Documente Academic
Documente Profesional
Documente Cultură
Typical applications
Service entrances and onsite generation
Energy savings
v Measure efficiency, reveal opportunities and verify savings
v Sub-bill tenants for energy costs
v Allocate energy costs to departments or processes
Integrated network comprising corporate intranet, Internet, serial, dial-up or wireless connections
Features
Cost-effective design
v Space saving: mounting depth of only 50 mm
v Simple retrofit: fits most cut-outs of previous analogue meters
v Easy installation: mounted without tools (just two clips)
Ease of use
v Bright, anti-glare, backlit LCD display
v Fast setup via display (all models) or via software (PM210)
v Compatible with entry-level PowerLogic PowerView software (PM210)
High accuracy metering
v Active energy certification under IEC62053-21 and ANSI C12.16
v Class 1.0 accuracy
Pulse outputs (PM200P)
v 2 outputs for kWh and kVARh pulsing
Communications
PowerLogic PM210 offers a 2-wire RS-485 port with standard Modbus
RTU protocol for remote monitoring to provide greater control over the
performance and overall health of your systems. Diagnose and isolate the
cause of power-related equipment or process problems. Baud rates range
from 9,600 bps to 19,200 bps. The PM210 is ready to use with PowerLogic
PowerView software and can integrate with energy management systems.
+0.8
92 0.0 (3.62)
+0.8
92 0.0
Installation
Mounting
(3.62)
Easily mounted without tools (just two clips) and with a mounting depth
of only 50 mm, you can install the PowerLogic PM200 series meters on
switchboard doors to maximise free space for electrical devices.
Circuit and control power connections
96
(3.78)
96
(3.78)
mm (in.)
Compatible with low and high voltage single-, two- and three-phase
systems. Direct connect inputs up to 480 V ac line-to-line or use voltage
(potential) transformers for higher voltage systems. All models offer a
universal AC or DC power supply.
Metering over-range
1.2 Un
Input impedance
2 M (Ph-Ph) / 1 M (Ph-N)
Frequency range
45 to 65 Hz
Current inputs
Nominal current
5 A or 1 A
Withstand
Load/burden
< 0.15 VA
Impedance
Control power
Operating range
AC frequency
45 to 65 Hz
Load/burden
Ride through
100 ms at 120 V ac
Software
The PowerLogic PM210 is compatible with PowerLogic PowerView software
to create a facility-level power monitoring system. Real-time data is
automatically uploaded and logged by the software for analysis at the
system level.
1
2
Measurements
0.5% from 1 A to 6 A
1%
Frequency: present
0.02 Hz from 45 to 65 Hz
Active energy
Instantaneous RMS.
PM210: See register 4048. Negative sign - indicates lag.
General specifications
Power summary display
Weight
Safety
Operating temp
-40 C to +85 C
Realtive humidity
5% to 95% RH at 50 C (non-condensing)
Altitude
Pollution degree
Installation category
Dielectric withstand
IP degree of protection
Immunity
Emissions
PM200
PM200P
PM210
Installation
Mounted without tools (just two clips) and
mounting depth of only 50 mm
Digital inputs/outputs
Two pulse outputs for kWh and kvarh
measurements
Communication
One Modbus RS-485 port
2-wire
Certificate No. 002188
Schneider Electric
35 Rue Joseph Monier
CS 30323
92506 Rueil Malmaison Cedex
Tel : +33 (0)1 41 29 70 00
Fax : +33 (0)1 41 29 71 00
www.powerlogic.com
www.schneider-electric.com
PLSED107020EN
ART# 832415
11-2008
2008 - Schneider Electric - All rights reserved
As standards, specifications and designs develop from time to time, always ask
for confirmation of the information given in this publication. PowerLogic, ION, ION
Enterprise, MeterM@il and Modbus are either trademarks or registered trademarks
of Schneider Electric.
Printed on recycled paper
Publishing : Schneider Electric
Production : Schneider Electric PMC
Printing : Imprimerie du Pont de Claix - made in France