Air Conditioning System

Welcome to LG Air Conditioning Division

The Worlds Best Seller

LG Electronics, Worlds Top for 4 Years


LG air conditioners: recognized as the best across the world...
According to Fuji-Keizai, one of Japans top market research
companies, LG Electronics (LGE) maintained its No.1 global
position for the fourth consecutive year since 2000 in terms of
AC unite sales a total of 8 million units (US$2billion) in 2003.
LGE started its air conditioner business in 1968. Although it was
a difficult time to enter the market during the Asian currency
crisis in 1997, the company expanded its export drive and
invested in R&D and production lines. Sales grew rapidly: from
4.1 million units in 2000, 4.9 million 1n 2001, 6.7 million in 2002
and then 8 million units in 2003. With a 25% CAGR (compound
annual growth rate), LGE continues to defend its prime position
in the AC units industry

New Leader in Multi V Technology

Caring for Environment

Environment Friendly
The environment of the future at LG Air conditioners
Keeping pace with developments in global environment policies, the
company has developed a new refrigerant
to replace Freon gas (R22), ahead of it being banned due to its
environmentally - damaging greenhouse effects.
On completion of market tests in 1999, the company launched its wall and
window mounted product ranges in 2000.
With a ceiling-type duct to be supplied from 2001, the company is
positioned to cover all air conditioner market sectors. This is our
environment-friendly policy protecting the environment for the future.

Welcome to LG Air Conditioning Division

LG Air Conditioners World-winning Technology...


LG offers a more advantageous business environment for its customers with its range of air conditioner features. Its
PLASMA Air Purifying System, first developed and marketed in 1999, has proved its effectiveness, and LG has since in
2000 developed the world's first semi-permanent PLASMA Heat Exchanger, enhancing the functionality of the core
component.
In 2001 the company introduced state-of-the-art digital telephone remote control technology, and developed the
Tele-control air conditioner, which is activated or stopped remotely via an ordinary telephone. To maintain its product
leadership in the market, LG Air conditioners places a lot of emphasis on improvements such as reduced energy
consumption, high efficiency, low noise compressors, ventilation systems and compact product dimensions, etc.

Great Company Great People


Brief History
Establishment
1947

Establishment of LG Group

1958

Establishment of LG Electronics Inc.

1962

Establishment of Digital Appliance Company

Growth

Test Tower

1968

Manufactured Koreas first Air Conditioners

1985

Introduced Koreas first Inverter Air Conditioners

1986

Exported Koreas first Window Air Conditioner to U.S.A

1989

Won the approval of ULs MDP & CSAs EEVP

1993

Obtained ISO 9001 Certification from BSI-QA

1994

Export Records USD 100 Mil.

Global Expansion
1995

Establishment of LGETA in China

1997

Establishment of LGEIL in India

1999

Establishment of LGEAT in Turkey

1999

Establishment of LGEMH in Vietnam

2001

Establishment of LGEAZ in Brazil

2002

Establishment of LGETH in Thailand

2002

Establishment of LGEIN in Indonesia

2002

Turnover of 1.8 Billion dollars (Expected)

New Leader in Multi V Technology

LGEAT Turkey
LGEIL India

LGETA China Tianjin


LGE Korea
LGETH Thailand
LGEMH Vietnam
LGEIN Indonesia

LGEAZ Brazil

The Future is Bright for LG Air Conditioners


LG Air conditioners, which first manufactured window type air conditioners in Korea in 1968, has undergone
tremendous growth to achieve a turnover of 1.8 billion dollars in 2002.
The company supplies over 7 million units to markets worldwide through its manufacturing sites in Korea,
China, India, Turkey, Vietnam, Thailand, Indonesia and Brazil.

Overseas Manufacturing Bases

LG Air Conditioning Division, Korea

LGE Tianjin Appliance Co., Ltd. China

LG Electronics Thailand. Thailand

LG Electronics Arcelik. Turkey

LGE New Delhi Ltd. India

LGE Haiphong Inc. Vietnam

LGE da Amazonia Ltd. Brazil

LG Electronics Indonesia. Indonesia

Multi V Installation Reference

Madrid, SPAIN
Doctor Garcia Tapia
Installation:Confaire

Cervia(Ravenna), ITALY
Hotel Lady Mary
Installation:Casa Service di Tosi Mario

New Leader in Multi V Technology

LG Air Conditioner into to the Global

Installation Reference
Gennevilliers, FRANCE
Office Building
Installation:Alize Clim

France
Portugal

UK
Belgium
Germany
Russia

China
Korea

Hungary
Italy

Spain

Philippine
Singapore
South Africa

Australia

Pampilhosa da serra, PORTUGAL


District Court
Installation:Climacer

What is Multi V ?

If you need highly efficient air conditioning system in your building, LG MULTI V is the right choice for you.

New Leader in Multi V Technology

Ease of installation with size and routing of pipework compared to water based systems, and also with the advantage of
less space for the outdoor units and flexible internal unit requirements, means that there are has lower installation
fees and reduced running costs.

What is

It's an inverter multi system with single connecting refrigerant pipe, which is composed of one outdoor
unit and some indoor units in series, so it saves energy greatly and makes the installation easy.
This efficient piping system allows a flexible assembly so that it can be
connected to various types of indoor unit while it reduces the installation cost.

VRF (individual A/C-Air Cooled)

Chiller (Central A/C-Water cooled)

Piping Work

- Easy pipe work(small pipe diameter)


- Fit for New B/D, extension B/D and reconstruction

- Hard pipe work (large pipe diameter)


- Hard to apply to existing facilities.

Control System

- Both individual and automatic central


control based on MICOM control

- manually individual control


or central control in a machine room

Installation

- Small installation area & light weight

- More than 3 times installation area

Installation
Operational Costs

- Low initial cost


- Low operational cost

- High initial & operational costs


Required continuous maintenance

System Structure

Model Line up

4.5 HP

Multi V system has a flexible piping connection and


exists in various types so that it can be used in any
kinds of spaces. Within the outdoor units capacity,
6~30 indoor units can be assembled in flexible
arrangement. This makes the designing and
installation much easier.
Also, a separate control for each room is possible
as well as various types of central controller

CRUN4580S

10 HP
Internet control

Central Control

CRUN10080S

New Leader in Multi V Technology

The LG Multi V system for R407C heat pump is a rapid response system in which up to 16 indoor units can operate on
the same refrigerant circuit in conjunction with a single outdoor unit. An inverter compressor enables the output of
the outdoor unit to be modulated in accordance with the cooling/heating demand of the zone which it controls.

The flexible indoor unit assembly is appropriate for different spaces, makes the installation easy and reduces the cost.

ART COOL Mirror

Wall Mounted Type

ART COOL

Low Static
1-Way Cassette Type

4-Way Cassette Type

Ceiling & Floor Type

Floor Standing(exposed) Type

High Static

Ceiling Concealed Duct Type

Floor Standing Type

Various assembly of Multi V indoor units

for Design

for Installation

We meet your needs with unique


LG technology

Anyone can install it simply


and easily

MULTI V will meet your needs with our unique technology.


First to innovate, First to perfect. It's the real technology!

We believe you will be impressed with an air conditioner


installation diagram as simple as this.
Now, simpler and easier!

- Technology of Suitability for Building

- LG One Stop Quotation

- Gold Fin

- Long Piping System

- Urethane Coated PCB

- Auto Addressing

- Plasma Air Purifying Filter

- Non-polarized Wire

- Environment-friendly Refrigerant

- Auto Restart

- Wide Variety of Indoor Units

- Sequential Start

- Ventilation System

- Self Diagnostic Program

New Leader in Multi V Technology

for Use

for Control

Always pleasant to use and highly


efficient in a variety of
environments

You can choose a control system


exactly right for you

Air conditioners must perform well in any kind of climate


environment. Highly efficient heating and cooling system,
Any where Any climate

If your needs are different, then the solutions must be


different. A new MULTI V control system to meet your
needs !

- Cooling for Low Ambient Temperature

- Simple Central Controller

- Heating for Extremely Cold Region

- Deluxe Central Controller

- Highest COP Level

- Various Controllers of MULTI V

- Wide Range of Operation


- Heat Recovery
- System Expansion

We have achieved a higher level of product reliability through 2 years of testing in the field and in our
MULTI V Test Tower, and through a differentiated design. Using an indoor unit automated addressing
and non-polarized wire communication, MULTI V has achieved convenience of installation and a zero
error rate. The system can be linked to a variety of stylish indoor units only offered by LG, and its
heating and cooling performance is superior than competitors in any climate.
Number 1 in the World For 3 Years - LG Air Conditioner!

11

for D esign
We meet your needs with unique LG technology
MULTI V will meet your needs with our unique technology. First to innovate, First to perfect. It's the real technology!

Technology of Suitability for Building


LG has developed an outdoor fan which creates high air volume with low noise. This has been achieved using air flow analysis on the
building's periphery and the outdoor unit's characteristics. This increases the acceptability of the unit in buildings by minimizing the noise
and vibration of the outdoor unit.

Around the Building

Around the Outdoor Units

External wind analysis

Velocity field analysis

Without the Hood

With the Hood

Anti Rust Gold Fin


The system's condensing coils durability has been increased by utilising gold fins with superior anti-corrosive qualities.

Salt Spray Test for 15 Days

After 15 Days

LG Gold Fin
Corrosion Free

Gold Coated Aluminum

After 15 Days

Conventional
Starting to corrode

Uncoated Aluminum
Salt Spray Test Result: After 360 hours [ Test Standard: KS D 9502, ASTM B-117 ]

New Leader in Multi V Technology

Urethane Coated PCB


First in the industry to coat the PCB with urethane, the MULTI V switches
and connectors are fully protected from moisture, dust etc to reduce the
risk of external shock.

Urethane Coated PCB

Conventional

PLASMA Air Purifying Filter

Clean Air

The indoor unit has a unique plasma air purifying filter which removes

Cover

impurities, such as dust, Odor and allergens, and supplies clean, fresh and
Odor free air.

Photo-Catalyst
Coated Mesh
Plasma ionizer
Rating Voltage=4.8kV

Dust Free! / Odor Free! / Anti-Allergy !

Case

Power
input terminal

Polluted Air

Designed for Environment-friendly Refrigerant


The MULTI V uses environment-friendly refrigerant to prevent
destruction of the ozone.

Wide Variety of Indoor Units


From 1, 2, and 4-way cassette types to convertible, concealed duct, wall mounted, Art Cool and the latest Art Cool mirror model,
LG offers a wide variety of indoor unit designs that will create an aesthetically pleasing interior.

Ventilation System
The ventilation system linked to the MULTI V uses a specially developed medium as a heat exchanger which in comparison to existing
metal heat exchangers, is three times more energy efficient. By allowing water molecules to pass through, the system maintains an
ideal 40-60% humidity and eliminates mold and viruses.

13

for I nstallation
Anyone can install it simply and easily
We believe you will be impressed with an air conditioner installation diagram as simple as this. Now, simpler and easier!

LG One Stop Quotation


Based on information regarding the expected MULTI V installation location, we could carry out a selection of the position, size and most
efficient indoor unit type. We have specially developed software that can automatically design the capacity, piping, and wiring for the system.
The LGOSQ easily carries out this process step-by-step, providing you with a timely, simple and accurate proposal, cost estimate, and all the
information you need prior to installation.

Introduction

Load Calculation

Equipment Selection(Worksheet)

Layout

Load Report

Equipment Selection(Tree)

Quotation

Annual Energy
Consumption

Long Piping System


This is the MULTI V tower, a new equipment testing facility for conducting air
conditioner experiments at different altitudes.
MULTI V tubing can be installed with a maximum piping length of 125 meters,
and a maximum vertical height of 50 meters.
The system achieves the highest
performance in the world, compared

Outdoor unit
(10HP)

to standard-length tubing, by using a


unique software algorithm which
optimally controls heating/cooling

Longest piping
length 100m

50m
15m

load, overheating and overcooling


Outdoor unit

levels.

New Leader in Multi V Technology

Indoor Air Flow and


Temperature Distribution

Auto Addressing
The outdoor unit automatically confirms the status of each indoor unit without the use of cumbersome dip switches, by storing and sending
specific numbers to the EEPROM, a part within the indoor unit. With auto addressing, the installation time is greatly reduced

Outdoor unit
(10HP)

Transmission Line

Indoor unit

Non-polarized Wire
Unlike the existing products where communication between the outdoor and indoor units is impossible if the polarization is different, you
can simply connect the outdoor and indoor units and the MULTI V algorithm will automatically find the correct polarity and enable
communications for a simple and easy installation.
Outdoor Unit Control Box
A B

A B

B A

A B

B A

Auto Restart
When there is a power cut during operation, the system will automatically restart from the same working condition when the power is
restored.

Sequential Start
If there are many outdoor units operating simultaneously, they are started sequentially to reduce power surge and increase safety.

Self Diagnostic Program


During installation, operation after installation, and after service, all problems can be
diagnosed easily and conveniently using a PC or notebook. If any error occurs, its error code
will be displayed on the controller screen making it convenient for the user to know about
the problem.

15

for U se
Always pleasant to use and highly efficient in a variety of environments
Air conditioners must perform well in any kind of climate environment. Highly efficient heating and cooling system, Any where Any climate

Cooling for Low Ambient Temperature


It is an ideal system for superior air conditioning performance, and for places requiring year-around constant temperature. Based on
temperature and pressure sensor information, the MULTI V system can control the fan speed and expansion valve using hot gas bypass
technology. This control is available even when the outdoor temperature drops to minus 5 degrees Celsius. It is an ideal system for places
requiring year-around constant temperature, such as computer rooms.

Heating for Extremely Cold Region


When the outdoor temperature is minus 10 degrees Celsius, the MULTI V can achieve air discharge temperatures exceeding 40~47 degrees
Celsius. With its unique anti-freezing refrigerant circuit technology, the system is capable of heating without additional heating
equipment even in cold climates where temperatures go below minus 20 degrees Celsius.

- Inverter Scroll Compressor is designed for prevention of liquid compression


- Refrigerant sub cooling circuit prevents from growing in outdoors
HEX at heating operation

Outdoor's
HEX

Check Valve
Region of frost prevention
Heating

Cooling

LEV

Inverter air conditioning /heating system boasts a wide operational range which
is a result of applying highly advanced new technologies such as the inverter
scroll compressor and electronic expansion valve. The operation is possible up
to 43C of outdoor temperature when cooling and down to -20C of outdoor
temperature while heating.

Available temperature of cooling/Heating

New Leader in Multi V Technology

Highest COP Level


We have achieved the highest level of COP in the industry by optimizing the design of the heat exchanger for even distribution of the
refrigerant, and by minutely controlling refrigerant with various sensors and electronic control.

Wide Range of Operation


The MULTI V always provides safe heating and air conditioning, even when the indoor unit load varies severely between 10 and 130 percent
of the outdoor unit's capacity, by employing a control algorithm that is distinctly different from other compressors.

Out

10HP

100%

Inverter Compressor

In

Inverter Motor

30 Hz - 120 Hz

Normal
Compressor

100%
Large

Inverter Compressor

Compressor
Capacity
Control

10%
Load

10%

Small

Inverter Driven Capacity Control

Heat Recovery
The true worth of MULTI V three pipe system is evident during its simultaneous automatic operation of heating and cooling with 1 system.

System Expansion
After completing installation of the MULTI V, if the indoor load changes so that it exceeds capacity, the system can easily be expanded by
adding extra indoor and outdoor units with capacities between 5HP and 30HP.

17

for C ontrol
You can choose a control system exactly right for you
If your needs are different, then the solutions must be different. A new MULTI V control system to meet your needs !

Various Controllers of MULTI V


The MULTI V can be centrally controlled through the Internet without the need for additional servers through an interface between the
Internet and an RS-485 communications network.

Remote Control PC

LAN

-Direct access to internet without computer


-Simple installation and operation using LAN cable
and user friendly simple GUI
-Remote control and monitoring by internet
-Schedule timer
-Individual or group control
-Indoor unit max 256
-Automatic upgrade of contents
-Available Ethernet protocol BMS

New Leader in Multi V Technology

Simple Central Controller


First, We have a simple central controller that can operate up to 128 units simultaneously.

- indoor unit max 16


- individual or total control
- Length max 1km

Deluxe Central Controller


And especially, with an intuitively designed GUI and a user-friendly touch panel, you can simultaneously control up to 256 indoor units, and
the system can be linked to the building management system.

- Indoor unit max 256


- 8.0 TFT LCD (800*600)
- Touch screen panel
- Available Ethernet protocol
- Time schedule function
- Error display and lock function
- Length max 1km

19

Volume table of indoor unit

Inverter short piping multi (For air cooling/heating)

Indoor Unit Type


7K

9K

12K

18K

24K

28K

36K

42K

48K

Wall Mounted Type (ART COOL Mirror)


Wall Mounted Type


Wall Mounted Type (ART COOL Wide)

Wall Mounted Type (ART COOL)


1-Way Cassette Type


4-Way Cassette Type

New Leader in Multi V Technology

Inverter short piping multi (For air cooling/heating)

Indoor Unit Type


7K

9K

12K

18K

24K

28K

36K

42K

48K

Convertible Type

Ceiling Duct Type (High Static)


Ceiling Duct Type (Low Static)


Floor Standing (Slim)


Floor Standing (Exposed)

21

Wall Mounted Type

Wide

Mirror

CRNN076SU*0
CRNN096SU*0
CRNN126SU*0

CRNN186SV*0

CRNN126SP*0

* DB :: Wood
Blue

Mirror
* RM :: Metal

M : Metal

B : Blue

CRNN076SRA0
CRNN096SRA0
CRNN126SRA0
CRNN186STA0

New Leader in Multi V Technology

CRNN096SP*0

Indoor unit

Jet Cool

Healthy Dehumidification

Jet cool function is for quick cooling. In this mode, strong and cool air is

With the use of a newly designed compressor, humidity is eliminated to

blown at high speeds for 30 minutes until the room temperature reaches to

create a comfortable atmosphere without overcooling the room.

18 C.

Auto Cleaning (Art Cool Only)


Remove odor & Save time to clean-up
Auto Clean helps to remove odor and save clean-up time. After using airconditioner, Auto Clean makes the inner part of Air conditioner dry for 30
min. It removes moisture and mould so you can enjoy odor-free air and save
time to cleam up.

Natural breeze by CHAOS Swing


The most pleasant air flow for the human body can be found within nature.
Countless data and verification resulted in the application of the new CHAOS

After Cooling Operation, Start Auto-Clean


automatically

theory to LG Air conditioners. The new CHAOS theory is a technology that


revives more natural air by controlling the angle and speed of the movement
of the vane. Compared with the frequency, the CHAOS air flow proved to be
very similar to natural air flow. The CHAOS swing also makes the room more
evenly cooled to stimulate a more natural environment which is most
comfortable for the human body.

In 30 minutes Auto-Clean makes


the inner part of Air conditioner be Dry

Low Noise Air Flow System


To provide a comfortable, pleasant, and well balanced environment, LG air
conditioners utilize a streamlined air fan and a unique design which create
smooth air flow from the air conditioner so that it operates under the lowest
noise level. The cross flow fan, stabilizer, and rear guide which are the

Up speed :12ms(Slow)
Down speed :6ms(fast)

causes of noise, have been redesigned by hydraulic engineering.

Wind-up Effects:
The Wind-up Effect is controlled
by the Vane Angle
Control to evenly distribute nature-like air
throughout the room.

of wind. With the best structure for the air path, the amount of friction has
been decreased providing the most quiet air conditioners in the world.
12ms

Auto Swing

CHAOS Swing
1.7C

Improved

24%

The number of revolutions has been decreased while increasing the amount

6ms

7Min
1.3C
76%

Improved

38%

Improved

6Min

14%

55%

Improved

3.17m2

80%

Cross Flow Fan

1.76m2

Temperature Gap

Preference of
Comfortable Feeling

Cooling Speed

Air-flow
Spreading Area

Stabilizer

Rear Guide

23

Ceiling Cassette Type

CRNN076TCA0
CRNN096TCA0
CRNN126TCA0

New Leader in Multi V Technology

CRNN126TEA0
CRNN186TEA0

CRNN366TDA0

Indoor unit

PLASMA Air Purifying System(Optional)

High-Ceiling corresponding operation

The PLASMA Air Purifying System developed uniquely by LG not only removes

According to the height of the ceiling, RPM of fan motor is selectable to

microscopic contaminants and dust, but also removes house mites, pollen,

increase air reaching distance.

and pet fur to help prevent allergic diseases like asthma. With a filter that

High Ceiling

can be used over and over again by simply washing with water, you can enjoy

3.0

General

clean fresh air without having to worry about changing the filter every two

2.7

years as in the past and save costs.

Dust Free! / Odor Free! / Allergy Free!

4 (M)

Air Velocity Distribution

Auto Changeover
With heat pump model,Cooling and heating operation is changed
automatically on the base of setting temp.
Initial Setting Temp:18C:(Memory the final setting temp)
Control of setting temp.
-Wired Remoted Controller:18~30C
-Reset Button in indoor unit: finally memorized temp.
-Wireless Remoted Controller: 23~27C

Low Noise with 3-Dimensional Turbo Fan


According to the height of the ceiling, RPM of fan motor is selectable to
increase air reaching distance.

40
37

1.5m

36

5m
31
28

Noise output measured in anechoic test room

Optimal Air Distribution

Hygienic and Easy-to-Clean Air Filter

Optimal air distribution with 4-way direcitional Air flow system.

Easy Detachment Filter Long life Anti-Bacteria Filter

4-way Auto Swing

25

Ceiling Concealed Duct Type

CRNN186BHA0
CRNN246BHA0

New Leader in Multi V Technology

CRNN076BNG0
CRNN096BJG0
CRNN126BJG0

Indoor unit

Linear *E.S.P Control

Group Control

* E.S.P: External Static Pressure

Always Air volume and sound kept as design regardless of

Operation Summary

E.S.P change Using This Technology , You can

Where several products are linked, one specific control device can control a

- Optimize Duct work Installation

specific number of products.

- Keep Capacity & Sound level as desired

Specific Operation

- Simplify model numbers

- Connecting line is linked to each of the indoor equipments

The Phase control motor Technology gives benefit of saving

forcommunication. A specific control device is connected to each of them and

money to Installer .

this control device can control the same function.

Desired Air Volume is obtained by controlling the Phase of Motor While

- Group control function is enabled by cutting an optional jump wire in the

installing the product and this makes your Duct Work system flexible E.S.P is

wired remote control. At this time, the main system will not respond in order

controlled from 0 to 8~10mmAq, Linearly

to prevent data collision.


- While executing group control command, use the random data (0-3minutes)
in the main body of indoor equipment for limiting starting current.
- Control device can control up to 16 indoor equipments.
1

16

GND
Signal Line
12V DC Power

H
L

Air volume

Air volume

Wired Remote
Controller

M
L

Air volume
at 2 mmAq

Air volume
at 10 mmAq

10

12

35

70

105

140

175

Static pressure(mmAq)

215

245

Controller

Child Lock Function


This function prevents children or others from tampering with the control

Zero power consumption use in standby


mode by adopting SMPS(Swiching Mode Power Supply)

buttons on the unit.

Power waste due to standby power

It is then controlled by the remote controller.

- Power is wasted if a plug is connected to an outlet even though

-All the buttons on indoor display panel will be locked.


-The unit will be controlled only by remote controller.

the appliance is turned off.


Development of super power-saving SMPS
(Swiching Mode Power Supply)
- Zero standby power by reducing 90% of standby power.

Two Thermistor Control

- No need to pull out every plug when appliance is not in use.

The twin thermistor control regulates the difference between the indoor
temperature and the temperature of the air the product produces, as to
ensure uniform room temperature. This is accomplished by taking two
temperatures, one for room and one for the air being discharged. Then the
sensors readings are adjusted for optimum room temperature.

Weekly Program
If necessary, an operator can make an On/Off reservation of the product for a
period of one week.

27

Ceiling and Floor Type

CRNN186VBA0

New Leader in Multi V Technology

CRNN076CAA0
CRNN096CBA0
CRNN126CCA0
CRNN186CDA0
CRNN246CEA0

Indoor unit

Airflow Direction Control

Auto Operation

Horizontal Airflow Direction Control.

The operation procedure is as following.

Manual Control
Adjust the horizontal airflow direction by manually moving the horizontal

Press Start/Stop Botton

airflow direction louver by hand.


Select Auto Operation Mode

Check the Room temperature

Operation
Indoor Fan Speed
Setting Temperature
Intake-air
Temperature

Are Automatically Decided By Fuzzy Rule.

Below 21 C

Operation Mode

Heating

Over 21 C~
Below 24 C

Over 24 C

Soft Dry

Cooling

If initial mode is decided, that mode is continued without the room temperature changing.

Vertical Airflow Direction Control.


Airflow Direction Control
The airflow direction can be adjusted as desired by using the remote
controller.

Natural breeze by CHAOS Swing


The most pleasant air flow for the human body can be found within nature.
Countless data and verification resulted in the application of the new CHAOS

This is effective when you want to cool yourself directly.

theory to LG Air conditioners.


The new CHAOS theory is a technology that revives more natural air by
controlling the angle and speed of the movement of the vane. Compared with
the frequency, the CHAOS air flow proved to be very similar to natural air

Horizontal

flow. The CHAOS swing also makes the room more evenly cooled to
stimulate a more natural environment which is most comfortable for the
human body.

Downward

Auto Swing

CHAOS Swing
1.7C

Improved

24%

7Min
1.3C
76%

Improved

38%

Improved

6Min

14%

Improved

55%

3.17m2

80%
1.76m2

Sleep Mode Auto Control


A touch of the Sleep Mode Button automatically programs the room air
conditioner to turn off, controls the indoor fan speed, and adjusts the setting

Temperature Gap

Preference of
Comfortable Feeling

Cooling Speed

Air-flow
Spreading Area

temperature to create a more comfortable sleep.

Auto Restart Function


In the event of sudden power failure, the auto start mechanism will
restore the A/C to its previous setting when power returns.

Wind from chaos A/C

Wind from conventional A/C

21
29

Floor Standing Type

CRNN286PKA0

New Leader in Multi V Technology

Indoor unit

PLASMA Air Purifying System (Optional)

Child Lock Function

The PLASMA Air Purifying System within the air conditioner removes

This function prevents children or others from tampering with the control

microscopic contaminants and dust to eliminate offensive odors and prevent

buttons on the unit.

allergic reactions. It can also be used as an air-purifying unit even though the

It is then controlled by the remote controller.

air-cooling function is off.

-All the buttons on indoor display panel will be locked.


-The unit will be controlled only by remote controller.

Anti-Bacteria Filter
It removes dust in the air as well as bacteria proliferation, making the indoor
atmosphere healthy.

Germ culture taken


from unfiltered air

With normal filter

Bacteria grows freely

Bacteria grows well

With LG Bio filter

98.5% Bacteria free

2-Way Auto Swing


Hot or cold air can be evenly distributed throughout the room as the auto
swing function blows air in 2 directions.

Dust electrode discharge

Dust particles

Pro-filter

Polluted
Air

Ionizer

+6.5KV
discharge

Dusts Collector

+
Odour

Generating
plasma

+
+

Purified
fresh Air

dusts alumimum coated


Odor molecule
electrode(-)
(3.25KV discharge)

Neuro Fuzzy Control


According to the temperature, air volume, and air velocity, the sensor will
automatically operate to make the most pleasant atmosphere.

31

Remote Controller

Deluxe Central Controller


- Indoor unit max 256

- Time schedule function

- 8.0 TFT LCD (800*600)

- Error display and lock function

- Touch screen panel

- Length max 1km

- Available Ethernet protocol

Simple Central Controller


- indoor unit max 16
- individual or total control
- Length max 1km

LCD Wired Remote Controller

(Ceiling Cassette Type)

24-Hour ON/ OFF Timer in 1 hour intervals

Operation Indication

TEST RUN Mode

Room Temperature Display

Self-Diagnosis function

Only 20mm thick

3-Step Fan Speed selection

LCD Wired Remote Controller

(Ceiling Duct Type)

24-Hour ON/ OFF Timer in 1hour intervals

Operation Indication

TEST RUN Mode

Room Temperature Display

Self-Diagnosis function

Only 20mm thick

3-Step Fan Speed selection

LCD Wireless Remote Controller

New Leader in Multi V Technology

Header Branch

ARBL054
12.7
15.88

Gas

Line Branch

19.05

4.5HP

6.35
9.52

Liquid
12.7

ARBL052S

15.9

15.9
19.1

ARBL057
12.7

12.7

Gas

15.88

Gas
15.9
12.7

19.05

4.5HP

4.5HP
Less than 29K

6.35

9.5
6.4

9.5

9.52

Liquid

Liquid

9.5
6.4

12.7

ARBL052L

19.1

25.4

ARBL104
15.88

15.9

19.1

Gas

19.05

Gas
15.9
12.7

28.58

4.5HP
29K or more

12.7
12.7

6.35
9.52

Liquid

Liquid

9.5
6.4

ARBL102S

12.7

19.1
15.9

15.9
19.1

Gas

12.7
15.9
12.7

ARBL107
15.88
19.05

Gas
28.58

10HP

10HP

Less than 61K

6.35

12.7
9.5

12.7

9.52

Liquid

Liquid

ARBL102L

10HP

9.5

9.5
6.4

12.7

28.6

28.6

ARBL1010

12.7
15.88

25.4

25.4

15.88

Gas

19.1
15.9

19.1

19.1

Gas

19.05

28.58

10HP
61K or more

12.7
15.9
12.7

Liquid

10HP

15.9
12.7
12.7
9.5
6.4

6.35

Liquid

9.52

12.7

33

Specifications

Outdoor Unit
Model

CRUN458S0

Cooling Capacity

(kW)

Heating Capacity

28.0

(kcal/h)

11,200

24,000

(Btu/hr)

44,000

95,500

(kW)
(kcal/h)
(Btu/hr)

Casing Color
Dimensions (WxHxD)

EER

COP

IVORY

900*1,225*370

1,246*1,519*700

(inch)

35.43*48.42*13.57

49.07*58.84*27.56
8.93

Heating

Btu/hrW

10.00

10.24
2.67 (2.25)

Cooling

W/W (kcal/hrW)

2.56 (2.08)

Heating

W/W (kcal/hrW)

2.93 (2.37)

3.00 (2.53)

-5~43 / -10~16

-5 ~48 / -20 ~ 21

Model

JT100BEVYE

JT100BEVTYE + JT212DATYE

Hermetically Sealed Scroll Type

Hermetically Sealed Scroll Type

cm3/rev

53.4

53.4+117.3

r.p.m

6,750

6,750, 3,450

3.5 x 1

(3.5 + 3.75) x 1

Starting Methed

Direct on Line

Direct on Line

Model

OBM-4012P2

ARE676E01

Type

Propeller Fan

Propeller Fan

84*2

271*2

kW

Motor Output x Number


Air Flow Rate(High)

W
cmm

70

180

cfm

2471

6354

Capacitor Run

Capacitor Run

Drive
Liquid Side

mm(inch)

12.7(1/2)

15.88(5/8)

Gas Side

mm(inch)

19.05(3/4)

28.58(1 1/8)

kg(lbs)

125

300

dBA

57

60

High Pressure Switch, Fan Motor Safety

High Pressure Switch, Fan Motor Safety

Thermostat, Inverter Overload Protector,

Thermostat, Inverter Overload Protector,

Over Current Relay, Fusible Plugs, Fuse

Over Current Relay, Fusible Plugs, Fuse

Net Weight
Noise Level(Sound Press, 1m, H/L/M)
Safety Device

Defrost Method
Control range of capacity

%
Refrigerant Name

Deicer

Deicer

10~115

10~130

R407C

R408C

Charge

3.5

10

Control

L.E.V.

L.E.V.

DAPHNE FVC68D

DAPHNE FVC68D

Refrigerant Oil
Charge Volume

Power Supply

107,500

8.24

Motor Output x Number

Refrigerant Oil

48,000

Btu/hrW

Number of Revolution

Refrigerant

27,080

Cooling

Piston Displacement

Pipe connections

31.5

12,091

(mm)

Type

Fan

14.1

WARM GRAY

Setting temperature range(Cooling/Heating)


Compressor

CRUN1008T0

13.0

CC
,V,Hz

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

New Leader in Multi V Technology

1,200

1,800

3, 380~415, 50

3, 380~415, 50

Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

Indoor unit | Wall Mounted Type


Model

CRNN076SRA0

CRNN096SRA0

CRNN126SRA0

CRNN186STA0

2,100

2,600

3,500

5,300

3,500

kcal/h

1,806

2,235

3,009

4,557

3,009

Btu/h

7,165

8,871

11,942

18,084

11,942

Kw

2,363

2,925

3,938

5,963

3,938

kcal/h

2,031

2,515

3,385

5,127

3,385

Btu/h

8,061

9,980

13,435

820,345

13,453

Cooling Capacity

Heating Capacity

Dimensions (W*H*D)

Coil

Rows x Steps x FPI

Moisture removal

mm

900*285*156

900*285*156

900*285*156

1090*314*172

570*570*137

inch

35.4*11.2*6.1

35.4*11.2*6.1

35.4*11.2*6.1

42.9*12.4*6.8

22.4*22.4*5.4

mm

2*12*20

2*12*20

2*12*20

2*132*20

2*132*20

l/h.

1.0

1.0

1.2

2.2

1.5

Cross Flow Fan

Cross Flow Fan

Cross Flow Fan

Cross Flow Fan

Turbo Fan

Type
Fan

Motor Output x Number


Air Flow Rate(High)

CRNN126SPA0

7.5

7.5

14.4

22

24

cmm

5.6

6.0

9.5

13.5

8.7

cfm

196

212

336

477

307

Phase control

Phase control

Phase control

Phase control

Phase control

Sound Absorbing Thermal Insulation Material

Foamed polystyrene

Foamed polystyrene

Foamed polystyrene

Foamed polystyrene

Foamed polystyrene

Air Filter

Resin Net(Washable)

Resin Net(Washable)

Resin Net(Washable)

Resin Net(Washable)

(Washable)

Fuse

Fuse

Fuse

Fuse

Fuse

Drive
Temperature Control

Microprocessor, Thermostat for cooling and heating

Safety Device
Pipe
Connections

Liquid Side

mm(inch)

6.35 (1/4)

6.35 (1/4)

6.35 (1/4)

9.52(3/8)

6.35(1/4)

Gas Side

mm(inch)

12.7 (1/2)

12.7 (1/2)

12.7 (1/2)

15.88 (5/8)

12.7(1/2)

25

25

25

25

12.2

7(15.4)

7(15.4)

8(17.6)

12(26.5)

35(77.2)

Drain Pipe(Internal Dia.)


Net Weight

kg(lbs)

Noise Level (Sound Press,1m, H/M/L)


Power Supply
Power Cable
Refrigerant Control

mm

dB3
,V,Hz

AWG#:P*mm2

33 / 31 / 28

36 / 33 / 29

40 / 38 / 36

40 / 39 / 34

40/36/31

1,220~240,50

1,220~240,50

1,220~240,50

1,220~240,50

1,220~240,50

12:3*2.5

12:3*2.5

12:3*2.5

12:3*2.5

12:3*2.5

L.E.V

L.E.V

L.E.V

L.E.V

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

L.E.V
Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

35

Specifications

Indoor unit | Ceiling Cassette Type


Model
Cooling Capacity

Heating Capacity

CRNN076TCA0

CRNN096TCA0

CRNN126TCA0

2,100

2,600

3,500

kcal/h

1,806

2,235

3,009

Btu/h

7,165

8,871

11,942
3,938

Kw

2,363

2,925

kcal/h

2,031

2,515

3,385

Btu/h

8,061

9,980

13,435
Galvanized Steel Plate

Casing
Dimensions (W*H*D)

Coil

Rows x Steps x FPI

Moisture removal
Fan

Galvanized Steel Plate

Galvanized Steel Plate

mm

860*390*180

860*390*180

860*390*180

inch

33.8*15.3*7.0

33.8*15.3*7.0

33.8*15.3*7.0

inch

12 x 2 x 18

12 x 2 x 21

12 x 2 x 21

l/h.

1.0

1.0

1.5

AMR-023E7

AMR-023E7

AMR-023E7
Cross Flow Fan

Model
Type
Motor Output x Number
Air Flow Rate(H/M/L)

Cross Flow Fan

Cross Flow Fan

14 x 1

14 x 1

14 x 1

cmm

6/5/4

7/6/5

10/9/8

cfm
Drive

225/197/168

246/216/195

353/317/283

Phase Control

Phase Control

Phase Control

Temperature Control

Microprocessor, Thermostat for cooling and heating

Sound Absorbing Thermal Insulation Material

Foamed polystyrene

Safety Device
Pipe Connections

Fuse, Thermal Fuse for Fan Motor


Liquid Side

mm(inch)

6.35 (1/4)

6.35 (1/4)

6.35 (1/4)

Gas Side

mm(inch)

12.7 (1/2)

12.7 (1/2)

12.7 (1/2)

25

25

25

17(37.5)

17(37.5)

17(37.5)

Drain Pipe(Internal Dia.)


Net Weight

mm

kg(lbs)

Noise Level (Sound Press,1.5m, H/M/L)


Power Supply

dB3
,V,Hz

AWG#:P*mm2

Power Cable
Refrigerant Control
Decoration Panels

Panel Color

(Option)

Dimensions (W*H*D)

35/32/29

37/34/31

39/36/35

1,220~240,50

1,220~240,50

1,220~240,50

12:3*2.5

12:3*2.5

12:3*2.5

L.E.V

L.E.V

L.E.V

mm

1050*480*30

1050*480*30

1050*480*30

inch

41.3*18.9*1.2

41.3*18.9*1.2

41.3*18.9*1.2

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

New Leader in Multi V Technology

Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

Indoor unit | Ceiling Cassette Type


Model
Cooling Capacity

Heating Capacity

CRNN126TEA0

CRNN186TEA0

CRNN366TD0

3,500

5,300

10,600

kcal/h

3,009

4,557

9,114

Btu/h

11,942

18,084

36,168

Kw

3,938

5,963

11,925

kcal/h

3,385

5,127

10,253

Btu/h
Casing
Dimensions (W*H*D)

Coil

Rows x Steps x FPI

Moisture removal
Fan

13,435

20,345

40,689

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

mm

570*570*269

570*570*269

840*840*288

inch

22.4*22.4*10.5

22.4*22.4*10.5

33.0*33.0*11.3

inch

2*11*19

2*11*19

2*12*21

l/h.

1.0

1.9

4.0

IC-9630LGAC

IC-9630LGAC

IC-1630LGPJ

Turbo Fan

Turbo Fan

Turbo Fan

20

22.4

52.5

11 / 10 / 9

13 / 12 / 10

25 / 23 / 21

Model
Type
Motor Output x Number
Air Flow Rate(H/M/L)

W
cmm
cfm

Drive

388/353/318

459/423/353

883/812/742

Phase control

Phase control

Phase control

Temperature Control

Microprocessor, Thermostat for cooling and heating

Sound Absorbing Thermal Insulation Material


Safety Device
Pipe Connections

Foamed polystyrene

Foamed polystyrene

Foamed polystyrene

Fuse, Thermal Fuse for Fan Motor

Fuse, Thermal Fuse for Fan Motor

Fuse, Thermal Fuse for Fan Motor

Liquid Side

mm(inch)

6.35 (1/4)

9.52 (3/8)

9.52 (3/8)

Gas Side

mm(inch)

12.7 (1/2)

15.88 (5/8)

19.05 (3/4)

Drain Pipe(Internal Dia.)


Net Weight

mm
kg(lbs)

Noise Level (Sound Press,1.5m, H/M/L)


Power Supply

dB3
,V,Hz

Panel Color

(Option)

Dimensions (W*H*D)

25
32(70.5)

38/35/32

41 / 39 / 37

40 / 38 / 36

1,220~240,50

1,220~240,50

12:3*2.5

12:3*2.5

12:3*2.5

L.E.V

L.E.V

L.E.V

White

White

White

Refrigerant Control
Decoration Panels

25
19(41.9)

1,220~240,50

AWG#:P*mm2

Power Cable

25
19(41.9)

mm

670*670*30

670*670*30

950*950*30

inch

26.4*26.4*1.2

26.4*26.4*1.2

37.4*37.4*1.2

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

37

Specifications

Indoor unit | Ceiling Concealed Duct Type


Model

CRNN186BHA0

Cooling Capacity

Heating Capacity

5,300

7,000

kcal/h

4,557

6,019

Btu/h

18,084

23,885

Kw

5,963

7,875

kcal/h

5,127

6,771

Btu/h

20,345

26,870

Galvanized Steel Plate

Galvanized Steel Plate

Casing
Dimensions (W*H*D)

Coil

mm

Rows x Steps x FPI

Moisture removal

880*260*450

880*260*450

inch

34.6*10.2*17.7

34.6*10.2*17.7

inch

2*10*21

3*10*21

l/h.

2.0

2.5

IC-13450LG13C

IC-13450LG13C

Sirocco Fan

Sirocco Fan

Model
Type
Fan

Motor Output x Number


Air Flow Rate(H/M/L)

External Static Pressure

118

118

cmm

16.5 / 14.5 / 13

18 / 16.5 / 14

cfm

583 / 512 / 459

636 / 583 / 494

Pa

78.5

78.5

Phase control

Phase control

Drive
Temperature Control

Microprocessor, Thermostat for cooling and heating

Sound Absorbing Thermal Insulation Material

Foamed polystyrene

Air Filter
Safety Device

Pipe Connections

Accossory

Fuse, Thermal Fuse for Fan Motor

Fuse, Thermal Fuse for Fan Motor

mm(inch)

9.52 (3/8)

9.52 (3/8)

Gas Side

mm(inch)

15.88 (5/8)

15.88 (5/8)

Drain Pipe(Internal Dia.)

mm
kg(lbs)

Noise Level (Sound Press,1.5m, H/M/L)

Power Cable

Foamed polystyrene

Accossory

Liquid Side

Net Weight

Power Supply

CRNN246BHA0

dB3
,V,Hz
AWG#:P*mm2

Refrigerant Control

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

New Leader in Multi V Technology

25

25

34(74.9)

35(77.2)

36 / 34 / 32

48 / 45 / 32

1,220~240,50

1,220~240,50

12:3*2.5

12:3*2.5

L.E.V

L.E.V

Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

Indoor unit | Ceiling Concealed Duct Type


Model
Cooling Capacity

Heating Capacity

CRNN076BNG0

CRNN096BJG0

CRNN126BJG0

2,100

2,600

3,500

kcal/h

1,806

2,235

3,009

Btu/h

7,165

8,871

11,942

2,363

2,925

3,938

kcal/h

2,031

2,515

3,385

Btu/h
Casing
Dimensions (W*H*D)

Indoor Coil

Tube Size(OD)

8,061

9,980

13,435

Galvanized Steel Plate

Galvanized Steel Plate

Galvanized Steel Plate

mm

783*220*520

873*220*520

873*220*520

inch

30.8*8.7*20.5

34.4*8.7*20.5

34.4*8.7*20.5

0.375(9.52)

0.375(9.52)

0.375(9.52)

14

14

14

D-7K

D-9K

D-12K

inch(mm)

Fins per inch


Indoor Fan

Model

motor

Type

Condenser inducted

Condenser inducted

Condenser inducted

Indoor Fan

Type

Sirocco Fan

Sirocco Fan

Sirocco Fan

1/150

1/150

2/150

730/670/620

590/540/510

810/720/650

No. Used/Diameter

EA/(mm)

Motor Step
Indoor Fan RPM

Indoor

(H/M/L)

Temperature Controller
Air Circulation
Pipe Connections

Drain Hose

6.4/6.0/5.4

7.0/6.5/6.0

10.2/9.2/8.2

Liquid Side

mm(inch)

6.35 (1/4)

6.35 (1/4)

6.35 (1/4)

Gas Side

mm(inch)

12.7 (1/2)

12.7 (1/2)

12.7 (1/2)
25

In diameter

mm

25

25

Out diameter

mm

30

30

30

kg(lbs)

24(52.9)

26(57.3)

26(57.3)

dB3

36/34/32

37/35/33

38/36/34

,V,Hz

1,230,50

1,230,50

1,230,50

L.E.V

L.E.V

L.E.V

R407C

R407C

R407C

Net Weight
Noise Level (Sound Press,1m, H/M/L)
Power Supply

Thermistor
CMM(CFM)

Refrigerant Control
Refrigerant Charge
Dimensions (W*H*D)

type
mm

783*220*520

873*220*520

873*220*520

inch

30.8*8.7*20.5

34.3*8.7*20.5

34.3*8.7*20.5

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

39

Specifications

Indoor unit | Ceiling and Floor Type


Model

CRNN186VBA0

Cooling Capacity

Heating Capacity

4,557

Btu/h

18,084

Kw

5,963

kcal/h

5,127

Btu/h

20,345

Casing

White

Dimensions (W*H*D)

Coil

Rows x Steps x FPI

Moisture removal

mm

1200*615*205

inch

47.24*24.21*8.07

inch

2*12*18

l/h.
Model

Cross Flow Fan

Motor Output x Number

Air Flow Rate(High)

cmm

cfm

Phase control

Temperature Control

Microprocessor, Thermostat for cooling and heating

Sound Absorbing Thermal Insulation Material

Foamed polystyrene

Air Filter

Accossory

Safety Device

Fuse, Thermal Fuse for Fan Motor


Liquid Side

mm(inch)

9.52 (3/8)

Gas Side

mm(inch)

15.88 (5/8)

Drain Pipe(Internal Dia.)


Net Weight

Power Cable

mm
kg(lbs)

Noise Level (Sound Press,1.5m, H/M/L)


Power Supply

30
13.5
477

Drive

Pipe Connections

2.5
IC-9430LGCG

Type
Fan

5,300

kcal/h

dB3
,V,Hz
AWG#:P*mm2

Refrigerant Control

17
30(66.1)
43 / 40 / 37
1,220~240,50
12:3*2.5
L.E.V

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

New Leader in Multi V Technology

Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

Indoor unit | Floor Standing(exposed) Type


Model
Cooling Capacity

Heating Capacity

CRNN076CAA0

CRNN096CAA0

CRNN126CAA0

CRNN186CAA0

CRNN246CAA0

2,100

2,600

3,500

5,300

7,000

kcal/h

1,806

2,235

3,009

4,557

6,019

Btu/h

7,165

8,871

11,942

18,084

23,885
7,875

2,363

2,925

3,938

5,963

kcal/h

2,031

2,515

3,385

5,127

6,771

Btu/h

8,061

9,980

13,435

20,345

26,870

mm

1050*620*218

1170*620*218

1170*620*218

1410*620*218

1530*620*218

inch

41.3*24.4*8.6

46.1*24.4*8.6

46.1*24.4*8.6

55.5*24.4*8.6

60.2*24.4*8.6

0.375(9.52)

0.375(9.52)

0.375(9.52)

0.375(9.52)

0.375(9.52)

14

14

14

14

14

Casing
Dimensions (W*H*D)

Indoor Coil

Tube Size(OD)

inch(mm)

Fins per inch


Indoor Fan

Model

motor

Type

Condenser inducted

Condenser inducted

Condenser inducted

Condenser inducted

Condenser inducted

Indoor Fan

Type

Blower

Blower

Blower

Blower

Blower

2/150

2/150

2/150

3/150

3/150

Thermistor

Thermistor

Thermistor

Thermistor

Thermistor
13.2/11.7/10.2

No. Used/Diameter

EA/(mm)

Motor Step
Indoor Fan RPM

Indoor

(H/M/L)

Temperature Controller
Air Circulation
Pipe Connections

Drain Hose

CMM(CFM)

6.4/5.9/5.4

7.0/6.5/6.0

10.2/9.2/8.2

11.9/10.5/9.2

Liquid Side

mm(inch)

6.35 (1/4)

6.35 (1/4)

6.35 (1/4)

9.52 (3/8)

9.52 (3/8)

Gas Side

mm(inch)

12.7 (1/2)

12.7 (1/2)

12.7 (1/2)

15.88 (5/8)

15.88 (5/8)

15

15

15

15

15

In diameter

mm

Out diameter

mm

Net Weight
Noise Level (Sound Press,1m, H/M/L)
Power Supply

kg(lbs)

22(48.5)

25(55.1)

25(55.1)

27.5(60.6)

32.5(71.7)

dB3

36/34/32

36/34/32

37/35/34

38/36/35

40/38/36

,V,Hz

1,230,50

1,230,50

1,230,50

1,230,50

1,230,50

L.E.V

L.E.V

L.E.V

L.E.V

L.E.V

type

R407C

R407C

R407C

R407C

R407C

mm

1050*620*218

1050*620*218

1050*620*218

1410*620*218

1530*620*218

inch

41.3*24.4*8.6

41.3*24.4*8.6

41.3*24.4*8.6

55.5*24.4*8.6

60.2*24.4*8.6

Refrigerant Control
Refrigerant Charge
Dimensions (W*H*D)

Notes:
1.Capacities are based on the following conditions:
Cooling
- Indoor temp. 27C(80.6F) DB/19C(66.2F) WB
- Outdoor temp. 35C(95F) DB/24C(75.2F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
Heating
- Indoor temp. 20C(68F) DB/15C(59F) WB
- Outdoor temp. 7C(44.6F) DB/6C(42.8F) WB
- Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2.Capacities are Net Capacities.
3.Due to our policy of innovation some specifications may be changed without notification.
4.L.E.V.:Linear Expansion Valve
5.To be added for more available Models

Conversion Formula
kcal/h = kW x 860
Btu/h = kW x 3414
cfm = m3/min x 35.3

41