces specified[ and the system will be fully
operational after the seismic event]."
Affected peak velocity acceleration (Av) for Project's location is [less than 0.10 (seismic
risk Zones 0 and 1)] [greater than or equal to 0.10, but less than 0.20 (seismic risk
Zone 2)] [greater than or equal to 0.20 (seismic risk Zones 3 and 4)].
Provide earthquake equipment required by ASME A17.1/CSA B44.
Provide seismic switch required by ASCE/SEI 7.

HYDRAULIC ELEVATORS

142400 - 5

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
2.5
2.6
2.7

Design earthquake spectral response acceleration short period (Sds) for Project is <Insert
value>.
Project's Seismic Design Category: [A] [B] [C] [D] [E] [F].
Elevator Component Importance Factor: [1.5] [1.0].

SCHEDULE 2 - ELEVATORS
PRODUCT DATA SHEET 0 - Elevator System, General: Manufacturer's standard elevator systems.
Unless otherwise indicated, manufacturers' standard components shall be used, as included in
standard elevator systems and as required for complete system.
PRODUCT DATA SHEET 1 - Elevator Description:
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13

Group Number: <Insert a different number for each group of elevators that share a
group operation system>.
Elevator Number(s): <Insert elevator number(s) as shown on Drawings>.
Emergency Elevator Number(s): <Insert elevator number(s) as shown on Drawings>.
Service Elevator Number(s): <Insert elevator number(s) as shown on Drawings>.
Type: Under-the-car single cylinder.
Type: Holeless, beside-the-car, single-acting, [single] [dual] cylinder.
Type: Holeless, beside-the-car, telescoping, [single] [dual] cylinder.
Type: Holeless, beside-the-car, roped hydraulic, [single] [dual] cylinder.
Rated Load: [2100 lb (953 kg)] [2500 lb (1135 kg)] [3000 lb (1362 kg)] [3500 lb (1589
kg)] [4000 lb (1816 kg)] [4500 lb (2043 kg)] [5000 lb (2270 kg)] <Insert value>.
Freight Loading Class for Service Elevators: Class A.
Rated Speed: [75 or 80 fpm (0.38 or 0.41 m/s)] [100 fpm (0.51 m/s)] [125 fpm
(0.64 m/s)] [150 fpm (0.76 m/s)] [175 fpm (0.89 m/s)] [200 fpm (1.0 m/s)] <Insert
value>.
Operation System: [Single automatic] [Selective-collective automatic] [Group
automatic].
Auxiliary Operations:
A.
B.
C.
D.
E.
F.
G.
H.

Standby power operation.


Standby-powered lowering.
Battery-powered lowering.
Automatic dispatching of loaded car.
Nuisance call cancel.
[Emergency hospital] [Priority] service at [all] <Insert floor designations>
floors.
Independent service for [service elevator] [one car in group] [all cars in group].
Loaded-car bypass.

1.14 Security Features:


[Card-reader operation] [Keyswitch operation] [Keypad
operation] [Car-to-lobby feature].
1.15 Dual Car-Control Stations: Provide two car-control stations[ in each elevator]; equip
only one with required keyswitches, if any.
1.16 Car Enclosures:
A.

Inside Width: [68 inches (1727 mm)] [80 inches (2032 mm)] [92 inches (2337
mm)] <Insert dimension> from side wall to side wall.

HYDRAULIC ELEVATORS

142400 - 6

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
B.
C.
D.
E.
F.
G.
H.
I.
J.

K.

L.
M.
N.
O.
P.

Inside Depth: [51 inches (1295 mm)] [57 inches (1448 mm)] [65 inches (1651
mm)] [108 inches (2743 mm)] <Insert dimension> from back wall to front wall
(return panels).
Inside Height: [94 inches (2388 mm)] [100 inches (2540 mm)] [104 inches (2642
mm)] [108 inches (2743 mm)] [112 inches (2845 mm)] <Insert dimension> to
underside of ceiling.
Front Walls (Return Panels): [Polished stainless steel, No. 8 finish] [Satin
stainless steel, No. 4 finish] [Polished bronze, lacquered] [Satin bronze,
lacquered] with integral car door frames.
Car Fixtures: [Polished stainless steel, No. 8 finish] [Satin stainless steel, No. 4
finish] [Polished bronze, lacquered] [Satin bronze, lacquered].
Side and Rear Wall Panels: [Powder coated steel] [Plastic laminate] [Satin
stainless steel, No. 4 finish] [Textured stainless steel] [Satin bronze, lacquered].
Reveals: [Powder coated steel] [Polished stainless steel, No. 8 finish] [Satin
stainless steel, No. 4 finish] [Polished bronze, lacquered] [Satin bronze,
lacquered].
Door Faces (Interior): [Powder coated steel] [Primed steel] [Polished stainless
steel, No. 8 finish] [Satin stainless steel, No. 4 finish] [Textured stainless steel]
[Polished bronze, lacquered] [Satin bronze, lacquered] [Plastic laminate].
Door Sills: [Aluminum, mill finish] [Bronze] [Nickel silver].
Ceiling: [Luminous ceiling] [Polished stainless steel, No. 8 finish] [Satin
stainless steel, No. 4 finish] [Polished bronze, lacquered] [Reflective metallicfinish, plastic-laminate, stainless steel] [Reflective metallic-finish, plasticlaminate, bronze].
Handrails: [1-1/2 inches (38 mm) round] [1/2 by 2 inches (13 by 50 mm)
rectangular] <Insert dimension(s)> [mirror-polished stainless steel, No. 8
finish] [satin stainless steel, No. 4 finish] [mirror-polished bronze, lacquered]
[satin bronze, lacquered], at [sides] [and] [rear] of car.
Floor: Manufacturer's standard carpet.
Floor prepared to receive carpet (specified in Section 096816 "Sheet Carpeting").
Floor prepared to receive resilient flooring (specified in Section 096500 "Resilient
Flooring").
Floor recessed and prepared to receive [dimension stone tile (specified in
Section 093033 "Stone Tiling")] [ceramic tile (specified in Section 093000
"Tiling")].
Floor Thickness, Including Setting Materials: <Insert thickness> above plywood
subfloor.

1.17 Hoistway Entrances:


A.
B.
C.
D.
E.

Width: [36 inches (914 mm)] [42 inches (1067 mm)] [48 inches (1219 mm)] [54
inches (1372 mm)] <Insert dimension>.
Height: [84 inches (2134 mm)] [96 inches (2438 mm)] <Insert dimension>.
Type: [Single-speed side sliding] [Two-speed side sliding] [Single-speed center
opening] [Two-speed center opening].
Frames [at First Floor] [at Basement Floors]: [Powder coated steel] [Primed
steel] [Polished stainless steel, No. 8 finish] [Satin stainless steel, No. 4 finish]
[Polished bronze, lacquered] [Satin bronze, lacquered].
Frames at Other Floors: [Powder coated steel] [Primed steel] [Polished stainless
steel, No. 8 finish] [Satin stainless steel, No. 4 finish] [Polished bronze,
lacquered] [Satin bronze, lacquered].

HYDRAULIC ELEVATORS

142400 - 7

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
F.

G.

H.
I.

Doors[ and Transoms] [at First Floor] [at Basement Floors]: [Powder coated
steel] [Primed steel] [Polished stainless steel, No. 8 finish] [Satin stainless steel,
No. 4 finish] [Textured stainless steel] [Polished bronze, lacquered] [Satin
bronze, lacquered] [Plastic laminate].
Doors[ and Transoms] at Other Floors: [Powder coated steel] [Primed steel]
[Polished stainless steel, No. 8 finish] [Satin stainless steel, No. 4 finish]
[Textured stainless steel] [Polished bronze, lacquered] [Satin bronze,
lacquered] [Plastic laminate].
Sills [at First Floor] [at Basement Floors]: [Aluminum, mill finish] [Bronze,
polished] [Nickel silver, polished].
Sills at Other Floors: [Aluminum, mill finish] [Bronze, polished] [Nickel silver,
polished].

1.18 Hall Fixtures [at First Floor] [at Basement Floors]: [Polished stainless steel, No. 8
finish] [Satin stainless steel, No. 4 finish] [Polished bronze, lacquered] [Satin bronze,
lacquered] [Recessed type with no exposed-metal surfaces].
1.19 Hall Fixtures at Other Floors: [Polished stainless steel, No. 8 finish] [Satin stainless
steel, No. 4 finish] [Polished bronze, lacquered] [Satin bronze, lacquered] [Recessed
type with no exposed-metal surfaces].
1.20 Additional Requirements:
A.
B.

Provide inspection certificate in each car, mounted under acrylic cover with frame
made from [polished stainless steel, No. 8 finish] [satin stainless steel, No. 4
finish] [polished bronze, lacquered] [satin bronze, lacquered].
Provide hooks for protective pads[ in all cars] and [one] [two] <Insert number>
complete set(s) of full-height protective pads.

SCHEDULE 3 - SYSTEMS AND COMPONENTS


PRODUCT DATA SHEET 0 - Pump Units: Positive-displacement type with a maximum of 10
percent variation between no load and full load and with minimum pulsations.
0.1

0.2
0.3

Pump shall be [submersible type with submersible squirrel-cage induction motor,


and shall be suspended inside oil tank from vibration isolation mounts] [or] [shall be
tank-top-mounted type with fan-cooled, squirrel-cage induction motor, and shall be
mounted on oil tank with vibration isolation mounts and enclosed in prime-painted
steel enclosure lined with 1-inch- (25-mm-) thick, glass-fiber insulation board].
Motor shall have [wye-delta] [or] [solid-state] starting.
Motor shall have variable-voltage, variable-frequency control.

PRODUCT DATA SHEET 1 - Hydraulic Silencers: System shall have hydraulic silencer containing
pulsation-absorbing material in blowout-proof housing at pump unit.
PRODUCT DATA SHEET 2 - Piping: Size, type, and weight of piping as recommended by elevator
manufacturer, with flexible connectors to minimize sound and vibration transmissions from
power unit.
2.1

Cylinder units shall be connected with dielectric couplings.

HYDRAULIC ELEVATORS

142400 - 8

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
2.2

Casing for Underground Piping: Schedule 40 PVC pipe complying with ASTM D 1785,
joined with PVC fittings complying with ASTM D 2466 and solvent cement complying
with ASTM D 2564.

PRODUCT DATA SHEET 3 - Hydraulic Fluid: Elevator manufacturer's standard [fire-resistant ]fluid
with additives as needed to prevent oxidation of fluid, corrosion of cylinder and other
components, and other adverse effects.
PRODUCT DATA SHEET 4 - Hydraulic Fluid: Nontoxic, biodegradable[, fire-resistant] fluid made
from vegetable oil with antioxidant, anticorrosive, antifoaming, and metal-passivating additives
and approved by elevator manufacturer for use with elevator equipment.
4.1

Product: Subject to compliance with requirements, provide "Hydro Safe" by Hydro Safe
Oil Division, Inc.

PRODUCT DATA SHEET 5 - Inserts: Furnish required concrete and masonry inserts and similar
anchorage devices for installing guide rails, machinery, and other components of elevator work.
Device installation is specified in another Section.
PRODUCT DATA SHEET 6 - Protective Cylinder Casing: PVC or HDPE pipe casing complying with
ASME A17.1/CSA B44, of sufficient size to provide not less than 1-inch (25-mm) clearance
from cylinder and extending above pit floor. Casing shall have means of monitoring
effectiveness to comply with ASME A17.1/CSA B44.
PRODUCT DATA SHEET 7 - Corrosion-Protective Filler:
A nontoxic, petroleum-based gel
formulated for filling the space between hydraulic cylinder and protective casing. Filler shall be
electrically nonconductive, displace or absorb water, and gel or solidify at temperatures below
60 deg F (16 deg C).
7.1

Products: Subject to compliance with requirements, [provide the following] [provide


one of the following] [available products that may be incorporated into the Work
include, but are not limited to, the following]:
A.
B.
C.

Hydro Safe Oil Division, Inc.; No-Ox-Id Liquid Elevator Casing Filler E-800.
Union-Gard, a division of Dome Services L.L.C.; Union-Gard 160.
<Insert manufacturer's name; product name or designation>.

PRODUCT DATA SHEET 8 - Car Frame and Platform: Welded[ or bolted] steel units.
PRODUCT DATA SHEET 9 - Guides: Roller guides; polymer-coated, nonlubricated sliding guides;
or sliding guides with guide-rail lubricators. Provide guides at top and bottom of car and
counterweight frames.
SCHEDULE 4 - OPERATION SYSTEMS
PRODUCT DATA SHEET 0 - General: Provide manufacturer's standard microprocessor operation
system as required to provide type of operation indicated.
PRODUCT DATA SHEET 1 - Auxiliary Operations: In addition to primary operation system features,
provide the following operational features for elevators where indicated:
HYDRAULIC ELEVATORS

142400 - 9

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
1.1

Single-Car Standby Power Operation: On activation of standby power, car is returned to


a designated floor and parked with doors open. Car can be manually put in service on
standby power, either for return operation or for regular operation, by switches in control
panel located at [main lobby] [fire command station] <Insert location>. Manual
operation causes automatic operation to cease.
1.2 Single-Car Standby-Powered Lowering: On activation of standby power, if car is at a
floor, it remains at that floor, opens its doors, and shuts down. If car is between floors, it
is lowered to a preselected floor, opens its doors, and shuts down. If car is below the
preselected floor, it is lowered to the next lower floor, opens its doors, and shuts down.
1.3 Single-Car Standby-Powered Lowering: On activation of standby power, car is lowered
to the lowest floor, opens its doors, and shuts down.
1.4 Single-Car Battery-Powered Lowering: If power fails and car is at a floor, it remains at
that floor, opens its doors, and shuts down. If car is between floors, it is lowered to a
preselected floor, opens its doors, and shuts down. If car is below the preselected floor, it
is lowered to the next lower floor, opens its doors, and shuts down. System includes
rechargeable battery and automatic recharging system.
1.5 Single-Car Battery-Powered Lowering: When power fails, car is lowered to the lowest
floor, opens its doors, and shuts down. System includes rechargeable battery and
automatic recharging system.
1.6 Group Standby Power Operation: On activation of standby power, cars are returned to a
designated floor and parked with doors open. Only one car is moved upward at a time,
with priority given to loaded cars. If a car cannot be returned after two attempts, it is
removed from the system. When all cars have been returned or removed from the
system, one car is automatically placed in service. If car selected for service cannot
operate within 60 seconds, the system removes car from service and places another car in
service. Cars can be manually put in service on standby power, either for return
operation or for regular operation, by switches in control panel located at [ main lobby]
[fire command station] <Insert location>. Manual operation causes automatic
operation to cease.
1.7 Group Standby Power Operation: On activation of standby power, cars are returned to
lowest floor and parked with doors open. If a car cannot be returned, it is removed from
the system. One car is selected for service on standby power by a switch located at
[main lobby] [fire command station] <Insert location>.
1.8 Group Standby-Powered Lowering: On activation of standby power, cars that are at a
floor remain at that floor, open their doors, and shut down. Cars that are between floors
are lowered to a preselected floor, open their doors, and shut down. Cars that are below
the preselected floor are lowered to the next lower floor, open their doors, and shut down.
1.9 Group Standby-Powered Lowering: On activation of standby power, cars are lowered to
the lowest floor, open their doors, and shut down.
1.10 Group Battery-Powered Lowering: If power fails, cars that are at a floor remain at that
floor, open their doors, and shut down. Cars that are between floors are lowered to a
preselected floor, open their doors, and shut down. Cars that are below the preselected
floor are lowered to the next lower floor, open their doors, and shut down. System
includes rechargeable battery and automatic recharging system.
1.11 Group Battery-Powered Lowering: When power fails, cars are lowered to the lowest
floor, open their doors, and shut down. System includes rechargeable battery and
automatic recharging system.
1.12 Automatic Dispatching of Loaded Car: When car load exceeds 80 percent of rated
capacity, doors start closing.

HYDRAULIC ELEVATORS

142400 - 10

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
1.13 Nuisance Call Cancel: When car calls exceed a preset number while car load is less than
a predetermined weight, all car calls are canceled. Preset number of calls[ and
predetermined weight] can be adjusted.
1.14 Loaded-Car Bypass: When car load exceeds 80 percent of rated capacity, car responds
only to car calls, not to hall calls.
1.15 Independent Service: Keyswitch in car-control station removes car from group operation
and allows it to respond only to car calls. Key cannot be removed from keyswitch when
car is in independent service. When in independent service, doors close only in response
to door close button.
1.16 [Emergency Hospital] [Priority] Service: Service is initiated by a [keyswitch] [card
reader] [remote switch] at designated floors. One elevator is removed from group
operation and directed to the floor where service was initiated. On arriving at the floor,
elevator opens its doors and parks[ and a lighted sign directs passengers to exit
elevator]. Car is placed in operation by selecting a floor and pressing door close button
or by operating keyswitch to put car in independent service. After responding to floor
selected or being removed from independent service, car is returned to group operation.
If car is not placed in operation within a preset time after being called, it is returned to
group operation.
PRODUCT DATA SHEET 2 - Security Features: Provide the following security features, where
indicated. Security features shall not affect emergency firefighters' service.
2.1

Card-Reader Operation: System uses card readers at [car-control stations] [and] [hall
push-button stations] to authorize calls. Security system determines which landings and
at what times calls require authorization by card reader. Provide required conductors in
traveling cable and panel in machine room for interconnecting card readers, other
security access system equipment, and elevator controllers. [Allow space as indicated
for card reader in car] [Provide stripe-swipe card reader integral with each carcontrol station].
A.

2.2
2.3

Keyswitch Operation:
Push buttons are activated and deactivated by security
keyswitches at [car-control stations] [and] [hall push-button stations]. Key is
removable [only in deactivated position] [in either position].
Keypad Operation: Allows each landing to be restricted or unrestricted. When a
restricted landing button is pressed, a "Restricted Floor" lamp lights and remains lit until
landing access code has been entered into a keypad or predetermined time period has
elapsed. Car calls for restricted landings do not register until landing access code is
entered into keypad within predetermined time period after landing button is pressed.
A.

2.4

Security access system equipment is [specified in Section 281300 "Access


Control."] [not in the Contract.]

Access codes are programmed at each car operating panel using a security
keyswitch. Keypad operation can be activated and deactivated by security
keyswitch at main landing.

Car-to-Lobby Feature: Feature, activated by keyswitch at main lobby, that causes [ car]
[all cars in a group] to return immediately to lobby and open doors for inspection. All
calls are cancelled and need to be re-activated.

HYDRAULIC ELEVATORS

142400 - 11

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
SCHEDULE 5 - DOOR REOPENING DEVICES
PRODUCT DATA SHEET 0 - Infrared Array: Provide door reopening device with uniform array of
36 or more microprocessor-controlled, infrared light beams projecting across car entrance.
Interruption of one or more light beams shall cause doors to stop and reopen.
PRODUCT DATA SHEET 1 - Nudging Feature: After car doors are prevented from closing for
predetermined adjustable time, through activating door reopening device, a loud buzzer shall
sound and doors shall begin to close at reduced kinetic energy.
SCHEDULE 6 - CAR ENCLOSURES
PRODUCT DATA SHEET 0 - General: Provide [powder coated-steel car enclosures to receive
removable] [steel-framed car enclosures with nonremovable] wall panels, with
[removable ]car roof, access doors, power door operators, and ventilation.
0.1
0.2

Provide standard railings complying with ASME A17.1/CSA B44 on car tops where
required by ASME A17.1/CSA B44.
See "Allowances" Paragraph in "Summary" Article for items to be provided under the
Elevator Car Allowance. Provide items not included in the Elevator Car Allowance as
needed for finished car[ including materials and finishes specified below].

PRODUCT DATA SHEET 1 - Materials and Finishes: Manufacturer's standards, but not less than the
following:
1.1
1.2

Subfloor: Exterior grade plywood, not less than 7/8-inch (22.2-mm) nominal thickness.
Floor Finish: [Specified in <Insert Section number>-<Insert Section title>] [Elevator
manufacturer's standard level-loop nylon carpet; color as selected by Architect from
manufacturer's full range].
1.3 Powder coated-Steel Wall Panels: Flush, metal construction; fabricated from cold-rolled
steel sheet. Provide with factory-applied finish; colors as selected by Architect from
manufacturer's full range.
1.4 Stainless-Steel Wall Panels: Flush, metal construction; fabricated from stainless-steel
sheet.
1.5 Bronze Wall Panels: Flush, metal construction; fabricated from bronze sheet.
1.6 Plastic-Laminate Wall Panels: Plastic laminate adhesively applied to [1/2-inch (13-mm)
fire-retardant-treated particleboard] [manufacturer's standard core] with[ plasticlaminate panel backing and] manufacturer's standard protective edge trim. Panels have
a flame-spread index of [25] [75] or less, when tested according to ASTM E 84. Plasticlaminate color, texture, and pattern as selected by Architect from [plastic-laminate]
[elevator] manufacturer's full range.
1.7 Fabricate car with recesses and cutouts for signal equipment.
1.8 Fabricate car door frame integrally with front wall of car.
1.9 Powder coated-Steel Doors: Flush, metal construction; fabricated from cold-rolled steel
sheet. Provide with factory-applied enamel finish; colors as selected by Architect from
manufacturer's full range.
1.10 Primed-Steel Doors: Flush, metal construction; fabricated from cold-rolled steel sheet.
Provide with factory-applied, rust-resistant primer for field painting.
1.11 Stainless-Steel Doors: Flush, metal construction; fabricated [from stainless-steel sheet]
[or] [by laminating stainless-steel sheet to exposed faces and edges of powder coated
HYDRAULIC ELEVATORS

142400 - 12

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.

1.12
1.13

1.14
1.15
1.16
1.17
1.18
1.19

cold-rolled steel doors using adhesive that fully bonds metal to metal without
telegraphing or oil-canning].
Bronze Doors: Flush, metal construction; fabricated by laminating bronze sheet to
exposed faces and edges of powder coated cold-rolled steel doors using adhesive that
fully bonds metal to metal without telegraphing or oil-canning.
Plastic-Laminate Doors: Flush, metal construction; fabricated by laminating plastic
laminate to exposed faces of powder coated cold-rolled steel doors and covering edges
with protective edge trim[ matching return panels]. Plastic-laminate color, texture, and
pattern as selected by Architect from [plastic-laminate] [elevator] manufacturer's full
range.
Unfinished-Steel Doors: Flush, metal construction; fabricated from cold-rolled steel
sheet, with factory-applied powder coat.
Sight Guards: Provide sight guards on car doors.
Sills: Extruded metal, with grooved surface, 1/4 inch (6.4 mm) thick.
Luminous Ceiling: Fluorescent light fixtures and ceiling panels of translucent acrylic or
other permanent rigid plastic.
[Metal] [Metallic-Finish, Plastic-Laminate] Ceiling: Flush panels, with [incandescent
downlights in the center of] [four low-voltage downlights in] each panel.[ Align
ceiling panel joints with joints between wall panels.]
Handrails: Manufacturer's standard handrails, of shape, metal, and finish indicated.

SCHEDULE 7 - HOISTWAY ENTRANCES


PRODUCT DATA SHEET 0 - Hoistway Entrance Assemblies: Manufacturer's standard horizontalsliding, door-and-frame hoistway entrances complete with track systems, hardware, sills, and
accessories. Frame size and profile shall accommodate hoistway wall construction.
0.1

Where gypsum board wall construction is indicated, frames shall be self-supporting with
reinforced head sections.

PRODUCT DATA SHEET 1 - Fire-Rated Hoistway Entrance Assemblies: Door and frame assemblies
shall comply with NFPA 80 and be listed and labeled by a testing and inspecting agency
acceptable to authorities having jurisdiction based on testing at as close-to-neutral pressure as
possible according to [NFPA 252] [or] [UL 10B].
1.1

Fire-Protection Rating: [1 hour] [1-1/2 hours] <Insert rating>[ with 30-minute


temperature rise of 450 deg F (250 deg C)].

PRODUCT DATA SHEET 2 - Materials and Fabrication: Manufacturer's standards, but not less than
the following:
2.1
2.2
2.3
2.4

Powder coated-Steel Frames: Formed from cold- or hot-rolled steel sheet. Provide with
factory-applied enamel finish; colors as selected by Architect from manufacturer's full
range.
Primed-Steel Frames: Formed from cold- or hot-rolled steel sheet. Provide with factoryapplied, rust-resistant primer for field painting.
Steel Subframes: Formed from cold- or hot-rolled steel sheet, with factory-applied
enamel finish or rust-resistant primer. Fabricate to receive applied finish as indicated.
Stainless-Steel Frames: Formed from stainless-steel sheet.

HYDRAULIC ELEVATORS

142400 - 13

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
2.5
2.6
2.7
2.8
2.9

2.10
2.11

2.12
2.13
2.14
2.15

Bronze Frames: Formed from cold- or hot-rolled steel sheet, with enamel finish, and
with formed-bronze sheet laminated to steel frames using adhesive that fully bonds metal
to metal without telegraphing or oil-canning.
Star of Life Symbol: Identify emergency elevators with star of life symbol, not less than
3 inches (76 mm) high, on both inside surfaces of hoistway door frames.
Powder Coated-Steel Doors[ and Transoms]:
Flush, hollow-metal construction;
fabricated from cold-rolled steel sheet. Provide with factory-applied enamel finish;
colors as selected by Architect from manufacturer's full range.
Primed-Steel Doors[ and Transoms]: Flush, hollow-metal construction; fabricated from
cold-rolled steel sheet. Provide with factory-applied, rust-resistant primer for field
painting.
Stainless-Steel Doors[ and Transoms]: Flush, hollow-metal construction; fabricated
[from stainless-steel sheet] [or] [by laminating stainless-steel sheet to exposed faces
and edges of powder coated cold-rolled steel doors using adhesive that fully bonds
metal to metal without telegraphing or oil-canning].
Bronze Doors[ and Transoms]: Flush, hollow-metal construction; fabricated by
laminating bronze sheet to exposed faces and edges of enameled cold-rolled steel doors
using adhesive that fully bonds metal to metal without telegraphing or oil-canning.
Plastic-Laminate Doors[ and Transoms]: Flush, hollow-metal construction; fabricated
by laminating plastic laminate to exposed faces of powder coated cold-rolled steel doors
and covering edges with protective edge trim[ matching door frames]. Plastic-laminate
color, texture, and pattern as selected by Architect from [plastic-laminate] [elevator]
manufacturer's full range.
Unfinished-Steel Doors[ and Transoms]: Flush, hollow-metal construction; fabricated
from cold-rolled steel sheet, with factory-applied enamel.
Sight Guards: Provide sight guards on doors matching door edges.
Sills: Extruded metal, with grooved surface, 1/4 inch (6.4 mm) thick.
Nonshrink, Nonmetallic Grout:
Factory-packaged, nonstaining, noncorrosive,
nongaseous grout complying with ASTM C 1107/C 1107M.

SCHEDULE 8 - SIGNAL EQUIPMENT


PRODUCT DATA SHEET 0 - General: Provide hall-call and car-call buttons that light when activated
and remain lit until call has been fulfilled. Fabricate lighted elements with [long-life lamps and
acrylic or other permanent, non-yellowing translucent plastic diffusers] [or] [LEDs].
PRODUCT DATA SHEET 1 - Car-Control Stations: Provide manufacturer's standard [recessed] [or]
[semirecessed] car-control stations. Mount in return panel adjacent to car door unless
otherwise indicated.
1.1
1.2

Mark buttons and switches for required use or function. Use both tactile symbols and
Braille.
Provide "No Smoking" sign matching car-control station, either integral with car-control
station or mounted adjacent to it, with text and graphics as required by authorities having
jurisdiction.

PRODUCT DATA SHEET 2 - Swing-Return Car-Control Stations: Provide car-control stations


mounted on rear of hinged return panel adjacent to car door and with buttons, switches,
controls, and indicator lights projecting through return panel but substantially flush with face of
return panel.
HYDRAULIC ELEVATORS

142400 - 14

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
2.1
2.2

Mark buttons and switches for function. Use both tactile symbols and Braille.
Provide "No Smoking" sign matching car-control station, either integral with car-control
station or mounted adjacent to it, with text and graphics as required by authorities having
jurisdiction.

PRODUCT DATA SHEET 3 - Emergency Communication System: Two-way voice communication


system, with visible signal, which dials preprogrammed number of monitoring station and does
not require handset use. System is contained in an integral cabinet, with identification,
instructions for use, and battery backup power supply.
PRODUCT DATA SHEET 4 - Firefighters' Two-Way Telephone Communication Service: Provide
[flush-mounted cabinet] [telephone jack] in each car and required conductors in traveling
cable for firefighters' two-way telephone communication service specified in [Section 283111
"Digital, Addressable Fire-Alarm System"] [Section 283112 "Zoned (DC Loop) FireAlarm System."]
PRODUCT DATA SHEET 5 - Car Position Indicator: Provide [illuminated, ]digital-type car position
indicator, located above car door or above car-control station. Also, provide audible signal to
indicate to passengers that car is either stopping at or passing each of the floors served. Include
travel direction arrows if not provided in car-control station.
PRODUCT DATA SHEET 6 - Hall Push-Button Stations: [Provide one hall push-button station at
each landing] [Provide one hall push-button station at each landing for each single
elevator or group of elevators, but not less than one station for each four elevators in a
group] [Provide hall push-button station at each landing as indicated].
6.1
6.2
6.3

Provide [manufacturer's standard wall-mounted units][units with flat faceplate for


mounting with body of unit recessed in wall].
Equip units with buttons for calling elevator and for indicating applicable direction of
travel.
Provide telephone jack in each unit for firefighters' two-way telephone communication
service specified in [Section 283111 "Digital, Addressable Fire-Alarm System"]
[Section 283112 "Zoned (DC Loop) Fire-Alarm System."]Possibly insert a provision
for either an "In Use" signal or a digital display of car position for single elevators.

PRODUCT DATA SHEET 7 - Hall Lanterns: Units with illuminated arrows; but provide single arrow
at terminal landings. Provide[ one of] the following:
7.1
7.2
7.3
7.4

Manufacturer's standard wall-mounted units, for mounting above entrance frames.


Units with flat faceplate for mounting with body of unit recessed in wall and with
illuminated elements projecting from faceplate for ease of angular viewing.
Units mounted in both jambs of entrance frame[ for each elevator].
Units mounted in both car door jambs[; may be used only for single elevators or for
two-car groups].

PRODUCT DATA SHEET 8 - Hall Annunciator: With each hall lantern, provide audible signals
indicating car arrival and direction of travel. Signals sound once for up and twice for down.
8.1

At manufacturer's option, audible signals may be placed on cars.

HYDRAULIC ELEVATORS

142400 - 15

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
PRODUCT DATA SHEET 9 - Hall Position Indicators: Provide [illuminated, ]digital-display-type
position indicators, located above[ each] hoistway entrance at ground floor. Provide units with
flat faceplate for mounting and with body of unit recessed in wall.
9.1

Integrate ground-floor hall lanterns with hall position indicators.

PRODUCT DATA SHEET 10 - Standby Power Elevator Selector Switches: Provide switches, as
required by ASME A17.1/CSA B44, where indicated.
Adjacent to switches, provide
illuminated signal that indicates when normal power supply has failed.[ For each elevator,
provide illuminated signals that indicate when they are operational and when they are at
the designated emergency return level with doors open.]
PRODUCT DATA SHEET 11 - Fire-Command-Center Annunciator Panel: Provide panel containing
illuminated position indicators for each elevator, clearly labeled with elevator designation;
include illuminated signal that indicates when elevator is operational and when it is at the
designated emergency return level with doors open. Provide standby power elevator selector
switch(es), as required by ASME A17.1/CSA B44, adjacent to position indicators. Provide
illuminated signal that indicates when normal power supply has failed.
PRODUCT DATA SHEET 12 - Emergency Pictorial Signs: Fabricate from materials matching hall
push-button stations, with text and graphics as required by authorities having jurisdiction,
indicating that in case of fire elevators are out of service and exits should be used instead.
Provide one sign at each hall push-button station unless otherwise indicated.
SCHEDULE 9 - FINISH MATERIALS
PRODUCT DATA SHEET 0 - General: Provide the following materials for exposed parts of elevator
car enclosures, car doors, hoistway entrance doors and frames, and signal equipment as
indicated.
PRODUCT DATA SHEET 1 - Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, commercial steel,
Type B, exposed, matte finish.
PRODUCT DATA SHEET 2 - Hot-Rolled Steel Sheet: ASTM A 1011/A 1011M, commercial steel,
Type B, pickled.
PRODUCT DATA SHEET 3 - Stainless-Steel Sheet: ASTM A 240/A 240M, Type 304.
PRODUCT DATA SHEET 4 - Textured Stainless-Steel Sheet: ASTM A 240/A 240M, Type 304 with
embossed texture rolled into exposed surface.
4.1
4.2

Product: Subject to compliance with requirements, provide "<Insert product name>"


by <Insert manufacturer's name>.
Metal surface is [satin polished] [satin relieved] [titanium nitride colored] [oxide
colored] [satin polished and titanium nitride colored] [satin relieved and titanium
nitride colored] [satin polished and oxide colored] [satin relieved and oxide colored]
[color coated and satin relieved] [color coated and bright relieved] after texturing.

PRODUCT DATA SHEET 5 - Stainless-Steel Bars: ASTM A 276, Type 304.

HYDRAULIC ELEVATORS

142400 - 16

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
PRODUCT DATA SHEET 6 - Stainless-Steel Tubing: ASTM A 554, Grade MT 304.
PRODUCT DATA SHEET 7 - Bronze Plate and Sheet: ASTM B 36/B 36M, Alloy UNS No. C28000
(muntz metal).
PRODUCT DATA SHEET 8 - Bronze
(architectural bronze).

Extrusions:

ASTM B 455,

PRODUCT DATA SHEET 9 - Bronze


Tubing:
Alloy UNS No. C23000 (red brass, 85 percent copper).

ASTM B 135

Alloy UNS No. C38500


(ASTM B 135M),

PRODUCT DATA SHEET 10 - Aluminum Extrusions: ASTM B 221 (ASTM B 221M), Alloy 6063.
PRODUCT DATA SHEET 11 - Nickel
Silver
Alloy UNS No. C74500 or No. C77600.

Extrusions:

ASTM B 151/B 151M,

PRODUCT DATA SHEET 12 - Plastic Laminate: High-pressure type complying with NEMA LD 3,
[Type HGS for flat applications] [Type HGL for flat applications] [Type HGP for
postformed applications] [and] [Type BKV for panel backing].
PART 3 - EXECUTION
SCHEDULE 0 - EXAMINATION
PRODUCT DATA SHEET 0 - Examine elevator areas, with Installer present, for compliance with
requirements for installation tolerances and other conditions affecting performance of the Work.
Verify critical dimensions and examine supporting structure and other conditions under which
elevator work is to be installed.
PRODUCT DATA SHEET 1 - Prepare written report, endorsed by Installer, listing conditions
detrimental to performance of the Work.
PRODUCT DATA SHEET 2 - Proceed with installation only after unsatisfactory conditions have been
corrected.
SCHEDULE 1 - INSTALLATION
PRODUCT DATA SHEET 0 - Excavation for Cylinder: Drill well hole in[ each] elevator pit to
accommodate installation of cylinder; comply with applicable requirements in Section 312000
"Earth Moving."
PRODUCT DATA SHEET 1 - Provide[ waterproof] well casing[ as necessary] to retain well-hole
walls.
PRODUCT DATA SHEET 2 - Install cylinder in protective casing within well hole. Before installing
protective casing, remove water and debris from well hole[ and provide permanent
waterproof seal at bottom of well casing].
2.1

Fill void space between protective casing and cylinder with corrosion-protective filler.

HYDRAULIC ELEVATORS

142400 - 17

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
2.2

Align cylinders and fill space around protective casing with fine sand.

PRODUCT DATA SHEET 3 - Install cylinder plumb and accurately centered for elevator car position
and travel. Anchor securely in place, supported at pit floor. Seal between [well] [protective]
casing and pit floor with 4 inches (100 mm) of nonshrink, nonmetallic grout.
PRODUCT DATA SHEET 4 - Install cylinder plumb and accurately centered for elevator car position
and travel. Anchor securely in place, supported at pit floor and braced at intervals as needed to
maintain alignment. Anchor cylinder guides at spacing needed to maintain alignment and avoid
overstressing guides.
PRODUCT DATA SHEET 5 - Welded Construction: Provide welded connections for installing
elevator work where bolted connections are not required for subsequent removal or for normal
operation, adjustment, inspection, maintenance, and replacement of worn parts. Comply with
AWS workmanship and welding operator qualification standards.
PRODUCT DATA SHEET 6 - Sound Isolation: Mount rotating and vibrating equipment on vibrationisolating mounts to minimize vibration transmission to structure and structure-borne noise due
to elevator system.
PRODUCT DATA SHEET 7 - Install piping above the floor, where possible.
piping in casing.
PRODUCT DATA SHEET 8 - Lubricate
manufacturers.

operating

parts

of

systems

as

Install underground
recommended

by

PRODUCT DATA SHEET 9 - Alignment:


Coordinate installation of hoistway entrances with
installation of elevator guide rails for accurate alignment of entrances with car. Where possible,
delay installation of sills and frames until car is operable in shaft. Reduce clearances to
minimum, safe, workable dimension at each landing.
PRODUCT DATA SHEET 10 - Leveling Tolerance: 1/4 inch (6 mm), up or down, regardless of load
and travel direction.
PRODUCT DATA SHEET 11 - Set sills flush with finished floor surface at landing.
PRODUCT DATA SHEET 12 - Locate hall signal equipment for elevators as follows, unless otherwise
indicated:
12.1 For groups of elevators, locate hall push-button stations between two elevators at center
of group or at location most convenient for approaching passengers.
12.2 Place hall lanterns either above or beside each hoistway entrance.
12.3 Mount hall lanterns at a minimum of 72 inches (1829 mm) above finished floor.
SCHEDULE 2 - FIELD QUALITY CONTROL
PRODUCT DATA SHEET 0 - Acceptance Testing: On completion of elevator installation and before
permitting elevator use (either temporary or permanent), perform acceptance tests as required
and recommended by ASME A17.1/CSA B44 and by governing regulations and agencies.

HYDRAULIC ELEVATORS

142400 - 18

Copyright 2010 AIA


MasterSpec Full Length
02/10
PRODUCT MASTERSPEC LICENSED BY ARCOM TO THYSSENKRUPP ELEVATOR.
PRODUCT DATA SHEET 1 - Advise Owner, Architect, and authorities having jurisdiction in advance
of dates and times that tests are to be performed on elevators.
SCHEDULE 3 - PROTECTION
PRODUCT DATA SHEET 0 - Temporary Use: [Limit temporary use for construction purposes to
one elevator. ]Comply with the following requirements for[ each] elevator used for
construction purposes:
0.1
0.2
0.3
0.4
0.5
0.6

0.7

Provide car with temporary enclosure, either within finished car or in place of finished
car, to protect finishes from damage.
Provide strippable protective film on entrance and car doors and frames.
Provide padded wood bumpers on entrance door frames covering jambs and frame faces.
Provide other protective coverings, barriers, devices, signs, and procedures as needed to
protect elevator and elevator equipment.
Do not load elevators beyond their rated weight capacity.
Engage elevator Installer to provide full maintenance service. Include preventive
maintenance, repair or replacement of worn or defective components, lubrication,
cleanup, and adjustment as necessary for proper elevator operation at rated speed and
capacity. Provide parts and supplies same as those used in the manufacture and
installation of original equipment.
Engage elevator Installer to restore damaged work, if any, so no evidence remains of
correction. Return items that cannot be refinished in the field to the shop, make required
repairs and refinish entire unit, or provide new units as required.

SCHEDULE 4 - DEMONSTRATION
PRODUCT DATA SHEET 0 - Check operation of[ each] elevator with Owner's personnel present
before date of Substantial Completion[ and again not more than one month before end of
warranty period]. Determine that operation systems and devices are functioning properly.
SCHEDULE 5 - MAINTENANCE
PRODUCT DATA SHEET 0 - Initial Maintenance Service: Beginning at Substantial Completion,
maintenance service shall include <Insert number> months' full maintenance by skilled
employees of elevator Installer. Include monthly preventive maintenance, repair or replacement
of worn or defective components, lubrication, cleaning, and adjusting as required for proper
elevator operation. Parts and supplies shall be manufacturer's authorized replacement parts and
supplies.
0.1
0.2
0.3

Perform maintenance during normal working hours.


Perform emergency callback service during normal working hours with response time of
[two] <Insert number> hours or less.
Include 24-hour-per-day, 7-day-per-week emergency callback service with response time
of [two] <Insert number> hours or less.

END OF SECTION 142400