Documente Academic
Documente Profesional
Documente Cultură
www.elsevier.com/locate/apthermeng
Abstract
This paper describes the study carried out to analyse a refrigeration system in cascade with a compression system at the low temperature stage and an absorption system at the high temperature stage to generate cooling at low temperatures, as well as the possibility of powering it by means of a cogeneration system. CO2 and NH3 have been considered as refrigerants in the compression
stage and the pair NH3H2O in the absorption stage. The analysis has been realized by means of a mathematical model of the refrigeration system implemented in a computer program and taking into account the characteristic operating conditions of a cogeneration system with gas engines. The paper presents the results obtained regarding the performance of the refrigeration system and the
adaptability between the power requirements of the refrigeration system and the power supplied by the cogeneration system taking
into account the present Spanish Regulations about the use of cogeneration systems.
2005 Elsevier Ltd. All rights reserved.
Keywords: Cascade refrigeration; Cogeneration; Compression; Absorption
1. Introduction
The integration of environmentally friendly refrigeration with cogeneration systems [1] appears to be an
interesting option since it could lead to autonomous systems with on-site power generation independent from
the electric grid [2].
In the refrigeration eld there are applications which
require the production of very high cooling power at low
temperatures, such as freezing processes and cold stores
for the storage of frozen products. Currently, dierent
congurations of vapor compression systems of double
stage with ammonia or synthetic refrigerants are generally applied to this type of applications. Two stage vapor
compression systems in cascade are also considered in
the general literature [3]. Moreover, recently the two
stage compression systems in cascade with CO2 as refrigerant in the low temperature stage are the object of
*
Corresponding author. Tel.: +34 986 812605; fax: +34 986 811995.
E-mail address: jseara@uvigo.es (J. Fernandez-Seara).
1359-4311/$ - see front matter 2005 Elsevier Ltd. All rights reserved.
doi:10.1016/j.applthermaleng.2005.07.015
important research and nowadays there are already several industrial and commercial installations successfully
running [4,5]. However, the disadvantage of the compression systems in this type of applications is their high
electricity consumption.
In this paper the analysis of an alternative refrigeration system that could reduce the electricity consumption in those applications is realized. The system is a
two stages cascade that consists of a single stage compression system for the generation of the cooling power
at low temperature and an absorption system in the high
temperature stage, as shown in Fig. 1. Both systems
share a heat exchanger, which operates simultaneously
as the condenser of the compression system and as the
evaporator of the absorption system. This refrigeration
system would decrease the electricity consumption compared to the two stages compression systems, since it is
only required to operate the compression system at the
low stage; meanwhile the absorption system is driven
by heat. Moreover, it could use environmentally friendly
working uids such as carbon dioxide or ammonia in
503
Nomenclature
COP
E
EEE
P
PE
PER
Q
Q0
T
coecient of performance ()
electrical power (kW)
equivalent electric eciency ()
pressure (Pa)
primary energy per unit time (kW)
primary energy ratio ()
heat (kW)
cooling duty (kW)
temperature (C)
Subscripts
a
absorption system
c
compression system
com
compression, compressor
con
condensation, condenser
el
electrical
eva
evaporation, evaporator
ex
extra
exh
exhaust gases
g
global
gen
generation, generator
h
heat
int
intermediate
lim
limit
max
maximum
minEEE minimum equivalent electric eciency
opt
optimal
p
pump
rec
recovered, reused
w
water
CONDENSER
RECTIFICATION
COLUMN
GENERATOR
LIQ.-VAP.
H.EX.
EXP.
VALVE
EVAPORATORCONDENSER
EXP.
VALVE
SOLUTION
H.EX.
EXP.
VALVE
PUMP
ABSORBER
COMPRESSOR
EVAPORATOR
504
Table 1
Model input data
General system data
Cooling duty, Q0 [kW]
Evaporation temperature at the
compression system, Teva,c [C]
Condensation temperature at
the compression system, Tcon,c [C]
Generation temperature at the
absorption system, Tgen [C]
Temperature of the water used
as external cooling medium, Tw [C]
Compression system
Liquid subcooling at the
condenser outlet, GSc [C]
Vapour superheat at the
evaporator outlet, GRc [C]
Absorption system
Temperature dierence at the
evaporatorcondenser, DTevacon [C]
Outletinlet temperature dierence
in the evaporator, DTeva,a [C]
Design condenser temperature
dierence, DTcon,a [C]
Liquid subcooling at the
condenser outlet, GSa [C]
Design absorber temperature
dierence, DTabs [C]
Refrigerant concentration,
Xref [kg/kg]
Distillation tower
reux, Re []
Absorber eciency, eabs []
Solution heat exchanger
eciency, esol.HX []
Liquidvapor heat exchanger
eciency, eLV HX []
Pump eciency, ep []
Pressure drop between evaporator
and absorber, DPevaabs [bar]
1
45
2
125
30
0
5
8
5
10
0
8
0.995
0.4
0.8
0.8
0.7
0.5
0.1
1
2
505
COPg
Q0
Qgen
Ecom
0:4
Ep
0:4
3. Cogeneration system
The cogeneration system considered in the analysis is
based on the use of gas engines. The system operating
conditions have been established taken into account
general literature data [6]. The exhaust gases and the
cooling water outlet temperatures (Texh and Tw) have
been considered as 600 C and 120 C, respectively.
The heat recovered from the exhaust gases is set at
18% of the primary energy, considering a cooling limit
(Texh,lim) of 90 C. The heat recovered from the engine
cooling water is considered 25% of the primary energy,
with a cooling limit (Tw,lim) of 25 C. The electrical eciency of the cogeneration plant is taken as 40%.
If the cascade refrigeration system is powered by the
cogeneration system, then the heat recovered from the
Qexh;rec
T exh T gen
0:18
PE
T exh T exh;lim
Qw;rec
T w T gen
0:25
PE
T w T w;lim
4
5
506
given by Eq. (6), according to the present Spanish regulations [7] relating to the use of cogeneration systems.
EEE
E
rec
PE Q0:9
Ecom Ep
0:4
T T
gen
0:18 0:25 T wwT w;lim
10
12
13
If T 6 90 C ! Qex
Tw T
0:18 0:25
PEh Qgen
T w T w;lim
14
Qgen
11
Q0
PE
PERg;minEEE
15
Q0 Eex Qrec;minEEE
PE
16
The calculations described above have been implemented as a Fortran subroutine in the simulation program of the cascade refrigeration system. Then, the
adaptability of the cogeneration system to the cascade
refrigeration system can be evaluated in each simulation
run and it is included in the parametric analysis.
system. Table 1 shows the general system operating conditions considered in the analysis. The following sections
show the noteworthy results.
4.1. Cascade refrigeration system
Fig. 2 shows the direct results provided by the simulation program considering the data in Table 1 with CO2
as refrigerant in the compression system. The white
boxes on the system diagram show the heat interchanged in each heat exchanger, the electric power required by the compressor in the compression system
and by the pump in the absorption system. The numbers
next to the characteristic points of the system show the
temperature values.
The results considering NH3 as refrigerant in the
compression system are also presented by the program
on the system scheme (as shown in Fig. 2). The main differences in the operating conditions of the system using
CO2 or NH3 as refrigerants in the compression stage are
due to the characteristic thermodynamic properties of
each refrigerant. Table 2 summarizes the major dierences. Note the high pressure levels in the compression
system when using CO2, as well as the low evaporation
pressure required when using NH3 at low temperature
levels. Another signicant parameter that makes a dierence between both refrigerants is the compressor discharge temperature. The high values of the discharge
temperature produced by NH3 should be taken into account at the design stage in order to select an adequate
intermediate temperature level and avoid the wellknown problems caused by excessive discharge temperatures on the compressor lubrication. The mass ow
and the volume ow at the compressor inlet are also
quite dierent. The mass ow of CO2 is higher than
the mass ow of NH3 due to the low refrigerant eect
produced by CO2. However, the volume ow of CO2
is much smaller than the volume ow of NH3 due to
the low specic volume of the CO2 at the compressor inlet state. The electric power required by the compressor
is slightly lower when using CO2 than when using NH3.
507
Table 2
Cascade system operating conditions with CO2 and NH3 as refrigerants in the compression stage
Cascade system operating conditions
CO2
NH3
8.427
33.472
14.762
0.702
53.14
1.262
0.143
3.976
2.953
6.204
96.73
1.233
0.384
2.602
0.427
0.253
0.406
2.463
0.427
0.254
COPc (-40)
COPg (-30)
COPc (-30)
COPa
COPg (-50)
11
0.55
10
0.50
0.45
0.40
COPc
7
0.35
6
0.30
5
COPa, COPg
508
0.25
0.20
0.15
2
1
0.10
-16
-12
-8
-4
12
16
Tint [C]
Fig. 3. Compression system COP (COPc), absorption system COP (COPa) and cascade system COP (COPg) vs. intermediate temperature level
(condensation temperature of the compression system) with CO2 as refrigerant in the compression stage and for evaporation temperatures of 30,
40 and 50 C.
COPg,max (CO2)
PERg,max (CO2)
COPg,max (NH3)
PERg,max (NH3)
1
0
-1
Tint,opt [C]
-2
-3
-4
-5
-6
-7
-8
-9
-50
-48
-46
-44
-42
-40
-38
-36
-34
-32
-30
Teva [C]
Fig. 4. Optimal intermediate temperature level (condensation temperature of the compression system) for maximum system COP and for maximum
PER with a EEE of 55% vs. evaporation temperature at the compression stage with CO2 and NH3 as refrigerants in the compression system.
with CO2 and NH3 as a function of the evaporation temperature. Results in Fig. 4 corroborate clearly that the
optimal intermediate temperature increases when the
evaporation temperature increases with both refrigerants. However, the eect of the evaporation temperature
on the optimal intermediate temperature is more signicant with NH3 than with CO2. The eects of the
absorption system design parameters such as the generation and the external cooling medium temperatures are
not presented here for the sake of brevity but they can
be established from data in Ref. [11].
It is noticeable that the optimal intermediate temperature level should be determined in a previous design
stage because of its inuence on the cascade system.
Therefore, the results from the simulation model can
be an outstanding tool at the design stage of the system.
4.2. Cogeneration system
Results for the signicant parameters required to
evaluate the suitability of powering the cascade refrigeration system by means of the cogeneration system
taking into account the use of CO2 and NH3 as refrigerants in the compression stage are collected in Table 3.
They have been obtained considering the data in Table 1
and expressed per unit of cooling power.
Results in Table 3 show clearly that the limiting
power is the heat required by the absorption system.
The primary energy needed to obtain the heat required
by the generator is much greater than the primary
energy per unit time needed to obtain the electricity
required by the cascade system. Therefore, taken into
account that the cogeneration system supplies the heat
required by the cascade system, then the electric power
generated by the cogeneration system surpasses the electric power required by the cascade system. Thus, there
will be extra electric power for selling or reusing in other
applications. These results express clearly that the energy requirements of the cascade refrigeration are very
dierent from the energy supplied by the cogeneration
509
system. They demonstrate the untting of the cogeneration system to the energy needs of the cascade system.
Another signicant result shown in Table 3 is the very
low value of the EEE obtained from the energy requirements of the cascade refrigeration system. It also clearly
shows that the electric to heat ratio required by the cascade system does not match the energy ratio provided by
the cogeneration system. The EEE is also much smaller
than the minimum value imposed by the Spanish Regulations of 0.55. Therefore, from the results obtained, it is
concluded that the use of a cogeneration system only to
power the absorptioncompression refrigeration system
should be discarded. Furthermore, if the cogeneration
system is used to power the cascade refrigeration system
and the extra electric power is reused or put on the market but no additional heat is recovered, then the EEE of
the cogeneration system is still below the limiting value
imposed by the Spanish regulations. Therefore, it would
be necessary to reuse in other applications part of the
heat that is not required by the refrigeration system in
order to attain the minimum value imposed to the
EEE. Therefore, it can be concluded that, if the cogeneration system is used to power the cascade refrigeration
system, then it will be necessary to make use of the extra
electric power and part of the extra heat in other applications, in order to full the present Spanish
Regulations.
The value of the PER of the global system (refrigeration and cogeneration system) without considering the
use of any extra electric or heat in other applications
is shown in Table 3. This result also reinforces the conclusion of discarding the option of coupling the cascade
refrigeration system with the cogeneration system as a
stand-alone unit.
The parametric analysis has been extended to the
parameters shown in Table 3 taking into account CO2
and NH3 as refrigerants in the compression stage. The
signicant results obtained considering the variation of
the intermediate temperature are shown in the following
gures.
Table 3
Refrigeration and cogeneration systems operating conditions
Operating conditions
CO2
NH3
2.933
0.384
0.025
0.41
17.497
1.024
6.589
0.029
0.492
1.361
0.057
0.512
2.865
0.406
0.025
0.431
17.09
1.078
6.405
0.031
0.491
1.33
0.059
0.511
510
Fig. 5 shows the eect of the intermediate temperature level (the condensation temperature of the compression system) on the EEE taking into account
evaporation temperatures of 30, 40 and 50 C
and CO2 and NH3 as refrigerants in the compression
system, when the cogeneration system attends only the
energy demands of the cascade refrigeration system.
The more signicant results are the very small values
of the EEE. It points out again the mismatch between
the energy requirements of the cascade system and the
energy distribution provided by the cogeneration system. The increase of the EEE when increasing the intermediate temperature is due to an increase in the
electrical power demanded by the compression system
and simultaneously to the reduction of the heat demanded by the absorption system. Therefore, if the
intermediate temperature increases, then the electrical
to heat ratio required by the cascade system will approach the energy ratio provided by the cogeneration
system.
Fig. 6 shows the extra electric energy and heat that
should be reused in other applications in order to attain
the minimum value of the EEE imposed by the Spanish
regulations taking into account the evaporation temperatures of 30, 40 and 50 C and CO2 as refrigerant
in the compression system, when the intermediate temperature level is varied. The surplus of the electrical
power decreases as the intermediate temperature in-
0.07
0.06
EEE
0.05
0.04
0.03
0.02
0.01
-16
-12
-8
-4
12
16
Tint [C]
Fig. 5. Equivalent electric eciency (EEE) vs. intermediate temperature level (condensation temperature at the compression stage) with CO2 and
NH3 as refrigerants in the compression system and evaporation temperatures of 30, 40 and 50 C.
Eex,minEEE (-50)
Eex,minEEE (-40)
rec,minEEE
(-40)
rec,minEEE
511
(-30)
Eex,minEEE (-30)
12
4.0
11
3.5
10
2.5
Eex,minEEE [kW]
Qrec,minEEE [kW]
3.0
7
2.0
6
1.5
5
1.0
4
-16
-12
-8
-4
0
Tint [C]
12
16
Fig. 6. Electricity surplus and heat that should be recovered in other application in order to attain the minimum EEE of 55% vs. the intermediate
temperature level (condensation temperature at the compression stage).
PERg,minEEE (-50)
PERg,minEEE (-40)
PERg,minEEE (-30)
PERg (-50)
PERg (-40)
PERg (-30)
0.54
0.07
0.53
0.52
0.06
0.50
0.05
PERg,minEEE
PER g
0.51
0.49
0.04
0.48
0.47
0.03
0.46
-16
-12
-8
-4
12
16
Tint [C]
Fig. 7. Primary energy ratio of the cascade-cogeneration system taking into account that the cogeneration system is used to power only the cascade
refrigeration system (PERg) and also considering the reusing of the extra electric and the extra heat needed to attain the EEE of 55% (PERg,minEEE)
vs. the intermediate temperature level (condensation temperature at the compression stage) with CO2 as refrigerant in the compression system and for
evaporation temperatures of 30, 40 and 50 C.
512
presents a maximum. The optimal intermediate temperatures from the viewpoint of the maximum global PER
considering CO2 and NH3 as refrigerants in the compression system as a function of the evaporation temperature are shown in Fig. 4. The intermediate temperature
that provides the maximum value for the global PER
does not coincide with the intermediate temperature that
provides the maximum COP of the cascade refrigeration
system (see Fig. 4). Therefore, if the cogeneration system
is used only to power the cascade refrigeration system,
then the intermediate temperature level should be selected based on the maximum of the global PER. Moreover, it can be seen that the optimal intermediate
temperature increases when the evaporation temperature increases with both refrigerants. However, the increase of the optimal intermediate temperature is
higher with NH3 than with CO2 as shown in Fig. 4.
References
5. Conclusions
The results shown in this paper and the results obtained in the complete analysis about the compressionabsorption cascade refrigeration system and the
possibilities of being powered by a cogeneration system
allows us to draw the following conclusions.
The use of CO2 or NH3 as refrigerants in the compression stage does not aect signicantly the operating
conditions at the absorption stage due to the condensation heat is similar with both refrigerants.
The intermediate temperature level is an important
design parameter that causes an opposite eect on the
COP of the compression and absorption systems. Therefore, the cascade system COP presents a maximum when
the intermediate temperature is varied. The intermediate
temperature that produces the maximum COP depends
on the evaporation temperature of the compression system. The eect of the evaporation temperature on the
optimal intermediate temperature is more signicant
with NH3 than with CO2 as refrigerant in the compression system. The optimal intermediate temperature level
should be determined in a previous design stage because
of its inuence on the cascade system. Therefore, the results from the simulation model can be an outstanding
tool at the system design stage.
The very low values of the EEE and the PER obtained when the cogeneration system is used only to
power the cascade refrigeration system show clearly that
the energy requirements of the cascade system and the
energy distribution provided by the cogeneration system
are very dierent. Therefore, the idea of powering the