Documente Academic
Documente Profesional
Documente Cultură
Application 2
Consider the autotransformer given below. The power transformer data has been
given: 175/175/30 MVA Autotransformer, YNyn0d1, 230/115/13.8 kV. The
current transformer ratios are as follows: HV CT ratio - 800/5, LV CT ratio 1200/5 and TV CT ratio 2000/5.
Idiff (pu)
Is-HS2
Is-HS1
Restraint region
K2
Operating region
K1
Is1
Is1/K1
Is2
Ibias (pu)
Solution Application 2
1. Ratio correction factors
Since the transformer has an on load tap changer on the HV side, the nominal
voltage of the HV winding must be set to the mid tap voltage level. According
to the nameplate data, the mid tap voltage is 218.5kV. The mid tap voltage can
also be calculated as follows:
(5 15 )
2
230 = 218.5kV
100
100 +
Mid tap position =
K amp , HVCT =
I nom,T 1CT
=
S ref
3Vnom, HV
K amp , LVCT =
1200
175 10 6
= 1.366
3 115 10 3
I nom ,T 3CT
=
S ref
3Vnom ,TV
= 1.730
3 218.5 10 3
I nom,T 5CT
=
S ref
3Vnom , LV
K amp ,TVCT =
800
175 10 6
2000
175 10 6
= 0.273
3 13.8 10 3
Calculate HV full load current at both tap extremities and LV and TV full load
current.
175 10 6
3 241500
= 418.37 A primary
418.37
= 2.615 A secondary
160
175 10 6
3 195.510 3
= 516.810 A primary
516.810
= 3.230 A secondary
160
145 10 6
3 115 10 3
= 727.963 A primary
727.963
= 3.033 A secondary
240
30 10 6
3 13.8 10 3
= 1255.109 A primary
1255.109
= 3.138 A secondary
400
0.476
= 0.095 pu
5
0.588
= 0.118 pu
5
Determine Ibias at both tap extremities (with mid tap correction). The
currents used in the Ibias calculation are the currents after ratio and vector
correction.
4.524 + 4.143 + 0.857
4.762
= 4.762 A =
= 0.9524 pu
2
5
5.588 + 4.143 + 0.857
5.294
Ibias at tap 19 =
= 5.294 A =
= 1.059 pu
2
5
Ibias at tap 1 =
Check Idiff < Iop by a 10% margin for each tap extremity and adjust Is1
and/or K1 as necessary.
Tap 1: Since Idiff = 0.095pu and 0.9Iop = 0.9 x 0.286 = 0.257pu, the error
introduced by the on load tap changer causes no mal operation considering K1 =
30% and Is1 = 0.2pu.
Tap 19: Since Idiff = 0.118pu and 0.9Iop = 0.9 x 0.347 = 0.312pu, the error
introduced by the on load tap changer causes no mal operation considering K1 =
30%, Is1 = 0.2pu, K2 = 80% and Is2 = 0.8pu.
66.7% of transformer nominal rating
Calculate HV, LV and TV load current at 66.7% of the nominal MVA rating.
The 66.7% is the interception between Is1 and K1. It is determined as Is1/K1
100% = (0.2/0.3) 100 = 66.7%.
175 10 6
3 241500
= 279.05 A primary
279.05
= 1.744 A secondary
160
175 10 6
3 195.510 3
= 344.71A primary
344.71
= 2.154 A secondary
160
145 10 6
3 115 10 3
= 485.551A primary
485.551
= 2.023 A secondary
240
30 10 6
TV full load current = 0.667
= 837.158 A primary
3 13.8 10 3
LV full load current =
837.158
= 2.093 A secondary
400
0.317
= 0.063 pu
5
Determine Ibias at both tap extremities (with mid tap correction). The
currents used in Ibias calculation are the currents after ratio and vector
correction.
Ibias at tap 1 =
Ibias at tap 19 =
0.393
= 0.0786 pu
5
Check Idiff < Iop by a 10% margin for each tap extremity and adjust Is1
and/or K1 as necessary:
Tap 1: Since Idiff = 0.063 pu and 0.9Iop = 0.9 x 0.2 = 0.18pu, then there is
sufficient safety margin with K1 = 30% and Is1 = 0.2 pu.
Tap 19: Since Idiff = 0.0786pu and 0.9Iop = 0.9 x 0.212 = 0.19pu, then there is
sufficient safety margin with K1 = 30% and Is1 = 0.2 pu.
The following graph shows the bias characteristic, the CT and tap changer errors
(assumed as 20%), and the bias, differential coordinates corresponding to full
load current and 66.7% of full load current. It can also be seen that it is
necessary to check the safety margin at the two knee-points of the bias
characteristic.