Boilers
A boiler is a device made from copper, steel, or cast iron to transfer heat from a combustion chamber (or electric
resistance coil) to water in either the liquid phase, vapor phase, or both. Boilers are classified both by the fuel used and by
the operating pressure. Fuels include gas, fuel oils, wood, coal, refuse-derived fuels, or electricity. This section focuses on
fossil fuel fired boilers. Boilers produce either hot water or steam at various pressures. Although water does not literally
boil in hot water boilers, they are called boilers, nevertheless. Steam is an exceptionally effective heat transport fluid due
to its very large heat of vaporization and coefficient of heat transfer, .
Pressure classifications for boilers for buildings are
Low Pressure:
Steam boilers with operating pressures below 15 psig (100 kPa). Hot water boilers
with pressures below 150 psig (1000 kPa); temperatures are limited to 250F (120C).
High Pressure:
Steam boilers with operating pressures above 15 psig (100 kPa). Hot water boilers
with pressures above 150 psig (1000 kPa); temperatures are above 250F (120C).
Heat rates
for steam boilers are often expressed in lbm
of steam produced per hour (or kW). The heating value of steam for these purposes is rounded off to 1000 Btu/lbm
. Steam boilers are available at heat rates of 50 to 50,000 lbm of steam per hour (15 to 15,000 kW). This overlaps the upper
range of furnace sizes noted in the previous section. Steam produced by boilers is used in buildings for space
heating, water heating, and absorption cooling. Water boilers are available in the same range of sizes as
are steam boilers: 50 to 50,000 MMBtu/hr (15 to 15,000 kW). Hot water is used in buildings for space
and water heating.
Since the energy contained in steam and hot water within and flowing through boilers is very large,
an extensive codification of regulations has evolved to assure safe operation. In the U.S. the ASME Boiler and Pressure
Vessel Code governs construction of boilers. For example, the Code sets the limits oftemperature and pressure on low
pressure water and steam boilers listed above. Large boilers are constructed from steel or cast iron. Cast iron boilers are
modular and consist of several identical heat transfer sections bolted and gasketed together to meet the required output
rating.Steel boilers are not modular but are constructed by welding various components together into one assembly. Heat
transfer occurs across tubes containing either the fire or the water to be heated. The former are called fire-tube boilers and
the latter water-tube boilers. Either material of construction can result in equally efficient designs. Small, light boilers of
moderate capacity are sometimes needed for use in buildings. For these applications, the designer should consider the use
of copper boilers.

Boiler Design and Selection for Buildings


The HVAC engineer must specify boilers based on a few key criteria. This section lists these but does
not discuss the internal design of boilers and their construction. Boiler selection is based on the
following criteria:
Boiler fuel type, energy content, heating value including altitude effects if gas fired (no effect
for coal or fuel oil boilers).
Required heat output net output rating in MMBtu/hr (kW)

Operating pressure and working fluid


Efficiency and part load characteristics
Other space needs, control system, combustion air requirements, safety requirements, ASME
code applicability

EXAMPLE OF BOILER:

Boiler cross-sectional drawing showing burner, heat exchanger, and flue connection. (From Rabl,A. and Kreider
J.F.,Heating and Cooling of Buildings , McGraw-Hill, New York, NY, 1994. With permission.)
The boiler heat output required for a building is determined by summing the
maximum heatingrequirement of all zones or loads serviced by the boiler during peak demand for steam or hot water and
adding to that (1) parasitic losses including piping losses and (2) initial loop fluid warm-up. Simply adding all of the peak
heating unit capacities of all the zones in a building can result in an oversized boiler since the zones do not all require peak
heating simultaneously. The ratio of the total of all zone loads under peak conditions to the total heating capacity installed
in a building is called the diversity.Additional boiler capacity may be needed to recover from night setback in massive
buildings. This transient load is called the pickup load and must be accounted for in both boiler and terminal heatingunit
sizing. Boilers are often sized by their sea-level input fuel ratings. Of course, this rating must be multiplied by the
applicable efficiency to determine the gross output of the boiler. In addition, if a gas boiler is not to be located at sea level,
the effect of altitude must be accounted for in the rating. Some boiler designs use a forced draft burner to force additional
combustion air into the firebox to offset part of the effect of altitude. Also, enriched or pressurized gas may be provided at
high altitude so that the heating value per unit volume is the same as at sea level.

Boilers can be classified into the following configurations:

http://upload.wikimedia.org/wikipedia/commons/3/3a/water boiler_3_english.png

Fire-tube boiler. Here, water partially fills a boiler barrel with a small volume left above to accommodate the
steam (steam space). This is the type of boiler used in nearly all steam locomotives. The heat source is inside a furnace
or firebox that has to be kept permanently surrounded by the water in order to maintain the temperature of the heating
surface just below boiling point. The furnace can be situated at one end of a fire-tube which lengthens the path of the hot
gases, thus augmenting the heating surface which can be further increased by making the gases reverse direction through a
second parallel tube or a bundle of multiple tubes (two-pass or return flue boiler); alternatively the gases may be taken
along the sides and then beneath the boiler through flues (3-pass boiler). In the case of a locomotive-type boiler, a boiler
barrel extends from the firebox and the hot gases pass through a bundle of fire tubes inside the barrel which greatly
increase the heating surface compared to a single tube and further improve heat transfer. Fire-tube boilers usually have a
comparatively low rate of steam production, but high steam storage capacity. Fire-tube boilers mostly burn solid fuels, but
are readily adaptable to those of the liquid or gas variety.

http://upload.wikimedia.org/wikipedia/commons/3/3a/Steam_Boiler_3_english.png
Water-tube boiler. In this type, the water tubes are arranged inside a furnace in a number of possible
configurations: often the water tubes connect large drums, the lower ones containing water and the upper ones, steam and
water; in other cases, such as a monotube boiler, water is circulated by a pump through a succession of coils. This type
generally gives high steam production rates, but less storage capacity than the above. Water tube boilers can be designed to

exploit any heat source and are generally preferred in high pressure applications since the high pressure water/steam is
contained within small diameter pipes which can withstand the pressure with a thinner wall.

Pot boiler" or "Haycock boiler": a primitive "kettle" where a fire heats a partially filled water container from
below. 18th century Haycock boilers generally produced and stored large volumes of very low-pressure
steam, often hardly above that of the atmosphere. These could burn wood or most often, coal. Efficiency was
very low.

Boiler fittings and accessories

Safety valve: It is used to relieve pressure and prevent possible explosion of a boiler.

Water level indicators: They show the operator the level of fluid in the boiler, also known as a sight glass, water
gauge or water column is provided.

Bottom blowdown valves: They provide a means for removing solid particulates that condense and lie on the bottom
of a boiler. As the name implies, this valve is usually located directly on the bottom of the boiler, and is occasionally
opened to use the pressure in the boiler to push these particulates out.

Continuous blowdown valve: This allows a small quantity of water to escape continuously. Its purpose is to prevent
the water in the boiler becoming saturated with dissolved salts. Saturation would lead to foaming and cause water
droplets to be carried over with the steam - a condition known as priming. Blowdown is also often used to monitor the
chemistry of the boiler water.

Flash Tank: High pressure blowdown enters this vessel where the steam can 'flash' safely and be used in a lowpressure system or be vented to atmosphere while the ambient pressure blowdown flows to drain.

Automatic Blowdown/Continuous Heat Recovery System: This system allows the boiler to blowdown only when
makeup water is flowing to the boiler, thereby transferring the maximum amount of heat possible from the blowdown
to the makeup water. No flash tank is generally needed as the blowdown discharged is close to the temperature of the
makeup water.

Hand holes: They are steel plates installed in openings in "header" to allow for inspections & installation of tubes and
inspection of internal surfaces.

Steam drum internals, A series of screen, scrubber & cans (cyclone separators).

Low- water cutoff: It is a mechanical means (usually a float switch) that is used to turn off the burner or shut off fuel
to the boiler to prevent it from running once the water goes below a certain point. If a boiler is "dry-fired" (burned
without water in it) it can cause rupture or catastrophic failure.

Surface blowdown line: It provides a means for removing foam or other lightweight non-condensible substances that
tend to float on top of the water inside the boiler.

Circulating pump: It is designed to circulate water back to the boiler after it has expelled some of its heat.

Feedwater check valve or clack valve: A non-return stop valve in the feedwater line. This may be fitted to the side
of the boiler, just below the water level, or to the top of the boiler. [3]

Top feed: In this design for feedwater injection, the water is fed to the top of the boiler. This can reduce boiler fatigue
caused by thermal stress. By spraying the feedwater over a series of trays the water is quickly heated and this can
reduce limescale.

Desuperheater tubes or bundles: A series of tubes or bundles of tubes in the water drum or the steam drum designed
to cool superheated steam. Thus is to supply auxiliary equipment that does not need, or may be damaged by, dry
steam.

Chemical injection line: A connection to add chemicals for controlling feedwater pH.
Steam accessories

Main steam stop valve:

Steam traps:

Main steam stop/Check valve: It is used on multiple boiler installations.

Combustion accessories

Fuel oil system:fuel oil heaters

Gas system:

Coal system:

Soot blower

Other essential items

Pressure gauges:

Feed pumps:

Fusible plug:

Inspectors test pressure gauge attachment:

Name plate:

Registration plate:

Auxiliary Steam Equipment


Steam systems have additional components needed to provide safety or adequate control in building thermal
systems. This section provides an overview of the most important of these components including steam traps and relief
valves.Steam traps are used to separate both steam condensate and noncondensable gases from live steam in steam piping
systems and at steam equipment. Steam traps trap or confine steam in heating coils, for example, while releasing
condensate to be revaporized again in the boiler. The challenge in trap selection is to assure that the condensate and gases
are removed promptly and with little to no loss of live steam. For example, if condensate is not removed from a heating
coil, it will become waterlogged and havemuch reduced heating capacity. A brief description of the most common types of
traps which should be used in HVAC applications follows.

Steam traps. (a) Disc trap; (b) thermostatic trap; (c) mechanical, inverted bucket trap. (From Rabl,
A. and Kreider J.F., Heating and Cooling of Buildings, McGraw-Hill, New York, NY, 1994. With permission.)

This type of trap operates on kinetic energy changes as condensate flows through and flashes into steam within
the trap. Steam flashed (i.e., converted from hot liquid to vapor) from hot condensate above the disc holds the trap closed
until the disc is cooled by cooler condensate. Steam line pressure then pushes the disc open. It remains open until all cool
condensate has been expelled and hot condensate is again present and flashes again to close the valve. The disc action is
made more rapid by the flow of condensate beneath the disc; the high velocities produce a low pressure area there in
accordance with Bernoullis equation and the disc slams shut. These traps are rugged and make a characteristic clicking
sound, making operational checking easy. They can stick open if a particle lodges in the seat. This design has relatively
high operating cost due to its live steam loss.
The bimetal unit within the housing opens the valve as condensate cools, thereby allowing condensate to exit the
trap. Significant subcooling of the condensate is needed to open the valve and operation can be slow. Other more complex
designs have more rapid response and reduced need for subcooling. The bimetal element can be replaced with a bellows
filled with an alcohol/water mixture permitting closer tracking of release setting as steam temperature changes. A trap that
has a temperature/pressure characteristic greater than the temperature/pressure of saturated steam will lose live steam,
whereas a trap with a T/p characteristic lying below the steam curve will build up condensate. The ideal trap has an
opening T/p characteristic identical with the T/p curve of saturated steam.

Piping arrangement for heating coil steam trap application. (From Rabl, A. and Kreider J.F., Heating and Cooling of
Buildings, McGraw-Hill, New York, NY, 1994. With permission.)
Mechanical traps operate on the density difference between condensate and live steam to displace afloat.
Mechanical trap the inverted-bucket trap that uses an open,upside down bucket with a small orifice. Steam flowing
with the condensate (that fills the housing outside of the bucket) fills the inverted bucket and causes it to float since the
confined steam is less dense thanthe liquid water surrounding the bucket. Steam bleeds through the small hole in the bucket
and condenses within the trap housing. As the bucket fills with condensate it becomes heavier and eventually sinks and
opens the valve. Steam pressure forces condensate from the trap. The design of this trap continuously vents
noncondensable gases, although the capacity for noncondensable gas flow (mostly air) rejection is limited by the size of
the small hole in the top of the bucket. This hole is limited in size by the need to control parasitic steam loss through the
same hole. Dirt can block the hole causing the trap to malfunction.
The trap must be mounted vertically. An inverted bucket trap has significantly smaller parasitic live steam losses than the
thermodynamic disc trap.Steam traps are used to drain condensate from steam headers and from equipment where
condensing
steam releases its heat to another fluid. Steam piping is sloped so that condensate flows to a collecting point where it is
relieved by the trap. At equipment condensate collection points, the trap is placed below the equipment where the
condensate drains by gravity.

Combustion analysis involves using the basic chemical reaction equation and the known composition of air to
determine the composition of flue gases. The inverse problem, finding the precombustion composition, is also of
importance when analyzing flue gases. The chemical reaction for stoichiometric combustion of methane is
CH4 + 2O2 -> CO2 + 2H2O

Recalling that the molecular weights are


Hydrogen (H2): 2
Methane (CH4): 16
Oxygen (O2): 32
Carbon Dioxide (CO2): 44
Water (H2O): 18
we can easily determine that 4.0 lb of oxygen per lb of methane are required for complete combustion.
Since air is 23% oxygen by weight, 17.4 lbm (or kg) of air per lbm (or kg) of fuel are required, theoretically.Operating
Characteristics of Steam Traps System needs Thermodynamics Float-thermostatic Inverted bucket
Maximum pressure (psig) 1740 465 2755

Maximum capacity (lb/h) 5250 100,000 20,500


Discharge Hot Hot Hot temperature, F (Close to saturated-steam temperature)
Discharge On/off Continuous On/off
Air venting Good Excellent Fair
Dirt handling Fair Good Good
Freeze resistance Good Poor Poor
Superheat Excellent Poor Fair
Waterhammer Excellent Fair Excellent
Varying load Good Excellent Good
Change in psi Good Excellent Fair
Backpressure Maximum 80% Good Good
Usual failure Open Closed/air vent open Open
Source: From Rabl, A. and Kreider, J.F., Heating and Coling of Buildings, McGraw-Hill, New
York, 1994. With permission.
2001 by CRC Press LLC
It is easy to show that on a volumetric basis (recall Avogadros law which states that one mole of any gas at the
same temperature and pressure occupies the same volume) the equivalent requirements are 2.0 ft3 of oxygen per ft3 of
methane for complete combustion. This oxygen requirement is equivalent to 8.7 ft3 of air per ft3 of methane. A rule of
thumb to check the preceding calculation is that 0.9 ft3 of air are required for 100 Btu of fuel heating value (about 0.25 m3
of air per MJ of heating value). For example,the heating value of natural gas is about 1000 Btu/ft3 requiring 9 ft3 of air
according to the above rule.
This compares well with the value of 8.7 ft3 previously calculated.
Combustion air is often provided in excess of this amount to guarantee complete combustion. Incomplete
combustion yields toxic carbon monoxide (CO) in the flue gas. This incomplete combustion is to be avoided not only as
energy waste but as air pollution. The amount of excess air involved in combustion is usually expressed as the excess air
fraction fexc air:

The amount of excess air provided is critical to the efficiency of a combustion process. Excessive air
both reduces combustion temperature (reducing heat transfer rate to the working fluid) and results in excessive heat loss
through the flue gases. Insufficient excess air results in incomplete combustion and loss of chemical energy in the flue
gases. The amount of excess air provided varies with the fuel and with the design of the boiler (or furnace).
Recommendations of the manufacturer should be followed. The optimum excess air fraction is usually between 10 and
50%.Flue gas analysis is a method of determining the amount of excess air in a combustion process. This information can
be used to find an approximate value of boiler efficiency. Periodic, regular analysis can provide a trend of boiler efficiency
with time, indicating possible problems with the burner or combustion equipment in a boiler or furnace. Flue gas analysis
is often expressed as the volumetric fraction of flue gases oxygen, nitrogen, and carbon monoxide. If these three values
are known, the excess air (%) can be found from (ASHRAE, 1997).

Example 2 Flue gas analysis


The volumetric analysis of flue gas from combustion of methane in a gas boiler is measured to be
10.5% carbon dioxide
3.2% oxygen
86.3% nitrogen
0% carbon monoxide
Find the amount of excess air. Is it within the recommended range suggested above?
Equation 4.1.5 will be used as follows:

The excess air is 16.3%, within the 10 - 50% range above

The efficiency of a steam boiler can be found from field measurements by:

Boiler Efficiency and Energy Calculations


A simpler, overall efficiency equation can be used for boiler energy estimates if the steam rate required

The loss term includes five parts:


1. Sensible heat loss in flue gases
2. Latent heat loss in flue gases due to combustion of hydrogen
3. Heat loss in water in combustion air
4. Heat loss due to incomplete combustion of carbon
5. Heat loss from unburned carbon in ash (coal and fuel oil)
Boilers can be tested for efficiency in laboratories and rated in accordance with standards issued by the Hydronics
Institute (formerly IBR, the Institute of Boiler and Radiator Manufacturers, and the SBI, the Steel Boiler Institute), the
American Gas Association (AGA), and other industry groups. In addition to cast iron boiler ratings, IBR ratings are
industry standards for baseboard heaters and finned-tube radiation. The ratings of the Hydronics Institute apply to steel
boilers (IBR and SBI are trademarks of the Institute). SBI and IBR ratings apply to oil- and coal-fired boilers while gas
boilers are rated by the AGA.
As noted earlier, efficiency under specific test conditions has very limited usefulness in calculating the annual energy
consumption of a boiler due to significant drop off of efficiency under part load conditions. For small boilers (up to 300
MBtu/hr [90 kW]), the U.S. Department of Energy has set a method for finding the AFUE (defined in the earlier section on
furnaces). Annual energy consumption must be known in order to perform economic analyses for optimal boiler selection.
For larger boilers, data specific to a manufacturer and an application must be used in order determine annual
consumption. Efficiencies of fossil fuel boilers vary with heat rate depending on their internal design. If the boiler has only
one or two firing rates, the continuous range of heat inputs needed to meet a varying heating load is achieved by cycling
the boiler on and off. However, as load decreases, efficiency decreases since the boiler spends progressively more and
more time in transient warm-up and cool-down modes during which relatively little heat is delivered to the load. At
maximum load, the boiler cycles
very little and efficiency can be expected to be near the rated efficiency of the boiler. Part load effects can reduce average
efficiency to less than half of the peak efficiency. Of course, for an oversized boiler, average efficiency is well below the
peak efficiency since it operates at part load for the entire heating season. This operating cost penalty persists for the life of
a building, long after the designer who oversized the system has forgotten the error.
To quantify part load effects we define the part-load ratio, PLR (a quantity between 0 and 1), as

A gas boiler is used to supply space heat to a building. The load varies linearly with ambient temperature
as shown in Table 4.1.5 below. If the efficiency of the boiler is 80% at peak, rated conditions, find the seasonal average
efficiency, annual energy input, and annual energy output using the data in the table. The boiler input at rated conditions is
8750 MBtu/hr corresponding to 12.5F temperature bin atwhich the load is 7000 MBtu/hr.
This boiler is turned off in temperature bins higher than 57.5F roughly corresponding to the limit of the heating
season; therefore, the standby losses above this temperature are zero. The values of the coefficients in the part load
characteristic Equation 4.1.9 are

Load data shown in the third column of Table 4.1.5 exhibit the linearity of load with ambient temperature.The part load
characteristic equation is

To find the total energy used by the boiler, one sums the fuel used column of Table 4.1.5 to find that 22,439 MMBtu are
used to meet the annual load of 10,525 MMBtu. The ratio of these two numbers is the overall annual boiler efficiency,
47%. This value is 41% less than the peak efficiency of 80%. Clearly, one must take part load effects into account in
annual energy calculations.

STEAM
When a given weight of a perfect gas is compressed or expanded at a constant temperature, the
product of the pressure and volume is a constant. Vapors, which are liquids in aeriform condition, on
the other hand, can exist only at a definite pressure corresponding to each temperature if in the
saturated state, that is, the pressure is a function of the temperature only. Steam is water vapor, and at
a pressure of, say, 150 pounds absolute per square inch saturated steam can exist only at a temperature
358 degrees Fahrenheit. Hence if the pressure of saturated steam be fixed, its temperature is also fixed,
and vice versa.
Saturated steam is water vapor in the condition in which it is generated from water with which it is in
contact. Or it is steam which is at the maximum pressure and density possible at its temperature. If any
change be made in the temperature or pressure of steam, there will be a corresponding change in its
condition. If the pressure be increased or the temperature decreased, a portion of the steam will be
condensed. If the temperature be increased or the pressure decreased, a portion of the water with
which the steam is in contact will be evaporated into steam. Steam will remain saturated just so long
as it is of the same pressure and temperature as the water with which it can remain in contact without a
gain or loss of heat. Moreover, saturated steam cannot have its temperature lowered without a
lowering of its pressure, any loss of heat being made up by the latent heat of such portion as will be
condensed. Nor can the temperature of saturated steam be increased except when accompanied by a
corresponding increase in pressure, any added heat being expended in the evaporation into steam of a
portion of the water with which it is in contact.
Dry saturated steam contains no water. In some cases, saturated steam is accompanied by water which
is carried along with it, either in the form of a spray or is blown along the surface of the piping, and
the steam is then said to be wet. The percentage weight of the steam in a mixture of steam and water is
called the quality of the steam. Thus, if in a mixture of 100 pounds of steam and water there is threequarters of a pound of water, the quality of the steam will be 99.25.
Heat may be added to steam not in contact with water, such an addition of heat resulting in an increase
of temperature and pressure if the volume be kept constant, or an increase in temperature and volume
if the pressure remain constant. Steam whose temperature thus exceeds that of saturated steam at a
corresponding pressure is said to be superheated and its properties approximate those of a perfect gas.
As pointed out in the chapter on heat, the heat necessary to raise one pound of water from 32 degrees
Fahrenheit to the point of ebullition is called the heat of the liquid. The heat absorbed during ebullition
consists of that necessary to dissociate the molecules, or the inner latent heat, and that necessary to
overcome the resistance to the increase in volume, or the outer latent heat. These two make up
the latent heat of evaporation and the sum of this latent heat of evaporation and the heat of the liquid
make the total heat of the steam. These values for various pressures are given in the steam tables,
pages 122 to 127.
The specific volume of saturated steam at any pressure is the volume in cubic feet of one pound of
steam at that pressure.
The density of saturated steam, that is, its weight per cubic foot, is obviously the reciprocal of the
specific volume. This density varies as the 1617 power over the [Pg 116]ordinary range of pressures
used in steam boiler work and may be found by the formula, D = .003027p.941, which is correct within
0.15 per cent up to 250 pounds pressure.
The relative volume of steam is the ratio of the volume of a given weight to the volume of the same
weight of water at 39.2 degrees Fahrenheit and is equal to the specific volume times 62.427.

As vapors are liquids in their gaseous form and the boiling point is the point of change in this
condition, it is clear that this point is dependent upon the pressure under which the liquid exists. This
fact is of great practical importance in steam condenser work and in many operations involving boiling
in an open vessel, since in the latter case its altitude will have considerable influence. The relation
between altitude and boiling point of water is shown in Table 12.
The conditions of feed temperature and steam pressure in boiler tests, fuel performances and the like,
will be found to vary widely in different trials. In order to secure a means for comparison of different
trials, it is necessary to reduce all results to some common basis. The method which has been adopted
for the reduction to a comparable basis is to transform the evaporation under actual conditions of
steam pressure and feed temperature which exist in the trial to an equivalent evaporation under a set of
standard conditions. These standard conditions presuppose a feed water temperature of 212 degrees
Fahrenheit and a steam pressure equal to the normal atmospheric pressure at sea level, 14.7 pounds
absolute. Under such conditions steam would be generated at a temperature of 212 degrees, the
temperature corresponding to atmospheric pressure at sea level, fromwater at 212 degrees. The weight
of water which would be evaporated under the assumed standard conditions by exactly the amount of
heat absorbed by the boiler under actual conditions existing in the trial, is, therefore, called the
equivalent evaporation from and at 212 degrees.
The factor for reducing the weight of water actually converted into steam from the temperature of the
feed, at the steam pressure existing in the trial, to the equivalent evaporation under standard conditions
is called the factor of evaporation. This factor is the ratio of the total heat added to one pound of steam
under the standard conditions to the heat added to each pound of steam in heating the water from the
temperature of the feed in the trial to the temperature corresponding to the pressure existing in the
trial. This heat added is obviously the difference between the total heat of evaporation of the steam at
the pressure existing in the trial and the heat of the liquid in the water at the temperature at which it
was fed in the trial. To illustrate by an example:
In a boiler trial the temperature of the feed water is 60 degrees Fahrenheit and the pressure under
which steam is delivered is 160.3 pounds gauge pressure or 175 pounds absolute pressure. The total
heat of one pound of steam at 175 pounds pressure is 1195.9 B. t. u. measured above the standard
temperature of 32 degrees Fahrenheit. But the water fed to the boiler contained 28.08 B. t. u. as the
heat of the liquid measured above 32 degrees Fahrenheit. Therefore, to each pound of steam there has
been added 1167.82 B. t. u. To evaporate one pound of water under standard conditions would, on the
other hand, have required but 970.4 B. t. u., which, as described, is the latent heat of evaporation at
212 degrees Fahrenheit. Expressed differently, the total heat of one pound of steam at the pressure
corresponding to a temperature of 212 degrees is 1150.4 B. t. u. One pound of water at 212
degrees [Pg 117]contains 180 B. t. u. of sensible heat above 32 degrees Fahrenheit. Hence, under
standard conditions, 1150.4 - 180 = 970.4 B. t. u. is added in the changing of one pound of water into
steam at atmospheric pressure and a temperature of 212 degrees. This is in effect the definition of the
latent heat of evaporation.
Hence, if conditions of the trial had been standard, only 970.4 B. t. u. would be required and the ratio
of 1167.82 to 970.4 B. t. u. is the ratio determining the factor of evaporation. The factor in the
assumed case is 1167.82 970.4 = 1.2034 and if the same amount of heat had been absorbed under
standard conditions as was absorbed in the trial condition, 1.2034 times the amount of steam would
have been generated. Expressed as a formula for use with any set of conditions, the factor is,
Hh
F=

(2)

970.4
Where H = the total heat of steam above 32 degrees Fahrenheit from steam tables,
h

= sensible heat of feed water above 32 degrees Fahrenheit from Table 22.

In the form above, the factor may be determined with either saturated or superheated steam, provided
that in the latter case values of H are available for varying degrees of superheat and pressures.
Where such values are not available, the form becomes,
H h + s(tsup tsat)
F =

(3)

970.4
Where s = mean specific heat of superheated steam at the pressure existing in the trial from saturated
steam to the temperature existing in the trial,
tsup

= final temperature of steam,

tsat

= temperature of saturated steam, corresponding to pressure existing,

(tsup tsat) = degrees of superheat.

The specific heat of superheated steam will be taken up later.


Table 19 gives factors of evaporation for saturated steam boiler trials to cover a large range of
conditions. Except for the most refined work, intermediate values may be determined by interpolation.
Steam gauges indicate the pressure above the atmosphere. As has been pointed out, the atmospheric
pressure changes according to the altitude and the variation in the barometer. Hence, calculations
involving the properties of steam are based on absolute pressures, which are equal to the gauge
pressure plus the atmospheric pressure in pounds to the square inch. This latter is generally assumed to
be 14.7 pounds per square inch at sea level, but for other levels it must be determined from the
barometric reading at that place.

Vacuum gauges indicate the difference, expressed in inches of mercury, between atmospheric pressure
and the pressure within the vessel to which the gauge is attached. For approximate purposes, 2.04
inches height of mercury may be considered equal to a pressure of one pound per square inch at the
ordinary temperatures at which mercury gauges are used. Hence for any reading of the vacuum gauge
in inches, G, the absolute pressure for any barometer reading in inches, B, will be (B - G) 2.04. If the
barometer is 30 inches measured at ordinary temperatures and not corrected to 32 degrees Fahrenheit
and the vacuum gauge 24 inches, the absolute pressure will be (30 - 24) 2.04 = 2.9 pounds per
square inch.

TABLE 19
FACTORS OF EVAPORATION
CALCULATED FROM MARKS AND DAVIS TABLES
Feed Steam Pressure by Gauge
Temperatur 50
60
70
80
90
e

100

110

120

130

140

150

160

170

180

190

200

210

220

230

240

250

Degre
es
Fahren
heit
32

1.214 1.217 1.219 1.221 1.223 1.223 1.226 1.228 1.229 1.230 1.231 1.232 1.233 1.234 1.235 1.235 1.236 1.237 1.237 1.238 1.239
3
0
4
5
3
3
5
0
2
4
4
3
3
2
0
7
4
2
8
4
0

40

1.206 1.208 1.211 1.213 1.215 1.216 1.218 1.219 1.220 1.222 1.223 1.224 1.225 1.225 1.226 1.227 1.228 1.228 1.229 1.230 1.230
0
7
1
1
0
8
1
6
9
1
1
1
0
9
7
4
2
9
5
1
7

50

1.195 1.198 1.200 1.202 1.204 1.206 1.207 1.209 1.210 1.211 1.212 1.213 1.214 1.215 1.216 1.217 1.217 1.218 1.219 1.219 1.220
7
4
8
8
7
5
9
3
6
7
8
7
7
6
4
1
8
6
2
8
4

60

1.185 1.188 1.190 1.192 1.194 1.196 1.197 1.199 1.200 1.201 1.202 1.203 1.204 1.205 1.206 1.206 1.207 1.208 1.208 1.209 1.210
4
1
5
5
4
1
6
0
3
4
5
4
4
3
1
8
5
3
9
5
1

70

1.175 1.177 1.180 1.182 1.184 1.185 1.187 1.188 1.190 1.191 1.192 1.193 1.194 1.195 1.195 1.196 1.197 1.198 1.198 1.199 1.199
0
8
2
2
1
9
3
7
0
1
2
1
1
0
8
5
2
0
6
2
8

80

1.164 1.167 1.169 1.172 1.173 1.175 1.177 1.178 1.179 1.180 1.181 1.182 1.183 1.184 1.185 1.186 1.186 1.187 1.188 1.188 1.189
9
5
9
0
8
6
0
5
7
9
9
8
8
7
5
3
9
7
3
9
5

90

1.154 1.157 1.159 1.161 1.163 1.165 1.166 1.168 1.169 1.170 1.171 1.172 1.173 1.174 1.175 1.176 1.176 1.177 1.178 1.178 1.179
5
2
6
7
6
3
8
2
5
6
7
5
5
4
0
0
6
4
0
6
2

100

1.144 1.147 1.149 1.151 1.153 1.155 1.156 1.157 1.159 1.160 1.161 1.162 1.163 1.164 1.165 1.165 1.166 1.167 1.167 1.168 1.169
3
0
3
4
3
0
5
9
2
3
4
3
3
2
0
7
4
1
8
4
0

110

1.134 1.136 1.139 1.141 1.143 1.144 1.146 1.147 1.148 1.150 1.151 1.152 1.153 1.153 1.154 1.155 1.156 1.156 1.157 1.158 1.158
0
7
1
1
0
8
2
7
9
0
1
0
0
9
7
4
2
9
5
1
7

120

1.123 1.126 1.128 1.130 1.132 1.134 1.135 1.137 1.138 1.139 1.140 1.141 1.142 1.143 1.144 1.145 1.145 1.146 1.147 1.147 1.148
7
4
8
9
7
5
9
4
6
8
8
8
7
6
4
2
9
6
2
8
4

130

1.113 1.116 1.118 1.120 1.122 1.124 1.125 1.127 1.128 1.129 1.130 1.131 1.132 1.133 1.134 1.134 1.135 1.136 1.136 1.137 1.138
4
1
5
6
5
2
7
1
4
5
5
5
4
3
1
9
6
3
9
5
1

140

1.103 1.105 1.108 1.110 1.112 1.113 1.115 1.116 1.118 1.119 1.120 1.121 1.122 1.123 1.123 1.124 1.125 1.126 1.126 1.127 1.127
1
8
2
3
2
9
4
8
1
2
3
2
1
0
9
6
3
0
6
2
8

150

1.092 1.095 1.097 1.100 1.101 1.103 1.105 1.106 1.107 1.108 1.109 1.110 1.111 1.112 1.113 1.114 1.115 1.115 1.116 1.116 1.117
8
5
9
0
9
6
1
5
8
9
9
9
8
7
6
3
0
7
3
9
6

160

1.082 1.085 1.087 1.089 1.091 1.093 1.094 1.096 1.097 1.098 1.099 1.100 1.101 1.102 1.103 1.104 1.104 1.105 1.106 1.106 1.107
5
2
6
7
6
3
8
2
5
6
7
6
5
4
3
0
7
4
0
6
3

170

1.072 1.074 1.077 1.079 1.081 1.083 1.084 1.085 1.087 1.088 1.089 1.090 1.091 1.092 1.093 1.093 1.094 1.095 1.095 1.096 1.096
2
9
3
4
3
0
5
9
2
3
3
3
2
1
0
7
4
1
7
3
9

180

1.061 1.064 1.067 1.069 1.070 1.072 1.074 1.075 1.076 1.078 1.079 1.080 1.080 1.081 1.082 1.083 1.084 1.084 1.085 1.086 1.086
9
6
0
1
9
7
1
6
8
0
0
0
9
8
6
4
1
8
4
0
6

190

1.051 1.054 1.056 1.058 1.060 1.062 1.063 1.065 1.066 1.067 1.068 1.069 1.070 1.071 1.072 1.073 1.073 1.074 1.075 1.075 1.076
6
3
7
7
6
4
8
3
5
6
7
6
6
5
3
0
7
5
1
7
3

200

1.041 1.043 1.046 1.048 1.050 1.052 1.053 1.054 1.056 1.057 1.058 1.059 1.060 1.061 1.062 1.062 1.063 1.064 1.064 1.065 1.066
2
9
3
4
3
0
5
9
2
3
4
3
2
1
0
7
4
1
7
3
0

210

1.030 1.033 1.036 1.038 1.039 1.041 1.043 1.044 1.045 1.046 1.048 1.048 1.049 1.050 1.051 1.052 1.053 1.053 1.054 1.055 1.055
9
6
0
0
9
7
2
6
8
9
0
9
9
8
6
3
0
8
4
0
6

[Pg 119]

The temperature, pressure and other properties of steam for varying amounts of vacuum
and the pressure above vacuum corresponding to each inch of reading of the vacuum gauge
are given in Table 20.
TABLE

20

PROPERTIES
OF
SATURATED
STEAM
CALCULATED FROM MARKS AND DAVIS TABLE

FOR

VARYING

AMOUNTS

OF

VACUUM

Absolute Temperature Heat of the Liquid Latent


Heat Total
Heat Density or Weight
Vacuum
Pressure Degrees
Above 32 Degrees Above 32 Degrees Above 32 Degrees per Cubic Foot
Ins. Hg.
Pounds Fahrenheit B. t. u.
B. t. u.
B. t. u.
Pounds
29.5

.207

54.1

22.18

1061.0

1083.2

0.000678

29

.452

76.6

44.64

1048.7

1093.3

0.001415

28.5

.698

90.1

58.09

1041.1

1099.2

0.002137

28

.944

99.9

67.87

1035.6

1103.5

0.002843

27

1.44

112.5

80.4

1028.6

1109.0

0.00421

26

1.93

124.5

92.3

1022.0

1114.3

0.00577

25

2.42

132.6

100.5

1017.3

1117.8

0.00689

24

2.91

140.1

108.0

1013.1

1121.1

0.00821

22

3.89

151.7

119.6

1006.4

1126.0

0.01078

20

4.87

161.1

128.9

1001.0

1129.9

0.01331

18

5.86

168.9

136.8

996.4

1133.2

0.01581

16

6.84

175.8

143.6

992.4

1136.0

0.01827

14

7.82

181.8

149.7

988.8

1138.5

0.02070

12

8.80

187.2

155.1

985.6

1140.7

0.02312

10

9.79

192.2

160.1

982.6

1142.7

0.02554

12.24

202.9

170.8

976.0

1146.8

0.03148

From the steam tables, the condensed Table 21 of the properties of steam at different
pressures may be constructed. From such a table there may be drawn the following
conclusions.
TABLE

21

VARIATION
IN
PROPERTIES
SATURATED STEAM WITH PRESSURE

OF

Pressure Temperature Heat of Latent Total


Pounds Degrees
Liquid Heat Heat
Absolute Fahrenheit B. t. u. B. t. u. B. t. u.
14.7

212.0

180.0

970.4 1150.4

20.0

228.0

196.1

960.0 1156.2

100.0

327.8

298.3

888.0 1186.3

300.0

417.5

392.7

811.3 1204.1

As the pressure and temperature increase, the latent heat decreases. This decrease, however, is less
rapid than the corresponding increase in the heat of the liquid and hence the total heat increases with an increase
in the pressure and temperature. The percentage increase in the total heat is small, being 0.5, 3.1, and 4.7 per
cent for 20, 100, and 300 pounds absolute pressure respectively above the total heat in one pound of steam at
14.7 pounds absolute. The temperatures, on the other hand, increase at the rates of 7.5, 54.6, and 96.9 per cent.
The efficiency of a perfect steam engine is proportional to the expression (t - t1)/t in which t and t1 are the
absolute temperatures of the saturated steam at admission and exhaust respectively. While actual engines only
approximate the ideal engine in efficiency, yet they follow the same general law. Since the exhaust temperature
cannot be lowered beyond present practice, it follows that the only available method of increasing the efficiency
is by an increase in the temperature of the steam at admission. How this may be[Pg 120]accomplished by an
increase of pressure is clearly shown, for the increase of fuel necessary to increase the pressure is negligible, as
shown by the total heat, while the increase in economy, due to the higher pressure, will result directly from the
rapid increase of the corresponding temperature.

TABLE
HEAT UNITS PER POUND AND WEIGHT PER CUBIC
BETWEEN 32 DEGREES FAHRENHEIT AND 340 DEGREES FAHRENHEIT

22
FOOT

OF

WATER

Temp- Heat Weight Temp- Heat Weight Temp- Heat Weight Temp- Heat Weight
erature Units per
erature Units per
erature Units per
erature Units per
Degrees per
Cubic Degrees per
Cubic Degrees per
Cubic Degrees per
Cubic

Fahren- Pound Foot


heit

Fahren- Pound Foot


heit

Fahren- Pound Foot


heit

Fahren- Pound Foot


heit

32

0.00 62.42

89

57.00 62.13 146

113.86 61.27 203

170.95 60.05

33

1.01 62.42

90

58.00 62.12 147

114.86 61.25 204

171.96 60.02

34

2.01 62.42

91

59.00 62.11 148

115.86 61.24 205

172.96 60.00

35

3.02 62.43

92

60.00 62.09 149

116.86 61.22 206

173.97 59.98

36

4.03 62.43

93

60.99 62.08 150

117.86 61.20 207

174.97 59.95

37

5.04 62.43

94

61.99 62.07 151

118.86 61.18 208

175.98 59.93

38

6.04 62.43

95

62.99 62.06 152

119.86 61.16 209

176.98 59.90

39

7.05 62.43

96

63.98 62.05 153

120.86 61.14 210

177.99 59.88

40

8.05 62.43

97

64.98 62.04 154

121.86 61.12 211

178.99 59.85

41

9.05 62.43

98

65.98 62.03 155

122.86 61.10 212

180.00 59.83

42

10.06 62.43

99

66.97 62.02 156

123.86 61.08 213

181.0 59.80

43

11.06 62.43

100

67.97 62.00 157

124.86 61.06 214

182.0 59.78

44

12.06 62.43

101

68.97 61.99 158

125.86 61.04 215

183.0 59.75

45

13.07 62.42

102

69.96 61.98 159

126.86 61.02 216

184.0 59.73

46

14.07 62.42

103

70.96 61.97 160

127.86 61.00 217

185.0 59.70

47

15.07 62.42

104

71.96 61.95 161

128.86 60.98 218

186.1 59.68

48

16.07 62.42

105

72.95 61.94 162

129.86 60.96 219

187.1 59.65

49

17.08 62.42

106

73.95 61.93 163

130.86 60.94 220

188.1 59.63

50

18.08 62.42

107

74.95 61.91 164

131.86 60.92 221

189.1 59.60

TempTempHeat Weight
Heat
erature
erature
Units per
Units
Degrees
Degrees
per
Cubic
per
FahrenFahrenPound Foot
Pound
heit
heit
51

19.08 62.41

108

TempWeight
Heat
erature
per
Units
Degrees
Cubic
per
FahrenFoot
Pound
heit

75.95 61.90 165

TempWeight
Heat
erature
per
Units
Degrees
Cubic
per
FahrenFoot
Pound
heit

132.86 60.90 222

Weight
per
Cubic
Foot

190.1 59.58

52

20.08 62.41

109

76.94 61.88 166

133.86 60.88 223

191.1 59.55

53

21.08 62.41

110

77.94 61.86 167

134.86 60.86 224

192.1 59.53

54

22.08 62.40

111

78.94 61.85 168

135.86 60.84 225

193.1 59.50

55

23.08 62.40

112

79.93 61.83 169

136.86 60.82 226

194.1 59.48

56

24.08 62.39

113

80.93 61.82 170

137.87 60.80 227

195.2 59.45

57

25.08 62.39

114

81.93 61.80 171

138.87 60.78 228

196.2 59.42

58

26.08 62.38

115

82.92 61.79 172

139.87 60.76 229

197.2 59.40

59

27.08 62.37

116

83.92 61.77 173

140.87 60.73 230

198.2 59.37

60

28.08 62.37

117

84.92 61.75 174

141.87 60.71 231

199.2 59.34

61

29.08 62.36

118

85.92 61.74 175

142.87 60.69 232

200.2 59.32

62

30.08 62.36

119

86.91 61.72 176

143.87 60.67 233

201.2 59.29

63

31.07 62.35

120

87.91 61.71 177

144.88 60.65 234

202.2 59.27

64

32.07 62.35

121

88.91 61.69 178

145.88 60.62 235

203.2 59.24

65

33.07 62.34

122

89.91 61.68 179

146.88 60.60 236

204.2 59.21

66

34.07 62.33

123

90.90 61.66 180

147.88 60.58 237

205.3 59.19

67

35.07 62.33

124

91.90 61.65 181

148.88 60.56 238

206.3 59.16

68

36.07 62.32

125

92.90 61.63 182

149.89 60.53 239

207.3 59.14

69

37.06 62.31

126

93.90 61.61 183

150.89 60.51 240

208.3 59.11

TempTempHeat Weight
Heat
erature
erature
Units per
Units
Degrees
Degrees
per
Cubic
per
FahrenFahrenPound Foot
Pound
heit
heit

TempWeight
Heat
erature
per
Units
Degrees
Cubic
per
FahrenFoot
Pound
heit

TempWeight
Heat
erature
per
Units
Degrees
Cubic
per
FahrenFoot
Pound
heit

Weight
per
Cubic
Foot

70

38.06 62.30

127

94.89 61.59 184

151.89 60.49 241

209.3 59.08

71

39.06 62.30

128

95.89 61.58 185

152.89 60.47 242

210.3 59.05

72

40.05 62.29

129

96.89 61.56 186

153.89 60.45 243

211.4 59.03

73

41.05 62.28

130

97.89 61.55 187

154.90 60.42 244

212.4 59.00

74

42.05 62.27

131

98.89 61.53 188

155.90 60.40 245

213.4 58.97

75

42.05 62.26

132

99.88 61.52 189

156.90 60.38 246

214.4 58.94

76

44.04 62.26

133

100.88 61.50 190

157.91 60.36 247

215.4 58.91

77

45.04 62.25

134

101.88 61.49 191

158.91 60.33 248

216.4 58.89

78

46.04 62.24

135

102.88 61.47 192

159.91 60.31 249

217.4 58.86

79

47.04 62.23

136

103.88 61.45 193

160.91 60.29 250

218.5 58.83

80

48.03 62.22

137

104.87 61.43 194

161.92 60.27 260

228.6 58.55

81

49.03 62.21

138

105.87 61.41 195

162.92 60.24 270

238.8 58.26

82

50.03 62.20

139

106.87 61.40 196

163.92 60.22 280

249.0 57.96

83

51.02 62.19

140

107.87 61.38 197

164.93 60.19 290

259.3 57.65

84

52.02 62.18

141

108.87 61.36 198

165.93 60.17 300

269.6 57.33

85

53.02 62.17

142

109.87 61.34 199

166.94 60.15 310

279.9 57.00

86

54.01 62.16

143

110.87 61.33 200

167.94 60.12 320

290.2 56.66

87

55.01 62.15

144

111.87 61.31 201

168.94 60.10 330

300.6 56.30

88

56.01 62.14

145

112.86 61.29 202

169.95 60.07 340

311.0 55.94

The gain due to superheat cannot be predicted from the formula for the efficiency of a perfect steam
engine given on page 119. This formula is not applicable in cases where superheat is present since only a
relatively small amount of the heat in the steam is imparted at the maximum or superheated temperature.
The advantage of the use of high pressure steam may be also indicated by considering the question from the
aspect of volume. With an increase of pressure comes a decrease in volume, thus one pound of saturated steam
at 100 pounds absolute pressure occupies 4.43 cubic feet, while at 200 pounds pressure it occupies 2.29 cubic
feet. If then, in separate cylinders of the same dimensions, one pound of steam at 100 pounds absolute pressure
and one pound at 200 pounds absolute pressure enter and are allowed to expand to the full volume of each
cylinder, the high-pressure steam, having more room and a greater range for expansion than the low-pressure
steam, will thus do more work. This increase in the amount of work, as was the increase in temperature, is large

relative to the additional fuel required as indicated by the total heat. In general, it may be stated that the fuel
required to impart a given amount of heat to a boiler is practically independent of the steam pressure, since the
temperature of the fire is so high as compared with the steam temperature that a variation in the steam
temperature does not produce an appreciable effect.
The formulae for the algebraic expression of the relation between saturated steam pressures, temperatures and
steam volumes have been up to the present time empirical. These relations have, however, been determined by
experiment and, from the experimental data, tables have been computed which render unnecessary the use of
empirical formulae. Such formulae may be found in any standard work of thermo-dynamics. The following
tables cover all practical cases.
Table 22 gives the heat units contained in water above 32 degrees Fahrenheit at different temperatures.
Table 23 gives the properties of saturated steam for various pressures.
Table 24 gives the properties of superheated steam at various pressures and temperatures.
These tables are based on those computed by Lionel S. Marks and Harvey N. Davis, these being generally
accepted as being the most correct.

[Pg 122]

TABLE
PROPERTIES
MARKS

23
OF
AND

SATURATED
DAVIS

STEAM
REPRODUCED
STEAM
TABLES

BY

PERMISSION
FROM
AND
DIAGRAMS

(Copyright, 1909, by Longmans, Green & Co.)

Pressure,
Temperature Specific Volume Heat of the Latent Heat of Total Heat of
Pounds Absolute Degrees F. Cu. Ft. per Pound Liquid, B. t. u. Evap., B. t. u. Steam, B. t. u.

101.83

333.0

69.8

1034.6

1104.4

126.15

173.5

94.0

1021.0

1115.0

141.52

118.5

109.4

1012.3

1121.6

153.01

90.5

120.9

1005.7

1126.5

162.28

73.33

130.1

1000.3

1130.5

170.06

61.89

137.9

995.8

1133.7

176.85

53.56

144.7

991.8

1136.5

182.86

47.27

150.8

988.2

1139.0

188.27

42.36

156.2

985.0

1141.1

10

193.22

38.38

161.1

982.0

1143.1

11

197.75

35.10

165.7

979.2

1144.9

12

201.96

32.36

169.9

976.6

1146.5

13

205.87

30.03

173.8

974.2

1148.0

14

209.55

28.02

177.5

971.9

1149.4

15

213.0

26.27

181.0

969.7

1150.7

16

216.3

24.79

184.4

967.6

1152.0

17

219.4

23.38

187.5

965.6

1153.1

18

222.4

22.16

190.5

963.7

1154.2

19

225.2

21.07

193.4

961.8

1155.2

20

228.0

20.08

196.1

960.0

1156.2

22

233.1

18.37

201.3

956.7

1158.0

24

237.8

16.93

206.1

953.5

1159.6

26

242.2

15.72

210.6

950.6

1161.2

28

246.4

14.67

214.8

947.8

1162.6

30

250.3

13.74

218.8

945.1

1163.9

32

254.1

12.93

222.6

942.5

1165.1

34

257.6

12.22

226.2

940.1

1166.3

36

261.0

11.58

229.6

937.7

1167.3

38

264.2

11.01

232.9

935.5

1168.4

40

267.3

10.49

236.1

933.3

1169.4

42

270.2

10.02

239.1

931.2

1170.3

44

273.1

9.59

242.0

929.2

1171.2

46

275.8

9.20

244.8

927.2

1172.0

48

278.5

8.84

247.5

925.3

1172.8

50

281.0

8.51

250.1

923.5

1173.6

52

283.5

8.20

252.6

921.7

1174.3

Pressure,
Temperature Specific Volume Heat of the Latent Heat of Total Heat of
Pounds Absolute Degrees F. Cu. Ft. per Pound Liquid, B. t. u. Evap., B. t. u. Steam, B. t. u.
54

285.9

7.91

255.1

919.9

1175.0

56

288.2

7.65

257.5

918.2

1175.7

58

290.5

7.40

259.8

916.5

1176.4

60

292.7

7.17

262.1

914.9

1177.0

62

294.9

6.95

264.3

913.3

1177.6

64

297.0

6.75

266.4

911.8

1178.2

66

299.0

6.56

268.5

910.2

1178.8

68

301.0

6.38

270.6

908.7

1179.3

70

302.9

6.20

272.6

907.2

1179.8[Pg 123]

72

304.8

6.04

274.5

905.8

1180.4

74

306.7

5.89

276.5

904.4

1180.9

76

308.5

5.74

278.3

903.0

1181.4

78

310.3

5.60

280.2

901.7

1181.8

80

312.0

5.47

282.0

900.3

1182.3

82

313.8

5.34

283.8

899.0

1182.8

84

315.4

5.22

285.5

897.7

1183.2

86

317.1

5.10

287.2

896.4

1183.6

88

318.7

5.00

288.9

895.2

1184.0

90

320.3

4.89

290.5

893.9

1184.4

92

321.8

4.79

292.1

892.7

1184.8

94

323.4

4.69

293.7

891.5

1185.2

96

324.9

4.60

295.3

890.3

1185.6

98

326.4

4.51

296.8

889.2

1186.0

100

327.8

4.429

298.3

888.0

1186.3

105

331.4

4.230

302.0

885.2

1187.2

110

334.8

4.047

305.5

882.5

1188.0

115

338.1

3.880

309.0

879.8

1188.8

120

341.3

3.726

312.3

877.2

1189.6

125

344.4

3.583

315.5

874.7

1190.3

130

347.4

3.452

318.6

872.3

1191.0

135

350.3

3.331

321.7

869.9

1191.6

140

353.1

3.219

324.6

867.6

1192.2

145

355.8

3.112

327.4

865.4

1192.8

150

358.5

3.012

330.2

863.2

1193.4

155

361.0

2.920

332.9

861.0

1194.0

160

363.6

2.834

335.6

858.8

1194.5

Pressure,
Temperature Specific Volume Heat of the Latent Heat of Total Heat of
Pounds Absolute Degrees F. Cu. Ft. per Pound Liquid, B. t. u. Evap., B. t. u. Steam, B. t. u.
165

366.0

2.753

338.2

856.8

1195.0

170

368.5

2.675

340.7

854.7

1195.4

175

370.8

2.602

343.2

852.7

1195.9

180

373.1

2.533

345.6

850.8

1196.4

185

375.4

2.468

348.0

848.8

1196.8

190

377.6

2.406

350.4

846.9

1197.3

195

379.8

2.346

352.7

845.0

1197.7

200

381.9

2.290

354.9

843.2

1198.1

205

384.0

2.237

357.1

841.4

1198.5

210

386.0

2.187

359.2

839.6

1198.8

215

388.0

2.138

361.4

837.9

1199.2

220

389.9

2.091

363.4

836.2

1199.6

225

391.9

2.046

365.5

834.4

1199.9

230

393.8

2.004

367.5

832.8

1200.2

235

395.6

1.964

369.4

831.1

1200.6

240

397.4

1.924

371.4

829.5

1200.9

245

399.3

1.887

373.3

827.9

1201.2

250

401.1

1.850

375.2

826.3

1201.5
[Pg 124] [Pl 124]

TABLE

24

PROPERTIES OF SATURATED
MARKS
AND
DAVIS

STEAM REPRODUCED
STEAM
TABLES

(Copyright, 1909, by Longmans, Green & Co.)

Degrees of Superheat

BY

PERMISSION FROM
AND
DIAGRAMS

Pressure
Pounds
Absolute

Saturated
50
Steam

100

150

200

250

300

t 162.3
v 73.3
h 1130.5

212.3 262.3 312.3 362.3 412.3 462.3


79.7
85.7
91.8
97.8
103.8 109.8
1153.5 1176.4 1199.5 1222.5 1245.6 1268.7

10

t 193.2
v 38.4
h 1143.1

243.2 293.2 343.2 393.2 443.2 493.2


41.5
44.6
47.7
50.7
53.7
56.7
1166.3 1189.5 1212.7 1236.0 1259.3 1282.5

15

t 213.0
v 26.27
h 1150.7

263.0 313.0 363.0 413.0 463.0 513.0


28.40 30.46 32.50 34.53 36.56 38.58
1174.2 1197.6 1221.0 1244.4 1267.7 1291.1

20

t 228.0
v 20.08
h 1156.2

278.0 328.0 378.0 428.0 478.0 528.0


21.69 23.25 24.80 26.33 27.85 29.37
1179.9 1203.5 1227.1 1250.6 1274.1 1297.6

25

t 240.1
v 16.30
h 1160.4

290.1 340.1 390.1 440.1 490.1 540.1


17.60 18.86 20.10 21.32 22.55 23.77
1184.4 1208.2 1231.9 1255.6 1279.2 1302.8

30

t 250.4
v 13.74
h 1163.9

300.4 350.4 400.4 450.4 500.4 550.4


14.83 15.89 16.93 17.97 18.99 20.00
1188.1 1212.1 1236.0 1259.7 1283.4 1307.1

35

t 259.3
v 11.89
h 1166.8

309.3 359.3 409.3 459.3 509.3 559.3


12.85 13.75 14.65 15.54 16.42 17.30
1191.3 1215.4 1239.4 1263.3 1287.1 1310.8

40

t 267.3
v 10.49
h 1169.4

317.3 367.3 417.3 467.3 517.3 567.3


11.33 12.13 12.93 13.70 14.48 15.25
1194.0 1218.4 1242.4 1266.4 1290.3 1314.1

45

t 274.5
v 9.39
h 1171.6

324.5 374.5 424.5 474.5 524.5 574.5


10.14 10.86 11.57 12.27 12.96 13.65
1196.6 1221.0 1245.2 1269.3 1293.2 1317.0

50

t 281.0
v 8.51
h 1173.6

331.0 381.0 431.0 481.0 531.0 581.0


9.19
9.84
10.48 11.11 11.74 12.36
1198.8 1223.4 1247.7 1271.8 1295.8 1319.7

60

t 287.1
v 7.78

337.1
8.40

387.1
9.00

437.1
9.59

487.1
10.16

537.1
10.73

587.1
11.30

h 1175.4

1200.8 1225.6 1250.0 1274.2 1298.1 1322.0

Degrees of Superheat
Pressure
Pounds
Absolute

Saturated
50
Steam

100

150

200

250

300

60

t 292.7
v 7.17
h 1177.0

342.7 392.7 442.7 492.7 542.7 592.7


7.75
8.30
8.84
9.36
9.89
10.41
1202.6 1227.6 1252.1 1276.4 1300.4 1324.3

65

t 298.0
v 6.65
h 1178.5

348.0 398.0 448.0 498.0 548.0 598.0


7.20
7.70
8.20
8.69
9.17
9.65
1204.4 1229.5 1254.0 1278.4 1302.4 1326.4

70

t 302.9
v 6.20
h 1179.8

352.9 402.9 452.9 502.9 552.9 602.9


6.71
7.18
7.65
8.11
8.56
9.01
1205.9 1231.2 1255.8 1280.2 1304.3 1328.3

75

t 307.6
v 5.81
h 1181.1

357.6 407.6 457.6 507.6 557.6 607.6


6.28
6.73
7.17
7.60
8.02
8.44
1207.5 1232.8 1257.5 1282.0 1306.1 1330.1

80

t 312.0
v 5.47
h 1182.3

362.0 412.0 462.0 512.0 562.0 612.0


5.92
6.34
6.75
7.17
7.56
7.95
1208.8 1234.3 1259.0 1283.6 1307.8 1331.9

85

t 316.3
v 5.16
h 1183.4

366.3 416.3 466.3 516.3 566.3 616.3


5.59
6.99
6.38
6.76
7.14
7.51
1210.2 1235.8 1260.6 1285.2 1309.4 1333.5

90

t 320.3
v 4.89
h 1184.4

370.3 420.3 470.3 520.3 570.3 620.3 [Pg 126]


5.29
5.67
6.04
6.40
6.76
7.11
1211.4 1237.2 1262.0 1286.6 1310.8 1334.9

95

t 324.1
v 4.65
h 1185.4

374.1 424.1 474.1 524.1 574.1 624.1


5.03
5.39
5.74
6.09
6.43
6.76
1212.6 1238.4 1263.4 1288.1 1312.3 1336.4

100

t 327.8
v 4.43
h 1186.3

377.8 427.8 477.8 527.8 577.8 627.8


4.79
5.14
5.47
5.80
6.12
6.44
1213.8 1239.7 1264.7 1289.4 1313.6 1337.8

105

t 331.4
v 4.23

381.4
4.58

431.4
4.91

481.4
5.23

531.4
5.54

581.4
5.85

631.4
6.15

110

h 1187.2

1214.9 1240.8 1265.9 1290.6 1314.9 1339.1

t 334.8
v 4.05
h 1188.0

384.8 434.8 484.8 534.8 584.8 634.8


4.38
4.70
5.01
5.31
5.61
5.90
1215.9 1242.0 1267.1 1291.9 1316.2 1340.4

Degrees of Superheat
Pressure
Pounds
Absolute

Saturated
50
Steam

100

150

200

250

300

115

t 338.1
v 3.88
h 1188.8

388.1 438.1 488.1 538.1 588.1 638.1


4.20
4.51
4.81
5.09
5.38
5.66
1216.9 1243.1 1268.2 1293.0 1317.3 1341.5

120

t 341.3
v 3.73
h 1189.6

391.3 441.3 491.3 541.3 591.3 641.3


4.04
4.33
4.62
4.89
5.17
5.44
1217.9 1244.1 1269.3 1294.1 1318.4 1342.7

125

t 344.4
v 3.58
h 1190.3

394.4 444.4 494.4 544.4 594.4 644.4


3.88
4.17
4.45
4.71
4.97
5.23
1218.8 1245.1 1270.4 1295.2 1319.5 1343.8

130

t 347.4
v 3.45
h 1191.0

397.4 447.4 497.4 547.4 597.4 647.4


3.74
4.02
4.28
4.54
4.80
5.05
1219.7 1246.1 1271.4 1296.2 1320.6 1344.9

135

t 350.3
v 3.33
h 1191.6

400.3 450.3 500.3 550.3 600.3 650.3


3.61
3.88
4.14
4.38
4.63
4.87
1220.6 1247.0 1272.3 1297.2 1321.6 1345.9

140

t 353.1
v 3.22
h 1192.2

403.1 453.1 503.1 553.1 603.1 653.1


3.49
3.75
4.00
4.24
4.48
4.71
1221.4 1248.0 1273.3 1298.2 1322.6 1346.9

145

t 355.8
v 3.12
h 1192.8

405.8 455.8 505.8 555.8 605.8 655.8


3.38
3.63
3.87
4.10
4.33
4.56
1222.2 1248.8 1274.2 1299.1 1323.6 1347.9

150

t 358.5
v 3.01
h 1193.4

408.5 458.5 508.5 558.5 608.5 658.5


3.27
3.50
3.75
3.97
4.19
4.41
1223.0 1249.6 1275.1 1300.0 1324.5 1348.8

155

t 361.0
v 2.92

411.0
3.17

461.0
3.41

511.0
3.63

561.0
3.85

611.0
4.06

661.0
4.28

h 1194.0

1223.6 1250.5 1276.0 1300.8 1325.3 1349.7

160

t 363.6
v 2.83
h 1194.5

413.6 463.6 513.6 563.6 613.6 663.6


3.07
3.30
3.53
3.74
3.95
4.15
1224.5 1251.3 1276.8 1301.7 1326.2 1350.6

165

t 366.0
v 2.75
h 1195.0

416.0 466.0 516.0 566.0 616.0 666.0


2.99
3.21
3.43
3.64
3.84
4.04
1225.2 1252.0 1277.6 1302.5 1327.1 1351.5

Degrees of Superheat
Pressure
Pounds
Absolute

Saturated
50
Steam

100

150

200

250

300

170

t 368.5
v 2.68
h 1195.4

418.5 468.5 518.5 568.5 618.5 668.5


2.91
3.12
3.34
3.54
3.73
3.92
1225.9 1252.8 1278.4 1303.3 1327.9 1352.3

175

t 370.8
v 2.60
h 1195.9

420.8 470.8 520.8 570.8 620.8 670.8 [Pg 127]


2.83
3.04
3.24
3.44
3.63
3.82
1226.6 1253.6 1279.1 1304.1 1328.7 1353.2

180

t 373.1
v 2.53
h 1196.4

423.1 473.1 523.1 573.1 623.1 673.1


2.75
2.96
3.16
3.35
3.54
3.72
1227.2 1254.3 1279.9 1304.8 1329.5 1353.9

185

t 375.4
v 2.47
h 1196.8

425.4 475.4 525.4 575.4 625.4 675.4


2.68
2.89
3.08
3.27
3.45
3.63
1227.9 1255.0 1280.6 1305.6 1330.2 1354.7

190

t 377.6
v 2.41
h 1197.3

427.6 477.6 527.6 577.6 627.6 677.6


2.62
2.81
3.00
3.19
3.37
3.55
1228.6 1255.7 1281.3 1306.3 1330.9 1355.5

195

t 379.8
v 2.35
h 1197.7

429.8 479.8 529.8 579.8 629.8 679.8


2.55
2.75
2.93
3.11
3.29
3.46
1229.2 1256.4 1282.0 1307.0 1331.6 1356.2

200

t 381.9
v 2.29
h 1198.1

431.9 481.9 531.9 581.9 631.9 681.9


2.49
2.68
2.86
3.04
3.21
3.38
1229.8 1257.1 1282.6 1307.7 1332.4 1357.0

205

t 384.0
v 2.24

434.0
2.44

484.0
2.62

534.0
2.80

584.0
2.97

634.0
3.14

684.0
3.30

h 1198.5

1230.4 1257.7 1283.3 1308.3 1333.0 1357.7

210

t 386.0
v 2.19
h 1198.8

436.0 486.0 536.0 586.0 636.0 686.0


2.38
2.56
2.74
2.91
3.07
3.23
1231.0 1258.4 1284.0 1309.0 1333.7 1358.4

215

t 388.0
v 2.14
h 1199.2

438.0 488.0 538.0 588.0 638.0 688.0


2.33
2.51
2.68
2.84
3.00
3.16
1231.6 1259.0 1284.6 1309.7 1334.4 1359.1

220

t 389.9
v 2.09
h 1199.6

439.9 489.9 539.9 589.9 639.9 689.9


2.28
2.45
2.62
2.78
2.94
3.10
1232.2 1259.6 1285.2 1310.3 1335.1 1359.8

Degrees of Superheat
Pressure
Pounds
Absolute

Saturated
50
Steam

100

150

200

250

300

225

t 391.9
v 2.05
h 1199.9

441.9 491.9 541.9 591.9 641.9 691.9


2.23
2.40
2.57
2.72
2.88
3.03
1232.7 1260.2 1285.9 1310.9 1335.7 1360.3

230

t 393.8
v 2.00
h 1200.2

443.8 493.8 543.8 593.8 643.8 693.8


2.18
2.35
2.51
2.67
2.82
2.97
1233.2 1260.7 1286.5 1311.6 1336.3 1361.0

235

t 395.6
v 1.96
h 1200.6

445.6 495.6 545.6 595.6 645.6 695.6


2.14
2.30
2.46
2.62
2.77
2.91
1233.8 1261.4 1287.1 1312.2 1337.0 1361.7

240

t 397.4
v 1.92
h 1200.9

447.4 497.4 547.4 597.4 647.4 697.4


2.09
2.26
2.42
2.57
2.71
2.85
1234.3 1261.9 1287.6 1312.8 1337.6 1362.3

245

t 399.3
v 1.89
h 1201.2

449.3 499.3 549.3 599.3 649.3 699.3


2.05
2.22
2.37
2.52
2.66
2.80
1234.8 1262.5 1288.2 1313.3 1338.2 1362.9

250

t 401.0
v 1.85
h 1201.5

451.0 501.0 551.0 601.0 651.0 701.0


2.02
2.17
2.33
2.47
2.61
2.75
1235.4 1263.0 1288.8 1313.9 1338.8 1363.5

255

t 402.8
v 1.81

452.8
1.98

502.8
2.14

552.8
2.28

602.8
2.43

652.8
2.56

702.8
2.70

h 1201.8

1235.9 1263.6 1289.3 1314.5 1339.3 1364.1

t = Temperature, degrees Fahrenheit.


v = Specific volume, in cubic feet, per pound.
h = Total heat from water at 32 degrees, B. t. u.

FIG. 15. GRAPHIC METHOD


CALORIMETER READINGS

OF

DETERMINING MOISTURE CONTAINED

IN

STEAM

FROM

CONDENSETE AT BOILER

Condensing boilers are water heaters in which a high efficiency (typically greater than 90%) is
achieved by using the waste heat in the flue gases to pre-heat the cold water entering the boiler. They
may be fuelled by gas or oil and are called condensing boilers because the water vapour produced during
combustion is condensed into water, which leaves the system via a drain. In many countries their use is
compulsory or encouraged with financial incentives.
Principles of work
In a conventional boiler, fuel is burned and the hot gases produced are passed through a heat exchanger where
much of their heat is transferred to water, thus raising the water's temperature.
One of the hot gases produced in the combustion process is water vapour (steam), which arises from burning
the hydrogen content of the fuel. A condensing boiler extracts additional heat from the waste gases by
condensing this water vapour to liquid water, thus recovering its latent heat of vaporization. A typical increase
of efficiency can be as much as 10-12%.[citation needed] The effectiveness of this condensing process varies, it
depends upon the temperature of the water returning to the boiler, but for the same conditions, it is always at
least as efficient as a non-condensing boiler.
The condensate produced is slightly acidic, 3-5 pH, so the choice of materials used in the areas where liquid is
present have to be suitable. At high temperature most commonly used are aluminium alloys and stainless steel,
in the low temperature areas plastics are most cost effective, for example uPVC and polypropylene.[1] The
production of condensate also requires the installation of a heat exchanger condensate drainage system. For a
basic installation this is the only difference required compared to a non-condensing boiler.
For the heat exchanger within a condensing boiler to be economical to manufacture, and for the appliance to be
manageable at installation, the smallest practical size for its output is preferred. This has produced heat
exchangers with very high combustion side resistance and so the use of a combustion fan to move the products
through narrow passageways has been adopted. This also has had the benefit of providing the energy for the
flue system as the expelled combustion gases are usually below 100C (212F) and as such have a density close
to air, with little buoyancy. The combustion fan helps to pump exhaust gas to the outside.
Efficiency
Condensing boiler manufacturers claim that up to 98% thermal efficiency can be achieved,[4] compared to 70%80% with conventional designs (based on the higher heating value of fuels). Typical models offer efficiencies
around 90%, which brings most brands of condensing gas boiler in to the highest available categories for energy
efficiency. In the UK, this is a SEDBUK (Seasonal Efficiency of Domestic Boilers in the UK) [5] Band A
efficiency rating, while in North America they typically receive an Eco Logo and/or Energy Star Certification.
Boiler performance is based on the efficiency of heat transfer and highly dependent on boiler size/output and
emitter size/output. System design and installation are critical. Matching the radiation to the Btu/Hr output of

the boiler and consideration of the emitter/radiator design temperatures determines the overall efficiency of the
space and domestic water heating system.
One reason for an efficiency drop is because the design and/or implementation of the heating system gives
return water (heat transfer fluid) temperatures at the boiler of over 55C (131F), which prevents significant
condensation in the heat exchanger.[6] Better education of both installers and owners could be expected to raise
efficiency towards the reported laboratory values. Natural Resources Canada [7] also suggests ways to make
better use of these boilers, such as combining the space and water heating systems. Some boilers (e.g. Potterton)
can be switched between two flow temperatures such as 63C (145F) and 84C (183F), only the former being
"fully condensing". However, the boilers are normally installed with the higher flow temperature by default
because a domestic hot water cylinder is generally heated to 60C (140F), and this takes too long to achieve
with a flow temperature only three degrees higher. Nevertheless, even partial condensing is more efficient than
a traditional boiler.
Most non-condensing boilers could be forced to condense through simple control changes. Doing so would
reduce fuel consumption considerably, but would quickly destroy any mild steel or cast-iron components of a
conventional high-temperature boiler due to the corrosive nature of the condensate, and is the reason why most
condensing boiler heat-exchangers are made from stainless steel or aluminum/silicon alloy. External stainless
steel economizers can be retrofitted to non-condensing boilers to allow them to achieve condensing efficiencies.
Temperature control valves are used to blend hot supply water into the return to avoid thermal shock or
condensation inside of the boiler.
The lower the return temperature to the boiler the more likely it will be in condensing mode. If the return
temperature is kept below approximately 55C (131F) the boiler should still be in condensing mode making
low temperature applications such as radiant floors and even old cast iron radiators a good match for the
technology.
Most manufacturers of the new domestic condensing boilers produce a very basic "fits all" in-built control
system that ends up with the boiler running in condensing mode only on initial heat-up, after which the
efficiency drops off, although it should still exceed that of older models (see the following three documents
published by the Building Research Establishment: Information Papers 10-88 and 19-94; General Information
Leaflet 74; Digest 339. See also Application Manual AM3 1989: Condensing Boilers by Chartered Institute of
Building Services Engineers).
Control
The control of the domestic condensing boiler is crucial to ensuring that it operates in the most economic and
fuel efficient way.
Almost all have modulating burners. The burners are usually controlled by an embedded system with built in
logic to control the output of the burner to match the load and give best performance.
Reliability
Condensing boilers are claimed to have a reputation for being less reliable, requiring professional installation
and regular service, and may also suffer if worked on by installers and plumbers who may not understand their
operation.[8] Claims of unreliability have been contradicted by research carried out by the UK-based Building
Research Establishment (see "Myths" below.)
Heat exchangers in condensing boilers are primarily manufactured using stainless steel and aluminum. Initial
testing and annual monitoring of the heat transfer fluid in condensing boilers with aluminum or stainless steel
heat exchangers is highly recommended. Maintenance of a slightly alkaline (pH 8 to 9) liquid with anticorrosion and buffering agents reduces corrosion of the aluminum heat exchanger. There is a feeling among
some professionals in the field that the condensate produced on the combustion side of the heat exchanger may
corrode an aluminum heat exchanger and shorten the boiler's life. Statistical evidence is not yet available since
condensing boilers with aluminum heat exchangers have not been in use long enough.

To ensure reliability, condensing boilers must be properly installed and maintained.


Myths
The Building Research Establishment, which is the UK's major research body for the building industry, has
produced guidance on domestic condensing boilers. This was originally published in 2003 as General
Information Leaflet 74 (GIL74), entitled "Domestic Condensing Boilers: the benefits and the myths". The
publication is based upon the BRE's long experience with installed condensing boilers since the 1980s, and is
now also published by the Energy Saving Trust as document CE52. It seeks to highlight the many myths and
misconceptions about condensing boilers, and to explain the known benefits. This guidance can be downloaded
from
the
Energy
Savings
Trust
web
site: http://www.energysavingtrust.org.uk/PublicationDownload/?p=1&pid=227

In particular, the BRE's research has found the following:


1. condensing boilers are nowadays just as reliable as standard boilers
2. condensing boilers are no more difficult to service, nor do they require more frequent servicing
3. servicing is not expensive; the only (minor) additional task is to check the correct function of the
condensate drain
4. condensing boilers are not difficult to install
5. condensing boilers are always more efficient than standard boilers, under all operating conditions

Controlling draught
Most boilers now depend on mechanical draught equipment rather than natural draught. This is because natural draught is
subject to outside air conditions and temperature of flue gases leaving the furnace, as well as the chimney height. All these
factors make proper draught hard to attain and therefore make mechanical draught equipment much more economical.

There are three types of mechanical draught:

Induced draught: This is obtained one of three ways, the first being the "stack effect" of a heated chimney, in which
the flue gas is less dense than the ambient air surrounding the boiler. The denser column of ambient air forces
combustion air into and through the boiler. The second method is through use of a steam jet. The steam jet oriented in
the direction of flue gas flow induces flue gasses into the stack and allows for a greater flue gas velocity increasing the
overall draught in the furnace. This method was common on steam driven locomotives which could not have tall
chimneys. The third method is by simply using an induced draught fan (ID fan) which removes flue gases from the
furnace and forces the exhaust gas up the stack. Almost all induced draught furnaces operate with a slightly negative
pressure.

Forced draught: Draught is obtained by forcing air into the furnace by means of a fan (FD fan) and ductwork. Air is
often passed through an air heater; which, as the name suggests, heats the air going into the furnace in order to
increase the overall efficiency of the boiler. Dampers are used to control the quantity of air admitted to the furnace.
Forced draught furnaces usually have a positive pressure.

Balanced draught: Balanced draught is obtained through use of both induced and forced draught. This is more
common with larger boilers where the flue gases have to travel a long distance through many boiler passes. The

induced draught fan works in conjunction with the forced draught fan allowing the furnace pressure to be maintained
slightly below atmospheric.