00813-0100-4697, Rev HA
January 2009
Head mount (DIN B) and Rail mount style with HART protocol and
complete temperature assembly.
Specifications
FUNCTIONAL
Inputs
Status
Outputs
Schedule Entries
Links
Virtual Communications Relationships (VCR)
20
30
20
PHYSICAL
Mounting
page 24.
Isolation
Isolation between all sensor channels is rated to 10Vdc over all
operating conditions. No damage will occur to the device with up to
600 Vdc between any sensor channel.
Power Supply
Powered over FOUNDATION fieldbus with standard fieldbus power
supplies. The transmitter operates between 9.0 and 32.0 V dc,
22 mA maximum. (Transmitter power terminals are rated
to 42.4 V dc.)
Transient Protection
The transient protector (option code T1) helps to prevent damage
to the transmitter from transients induced on the loop wiring by
lightning, welding, heavy electrical equipment, or switch gears.
This option is installed at the factory for the Rosemount 848T and
is not intended for field installation.
Update Time
Approximately less than 1.5 seconds to read all 8 inputs.
Humidity Limits
099% non-condensing relative humidity
Paint
Aluminum
Plastic
Stainless Steel
Aluminum Explosion-proof
Epoxy Resin
NA
NA
NA
Weight
Assembly
Turn-on Time
Performance within specifications is achieved in less than 30
seconds after power is applied to the transmitter.
Alarms
The AI and ISEL function blocks allow the user to configure the
alarms to HI-HI, HI, LO, or LO-LO with a variety of priority levels
and hysteresis settings.
Weight
oz
lb
7.5
78.2
58.1
77.0
557
.47
4.89
3.68
4.81
34.8
kg
.208
2.22
1.65
2.18
15.5
(1) Add 35.2 oz (2.2 lb, 0.998 kg) for nickel-plated brass glands
Environmental Ratings
Type 4X, and CSA Enclosure Type 4X, and IP66 with optional
junction box. JX3 Explosion-proof enclosure rated to -4 F (-20
C).
FUNCTION BLOCKS
FOUNDATION
fieldbus
Stability
0.1% of reading or 0.1 C (0.18 F), whichever is greater, for
2 years for RTDs.
0.1% of reading or 0.1 C (0.18 F), whichever is greater, for
1 year for thermocouples.
Self Calibration
The transmitters analog-to-digital circuitry automatically
self-calibrates for each temperature update by comparing the
dynamic measurement to extremely stable and accurate internal
reference elements.
Vibration Effect
Transmitters are tested to the following vibration conditions with no
effect on performance:
Frequency
10 - 60 Hz
60 - 2000 Hz
Acceleration
0.21 mm peak displacement
3g
Sensor Reference
200 to 550
200 to 550
200 to 850
200 to 645
200 to 850
60 to 100
200 to 850
200 to 300
70 to 300
50 to 250
-185 to 200
-185 to 200
-50 to 200
-50 to 200
328 to 1022
328 to 1022
328 to 1562
328 to 1193
328 to 1562
140 to 212
328 to 1562
328 to 572
94 to 572
58 to 482
-365 to 392
-365 to 392
-122 to 392
-122 to 392
0.57
0.28
0.30
0.30
0.50
0.30
0.38
0.40
0.30
3.20
0.48
0.96
0.48
0.96
1.03
0.50
0.54
0.54
0.90
0.54
0.68
0.72
0.54
5.76
0.86
1.73
0.86
1.73
100 to 300
212 to 572
301 to 1820
573 to 3308
200 to 1000
328 to 1832
180 to 760
292 to 1400
180 to 1372
292 to 2502
200 to 1300
328 to 2372
0 to 1768
32 to 3214
0 to 1768
32 to 3214
200 to 400
328 to 752
200 to 900
328 to 1652
200 to 600
328 to 1112
0 to 2000
32 to 3632
-200 to 800
-392 to 1472
-50 to 85
-58 to 185
10 to 100 mV
0 to 2000 ohms
420 mA
420 mA
6.00
10.80
1.54
2.78
0.40
0.72
0.70
1.26
1.00
1.80
1.00
1.80
1.50
2.70
1.40
2.52
0.70
1.26
0.70
1.26
0.70
1.26
1.60
2.88
0.71
1.28
0.90
0.50
0.05 mV
0.90 ohm
0.01 mA
0.01 mA
Accuracy Notes
Alarm Levels
Accuracy
3.9 to 20.8 mA
0.01mA
3.8 to 20.5 mA
0.01mA
RTD
Pt 50 ( = 0.00391)
0.004 C (0.0072 F)
NA
Pt 100 ( = 0.00391)
0.002 C (0.0036 F)
NA
Pt 100 ( = 0.00385)
0.003 C (0.0054 F)
NA
Pt 100 ( = 0.003916)
0.003 C (0.0054 F)
NA
Pt 200 ( = 0.003916)
0.004 C (0.0072 F)
NA
Pt 200 ( = 0.00385)
0.004 C (0.0072 F)
NA
Pt 500
0.003 C (0.0054 F)
NA
Pt 1000
0.003 C (0.0054 F)
NA
Cu 10
0.03 C (0.054 F)
NA
Cu 100 (a=428)
0.002 C (0.0036 F)
NA
Cu 50 (a=428)
0.004 C (.0072 F)
NA
Cu 100 (a=426)
0.002 C (0.0036 F)
NA
Cu 50 (a=426)
0.004 C (.0072 F)
NA
Ni 120
0.003 C (0.0054 F)
NA
R 1000
300 R < 1000
100 R < 300
Type E
0.005 C + (0.00043% of R)
All
0.0054 C + (0.00029% of R)
0.0054 C + (0.0025% of |R|)
R0
R<0
Type K
0.0061 C + (0.00054% of R)
0.0061 C + (0.0025% of |R|)
R0
R<0
Type N
0.0068 C + (0.00036% of R)
All
Type R, Type S
0.016 C
0.023 C - (0.0036% of R)
R 200
R < 200
0.0064 C
0.0064 C + (0.0043% of |R|)
R0
R<0
GOST Type L
0.007 C
0.007 C + (0.003% of IRI)
R0
R<0
Millivolt
0.0005 mV
NA
0.0084 ohms
NA
420 mA (Rosemount)
0.0001 mA
NA
4-20 mA (NAMUR)
0.0001 mA
NA
FOUNDATION
fieldbus
NIST Type
(1) Change in ambient is in reference to the calibration temperature of the transmitter (20 C (68 F) typical from the factory).
= 0.31C
Product Certifications
HAZARDOUS LOCATIONS CERTIFICATION
North American Certificates
Power/Bus
Sensor
I5
Uo = 3.01V
Io = 3.38mA
Po = 0.01W
Ca = 0.34 F
La = 40 mH
Uo = 12.02 V
Io = 13.5 mA
Po = 0.04 W
Ca = 1.36 F
La = 160 mH
IE
N5
NK
Power/Bus
Sensor
Ui = 17.5 V
Ii = 380 mA
Pi = 5.32 W
Ci = 2.1 nF
Li = 0
Uo = 12.02 V
Io = 13.5 mA
Po = 0.04 W
Ca = 1.36 F
La = 160 mH
IF
Power/Bus
Sensor
Ui = 30 V
Ii = 300 mA
Ci = 2.1 nF
Li = 0
Uo = 12.02 V
Io = 11.8 mA
Ca = 1.36 F
La = 225 mH
Ui = 17.5 V
Ii = 380 mA
Ci = 2.1 nF
Li = 0
Uo = 12.02 V
Io = 11.8 mA
Ca = 1.36 F
La = 225 mH
Class I, Division 2
Suitable for use in Class I, Division 2, Groups A, B, C, D.
when installed per Rosemount drawing 00848-4403.
Temperature Code:
T3C = ( 50 Ta 60 C)
Must be installed in a suitable enclosure as determined
acceptable by the local inspection authority.
European Certifications
ATEX Certifications
I1
Intrinsic Safety
Certification Number: Baseefa02ATEX0010X
ATEX Marking
II 1 G
EEx ia IIC T4 (Tamb = 50 to 60 C)
1180
TABLE 8. ATEX Approved Entity Parameters
Power/Bus
Sensor
Ui = 30 V
Ii = 300 mA
Pi = 1.3 W
Ci = 0
Li = 0
Uo = 12.5 V
Io = 66 mA
Po = 40 mW
Ci = 0
Li = 0
NE
Power/Bus
Sensor
Ui = 17.5 V
Ii = 380 mA
Pi = 5.32 W
Ci = 0
Li = 0
Uo = 12.5 V
Io = 66 mA
Po = 40 mW
Ci = 0
Li = 0
ATEX Type n
Certification Number: BAS01ATEX3199X
ATEX Marking
II 3 G
EEx nL IIC T5 (Tamb = 40 to 65 C)
Power/Bus
Sensor
Ui = 42.4 V
Ci = 0
Li = 0
Uo = 5 V
Io = 2.5 mA
Co = 1000 F
Lo = 1000 mH
FOUNDATION
fieldbus
N6
Power/Bus
FOUNDATION
fieldbus
Sensor
Uo = 5V dc
Io = 2.5 mA
Co = 1000 F
Lo = 1000 mH
COMPONENT Approval
Certification Number: BAS01ATEX3198U
ATEX Marking
II 3 G
EEx nA nL IIC T4 (Tamb = -50 to 85 C)
EEx nA nL IIC T5 (Tamb = -50 to 70 C)
NOTE: NF is valid with S001 Input Type ONLY
Sensor
Uo = 5V dc
Io = 2.5 mA
Co = 1000 F
Lo = 1000 mH
IECEx Certifications
I7
Uo = 12.5 V
Io = 66 mA
Po = 40 mW
Ci = 0
Li = 0
IECEx FISCO
Certificate No.: IECExBAS06.0093X
Ex ia IIC T4 (Tamb = 50 to 60 C)
10
Uo = 12.5 V
Io = 66 mA
Po = 40 mW
Ci = 0
Li = 0
Sensor
Uo = 5V dc
Io = 2.5 mA
Co = 1000 F
Lo = 1000 mH
Sensor
Uo = 5V dc
Io = 2.5 mA
Co = 1000 F
Lo = 1000 mH
Brazilian Certifications
FOUNDATION
fieldbus
11
Dimensional Drawings
Junction Boxes with no entries (option codes JP1, JA1, and JS1) external dimensions are the same as those
outlined for the other junction box materials in this section.
Rosemount 848T
Top View
Security Switch
Side View
3-D View
1.7
(43)
Simulation Switch
6.7
(170)
3.7
(93)
Removable Wiring
Connection
Dimensions are in inches (millimeters)
3-D View
10.24 (260)
Ground Screw
Side View
Front View
7.84 (199.2)
2.44 (62)
1.57 (40)
6.30 (160)
4.41 (112)
1.73 (44)
2.28 (58)
1.10 (28)
3.78 (96)
12
Top View
3-D View
9.91 (231)
7.7 (196)
Ground Screw
Side View
Front View
9.14 (232.2)
1.8 (46)
1.1 (28)
7.72 (196)
6.61 (168)
1.73 (44)
4.0 (102)
2.4 (62)
1.8 (47)
1.2 (30)
3-D View
10.2 (260)
Front View
Side View
157 (40)
2.44 (62)
10.2 (260)
3.5 (89)
1.7 (42)
13
3-D View
9.1 (231)
7.7 (196)
Ground Screw
Front View
Side View
1.4 (35)
1.1 (27)
2.8 (70)
1.2 (30)
4.0 (102)
2.4 (62)
1.6 (42)
1.8 (4.7)
0.06 (1.5)
Five Plugged 0.86-in. diameter holes suitable for installing 1/2-in. NPT fittings
MOUNTING OPTIONS
Aluminum/Plastic Junction Box
(styles JA and JP)
Front View
5.1
(130)
10.2
(260)
Side View
Side View
4.7
(119)
14
Product Description
848T
Code
Communications Protocol
F
Code
I5(4)
FOUNDATION fieldbus digital signal (includes AI, MAI, and ISEL function blocks, and Backup Link Active Scheduler)
Product Certifications(1)
Rosemount Junction
Box required?
No
IE
No
N5
Yes
E6
Yes(2)
NK
FM Class 1, Division 2
No
I6(4)
No
IF(4)
No
N6
No
I1
No
IA
No
N1
Yes
NC
No(3)
ND
Yes
NE(4)
Yes
NF(4)
No(3)
I7
No
IG
No
N7
Yes
NJ
No(3)
NA
No Approval
No
Code
Input Types
S001
S002(5)
Code
FOUNDATION
fieldbus
Model
T1
Transient Protection
Mounting Kit Options
B6
Mounting Bracket for 2-in. pipe mounting and for panel mounting SST bracket and bolts
Enclosure Options
JP1
JP2
Plastic Box, Cable Glands (9 x M20 nickel-plated brass glands for 7.511.9 mm unarmored cable)
JP3
Plastic Box, Conduit Entries (5 plugged holes, suitable for installing 1/2-in. NPT fittings)
JA1
JA2
Aluminum Cable Glands (9 x M20 nickel-plated brass glands for 7.511.9 mm unarmored cable)
JA3
Aluminum Conduit Entries (5 plugged holes, suitable for installing 1/2-in. NPT fittings)
JS1
JS2
Stainless Steel Box, Cable Glands (9 x M20 nickel-plated brass glands for 7.511.9 mm unarmored
cable)
JS3
Stainless Steel Box, Conduit Entries (5 plugged holes, suitable for installing 1/2-in. NPT fittings)
JX3
Explosion-Proof Box, Conduit Entries (4 plugged holes, suitable for installing 1/2-in. NPT fittings)
Custom Software Configuration Request
C1
F5
Product Description
FOUNDATION
fieldbus
Calibration Certification
5-Point Calibration
C4
Q4
GE(7)
GM
(7)
I5
S001
T1
B6
JA2
Wiring
Rosemount 848T Sensor Wiring Diagram
1 2 3
2-wire RTD
and Ohms
1 2 3
3-wire RTD
and Ohms*
1 2 3
Thermocouples
and Millivolts
Standard Configuration
Unless otherwise specified, the transmitter will be shipped as
follows for all eight sensors:
Standard Configuration Settings
Sensor Type(1)
Damping(1)
Measurement Units(1)
Output(1)
Line Voltage Filter(1)
Temperature Specific
Blocks
FOUNDATION fieldbus
Function Blocks
Input Transient Filter(1)
(1) For all eight sensors
16
Thermocouple Type J
5 seconds
C
Linear with Temperature
60 Hz
Sensor Transducer Block (1)
Analog Input (8)
Multiple Analog Input (1)
Input Selector (4)
Enabled
= Default
Customer Information
Tagging
Hardware Tag: __________________________________________________________
Software Tag: __________________________________________________________
Function Block Type (select one only)
Enable Write Protect
Damping ______________________
NOTE
The C1 option is required to factory configure each sensor differently. The C1 option is also required for factory configuration of
process alerts and sensor tag.
All eight sensors configured identical to Sensor 1 (Fill out Sensor 1 only). Otherwise, each sensor must be individually
configured.
Sensor 1
Sensor 2
Sensor 3
Tag __________________________________________
Tag __________________________________________
Tag __________________________________________
Type
Type
Type
mV
mV
mV
Ohms
Ohms
Ohms
Type J
Type J
Type J
17
Sensor 1
Sensor 2
Sensor 3
None
None
None
Number of Leads
2-wire
3-wire
C
F
R
mA
Alarms(1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
Number of Leads
2-wire
3-wire
C
F
R
mA
Alarms(1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
(1)
(2)
Alarms are not enabled. Alarms must be enabled when the device is commissioned by the user.
Sensor 4
Sensor 5
Number of Leads
2-wire
3-wire
C
F
R
mA
Alarms(1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
Sensor 6
Tag __________________________________________
Tag __________________________________________
Tag __________________________________________
Type
Type
Type
mV
mV
mV
Ohms
Ohms
Ohms
Type J
Type J
Type J
None
None
Number of Leads
2-wire
3-wire
C
F
R
mA
Alarms(1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
Number of Leads
2-wire
None
3-wire
C
F
R
mA
Alarms (1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
(1)
(2)
Alarms are not enabled. Alarms must be enabled when the device is commissioned by the user.
18
Number of Leads
2-wire
3-wire
C
F
R
mA
Alarms(1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
Sensor 7
Type
Type
mV
mV
Ohms
Ohms
Type J
Type J
None
None
Number of Leads
2-wire
3-wire
C
F
R
mA
Alarms(1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
FOUNDATION
fieldbus
Tag __________________________________________
Number of Leads
2-wire
3-wire
C
F
R
mA
Alarms(1)(2)
HI HI Alarm ___________________________*(+ infinity)
HI Alarm______________________________*(+ infinity)
LO Alarm _____________________________*(- infinity)
LO LO Alarm __________________________*(- infinity)
(1)
(2)
Alarms are not enabled. Alarms must be enabled when the device is commissioned by the user.
19