ASCON spa
GENERAL INDEX
1
SERIAL COMMUNICATIONS
(see the instruction manual SERIAL COMMUNICATION
SUPPLEMENT supplied separately)
1 IDENTIFICATION OF MODEL
Thank you for choosing an ASCON controller
The instruments of the XP series belong to the last generation of
microprocessor based controller, are universal, very powerful but
simple to use.
They are fitted with AUTO-TUNE, as aid for system start-up, and serial
communication for introduction into a distributed control network.
They are complete because all possible variables are always present.
Configuration of the instrument permits determination of the operating
mode according to the application required.
Configuration code
XP - A B C D
3
5
B
None
20mA C.L. Std Ascon protocol
20mA C.L. Modbus/Jbus protocol
0
1
2
Retransmission output Y4
None
Fitted (4...20 mA or 0...10 Vdc)
0
1
Set point
OPTIONS
Power supply
Standard
(up to 4 mem. or Loc./Rem.)
Time-programmable
(11 segments)
0
1
1
275.8
275.8
4 50
1 IDENTIFICATION OF MODEL
1.2 Configuration code
Beginning and end of
scale
Configuration code
E F 5 H
I L M N
OPZIONI
2nd
part
1st part
Model code
Input X
E
F
5
H
Main output Y1
275.8
275.8
4 50
I
L
M
N
Auxiliary output Y2
Auxiliary output Y3
Retransmission output Y4
Set point W
Beginning and end of scale
((for configurable scales only))
O
P
9.999
9999
C0
12
Program holden
15
11
Auxiliary output Y2 ON
13
14
5
4
6
9
8
Functions (menu)
19
Auxiliary window N
Auxiliary output Y3 ON
275.8
275.8
4 50
2
10
3
Withdrawal screw
7a
18
17
20
21
Increment digit
Select digit
Confirm data
Automatic/Manual
Front cover
NUMERIC INDICATORS X, W, Y, N
1 - Process
The value of measure X is expressed in engineering
variable (X) (green) units.
If above end of scale
If below beginning of scale
- In programmation: displays parameter values
10
- In configuration: displays the values of the 1st part
of the configuration code (see enclosed leaflet)
8888
____
8888
----
275.8
275.8
50
4 - Auxiliary
Normally off, lights up to display
window N (green) a - the selected N of 1 of the 4 stored Set points ,
in which case led 5 W lights up too
7.5
b - the N of the segment in execution (option with
programmable set, see chapter 11)
a
b
in this case, led 6 SG lights up too
4
4 4
7b - Output Y1 (decrease)
8 - Output Y2 (red)
9 - Output Y3 (red)
MAN
11 - Remote (green)
REM
12 - Auto-Tune (green)
AT
14 - In execution (green)
RUN
275.8
275.8
4 50
Only for
instruments with
time - programmable
option
Standard configuration:
(1 Local + 4 storable used for:
modifying the Set point
recalling the 4 memorized Set points
(see enclosed leaflet)
Remote Set configuration:
(1 Local + 1 Remote) used for:
passing from Local to Remote Set point
and viceversa (see enclosed leaflet)
Programmed Set configuration:
(see chapter 11)
to recall the Local operating Set point
to start, stop, start again the
execution of the memorized programme
17 - Digit selection
18 - Increment digit
19 - Functions
Keys for
modifying
numeric
values of
any data
20 - Enter
21 - Auto/Man
3 DIMENSIONS - INSTALLATION
3.1 - Overall dimensions (in compliance with DIN 43700)
48
14
150
65 min.
96
W
A/M
110
min.
Front cover
projection
92
Advised
thickness 1 16
+0.8
+0.6
45
Panel apertures
Holding
hooks
AMBIENT
Temperature: 0 50C
Humidity : 30 ... 85uR%
C Screw locking
275.8
275.8
4 50
Locking
screws
Do NOT force
labels supplied
cross-screwdriver
if different from
C, remove and
apply plate with
requested unit.
Pa
kPa
HR%
MPa
mV
l/m
m3/h
mA
Nm3/h
CO%
kW
O2%
psi
Bar
rh
4 ELECTRICAL WIRING
A Terminal board
Wiring
protection plate
2
Rotate
downwards
Plate screw
Cold joint
compensation
thermometer
3 gilded
terminals for
input signals
Cable wires
section N
With eyelet
terminals
6.9 max.
With fork
terminals
1
6.9 max.
1
Rotate
upwards
0.25 2.5
AWG
22 14
2
Depress the plate to
engage the pin
67
Preferential
4 ELECTRICAL WIRING
Although this controller is designed to resist the heaviest disturbances
present in industrial environments (level IV of standard (IEC 801-4), it is
advised to keep to the following precautions:
Precautions
D E
D E
Serial communication A
Analogic inputs B
Logic inputs and analogic
signals C
Input D
Outputs E
Wiring diagram
1
COM
TX
Serial
communication
(optional)
3
RX
IL1
4
Logic
inputs
IL2
4
3
420 mA
A
2 wire
transmitter
Input
process
variable (X)
B
B
mA
Volt
J, L,
K, S
7
9
22
13
23
Y3
24
Y2
14
Auxiliary
outputs
15
+ 24 Vdc
(2)
12
IL3
11
21
25
0%
16
26
100%
27
Y1
Relay increase
17
Relay decrease
Y1
18
Retransmission
Y4
output
(option)
28
19
29
20
10
Pt100
(1)
Main
output
4 ELECTRICAL WIRING
Schema
1
Singledipower
collegamento
supply
11
Single power supply
12
"Switching" type
Standard: 100 to 240 Vac - 15% + 10%
for low tension: 24 Vac -15% + 10%
24 Vdc 15%
Absorbed power 4VA
Respect polarities
9
The eventual shield must be well earthed
at only one end
Note:
with a 15 mt. probe to controller distance and
a 1.5 sq.mm. section cable, the error is
about 1C.
10
420 mA
+24
Vdc
+24 Vdc
+24 Vdc
Transmitter
9
Rin = 30 per mA
Rin = 10 K per Volt
X
i
9
Transmitter
com.
Rin
Rin
Rin
4 ELECTRICAL WIRING
Schema
3
Remote
di collegamento
Set point input
Rin = 30 per mA
Rin = 330 K per V
In current
4..20 mA
In voltage
0..10Vdc
5
Remote Set point mA, Volt Rin
NOT galvanically
isolated
25
4 Logic inputs
External contacts COM
H C1
H C2
IL1
IL2
H C3
IL3
21
22
23
24
25
y.1.
26
100%
y.h.
27
Total
stroke
Useful
stroke
100%
6 Main output Y1
16
Y1
17
Y1
18
Relay
increase
V~
Relay
decrease
M
~
10
4 ELECTRICAL WIRING
7 Auxiliary outputs Y2 - Y3 (see p. 12)
Load
Y3
13
V~
14
Y2
15
Load
Galvanically isolated
4..20mA, 10Vdc max. or
0..10Vdc, 20mA max.
28
Y4
29
Retransmission
output Y1F
(option)
Retransmission:
of measurement X
of Set point W
A 420 mA
V 010 Vdc
1
Transmission
TX
2
Zener
Reception 2,7 V
3
RX
11
W1
Active high
(above)
Active low
(under)
H
W
-300 units
+300 units
Band
On
Off
W1
Active Out
Active In
H
H
IWI
IWI
-300 units
+300 units
Independent
On
Off
W1
On
Off
H
Active high
(above)
Active low
(under)
W
Beginning of scale
End of scale
(1) The Set point of Y2 and Y3 is not limited by the limits of the main
Set point W1, but only by the scale span.
inhibition
W1
On
Off
Startup
W1
W
inhibition
Active high
(above)
Active low
(below)
On
Off
Startup
12
275.8
275.8
4 50
Gas
mA
Time-programmable intervention
Only available with the Programmable Set point option.
The ON or OFF state of the auxiliary outputs Y2 and/or Y3 can be
selected for every segment of the programme.
(See chapter 11)
13
6 PASSWORDS
In order to prevent tampering or inadvertent alterations of the configuration
or of some important parameters at the programming stage, 2 passwords
have to be entered.
WpAss
NO
OK
3333
3333
Return to normal
function
YES
Introduction into configuration
WpAss
NO
OK
Return to normal
function
YES
Introduction into the 5th group
14
1111
1111
275.8
275.8
4 50
H C1
H C2
IL1
IL2
H C3
IL3
21
22
23
24
275.8
275.8
4 50
RS232
Interface
C1
IL2
C2
Type of modification
IL3
C3
Version with
programmable Set point
(option)
No action
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
passage
Local Sp. to Remote Sp.
__
Passage to successive
segment (NEXT)
__
Temporary stop
of programme
__
Programme startup
RUN
HLD
Note 1: Is possible to fix the selected Set point holding closed the relative contacts.
While they are closed is possible to make changment from Auto/Man or Man/Auto but
it is not possible to change Set point
15
12 TECHNICAL DATA
Accuracy
(25C. amb.)
Process
variable
(configurable)
Auxiliary
inputs
Thermocouples
Direct current
4..20mA, 0..20mA, Ri 30
Direct voltage
With
configurable
scale field
Set point
(standard
version)
Local/Remote
Set point
Control
mode
Number of repetitions
1..9999
Current
4..20mA, Ri30
Voltage
0..10Vdc, Ri 330k
Algorithm
0,5..999,9%
0,1..100min., excludable
0,01..10min., excludable
Dead zone
Auto - Tune
Auto/Man
Station
Not isolated
accuracy:
0,1% a 25C
16
12 TECHNICAL DATA
Three states: Increase - stop - Decrease
Main
output Y1
Action mode
Hysteresis
0,1..10%
Auxiliary
outputs
Y2 - Y3
Type of Set point
(configurable)
deviation
band
0...300 steps
independent
Loop-Break-Alarm
(signal of control loop defect)
Special functions
Retransmission Current
output Y4
(option)
Voltage
time-programmable
(only for Set programmable option)
4..20mA (450 max, 10Vdc max)
0..10Vdc (500 min, 20mA max)
galvanically
isolated
Serial
Interface 20mA C.L. passive and galvanically isolated
communication
For other data, see manual
(option)
On three levels for: modification, indication only,
no access
Immunity to disturbances level IV, standard IEC 801-4
Access to parameters
Protections
Single
power
supply
Standard model
Absorbed power
about 4VA
Auxiliary
24Vdc 10%, 20mA max. for 2-wire or 3 or 4-wire transmitter
power supply
General
features
Isolation group
Climatic group
Ambient
Protection
Material
Self-extinguishing 94V1
Weight
about 480 g.
Dimensions
17
GUARANTEE
The equipment is guaranteed free from
manufacturing defects for 1 year after
installation, for a maximum of 18 months after
delivery.
Faults caused by use other than that described
in these operating instructions are excluded
from the guarantee.
ASCON spa
20021 Bollate (Milano), Italy
Via Falzarego, 9/11 - Tel. (0039 - 2) 33337.1
Fax (0039 - 2) 3504243 - Telex 322451 ASCON I