FISA TEHNICA CENTRALA CU RECUPERATOR DE CALDURA

DDM - 12/12 M7A2 3F 2V 2.2 kW


DESCRIERE CENTRALA CU RECUPERATOR DE CALDURA
1
2
3
4
5

Ventilator centrif ugal dubluas pirant NICOT RA DDM 12/12 3 F 2V - 9000


Recuperator de caldura aer aer REC AL 040 - 2 buc.
Filtru G4 550x550x50 mm - 1 buc.

Baterie electrica NK 700x400 -27-3 - 1 buc (montaj in afara centralei)


Temperatura de functionare -2 0 C +50 C

DESCRIERE VENTILATOR
1
2
3
4

Ventilator centrif ugal dubluaspirant


Carcasa confectionata din tabl a galvanizata
Rotor din tabla galvanizata
Motor cu rotor extern grad de protec tie IP - 54

mc/h - 2 buc.

RECUPERATOR DE CALDURA AER - AER

CONSTRUCTIE
1
2
3

Cadru din profil de aluminiu grosime 35 mm


Panouri tabla zincata izolate termic si fonic
Izolatie aluminizata grosime 19 mm

DIAGRAMA VENTILATOR

DIMENSIUNI VENTILATOR

FILTRU G4 550x550x50
1.
2.

Rama tabla galvanizata


Dimensiuni 55 0x55 0x50 mm

HEATERS

Series

finning to enlarge heat exchange area. NK-series

NK

heaters are supplied with two thermostatic switches

protecting the heating elements from contamination.


Heater may be installed in front or behind the

that provide overheating control:

fan. If the heater is placed in front of the fan its


recommended to anticipate air duct between them in
the distance not less than two connecting diameters
in order to stabilize air flow, as well as not to exceed
maximum allowed temperature inside the fan.

primary protection with automatic restart


(response temperature +50). After cooling down
the thermostatic switch automatically closes the
heaters control circuit.
emergency protection with manual restart

Air heater needs to be connected on the

(response temperature +90). In case of actuation


of emergency protection power supply can be fed to
the heating device only after the failure condition has
been reset manually.
Several power capacity versions are available for each
unit size. Greater output capacity can be achieved if
heaters are attached consequently one after one.
!

counterflow principle, otherwise its capacity will be


reduced by 5-15%. All estimated nomographic charts,
included in the catalogue, are true for such type of
connection;
If water is used as heat carrying agent the heating
devices can be installed only inside the premises. In
case of outdoor mounting an antifreezing mixture
should be used as heat carrying agent (for example,

Application

ethylene glycol solution);

Electric heaters are designed for heating the incoming


air in ventilation systems with rectangular cross-

section. Heaters are used to warm the air in heating

on round air ducts. Water heaters may be installed in

facilities, ventilation and air conditioning systems in


various premises.

any position allowing its deairing. Air flow direction

provides complex control and freezing protection:

should correspond with the direction of the arrow

"# automatic control of power adjustment and air

placed on air heater.


It is recommended to install the heater in position

heating temperature;

that ensures uniformly distributed air flow across the


full width of cross-section.
Air filter should be installed in front of the heater

heating process;
"# application of air dampers supplied with servo-

Design

The case and terminal box are made of galvanized


sheet steel and the heating elements are made of
stainless steel. Heaters are supplied with additional

Mounting
Design of the heater allows fixing it by clamps

For correct and safe operation of heaters we


recommend you to use automation system that

"# ventilation system startup with heaters pre-

controlled actuator with a pull-back spring;

"# tracking filter condition by means of differential


pressure sensor;
"#shutting down fan in case of heater frost threat.

Legend:
Series

Flange diameter (WxH), mm

NK

400200; 500250; 500300;


600300; 600350; 700400;
800500; 900500; 1000500.

Heaters capacity, kW
4,5; 6; 7,5; 9; 10,5; 12; 18; 21;
24; 27; 36; 45; 54

Phase

3 - phase

Consumption
current, A

Voltage, V

Power,
kW

Quantity
of heating
elements x kW

N 400x200-4,5-3

330

6,5

400

4,5

3x1,5

N 400x200-6,0-3

440

8,7

400

6,0

3x2,0

N 400x200-7,5-3

550

10,9

400

7,5

3x2,5

N 400x200-9,0-3

660

13,0

400

9,0

3x3,0

N 400x200-10,5-3

770

15,2

400

10,5

3x3,5

N 400x200-12,0-3

880

17,4

400

12,0

3x4,0

N 400x200-15,0-3

1100

21,7

400

15,0

3x5,0

N 500x250-6,0-3

440

8,7

400

6,0

3x2,0

N 500x250-7,5-3

550

10,9

400

7,5

3x2,5

N 500x250-9,0-3

660

13,0

400

9,0

3x3,0

N 500x250-10,5-3

770

15,2

400

10,5

3x3,5

N 500x250-12,0-3

880

17,4

400

12,0

3x4,0

N 500x250-15,0-3

1100

21,7

400

15,0

3x5,0

N 500x250-18,0-3

1320

26,0

400

18,0

3x6,0

N 500x250-21,0-3

1540

30,0

400

21,0

3x7,0

N 500x300-6,0-3

440

8,7

400

6,0

3x2,0

N 500x300-7,5-3

550

10,9

400

7,5

3x2,5

N 500x300-9,0-3

660

13,0

400

9,0

3x3,0

N 500x300-10,5-3

770

15,2

400

10,5

3x3,5

N 500x300-12,0-3

880

17,4

400

12,0

3x4,0

N 500x300-15,0-3

1100

21,7

400

15,0

3x5,0

N 500x300-18,0-3

1320

26,0

400

18,0

3x6,0

N 500x300-21,0-3

1540

30,0

400

21,0

3x7,0

N 600x300-9,0-3

660

13,0

400

9,0

3x3,0

N 600x300-12,0-3

880

17,4

400

12,0

3x4,0

N 600x300-15,0-3

1100

21,7

400

15,0

3x5,0

N 600x300-18,0-3

1320

26,0

400

18,0

3x6,0

N 600x300-21,0-3

1540

30,0

400

21,0

3x7,0

N 600x300-24,0-3

1760

34,7

400

24,0

3x8,0

N 600x350-9,0-3

660

13,0

400

9,0

3x3,0

N 600x350-12,0-3

880

17,4

400

12,0

3x4,0

N 600x350-15,0-3

1100

21,7

400

15,0

3x5,0

N 600x350-18,0-3

1320

26,0

400

18,0

3x6,0

N 600x350-21,0-3

1540

30,0

400

21,0

3x7,0

N 600x350-24,0-3

1760

34,7

400

24,0

38,0

N 700x400-18-3

1320

26,0

400

18,0

63,0

N 700x400-27-3

1980

39,0

400

27,0

93,0

N 700x400-36-3

2640

52,0

400

36,0

123,0

N 800x500-27-3

1980

39,0

400

27,0

93,0

N 800x500-36-3

2640

52,0

400

36,0

123,0

N 800x500-54-3

3960

78,0

400

54,0

183,0

N 900x500-45-3

3300

65,0

400

45,0

153,0

N 900x500-54-3

3960

78,0

400

54,0

183,0

N 1000x500-45-3

3300

65,0

400

45,0

153,0

N 1000x500-54-3

3960

78,0

400

54,0

183,0

HEATER SERIES NK

Min. air pass,


m3/h