Sunteți pe pagina 1din 57

Auto-Reclose on

Distribution Networks

Agenda

1st topic

Why Perform Auto-Reclose ?

Page 3

2nd topic

Where can we apply Auto-Reclose ?

Page 7

3rd topic

Terminology, Sequences & Settings

Page 15

4th topic

Check Synchronism

Page 46

5th topic

Conclusion

Page 56

Auto-Reclose on Distribution Networks MStockton 2012 - P 2


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Why Perform Auto-Reclose ?


What is Auto-Reclose
Pre-Fault
PTOC
RREC

It is a Control Technique
Trip

Trip

PTOC

Fault

RREC
Reclose
PTOC
Close

Auto-Reclose is the automatic closure


of a Circuit Breaker without the
intervention of a person

Fault

IEC61850 (parts -5 and 7-4) both


include autoreclose as a Protection
Related function, with a logical node
name of RREC
ANSI / IEEE
C37.2
reference 79
O
I
IEC 60617 symbol:

RREC

Auto-Reclose on Distribution Networks MStockton 2012 - P 3


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Why Perform Auto-Reclose ?


What are the Benefits ?
Continuity of Supply
Restoration is Automatic, therefore quicker
Shorter duration of Power Outages
Fewer Customer Minutes Lost

Reduced Asset Damage


Autoreclose permits use of faster, non-discriminative protection
Some overtripping is deemed acceptable

Less chance of faults evolving to more damaging scenarios


Lower pre-heating of CB contacts
May reduce maintenance requirements ?

Auto-Reclose on Distribution Networks MStockton 2012 - P 4


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Why Perform Auto-Reclose ?


What are the Benefits ?
Reduction in Operating Costs (OPEX)
Reduced requirement for substation visits
Reduction in damage of asset
Increase in capital costs (CAPEX)
Higher price of switchgear capable of autoreclose duty
Additional control relay (Autoreclose & Check Sync)

Improve System Stability


Not traditionally considered at Distribution voltages
Traditionally the distribution network was/is radial in design

With modern networks (Embedded generation) a definite


consideration

Part of the SMART Grid


Auto-Reclose on Distribution Networks MStockton 2012 - P 5
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Agenda

1st topic

Why Perform Auto-Reclose ?

Page 3

2nd topic

Where can we apply Auto-Reclose ?

Page 7

3rd topic

Terminology, Sequences & Settings

Page 15

4th topic

Check Synchronism

Page 46

5th topic

Conclusion

Page 56

Auto-Reclose on Distribution Networks MStockton 2012 - P 6


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Where Can We Apply Auto-Reclose ?


What Dictates Application ?
Type and relative quantities of Fault
Type of Plant
Circuit Breaker Capabilities
HUMAN SAFETY
On some areas of distribution networks, human safety will be the
overriding decision even when autoreclose seems applicable
Consider overhead line feeders in sparsely populated areas
Auto-Reclose on Distribution Networks MStockton 2012 - P 7
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Where Can We Apply Auto-Reclose ?


Fault Types
Permanent Faults
Require human intervention to resolve
Successive re-energisations of the system will extend the damage

Self Clearing Faults


No permanent damage to the power system
When cleared, the power system can be safely re-energised
Further classification:
Transient: Cleared by immediate isolation of the fault when the CB is
opened
Semi-Permanent: Cleared after a short time of isolation of the fault,
when the cause of the fault has been burnt or blown away

Auto-Reclose on Distribution Networks MStockton 2012 - P 8


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Where Can We Apply Auto-Reclose ?


Fault Types related to Plant Items
Transformers
Most faults are PERMANENT and require investigation &
rectification

Machines (motors & generators)


Most faults on machines are PERMANENT and require
investigation & rectification

Underground Cables
Most faults are considered as PERMANENT, require investigation
& rectification
Pecking faults may be self healing initially but consequential
weakening of the insulation requires intervention
Auto-Reclose on Distribution Networks MStockton 2012 - P 9
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Where Can We Apply Auto-Reclose ?


Fault Types related to Plant Items
Overhead Lines
Can have all fault types:
Permanent: Broken Conductors or Insulators
Transient: Insulator flashovers due to switching or lightning transient
overvoltages, conductor clashing (due to high winds or ice shedding)
Semi-Permanent: Phases bridged by animals or vegetation

Relative incidence depends upon the voltage level as this dictates


the spacing between conductors
Typical figures are 80-85% transient, 5 to 10% semi-permanent and
10% permanent
Statistically, 70-90% of all faults are -E faults at EHV
Auto-Reclose on Distribution Networks MStockton 2012 - P 10
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Where Can We Apply Auto-Reclose ?


Fault Types related to Plant Items
Auto-Reclose is generally applied to Overhead Lines only
Auto-Reclose on Mesh Busbar arrangements although controlling
other CBs, only provides auto-reclose for line faults

Auto-Reclose is generally not applied to Underground Cables,


Transformers or Machines
May be required for auto-reclose action on Mesh Busbar
arrangements
May be required for auto-reclose action on embedded generation
incomer circuits to restore connection to utility network (after
network faults)

Auto-Reclose on Distribution Networks MStockton 2012 - P 11


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Where Can We Apply Auto-Reclose ?


Circuit Breaker Capability

In order for the system to be safe, it is considered that the CB must always be
capable of achieving the open state safely ie tripping and breaking fault current

Circuit Breakers are required to declare an operating or duty cycle by ANSI/IEEE


and IEC standards, typically of the form
O t CO t CO , where
t is the minimum time between initial tripping before reclosure can be attempted
t is the minimum time between subsequent tripping and reclosure events

Not all current breaking devices are intended for auto-reclose application

The times t and t will affect the settings for the auto-reclose relay and hence
define whether auto-reclose can be effective

Auto-Reclose on Distribution Networks MStockton 2012 - P 12


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Where Can We Apply Auto-Reclose ?


Examples of Auto-Reclose Applications
Simple OHL Application
PTOC
RREC
Embedded
Generation

Public
Public
Network
Network

G59
RREC
OHL Circuit
RREC
PDIS

RREC

Transformer Circuit

Conventional OHL Application


Protection relay & auto-reclose relay
operate for OHL faults only
Control of single CB only
Embedded Generation Application
Protection relay used to disconnect
generation for network faults eg
interconnection (G59) protection
Auto-reclose used to re-connect
distributed generation automatically
when network recovers
Mesh Corner Application
OHL protection relay triggers three
auto-reclose relays, including relay on
LV side of transformer circuit
Auto-reclose relays operate to restore
supply for transient faults
Permanent (and transformer) faults
cause auto-isolation prior to autoreclose

RREC

Auto-Reclose on Distribution Networks MStockton 2012 - P 13


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Agenda

1st topic

Why Perform Auto-Reclose ?

Page 3

2nd topic

Where can we apply Auto-Reclose ?

Page 7

3rd topic

Terminology, Sequences & Settings

Page 15

4th topic

Check Synchronism

Page 46

5th topic

Conclusion

Page 56

Auto-Reclose on Distribution Networks MStockton 2012 - P 14


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Successful Auto-Reclose for Transient Fault
Trip
Close

Fault

PTOC
RREC

Fault
Inception

Arc
Extinguished

Trip

Protection
Reset

Fault Clearance Time

Closing
Pulse

Contacts
Contacts
Make
Fully Closed

Dead Time

End of
Sequence

Recovery Time

System
Disturbance Time
Protection Relay

Operating Time

Operated

Reset Time

Contacts
Separate
Opening
Arcing
Time
Time

Contacts
Fully Open
Closing
Time

Circuit Breaker
CB Operating Time

CB Reclaim Time
Dead Time

Closing
Pulse
Reclaim Time

Auto-Reclose Relay
Auto-Reclose in Progress (ARIP)

Time (non-linear)
Auto-Reclose on Distribution Networks MStockton 2012 - P 15
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Unsuccessful Auto-Reclose for Permanent Fault
Trip
Close

Fault

PTOC
RREC

Fault
Inception

Arc
Extinguished

Trip

Protection
Reset

Fault Clearance Time

Closing
Pulse

Contacts
Re-Trip
Make
Contacts
onto
Fully Closed
Fault

Dead Time

Arc
Extinguished

Fault Clearance Time

Protection
Reset

End of
Sequence

Recovery Time

System
Protection Relay

Operating Time

Operated

Reset Time

Contacts
Separate
Opening
Arcing
Time
Time

Contacts
Fully Open

Disturbance Time
Operating Time

Closing
Time

Operated

Reset Time

Contacts
Separate
Opening
Arcing
Time
Time

Contacts
Fully Open

Circuit Breaker
CB Operating Time

CB Operating Time
Dead Time

CB Reclaim Time

Closing
Pulse
Reclaim Time

Auto-Reclose Relay
Auto-Reclose in Progress (ARIP)

Auto-Reclose Lockout

Time (non-linear)
Auto-Reclose on Distribution Networks MStockton 2012 - P 16
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Speed
For system stability, the System Disturbance Time should be
minimised
Fast (instantaneous) Protection
Short Dead Times

High Speed Auto-Reclose (HSAR):


Fault initiation to CB Closure is less than 1 second

Low Speed or Delayed Auto-Reclose (DAR):


Fault initiation to CB Closure is greater than 1 second (but often
10s of seconds)
Generally only applicable on highly interconnected systems (where
system synchronism is maintained) or on single sourced, radial
systems
Auto-Reclose on Distribution Networks MStockton 2012 - P 17
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Protection
Fast Protection is preferred to minimise system disturbance
At higher voltages, fast, discriminating protection is normal
Eg Line Differential, Phase Comparison, Directional Comparison,
Distance (Z1 or Aided Schemes)

At lower voltages, fast, discriminating protection may not be


available but auto-reclose allows:
Fast, non-discriminating (overreaching) protection for the initial
trip cycle
Eg Instantaneous OC/EF, Distance (Z1 Extension)

Slower, discriminating protection for the final trip


Eg IDMT Overcurrent/Earth Fault
Auto-Reclose on Distribution Networks MStockton 2012 - P 18
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Example of Auto-Reclose Application (Distance Z1 Extension)
Z3

Fast (Non-discriminating) Z1X trip causes


initial trip to cover 100% of line length from
both ends
Some possibility of tripping for adjacent
lines

Z2
Z1

Z1X

Z1X

Z1

After reclosure, the Z1X element is inhibited, so


that discriminating distance protection is used

Z2
Z3

Advantage transient faults are cleared quickly


A/R
Z1X

&

A/R
Z1X

&

Z1

Z2
Z3

Z1

t2

t2

Z2

t3

t3

Z3

Trip Trip

Auto-Reclose on Distribution Networks MStockton 2012 - P 19


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time
Sequence diagrams showed two Dead Times
System Dead Time
Time when arc goes out, to when CB contacts touch

Relay Dead Time

Typically from protection reset to start of close pulse

For stability, the System Dead time must be minimised


System Dead Time needs to consider:

Load Type
Protection Reset Time
Fault De-ionisation Time
Circuit Breaker Capabilities

Auto-Reclose on Distribution Networks MStockton 2012 - P 20


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time & Load Type

Predominantly Motors
Induction machines will typically ride through 0.5s supply interruptions
Synchronous machines will lose synchronism quickly, typically in less than
0.3s
Generally allow for 3-10s dead times (to allow UV isolation of machines)

Street Lighting
For safety (traffic, theft, violence) outages should be minimised, typically
1-2 seconds

Domestic
Traditionally, could be long (measured in minutes)
Modern systems impose penalties due to outages, therefore minimised
(according to local legislation)

Auto-Reclose on Distribution Networks MStockton 2012 - P 21


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time & Load Type
Embedded Generation
Generally treated as a negative load
Similar to motor considerations
Minimum dead time to allow safe disconnection of generation
Can be set much longer (minutes) to allow for system to stabilise
prior to reconnection

Future systems cannot follow this approach


Embedded generation will be required to stay on-line and ride
through system faults as much as possible
Reconnection will need to occur as quickly as safely possible

Auto-Reclose on Distribution Networks MStockton 2012 - P 22


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time & Protection Reset
Usually the Auto-Reclose Dead time only starts when the
protection trip resets
Check scheme some simple schemes start the Dead Time earlier!

Protection should fully reset during dead time


Ensures that a fully discriminative trip can occur on reclosure

Technology considerations
Electromechanical (Induction Disc) relays had long resets
(seconds)
Static relays designed with Instantaneous Reset (<50ms typical)
Numeric relays give the option of both what is best?

Auto-Reclose on Distribution Networks MStockton 2012 - P 23


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time & Fault De-ionisation

Must allow for the ionised air at the fault point to disperse
Ionised air constitutes a conduction path
De-ionisation time depends upon:
System Voltage
Type of Fault
Current Weather Conditions
Fault Clearance Time
Difficult to establish an exact time
Approximate formula is (10.5+KV/34.5) cycles
For 66kV: 250ms (@50Hz); 210ms (@60Hz)
For 132kV: 290ms (@50Hz); 240ms (@60Hz)

Usually considered on HV systems only distribution systems have CB


operating time criteria that are more onerous

Auto-Reclose on Distribution Networks MStockton 2012 - P 24


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time & CB Capability

In order for the system to be safe, it is considered that the CB must always be
capable of achieving the open state safely ie tripping and breaking fault
current

Circuit Breakers are required to declare an operating or duty cycle by


ANSI/IEEE and IEC standards, typically of the form

O t CO t CO , where
t is the minimum time between initial tripping before reclosure can be
attempted
t is the minimum time between subsequent tripping and reclosure events

t defines the CB mechanism reset

t may be more significant (if longer) for multi-shot schemes

Auto-Reclose on Distribution Networks MStockton 2012 - P 25


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time & CB Capability
Mechanism Reset + Closing Time imposes a minimum system
dead time
Significant for HSAR to satisfy stability requirements

Most CBs have a trip free mechanism


Tripping is the priority and can interrupt the closing stroke
After tripping the trip free mechanism must be reset before
attempting closure

Auto-Reclose on Distribution Networks MStockton 2012 - P 26


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Dead Time & CB Capability
Fault
Inception

Arc
Extinguished

Trip

Closing
Pulse

Fault Clearance Time

Contacts
Contacts
Make
Fully Closed

Dead Time

Recovery Time

System
Contacts
Separate
Opening
Arcing
Time
Time

Disturbance Time

Contacts
Fully Open

Closing
Time

T1

T2

Circuit Breaker
CB Operating Time

Time (non-linear)
Oil
11kV

Vacuum
15kV

Oil
132kV

Air
380kV

SF6
132kV

SF6
380kV

Opening Time (msec)

60

38

30

35

40

20

Operating Time (msec)

100

53

60

45

70

50

T1 (msec)

80

23

200

235

30

10

Closing Time (msec)

160

48

350

65

80

60

Minimum Dead Time (msec)

240

280

550

300

110

70

T2 (msec)

20

70

10

20

120

40

Auto-Reclose on Distribution Networks MStockton 2012 - P 27


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Closing Pulse
Needs to be of sufficient duration to release the closing
mechanism eg spring
Usually a fixed pulse duration to ensure mechanism is fully
operated
Can be terminated by the CB auxiliary contact
Anti-pumping is required to prevent repetitive open/close in
quick succession when both trip & close circuits are active
Trip circuit is given priority !

Auto-Reclose on Distribution Networks MStockton 2012 - P 28


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Reclaim Time
The Auto-Reclose device should not reset before the Protection
has had time to operate, to ensure that permanent and semipermanent faults are seen as part of the same Auto-Reclose
sequence
Set Reclaim Time > Maximum Protection Operating Time
Set shorter reclaim time and inhibit its timing if a fault is detected
by use of a protection start signal

Reclaim Timer settings need to consider:


Supply Continuity
Fault Incidence/Past Experience
Switchgear Capability & Maintenance requirements
Auto-Reclose on Distribution Networks MStockton 2012 - P 29
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Reclaim Time
Supply Continuity
Setting a long reclaim time risks that separate fault events will be
seen as the same fault and cause inadvertent lockout of the autoreclose cycle
Setting a short reclaim time imposes a risk that a permanent fault
isnt detected
The appropriate setting is largely dictated by knowledge of past
network events

Auto-Reclose on Distribution Networks MStockton 2012 - P 30


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Example of Long Reclaim Time Settings
Trip

Permanent
Fault

RREC

Close
Fault
PIOC
Arc
Inception Trip Extinguished

PIOC & PTOC

PTOC
Trip &
CB Contacts
Lockout
Make onto Fault
Maximum PTOC
Time =30s

Arc
Extinguished

Time (non-linear)

Reclaim Time >30s

Trip

Trip
Close
Fault F1
Arc
Inception PIOC
Trip Extinguished

PIOC & PTOC

F1

F2

RREC
PTOC
Fault F2
Trip &
Inception
CB Contacts
Lockout
Make
Maximum PTOC
Time =30s

Arc
Extinguished

Reclaim Time >30s

Advantages
Correctly identifies the
permanent fault condition &
trips to lockout on the
discriminative (IDMT) trip
Minimises CB duty
Disadvantages
Incorrectly identifies two
successive independent
transient faults as a permanent
fault condition
Leads to unwanted lockout &
unplanned outages

Time (non-linear)

Auto-Reclose on Distribution Networks MStockton 2012 - P 31


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Example of Short Reclaim Time Settings
Trip

RREC

Close
Fault
PIOC
Arc
Inception Trip Extinguished

Permanent
Fault

PIOC & PTOC

PTOC
Trip &
CB Contacts
Lockout
Make onto Fault
Maximum PTOC
Time =30s

Arc
Extinguished

Reclaim Time Setting = 10s

Time (non-linear)

Reclaim Time Extended by Start signal


operation to allow Trip & Lockout

PTOC
Start

Trip

Trip
Close
Fault F1
Arc
Inception PIOC
Trip Extinguished

F1

PIOC & PTOC

F2

RREC

CB Contacts
Make

Fault F2
Inception

PIOC
Trip

Advantages
Correctly identifies the
permanent fault condition &
trips to lockout on the
discriminative (IDMT) trip
Correctly identifies two
successive independent
transient faults & recloses for
each
Disadvantages
Increased switchgear duty,
especially in areas of frequent
lightning

Arc
Extinguished CB Contacts
Make

Time (non-linear)

Reclaim Time = 10s

Reclaim Time = 10s

Auto-Reclose on Distribution Networks MStockton 2012 - P 32


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

May require remote AutoReclose Control

Terminology, Sequences & Settings


Reclaim Time & CB Capability

In order for the system to be safe, it is considered that the CB must always be
capable of achieving the open state safely ie tripping and breaking fault
current

Circuit Breakers are required to declare an operating or duty cycle by


ANSI/IEEE and IEC standards, typically of the form

O t CO t CO , where
t is the minimum time between initial tripping before reclosure can be
attempted
t is the minimum time between subsequent tripping and reclosure events

t effectively imposes a minimum reclaim time as this is the taken to reenergise the breaker (spring winding, establish air pressure, etc)

Usually a contact is made available to the auto-reclose device to indicate


when the CB is ready for operation (Springs Charged)
Used to inhibit reclosure until safe

Auto-Reclose on Distribution Networks MStockton 2012 - P 33


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Reclaim Time
Theoretically, the Reclaim Time can be set <1s for modern highspeed protection relays due to reset times <<500ms
Practically, the Reclaim Time is unlikely to be set <5s to relieve
the duty on the switchgear
More commonly, longer reclaim times are used

Auto-Reclose on Distribution Networks MStockton 2012 - P 34


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Number of Shots
In auto-reclose, every attempted reclosure of the CB is termed a
Shot
Single shot schemes predominate at higher voltage levels
Increased risk of plant damage for multiple shots
Increased system disturbance and risk of stability issues
Increased plant maintenance requirements

At lower voltages (distribution), multi-shot schemes can be


considered
Use very dependent upon knowledge of faults on the network

Auto-Reclose on Distribution Networks MStockton 2012 - P 35


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Successful Auto-Reclose for Semi-Permanent Fault
Trip
Close
Fault
Inception

Fault

PTOC
RREC

Arc
Protection
Extinguished Reset

Trip

Fault Clearance Time

Closing
Pulse

Contacts
Make

Contacts
Re-Trip
Make
onto Contacts
Fault Fully Closed

Dead Time

Arc
Protection
Extinguished Reset

Closing
Pulse

Dead Time

Fault Clearance Time

Contacts
End of
Fully Closed Sequence
Recovery Time

System
Disturbance Time
Protection Relay

Op. Time

Operated

Reset

Contacts
Separate
Opening
Arcing
Time
Time

Contacts
Fully Open

Op. Time

Closing
Time

Operated
Contacts
Separate
Opening
Arcing
Time
Time

Reset
Contacts
Fully Open
Closing
Time

Circuit Breaker
CB Operating Time

CB Operating Time
Dead Time 1

Closing
Pulse

Dead Time 2
Reclaim Time

Auto-Reclose Relay

Closing
Pulse
Reclaim Time

Auto-Reclose in Progress (ARIP)

Time (non-linear)
Auto-Reclose on Distribution Networks MStockton 2012 - P 36
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Number of Shots
Typical experience from areas of frequent thunderstorms
83.25% are successful 1st Shot reclosures
Additional 10.05% are successful for 2nd Shot reclosures
(Dead Time 15-45s)
Additional 1.42% are successful for 3rd Shot reclosures
(Dead Time 120s)

This suggest that 1 or 2 shot schemes are the most successful


with limited benefit from further attempts
Almost imposes minimal additional duty on switchgear

Auto-Reclose on Distribution Networks MStockton 2012 - P 37


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Number of Shots
Benefits of Multi-Shot Auto-Reclose
Improved Supply Continuity
Helps prevent lockout during thunderstorms
Systems with relatively high levels of semi-permanent faults
First shot may be unsuccessful
Second shot allows for the bridging material (vegetation or animal) to
burn itself clear and give successful re-closure

Helps on systems with fused spurs


Promotes fuse operation for low fault levels
Saves fuses for some transient faults

Auto-Reclose on Distribution Networks MStockton 2012 - P 38


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Example of Multi-shot schemes with Fused Tees

Trip
Close

PIOC & PTOC


RREC
Permanent
Fault (Low IF)

Trip
Close

PIOC & PTOC


RREC
Transient
Fault (Low IF)

For Permanent Faults with low IF


Fuse may not blow before PTOC
If fault reapplied during autoreclose, the fuse will be preheated and may eventually blow
before the PTOC element
Maintains supply to most
customers
For Transient Faults
PIOC element may operate
before fuse
Maintains supply to all
customers after a brief
interruption (No need to replace
fuse)

Auto-Reclose on Distribution Networks MStockton 2012 - P 39


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Lockout
If auto-reclosure is unsuccessful the auto-reclose device will
lockout and prevent further reclose attempts. Other causes
include:
Failure of the CB to open & clear the fault when protection has
operated
Lack of CB energy within an acceptable time period
Lack of synchronism when attempting reclosure
Too many CB operations (maintenance)
Too many CB operations in a defined period (Excessive Fault
Frequency)
Operation of protection that doesnt initiate auto-reclose (BAR
input)
Eg Busbar protection, VT Buchholz, etc
Auto-Reclose on Distribution Networks MStockton 2012 - P 40
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Reset from Lockout
Once Lockout is attained, reset mechanisms include:
Manual reset (either locally or via telecontrol)
After Manual CB closure (either local or via telecontrol) usually
with a time delay and/or detection of healthy load state for a
period
Automatically timed reset after lockout occurrence

In all cases, the condition(s) causing lockout needs to have been


resolved

Auto-Reclose on Distribution Networks MStockton 2012 - P 41


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Other Auto-Reclose Interlocks

Many specific auto-reclose programmes have been developed to correspond


to specific network demands

These generally impose additional interlocking at various points in the autoreclose cycle. Examples include:
Pre-tripping interlocks to ensure CB was closed prior to protection
operation, voltages measured at both sides of CB are healthy and
available
Interlocks to prevent the Dead Time starting unless the CB is seen to have
opened and checks on the voltage to ensure that the circuit is deenergised
Interlocks to ensure the Dead Time only runs when the correct voltage
conditions are met
Interlocks to bypass the Dead Time as soon as the voltages are in
synchronism
The suitability of any auto-reclose device should be checked against the
required functionality

Auto-Reclose on Distribution Networks MStockton 2012 - P 42


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Sequence Co-ordination

On LV networks, it is impossible to have switching stations at all required


locations
Fused spurs are used
Pole Mounted Reclosers (PMR) are used

Upstream auto-reclose relays should discriminate with the installed PMRs


Co-ordinate the reclose cycles
Carefully select the auto-reclose sequences on both PMRs and switching stations
to ensure that the PMRs lockout for downstream faults.

Utilise sequence co-ordination


This ensures that the upstream auto-reclose device monitors but doesnt trip for
downstream events which are controlled by the PMRs
Upstream protection and auto-reclose only trips when PMR sequences have
completed but without the need for additional reclose attempts
Auto-Reclose on Distribution Networks MStockton 2012 - P 43
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Terminology, Sequences & Settings


Auto-Reclose Mode Selection

Most schemes will have simple Auto-Reclose In/Out selection

If remote selection, is possible then care should be taken


Any local selection should override the remote selection
Eg if a local user switches DAR out of service for testing purposes, to remain
safe it is necessary to ensure that the DAR can not be switched back into
service remotely

With Auto-Reclose switched out of service, non-discriminating protection


should be blocked
Eg Instantaneous elements, Distance Z1X

If Live Line working is permitted


Auto-Reclose should be switched out of service
Auto-Reclose mode selection by telecontrol should be disabled
All instantaneous (including non-discriminating) elements should be
enabled

Auto-Reclose on Distribution Networks MStockton 2012 - P 44


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Agenda

1st topic

Why Perform Auto-Reclose ?

Page 3

2nd topic

Where can we apply Auto-Reclose ?

Page 7

3rd topic

Terminology, Sequences & Settings

Page 15

4th topic

Check Synchronism

Page 46

5th topic

Conclusion

Page 56

Auto-Reclose on Distribution Networks MStockton 2012 - P 45


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Terminology

Check Sync refers to the check of voltages either side of a CB that is to be


reclosed, either manually or during an auto-reclose cycle. It monitors

Angle Difference the difference in phase angle between the voltages


Slip Frequency the difference in frequency between the voltages
Voltage Magnitude the absolute value of the voltage
Voltage Difference the difference in magnitude between the voltages

Combinations of these measurements are used to ascertain if it is safe to close the


CB

Check synchronism is usually measured on a single phase

A Check Synchronism device only checks the status it doesnt issue control pulses
to bring systems into synchronism
Synchronising controls are issued from a Auto-Synchroniser, or manually

Auto-Reclose on Distribution Networks MStockton 2012 - P 46


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Terminology
Line Voltage is the voltage measured on the protected circuit
Measured from a circuit VT

Bus Voltage is the voltage measured behind the protected circuit


Measured from a busbar VT, or from a suitable circuit VT via a
voltage selection scheme

Generally we consider the Bus Voltage as the reference with the


Line Voltage rotating relative to it

Auto-Reclose on Distribution Networks MStockton 2012 - P 47


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Terminology
0

Nominal Volts

Live Volts

Dead Voltage is when the measurement


indicates a de-energised state

VBUS
In Sync
Region

VLINE

Live Voltage is when the measurement


indicates an energised state
Voltages between the Dead and Live
voltage bands are undefined

Dead Volts

For In Sync or System Split


measurement both voltages must be Live
In Synchronism is when the voltages are
less than X apart
System
Split
Region

180

System Split is when the voltages are


180 apart
On System Split detection the
criteria for permitting closure may
change

Auto-Reclose on Distribution Networks MStockton 2012 - P 48


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Check Synchronism & Auto-Reclose

To permit CB closure during an auto-reclose cycle it will often be necessary to


confirm that the voltages either side of the breaker are suitable

The Check Synchronism device performs this task. Suitable states for closure
are one or more of the following:
In Sync - when both voltages are Live and within X apart
Dead Line Charging when the Bus voltage is live and the Line voltage
is dead
Dead Bus Charging when the Line voltage is live and the Bus voltage
is dead
When the Line and Bus voltages are both dead (less common)

For the In Sync condition, the dead time may be shortened or even ignored

Auto-Reclose on Distribution Networks MStockton 2012 - P 49


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Revertive Dead Line Charging
End Y

End X

Trip
Close

PIOC & PTOC

PIOC & PTOC

RREC

RREC

RSYN

RSYN

Dead Line Charge


Time = 5s

Trip
Close

Dead Line Charge


Time = 15s

IEC61850 (parts -5 and 7-4) both include


Check Synchronising as a Protection Related
function, with a logical node name of RSYN
End X attempts to reclose first after 5 seconds,
to charge the dead line
If reclose is successful, End Y will
immediately reclose assuming an In
Sync condition is measured
If reclose is unsuccessful, End Y will
reclose after a further 10s, to charge the
dead line
End X is the permitted to reclose
assuming an In Sync condition is
measured
Typical Dead Line Charge settings are in the
range of 5s to 60s

Auto-Reclose on Distribution Networks MStockton 2012 - P 50


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Predictive Closure
0

Nominal Volts

Live Volts

With the voltage in the In Sync region,


contact closure of the breaker can occur with
some phase angle difference

VBUS
In Sync
Region

Dead Volts

System
Split
Region

180
Auto-Reclose on Distribution Networks MStockton 2012 - P 51

Some Check Synchronism elements have a


Predictive Closure facility
Monitors the frequency of rotation of
the vectors
With knowledge of the CB closing
time, it predicts when to issue the
closing pulse such that contact closure
occurs when the phase angle
difference is virtually 0
This places less stress on the CB and
the system but may delay the overall
Predictive Closure
time to closure
Region. Close pulse

VLINE

issued to promote
closure at top dead
centre

ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Concerns with Check Synchronism

At some point, two vectors rotating at different frequencies will have little or
no phase angle

Some customers perceive a risk that the check synchronism could be defeated
at Manual Closure by maintaining the close command and waiting for the in
synchronism signal . Risk is overcome by: Use of Slip Frequency measurement & blocking, and/or
Use of Guard Relays
An additional perceived risk, is that the output contacts of the check sync
relay could be damaged and hence give erroneous in synchronism signals
Risk overcome by use of additional logic that prevents the output being
used if it is present before the request to close
With modern numeric relays and Programmable Scheme Logic, these
facilities can all be mimicked and the risk negated

Auto-Reclose on Distribution Networks MStockton 2012 - P 52


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Concerns of Damaged Check Synch Relay

Auto-Reclose on Distribution Networks MStockton 2012 - P 53


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Check Synchronism
Implementation in Modern Numeric Relay

Auto-Reclose on Distribution Networks MStockton 2012 - P 54


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Agenda

1st topic

Why Perform Auto-Reclose ?

Page 3

2nd topic

Where can we apply Auto-Reclose ?

Page 7

3rd topic

Terminology, Sequences & Settings

Page 15

4th topic

Check Synchronism

Page 46

5th topic

Conclusion

Page 56

Auto-Reclose on Distribution Networks MStockton 2012 - P 55


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Auto-Reclose on Distribution Networks


Conclusions
Traditionally this has been limited to Delayed Auto-Reclose with
little or no concern for synchronism check or stability
Modern networks are pushing for more efficient use of the
network, with fewer and shorter supply interruptions
Increase requirement for Check Synchronism
Use of faster protection, shorter dead times and reclaim times

Scheme settings are largely dependent upon network fault


history
CB Capability and understanding has a large impact on possible
auto-reclose scheme selection & settings
Auto-Reclose on Distribution Networks MStockton 2012 - P 56
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject
to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular
purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

www.alstom.com

S-ar putea să vă placă și