Project

Job ref

Exercise 7b)
Part of structure

Sheet no

one way slab


Drawing ref.

Calc by

see Ref

1/3

Date

KW

Check by Date

15/11/2010

Calculations

Ref

Output

Exercise 6b):
Task

A 250 mm deep 6000 x 4000 mm wide rectangular slab is required to support


office loads.
fck = 30 MPa, fyk = 500 MPa.
Assume 300 mm wide supports, a 50-year design life and a requirement for
a 2-hour resistance to fre in an external but sheltered environment.

1. Load Arrangement:

Part plan of flat slab

top reinf.

top reinf.
@
corne
r

bottom reinf.
top
reinf. direction
of span

Plan View
reinf. bottom reinf.
Secti
on

top

ref

Project

Job ref

Exercise 7b)
Part of structure

Sheet no

one way slab


Drawing ref.

Calc by

2. Actions
Permanent
Self-weight
Finishes
Variable
Offices

Exp. 4.1

BS EN 1992-1-2,
Table 5.9

Output

qk = 4.0 kN / m2

3. Nominal cover, cnom


cnom = cmin + cdev
where

4.4.1.2

15/11/2010

0.30m 25kN/m3 = 7.5 kN / m2


= 1.0 kN / m 2
gk = 8.5 kN /
m2

Table A1

EN 1992

KW

Check by Date

Calculations

Ref

BS EN 1991-1-1

2/3

Date

see Ref

ref

(See Tutorial 6)

cmin = max[cmin,b; cmin,dur; 10 mm]

where
cmin,b = 12 mm, assuming 12 mm
diam. reinf. cmin,dur = 15 mm for XC1
and using C30/37
cdev = 10 mm

cnom = 25 mm

Fire For 2 hours resistance, amin = 40 mm critical

cnom = 34 mm

cnom = amin - diam. of reinforcement/2 = 40mm - 12mm/2 = 34.0mm >


25.0mm
BS EN 1990
Exp. (6.10)

4. Load combination
Ultimate load, n
By inspection, Exp. (6.10) is critical.
n = 1.35 8.50kN / m2 + 1.5 4.0kN / m2 = 17.5 kN / m2
Arrangement
Choose to use all-and-alternate-spans-loaded load cases, i.e. use coefficients.
The use of Table 5.6 in BS EN 199212 is restricted to where redistribution
does not exceed 15%. (minimum cover for fre)
The coefficients used presume 0% redistribution at supports. As the amount of
redistribution is less than 20%, there are no restrictions on reinforcement grade.
5. Design moments
Moment @ support

2.2 kN m

= w l2/2 = 17.5 x (0.5m)2 /2 =

2.2 kN m Moment @ mid span = w

l2/8

= 17.5 x

(4m)2

= 35 kN m Note: Cantelever moment ignored assume


that cantelever is not Moment @ corner
17.5 x (0.7m)2 /2 = 4.3 kN m

= w l2/2 =

35.0 kN m

/8
4.3 kN m

Project

Job ref

Exercise 7b)
Part of structure

Sheet no

one way slab


Drawing ref.

Calc by

see Ref

3/3

Date

KW

Check by Date

15/11/2010

Calculations

Ref

Output

6. Flexural design
Effective depth:
Assuming 12 mm reinforcement:
mid span M

d = 250 mm- 34mm - 12mm/2 = 210mm

(b= 1m strip of slab!!!)

K = MEd / bd2 fck =35.0 kNm x 10^6 / (1000mm x (210mm)^2 x 30N/mm 2) =


0.026
OK

Klim = 0.168 > K = 0.026


from tablez / d = 0.98 (good practice is to reduce z/d = 0.95 He therefore use
0.95)

z/d =
0.95

Limitation of x/d C30 <C50 therefore


xu /d = 0.45 (elastic analysis + redistribution + assessment of rotation capacity)
x / d table = 0.05 0.45

OK

Table 5.1

z = 210mm x 0.95 = 199 mm


Standard Method
Detailing Struct.
Concrete P 179

As, req = M / (0.87 z fyk) =


404mm2

35.0 kNm x 10^6 / (0.95 x 199mm x 500N/mm 2) =

Try : H 12 250mm centre to centre therefore As, prov. = 452 mm 2


( = As, req / As, prov. = 404mm2/
452mm2 = 0.89) Reinforcement is at 89%
of its capacity.
Beam strip moment for 500mm cantilever. (worst case in corner)
OK
K = MEd / bd2 fck =4.3 x 10^6 / (1000 x 210^2 x 30) = 0.003
z/d =
0.95

Klim = 0.168 > K = 0.003


from tablez / d = 0.99 (good practice is to reduce z/d = 0.95 therefore use
Limitation of x/d C30 <C50 therefore

OK

xu /d = 0.45 (elastic analysis + redistribution + assessment of rotation capacity)


x / d table = 0.04 <
0.45 z = 210x 0.95
7. Minimum amount of reinforcement (check for whole slab)
Concrete Centre

As,min =

How to design

0.15% x 1000mm x 215mm =

322.5 mm

P19
Table 6

Therefore provide H 12 250mm As, prov. = 452mm for all fexure


reinforcement.

OK

8. Maximum amount of reinforcement(check for whole slab)


As,max =
10000mm

0.04 Ac =
2

> > 2 x 452

0.04 x 1000mm x 250mm =


2
mm

OK