Sunteți pe pagina 1din 35

Engineering Data

ED15063-5
Group: Controls
Part Number: ED 15063
Date: June 2013
Supersedes: ED15063-4

MicroTech II
Chiller Unit Controller
Protocol Information
Modbus Protocol

WSC

Water-Cooled Centrifugal, Single-Compressor

WDC

Water-Cooled Centrifugal, Dual-Compressor

WPV

Water-Cooled Centrifugal, Single-Compressor

HSC

Water-Cooled Single-Compressor Centrifugal, Heat Recovery

HDC

Water-Cooled Dual-Compressor Centrifugal, Heat Recovery

TSC

Water-Cooled Single-Compressor Centrifugal, Templifier

WMC

Water-Cooled Centrifugal, Magnetic Bearing

WCC

Water-Cooled Centrifugal, Counterflow

AGZ

Air-Cooled Global Scroll

ACZ

Air-Cooled Scroll Condensing Unit

WGZ

Water-Cooled Global Scroll

AGS

Air-Cooled Global Screw

WGS

Water-Cooled Global Screw

TGZ

Templifier Water Heater

2013 Daikin McQuay

Table of Contents
TABLE OF CONTENTS........................................................................................................................................................ 2
LIMITED WARRANTY .............................................................................................................................................................. 4
NOTICE .................................................................................................................................................................................. 4
REVISION HISTORY ............................................................................................................................................................... 4
SOFTWARE REVISION ........................................................................................................................................................... 4
REFERENCE DOCUMENTS .................................................................................................................................................... 4
INTRODUCTION .................................................................................................................................................................... 6
CHILLER MODELS ................................................................................................................................................................. 6
CONTROLLER DATA POINTS ................................................................................................................................................. 6
MODBUS PROTOCOL INFORMATION ............................................................................................................................ 7
COMPATIBILITY ...................................................................................................................................................................... 7
PROTOCOL DEFINITIONS ...................................................................................................................................................... 7
VALID FUNCTION CODES ...................................................................................................................................................... 7
VALID ERROR CODES ........................................................................................................................................................... 8
MODBUS DATA POINT ........................................................................................................................................................... 8
EXAMPLE DATA POINT: CHILLER ENABLE ............................................................................................................................ 8
CONFIGURING THE UNIT CONTROLLER ................................................................................................................................ 8
SET UP THE UNIT FOR NETWORK CONTROL ........................................................................................................................ 8
TYPICAL APPLICATION: MINIMUM INTEGRATION ..................................................................................................... 9
DISPLAY IMPORTANT DATA POINTS ..................................................................................................................................... 9
COMPREHENSIVE DATA POINT TABLES ................................................................................................................... 10
MODBUS DATA POINTS ....................................................................................................................................................... 10
DETAILED DATA POINT INFORMATION ...................................................................................................................... 13
ACTIVE SETPOINT ............................................................................................................................................................... 14
ACTUAL CAPACITY .............................................................................................................................................................. 14
ACTUAL RPM ...................................................................................................................................................................... 14
CAPACITY LIMIT OUTPUT .................................................................................................................................................... 14
CAPACITY LIMIT SETPOINT ................................................................................................................................................. 14
CAVITY TEMPERATURE ....................................................................................................................................................... 15
COMPRESSOR DISCHARGE TEMPERATURE ....................................................................................................................... 15
CHILLER ENABLE ................................................................................................................................................................ 15
CHILLER LIMITED................................................................................................................................................................. 15
CHILLER LOCAL/REMOTE ................................................................................................................................................... 15
CHILLER MODE OUTPUT ..................................................................................................................................................... 15
CHILLER MODE SETPOINT .................................................................................................................................................. 16
COMPRESSOR 2 ACTIVE CAPACITY LIMIT ............................................................................................................................ 16
CHILLER STATUS ................................................................................................................................................................ 16
CHILLER POWER .................................................................................................................................................................. 16
COMPRESSOR CURRENT .................................................................................................................................................... 16
COMPRESSOR DISCHARGE TEMPERATURE ....................................................................................................................... 17
COMPRESSOR PERCENT RLA ............................................................................................................................................ 17
COMPRESSOR POWER ....................................................................................................................................................... 18
COMPRESSOR RUN HOURS ................................................................................................................................................ 18
COMPRESSOR SELECT .......................................................................................................................................................... 19
COMPRESSOR STARTS ....................................................................................................................................................... 19
COMPRESSOR SUCTION LINE TEMPERATURE ................................................................................................................... 20
COMPRESSOR VOLTAGE .................................................................................................................................................... 20
CONDENSER ENTERING WATER TEMPERATURE ............................................................................................................... 21
CONDENSER FLOW SWITCH STATUS ................................................................................................................................. 21
2

ED 15063-5

CONDENSER LEAVING WATER TEMPERATURE .................................................................................................................. 21


CONDENSER PUMP RUN HOURS ........................................................................................................................................ 21
CONDENSER REFRIGERANT PRESSURE ............................................................................................................................. 21
CONDENSER SATURATED REFRIGERANT TEMPERATURE .................................................................................................. 21
CONDENSER WATER FLOW RATE ...................................................................................................................................... 22
CONDENSER WATER PUMP STATUS ..................................................................................................................................... 22
COOL SETPOINT .................................................................................................................................................................. 22
DESIGN RPM ...................................................................................................................................................................... 22
EVAPORATOR ENTERING WATER TEMPERATURE .............................................................................................................. 22
EVAPORATOR FLOW SWITCH STATUS ................................................................................................................................ 22
EVAPORATOR LEAVING WATER TEMPERATURE FOR UNIT ................................................................................................ 22
EVAPORATOR LEAVING WATER TEMPERATURE FOR COMPRESSOR ................................................................................. 23
EVAPORATOR PUMP RUN HOURS ...................................................................................................................................... 23
EVAPORATOR REFRIGERANT PRESSURE ........................................................................................................................... 23
EVAPORATOR SATURATED REFRIGERANT TEMPERATURE ................................................................................................ 23
EVAPORATOR WATER FLOW RATE ..................................................................................................................................... 24
EVAPORATOR WATER PUMP STATUS ................................................................................................................................. 24
HEAT RECOVERY ENTERING WATER TEMPERATURE ........................................................................................................ 24
HEAT RECOVERY LEAVING WATER TEMPERATURE ........................................................................................................... 24
HEAT SETPOINT .................................................................................................................................................................. 24
ICE SETPOINT ...................................................................................................................................................................... 24
IGV PERCENTAGE OPEN .................................................................................................................................................... 24
INVERTER TEMPERATURE ................................................................................................................................................... 25
LIQUID LINE REFRIGERANT PRESSURE .............................................................................................................................. 25
LIQUID LINE REFRIGERANT TEMPERATURE ........................................................................................................................ 25
MAXIMUM RPM ................................................................................................................................................................... 25
MINIMUM RPM .................................................................................................................................................................... 25
OIL FEED PRESSURE .......................................................................................................................................................... 26
OIL FEED TEMPERATURE .................................................................................................................................................... 26
OIL SUMP PRESSURE .......................................................................................................................................................... 26
OIL SUMP TEMPERATURE ................................................................................................................................................... 26
OUTDOOR AIR TEMPERATURE ............................................................................................................................................ 27
PUMP SELECT ..................................................................................................................................................................... 27
RUN ENABLED ..................................................................................................................................................................... 27
ALARMS ................................................................................................................................................................................ 28
ALARM CLASSES ................................................................................................................................................................. 28
FAULT ALARMS .................................................................................................................................................................... 28
PROBLEM ALARMS .............................................................................................................................................................. 28
WARNING ALARMS .............................................................................................................................................................. 28
ALARM HANDLING ............................................................................................................................................................... 28
ALARM DIGITAL OUTPUT ..................................................................................................................................................... 28
CLEAR ALARMS ................................................................................................................................................................... 28
ACTIVE ALARMS .................................................................................................................................................................. 29
INDEX OF DETAILED POINT INFORMATION ............................................................................................................... 34

ED 15063-5

Limited Warranty
Consult your local Daikin McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local
Daikin McQuay Representative, go to www.daikinmcquay.com.

Notice
2013 Daikin McQuay, Minneapolis MN. All rights reserved throughout the world.
Daikin McQuay reserves the right to change any information contained herein without prior notice. The user is
responsible for determining whether this product is appropriate for his or her application.
The following are trademarks or registered trademarks of their respective companies. Modbus is a registered
trademark of Gould, Inc. Windows is a registered trademark of Microsoft Corporation. MicroTech II is a registered
trademark of Daikin McQuay.

Revision History
ED 15063-0
ED 15063-1

May 15, 2003


May 18, 2005

ED 15063-2

Nov 22, 2005

ED 15063-3

April 14, 2009

ED 15063-5

Jan 21, 2013

Preliminary release.
Added points for Solid State Starter Current, Voltage, Power and Power Factor
Corrected some incorrect register listings
Changed doc to have only Holding Registers and Coils
Added WGS and WMC data
Added WMC, HSC HDC, and TSC to front page and Chiller Model table
Added WCC to front page and Chiller Model table
Corrected Modbus Alarms table
Added Compressor Current, Compressor Power and Compressor Voltage to the
Compressor Select Table
Added TGZmodel to all applicable tables. Removed reference to OITS panel and
added reference to unit keypad details in the Set up unit for network control
section. Added Index column to Comphrenesive Data Point table; corrected Chiller
Status holding register in table and also in detailed data section. Removed reference
to Chiller On/Off--use Run Enabled instead.
Added individual compressor data points.

Software Revision
This edition documents all versions of the standard MicroTech II Chiller Unit Controller firmware and all subsequent
revisions until otherwise indicated.

Reference Documents
Company

Number

Title

Source

McQuay International

IOMM WSC WDC

The McQuay DISTINCTION Series Single/Dual Compressor


Centrifugal Chillers Installation, Operating and Maintenance Manual

www.mcquay.com

McQuay International

OM CentrifMicro II

McQuay International

IM 743

McQuay International

IMM AGS
IMM AGSB

McQuay International

IOMM ACZ/AGZ

McQuay International

IOMM ACZ

McQuay International

MicroTech II Controller for Centrifugal Chillers and Templifiers


Operating Manual
MicroTech II Chiller Unit Controller Modbus Communication Module
Installation Manual
GeneSys Air-Cooled Screw Compressor Chiller
Air-Cooled Scroll Condensing Unit & Air-Cooled Scroll Chiller
w/Remote Evaporators Installation, Operation, and Maintenance Manual
Air-Cooled Scroll Condensing Unit Installation, Operation, and
Maintenance Manual

www.mcquay.com
www.mcquay.com
www.mcquay.com
www.mcquay.com
www.mcquay.com

IOMM AGZ
IOMM AGZ1

Air-Cooled Scroll Compressor Chiller & Air-Cooled Scroll Compressor


Water Chiller Installation, Operation, and Maintenance Manual

www.mcquay.com

McQuay International

IOMM WGZ

Water-Cooled Scroll Compressor Chiller Installation, Operation and


Maintenance Manual

www.mcquay.com

McQuay International

IOMM WPV

WPV Centrifugal Compressor Chillers Installation, Operating and


Maintenance Manual

www.mcquay.com

ED 15063-5

McQuay International

OM AGS

McQuay International

IOMM TSC

McQuay International

OMM TGZ

Modbus-IDA.ORG
Modbus-IDA.ORG

GeneSys Air-Cooled Screw Compressor Chiller Operation Manual


MicroTech II Templifier Single Compressor Centrifugal Installation,
Operation, and Maintenance Manual
MicroTech II Templifier TGZ Heat Recovery Water Heaters Operating
Manual
MODBUS Application Protocol Specification V1.1b
MODBUS over Serial Line Specification and Implementation Guide
V1.02

www.mcquay.com
www.mcquay.com
www.mcquay.com
www.Modbus.org
www.Modbus.org

ED 15063-5

Introduction
This document contains the necessary information to incorporate a MicroTech II Chiller Unit Controller from Daikin
McQuay into your Building Automation System (BAS). It includes all necessary Modbus variables and corresponding
MicroTech II Chiller Unit Controller data points. Modbus terms and principles are not defined. Refer to the appropriate
specifications for definitions and details.

Chiller Models
The following table lists the model designators of Daikin McQuay Chiller units and the corresponding description.
WSC Water-Cooled Centrifugal, Single-Compressor
WDC Water-Cooled Centrifugal, Dual-Compressor
WPV Water-Cooled Centrifugal, Single-Compressor
HSC
Water-Cooled Single-Compressor Centrifugal, Heat Recovery
HDC Water-Cooled Dual-Compressor Centrifugal, Heat Recovery
TSC
Water-Cooled Single-Compressor Centrifugal, Templifier
WMC Water-Cooled Centrifugal, Magnetic Bearing
WCC Water-Cooled Centrifugal, Counterflow
AGZ
Air-Cooled Global Scroll
ACZ
Air-Cooled Scroll Condensing Unit
WGZ Water-Cooled Global Scroll
AGS
Air-Cooled Global Screw
WGS Water-Cooled Global Screw
TGZ
Templifier Water Heater

Controller Data Points


The MicroTech II Chiller Unit Controller contains data points or unit variables that are accessible from three different
user interfaces: the unit keypad/display, the Operator Interface Touch Screen, or a Modbus serial network. Not all points
are accessible from each interface. This manual lists all important data points and the corresponding network path for
each applicable interface. Refer to the applicable Operation Manual for keypad/display and Operator Interface Touch
Screen details. See Reference Documents on page 4 for manual part numbers.

ED 15063-5

Modbus Protocol Information


Compatibility
The MicroTech II Chiller Unit Controller can be configured in an interoperable Modbus network. The controller must
have the corresponding Modbus Communication Module installed.
The MicroTech II Chiller Unit Controller conforms to the Modbus Standards published at www.Modbus.org. See the
Reference Documents on page 4.

Protocol Definitions
The Modbus protocol is a standardized Application Level (OSI Level 7) protocol used in interoperable Industrial Control
networks. Modbus provides the communication infrastructure necessary to integrate products manufactured by different
vendors and to integrate control services that are now independent.
It specifies how requests from the client are sent to a server and how servers reply. The client constructs a PDU (protocol
data unit) and sends it to a specific server or broadcasts it to all servers. The PDU contains a function code that defines
the action the client is requesting from the server(s). The PDU also includes a data field that further defines the action to
the server, for example, the location of the data to be read.
A normal reply from a server includes the same function code and a response data field. In the case of a read operation,
the response data field contains the requested data. In the case of a write operation, the response data field contains an
echo of the write data of the request command. If the server detects an error in the transmission, the reply to the client
includes and exception function code and the response data field contains an exception code.
Controllers can communicate on standard Modbus networks using one of two transmission modes: ASCII or RTU. Users
select the serial port communication parameters (baud rate, parity mode, etc), during configuration of the controller. The
mode and serial parameters must be the same for all devices on a Modbus network. Transmission mode determines how
information is packed into the message fields and decoded. In RTU mode, each byte contains two hexadecimal
characters, and in ASCII mode, each byte contains one ASCII character. The MicroTech II Chiller Unit Controller uses
the RTU mode only.
The MicroTech II Chiller Unit Controller uses the following data structure: 8 data bits, 1 or 2 stop bits, and no parity bit.
It uses data transmission rates from 1200 to 19200 bps.

Valid Function Codes


The MicroTech II Chiller Unit Controller supports eight public function codes.
Function Code

Description

Definition

04 (0x04)

Read Input Registers

05 (0x05)

Write Single Coil

This function code reads status from 1 to 2000 contiguous coils in a remote
device.
This function code reads status from 1 to 2000 contiguous discrete inputs in a
remote device.
This function code reads the contents of a contiguous block of holding registers in
a remote device.
This function code reads from 1 to approx. 125 contiguous input registers in a
remote device.
This function code writes a single output to either ON or OFF in a remote device.

06 (0x06)

Write Single Register

This function code writes a single holding register in a remote device.

15 (0x0F)

Write Multiple Coils

16 (0x10)

Write Multiple Registers

01 (0x01)

Read Coils

02 (0x02)

Read Discrete Inputs

03 (0x03)

Read Holding Registers

This function code forces each coil in a sequence of coils to either ON or OFF in
a remote device.
This function code writes a block of contiguous registers (1 to approx. 120
registers) in a remote device.

ED 15063-5

Valid Error Codes


The MicroTech II Chiller Unit Controller supports three error or exception codes.
Error Codes
Description
Definition
01
02
03

Illegal Function
Illegal Data Address
Illegal Data Value

The function code received in the query is not an allowable action for the server (or slave).
The data address received in the query is not an allowable address for the server (or slave).
A value contained in the query data field is not an allowable value for server (or slave).

Modbus Data Point


Each data point accessible from a Modbus network is described with a table that gives the data type and index. If the
data point represents an enumerated variable, the enumerations are also listed.

Example Data Point: Chiller Enable


This output data point indicates the current state of the chiller. The OFF state is represented by 0, and the ON state is
represented by 1. (D2)
Data Type

Index

Measurement

Units

Valid Range

Coil

Chiller State

NA

0 = Disable (Off)
1 = Enable (On)

Data Type

Data is represented as either single-bit elements or 16-bit elements. A single-bit element is referred to as a Discrete Input
when it refers to read-only data and as a Coil when it refers to read-write data. A 16-bit element is referred to as a Input
Register when it refers to read-only data and as an Holding Register when it refers to read-write data.
Index

There can be as many as 65,536 elements of each data type in a Modbus device. Data elements are numbered from 1 to
65,536 in each type. Data elements are addressed with an index in the range from 0 to 65,535. The index is not the
address of the data element in the unit controller memory. The index is used in Modbus PDUs to specify the location of
the data in the unit controller. This means, for example, that data element number 1 is addressed using index 0 in the
PDU.
Valid Range

Some properties are standard data types and some are enumerated sets. If the property value represents a range of values,
e.g., temperature or pressure, a range of values is given. If the property value is an enumerated set, all enumerated values
and corresponding meaning are given.

Configuring the Unit Controller


The MicroTech II Chiller Unit Controller and the Modbus Communication Module together are designed, programmed,
and configured at the factory to be a chiller unit controller accessible over a Modbus network. No additional
programming is required to make this a chiller unit controller. The unit controller is ready to operate with the default
values of the various parameters set at the factory. Default values may be changed with the unit keypad or via the
network. Parameters must be adjusted to accommodate your particular network. See the appropriate Operation Manual
for default values and keypad operating instructions and the Modbus Communication Module Installation Manual (see
Reference Documents section for manual part numbers.)
When you have integrated the unit into your network, you can monitor and control unit operation from your workstation.
At a minimum, you can:
Display and monitor data points
Turn the unit on or off
Operate the unit safely

Set up the Unit for Network Control


Setup for Centrifugal Chiller MicroTech II Network Control:

1.
2.
8

Disable the chiller. The chiller should not be operating while performing this setup.
At the chiller unit keypad:
ED 15063-5

a. In the Set Unit Setpoint screen 14, set the BAS Protocol to Modbus. Use the Manager Password of 2001.
b. In the Set Unit Setpoint screen 1, set the Control Source to Local.
Verify with the chiller/control company technician that the chiller is operational on BAS.
In the Set Unit Setpoint screen 1, set the Control Source to BAS.

3.
4.

Setup for all Other Chillers MicroTech II Network Control:

1.
2.
3.
4.

Set the Set Unit Setpoint screen 1 initially to Source = Keypad.


Verify that Modbus is selected as the Protocol in the applicable menu screen shown in the table below.
Verify with the chiller/control company technician that the chiller is operational on a BAS.
Set the Unit Setpoint screen 1 to Source = Network.

Model
Menu Screen
Password

AGZ-A

ACZ-A

AGZ-B

ACZ-B

7
2001

6
2001

10
2001

7
2001

AGS-A,
B, DP
12
8945

AGS-C

AGS-D

WGS

WGZ/TGZ

16
8453

17
8745

15
8745

10
2001

NOTE: Models AGZ-A/B, ACZ-A/B, and WGZ have one unit controller, while models AGS-B/C and WGS have one
unit controller and multiple circuit controllers. Unit settings for AGS-B/C and WGS models are adjusted on the unit
controller.

Typical Application: Minimum Integration


Display Important Data Points
Typical workstation displays of MicroTech II Unit Controller attributes include the following significant data points
(page number of detailed description in parenthesis). Each data point is identified with a number that also identifies it in
the Comprehensive Data Point Tables. These data points are also shaded in the comprehensive tables so that you can
distinguish them. References in the text of this section also identify these data points with a number and shading.
Table 1: Significant Data Points

No.

Configuration

No.

Chiller Status (12)

Chiller Mode Setpoint


(12)

5
6

Actual Capacity (11)

Chiller Enable (11)

Temperatures
Evaporator Entering
Water Temperature (16)
Evaporator Leaving
Water Temperature (16)
Condenser Entering
Water Temperature (15)
Condenser Leaving
Water Temperature (15)

No.

Setpoints

No.

Alarms

Cool Setpoint (16)

11

Alarm Digital Output


(20)

10

Capacity Limit Setpoint


(11)

12

Clear Alarms (20)

13

Active Alarms (21)

You can display any number of additional data points based on job requirements or individual preference. See Modbus
Data Points on page 8 for lists of all Modbus Variables available to the network. For a more detailed description of all
available data points, see the Detailed Data Point Information section on page 13 of this document.

ED 15063-5

Comprehensive Data Point Tables


Modbus Data Points
Note: See the appropriate Operation Manual for specific data ranges and default values.
Network Control
Property
Active Setpoint
Actual Capacity (3)
Actual RPM
Compressor #1
Compressor #2
Capacity Limit (Output) (10)
Capacity Limit Setpoint (10)
Cavity Temperature
Compressor #1
Compressor #2
Chiller Enable (Input) (4)
Chiller Limited
Chiller Local/Remote
Chiller Mode Output
Chiller Mode Setpoint
Compressor 2 Active Capacity
Limit

Page

Read/
Write

14
14
14

R
R
R

14
14
15

R
W
R

Data Type

Index

Description

Holding Register
Holding Register

40003
40011

-40- 199F
0 - 160%
0-32678

Holding Register
Holding Register
Holding Register
Holding Register

40247
40251
40043
40004

0 - 160%
0 - 160%

40086
40106
2
7
6
40148
40146

0=Off, 1=On
0=Not Limited, 1=Limited
0=Remote, 1=Local
1=ICE, 2=COOL, 3=HEAT
1=ICE, 2=COOL, 3=HEAT

40108

15
15
15
15
16

R/W
R
R
R
R/W

Holding Register
Holding Register
Coil
Coil
Coil
Holding Register
Holding Register

16

Holding Register

*Chiller Status (1)

16

Holding Register

40147

Chiller Power
Compressor Current
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6

16
16

R
R

Holding Register

40245

Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register

40027
40096
40110
40115
40120
40125

Compressor Discharge
Temperature
Compressor Select
Compressor #2

17

Holding Register
Holding Register

40020
40092

Compressor Percent RLA


Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6

17

Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register

40026
40095
40109
40114
40119
40124

Compressor Power
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6
Compressor Run Hours
Compressor Select
Compressor #2
Compressor #3

18

Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register

40028
40097
40111
40116
40121
40126

Holding Register
Holding Register
Holding Register

40175
40236
40239

10

18

WSC, WDC, WPV,


0=Off, 1=Start,
WMC, WCC, HSC,
2=Run, 3=PreTSC, HDC Models
Shutdown, 4=Service
ACZ, AGS, AGZ,
1=Off, 2=Start,
WGS, WGZ, TGZ
3=Run, 4=PreModels
Shutdown, 5=Service
Totalized compressor kilowatts.
0 - 65,535

-460- 621F
-460- 621F
0 -110%

0 - 65,535

0 - 65,535

ED 15063-5

Network Control
Property
Compressor #4
Compressor Select
Compressor Starts
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor Suction Line
Temperature
Compressor Select
Compressor #2
Compressor Voltage
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6
*Condenser Entering Water
Temperature (7)
Condenser Flow Switch Status
*Condenser Leaving Water
Temperature (8)
Condenser Pump Run Hours
Pump Select
Pump #2
Condenser Refrigerant
Pressure
Compressor Select
Compressor #2
Condenser Saturated
Refrigerant Temperature
Compressor Select
Compressor #2

Page

Read/
Write

18
19

R/W
R

20

20

Holding Register
Holding Register

40242
40161

Holding Register
Holding Register
Holding Register
Holding Register

40174
40235
40238
40241

Holding Register

40016

-40- 244F

Holding Register

40089

-40- 244F

Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register

40030
40099
40113
40118
40123
40128

Description
See page 13
0 - 65,535

0 - 65,535

20

Holding Register

40008

-40 - 244F

21

Coil

0=No Flow, 1=Flow

21

Holding Register

40009

-40 - 244F

21

R
Holding Register
Holding Register

40177
40233

0 - 65,535
0 - 32767

Holding Register
Holding Register

40022
40094

-3276.8 3276.7 psi


-3276.8 3276.7 psi

Holding Register

40021

-40 - 244F

Holding Register

40093

-40 - 244F

Holding Register

40025

0 - 65,535 (Requires field provided flow


measurement device)

Holding Register
Holding Register

40254
40255

Holding Register
Holding Register

40249
40253

Holding Register
Holding Register

40087
40107

Holding Register
Holding Register

40246
40250
40248
40252
32
40002

0=Pump Off Request, 1=Pump On Request


10 - 120F

21

21

22

Design RPM

22

11

Index

Condenser Water Flow Rate


Compressor #1
Compressor #2
IGV Percentage Open
Compressor #1
Compressor #2
Inverter Temperature
Compressor #1
Compressor #2
Maximum RPM
Compressor #1
Compressor #2
Minimum RPM
Compressor #1
Compressor #2
Condenser Water Pump Status
*Cool Setpoint (9)
*Evaporator Entering Water
Temperature (5)
Evaporator Flow Switch Status
Evaporator Leaving Water
Temperature for Unit(6)
*Evaporator Leaving Water
Temperature for Compressor

Data Type

24
R
25

25

25

0-32678

0-32678

22
22

R
R/W

Holding Register
Holding Register
Coil
Holding Register

22

Holding Register

40005

-40 - 244F

22

Coil

0=No Flow, 1=Flow

22

Holding Register

40007

-40 - 244F

23

R
Holding Register

40015

-40 - 244F

ED 15063-5

Network Control
Property

Read/
Write

Page

Compressor Select
Compressor #2
Evaporator Pump Run Hours
Pump Select
Pump #2
Evaporator Refrigerant
Pressure
Compressor Select
Compressor #2

23

23

Evaporator Water Flow Rate

24

Index

Description

Holding Register

40088

-40 - 244F

Holding Register
Holding Register

40176
40232

0 65,535
0 65,535

Holding Register
Holding Register

40018
40091

-3276.8 3276.7 psi


-3276.8 3276.7 psi

Holding Register
Holding Register

40017
40090

Holding Register

40019
30

-40 - 244F
-40 - 244F
0 - 65,535 (Requires field provided flow
measurement device)
0=Pump Off Request, 1=Pump On Request

40023

-40 - 244F

40024

-40 - 244F

40006
40051

50 - 120F
15 - 35F, Default=25F

40039

-22592 - 22591 psi

40037
40105

-40- 244F
-40- 244F

40033
40101

-22592 - 22591 psi


-22592 - 22591 psi

40035
40103

-40 - 244F
-40 - 244F

40034
40102

-22592 - 22591 psi


-22592 - 22591 psi

40036
40104
40040
20
3

-40 - 244F
-40 - 244F
-40 - 244F
0=Pump No. 1, 1=Pump No. 2
0=OFF, 1=Run Allowed

23

Evaporator Saturated
Refrigerant Temperature
Compressor Select
Compressor #2

Data Type

Evaporator Water Pump Status


24
R
Coil
Heat Recovery Entering Water
24
R
Holding Register
Temperature
Heat Recovery Leaving Water
24
R
Holding Register
Temperature
Heat Setpoint
24
R/W
Holding Register
Ice Setpoint
24
R/W
Holding Register
Liquid Line Refrigerant
25
R
Holding Register
Pressure
25
R
Liquid Line Refrigerant
Temperature
Compressor Select
Holding Register
Compressor #2
Holding Register
26
R
Oil Feed Pressure
Holding Register
Compressor Select
Compressor #2
Holding Register
26
R
Oil Feed Temperature
Compressor Select
Holding Register
Compressor #2
Holding Register
26
R
Oil Sump Pressure
Holding Register
Compressor Select
Compressor #2
Holding Register
26
R
Oil Sump Temperature
Compressor Select
Holding Register
Compressor #2
Holding Register
Outdoor Air Temperature
27
R
Holding Register
Pump Select
27
R/W
Coil
Run Enabled
27
R
Coil
*Boldface indicates data points required for typical minimum integration.

Chiller Alarm Variables


Network Control
Property
Alarm Digital Output
(11)
Clear Alarms (12)
Active Alarms (13)

12

Page

Read/Write

28
28
29

Data Type

Index

Description

Coil

0-No Alarm, 1=Alarm

R/W

Coil

25

Holding Register

4013040145

0=Normal, 1=Clear Alarm


16 Holding Registers: Each bit representing an
alarm condition

ED 15063-5

Detailed Data Point Information


This section lists the information (the data) that is available to the Industrial Control System via the Modbus RTU
protocol. This information is used to safely operate and log the performance of the chiller. The systems integrator also
uses this information when creating custom graphics.
Table 2: Data Points for Chiller Models

Data Point
Active Alarms
Active Setpoint
Actual Capacity
Actual RPM
Alarm Digital Output
Capacity Limit Output
Capacity Limit Setpoint
Cavity Temperature
Chiller Enable
Chiller Limited
Chiller Local/Remote
Chiller Mode Output
Chiller Mode Setpoint
Chiller Status
Compressor Current***
Compressor Discharge Temperature
Compressor Percent RLA
Compressor Power***
Compressor Run Hours
Compressor Select
Compressor Starts
Compressor Suction Line Temperature
Compressor Voltage***
Condenser Entering Water Temperature
Condenser Flow Switch Status
Condenser Leaving Water Temperature
Condenser Pump Run Hours
Condenser Refrigerant Pressure
Condenser Saturated Refrigerant Temperature
Condenser Water Flow Rate
Condenser Water Pump Status
Cool Setpoint
Design RPM
Evaporator Entering Water Temperature
Evaporator Flow Switch Status
Evaporator Leaving Water Temperature for
Compressor
Evaporator Leaving Water Temperature for Unit
Evaporator Pump Run Hours
Evaporator Refrigerant Pressure
Evaporator Saturated Refrigerant Temperature
Evaporator Water Flow Rate
Evaporator Water Pump Status
Heat Recovery Entering Water Temperature
Heat Recovery Leaving Water Temperature
Heat Setpoint
Ice Setpoint
IGV Percentage Open
Inverter Temperature
Liquid Line Refrigerant Pressure
Liquid Line Refrigerant Temperature
Maximum RPM
Minimum RPM
Network Clear Alarm
Oil Feed Pressure**
Oil Feed Temperature**
Oil Sump Pressure**
Oil Sump Temperature**
Outdoor Air Temperature
Pump Select
Run Enabled

WSC/WDC/WPV/WMC
/WCC/HSC/TSC/HDC

AGZ

ACZ

WGZ/TGZ

AGS

WGS

X
X
X

X
X
X

X
X

X
X
X

X
X
X

X
X
X

X
X
X

X
X*
X*

X
X*
X

X
X
X

X
X
X

X
X
X

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

X
X*
X
X
X
X

X
X*
X
X
X
X

X
X
X
X
X
X

X
X
X
X

X
X
X
X
X
X
X
X

X
X
X

X
X

X
X
X
X
X
X
X
X
X
X

X
X
X
X

X
X
X

X
X

X
X
X

X
X
X

X
X
X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

*Dual circuit models only

13

X
X
X
X
X
X
X
X
X

X
X

X
X
X
X
X

ED 15063-5

**Not in WMC model


***Optional. Solid State Starter required

Active Setpoint
This output data point indicates the current value of the Leaving Water Temperature setpoint. Based on the operating
mode of the chiller, this value is derived from the Cooling Setpoint, Ice Setpoint or Heating Setpoint. The default mode
is Cooling and is used unless changed by the Chiller Mode Setpoint. (A2)
Data Type
Holding Register

Index
40003

Measurement
Temperature

Units
F x 10

Valid Range
-40-199F

Actual Capacity
This output data point indicates the percent of capacity the chiller is currently producing. It may be more or less than the
nominal capacity of the chiller. (A10)
Data Type
Holding Register

Index
40011

Measurement
Percent of chiller capacity

Units
% x 10

Valid Range
0% to 160%

Actual RPM
This variable indicates the actual speed of the compressor. (I118 & I122)
Compressor #1

Data Type
Holding Register

Index
40247

Measurement
Revolutions Per Minute

Units
RPM

Valid Range
0-32768

Compressor #2

Data Type
Holding Register

Index
40251

Measurement
Revolutions Per Minute

Units
RPM

Valid Range
0-32768

Capacity Limit Output


This output data point is a measure of the ratio of operating capacity to full capacity expressed in percent. It indicates the
current value of the Capacity Limit Setpoint. (A42)
Data Type
Holding Register

Index
40043

Measurement
Percent of maximum capacity

Units
% x 10

Valid Range
0% to 160%.

Capacity Limit Setpoint


Capacity Limit is a measure of the ratio of operating capacity to full capacity expressed in percent. This level may be
adjusted via an operator workstation or other network device, but cannot be adjusted above a factory-specified limit. If
the chiller control source is set to network at the unit keypad, this input data point sets the operating value (input) for
the chiller. Refer to the appropriate Operation Manual for suitable data point values. (A3).
Data Type
Holding Register

14

Index
40004

Measurement
Percent of maximum capacity

Units
% x 10

Valid Range
0% to 160%.

ED 15063-5

Cavity Temperature
This output data point indicates the current temperature of the compressors motor stator cavity. (A85 & A105)
Compressor #1

Data Type
Holding Register

Index
40086

Measurement
Temperature

Units

Valid Range

Units

Valid Range

Fx10

Compressor #2

Data Type
Holding Register

Index
40106

Measurement
Temperature

Fx10

Compressor Discharge Temperature


This output data point indicates the current compressor refrigerant discharge temperature of the compressor selected with
Compressor Select on page 18. (A19)
Data Type
Holding Register

Index
40020

Measurement
Temperature

Units
F x 10

Valid Range
-460-621F

Compressor #2

Data Type
Holding Register

Index
40092

Measurement
Temperature

Units
F x 10

Valid Range
-460-621F

Chiller Enable
This input data point enables the chiller to run if operating conditions are satisfied, or disables the chiller from running.
(D1)
Data Type
Coil

Index
2

Measurement
Chiller State

Units

Valid Range
0 = Disable (Off)
1 = Enable (On)

NA

Chiller Limited
This output data point indicates whether chiller operation is limited in some way. If conditions exist that limit operation,
the chiller may be prevented from reaching the Leaving Water Temperature setpoint. (D6)
Data Type
Coil

Index
7

Measurement
Status

Units

Valid Range
0 = Not Limited
1 = Limited

NA

Chiller Local/Remote
The Local/Remote output data point indicates whether the chiller is in local control or allowed to be controlled remotely
over the network. (D5)
Data Type
Coil

Index
6

Measurement
Mode

Units

Valid Range
0= Remote
1 = Local

NA

Chiller Mode Output


This output data point indicates the current operating mode of the chiller. (I19)
Data Type

15

Index

Measurement

Units

Valid Range

ED 15063-5

Holding Register

40148

HVAC Mode

1. ICE
2. COOL
3. HEAT

NA

Chiller Mode Setpoint


The Chiller Mode input data point sets the mode of operation of the chiller from the network. (I17)
Data Type
Holding Register

Index
40146

Measurement

Units

HVAC Mode

Valid Range
1. ICE
2. COOL
3. HEAT

NA

Compressor 2 Active Capacity Limit


This variable indicates the active capacity limit for compressor 2. (A107)
Data Type
Holding Register

Index
40108

Measurement

Units

Percent

NA

Valid Range
0-100%

Chiller Status
This output data point indicates the current state of the chiller. (I18)
Data Type

Holding Register

Index

40147

Measurement

Chiller State

Units

Models

Valid Range

WSC, WDC, WPV,


WMC, WCC, HSC, TSC,
HDC

0=Off, 1=Start, 2=Run,


3=Pre-Shutdown,
4=Service

ACZ, AGS, AGZ, WGS,


WGZ,TGZ

1=Off, 2=Start, 3=Run,


4=Pre Shutdown,
5=Service

NA

Chiller Power
This variable indicates the totalized compressor kilowatts. (I116).
Data Type
Index
Measurement
Holding Register

40245

Electric Power

Units
kiloWatts

Valid Range
0-1000

Compressor Current
Compressor Select

This output data point indicates the compressor current of the compressor selected with Compressor Select on page 18.
(A26)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40027

Electric Current

Amperes

0 -65,535

Compressor #2

This output data point indicates the compressor 2 current. (A95)


Data Type
Index
Measurement
Holding Register

40096

Electric Current

Units
Amperes

Valid Range
0 -65,535

Compressor #3

This output data point indicates the compressor 3 current. (A109)


Data Type
Index
Measurement
Holding Register

16

40110

Electric Current

Units
Amperes

Valid Range
0 -65,535

ED 15063-5

Compressor #4

This output data point indicates the compressor 4 current. (A114)


Data Type
Index
Measurement
Holding Register

40115

Electric Current

Units
Amperes

Valid Range
0 -65,535

Compressor #5

This output data point indicates the compressor 5 current. (A119)


Data Type
Index
Measurement
Holding Register

40120

Electric Current

Units
Amperes

Valid Range
0 -65,535

Compressor #6

This output data point indicates the compressor 6 current. (A124)


Data Type
Index
Measurement
Holding Register

40125

Electric Current

Units
Amperes

Valid Range
0 -65,535

Compressor Discharge Temperature


This output data point indicates the current compressor refrigerant discharge temperature of the compressor selected with
Compressor Select on page 18. (A19)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40020

Temperature

F x 10

-460-621F

Compressor #2

This output data point indicates the compressor 2 discharge temperature. (A91)
Data Type
Index
Measurement
Units
Holding Register

40092

Temperature

F x 10

Valid Range
-460-621F

Compressor Percent RLA


This output data point indicates the current percent RLA for the compressor motor of the compressor selected with
Compressor Select on page 18. (A25)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40026

Percent RLA

% x 10

0 -110%

Compressor #2

This output data point indicates the compressor 2 percent RLA. (A94)
Data Type
Index
Measurement
Holding Register

40095

Percent RLA

Units
% x 10

Valid Range
0 -110%

Compressor #3

This output data point indicates the compressor 3 percent RLA. (A108)
Data Type
Index
Measurement
Holding Register

40109

Percent RLA

Units
% x 10

Valid Range
0 -110%

Compressor #4

This output data point indicates the compressor 4 percent RLA. (A113)
Data Type
Index
Measurement
Holding Register

40114

Percent RLA

Units
% x 10

Valid Range
0 -110%

Compressor #5

This output data point indicates the compressor 5 percent RLA. (A118)
Data Type
Index
Measurement
Holding Register

17

40119

Percent RLA

Units
% x 10

Valid Range
0 -110%

ED 15063-5

Compressor #6

This output data point indicates the compressor 6 percent RLA. (A123)
Data Type
Index
Measurement
Holding Register

40124

Percent RLA

Units
% x 10

Valid Range
0 -110%

Compressor Power
This output data point indicates the current compressor power of the compressor selected with Compressor Select on
page 18. (A27)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40028

Electric Power

kiloWatts

0-65,535

Compressor #2

This output data point indicates the current compressor 2 power. (A96)
Data Type
Index
Measurement
Holding Register

40097

Electric Power

Units
kiloWatts

Valid Range
0-65,535

Compressor #3

This output data point indicates the current compressor 3 power. (A110)
Data Type
Index
Measurement
Holding Register

40111

Electric Power

Units
kiloWatts

Valid Range
0-65,535

Compressor #4

This output data point indicates the current compressor 4 power. (A115)
Data Type
Index
Measurement
Holding Register

40116

Electric Power

Units
kiloWatts

Valid Range
0-65,535

Compressor #5

This output data point indicates the current compressor 5 power. (A120)
Data Type
Index
Measurement
Holding Register

40121

Electric Power

Units
kiloWatts

Valid Range
0-65,535

Compressor #6

This output data point indicates the current compressor 6 power. (A125)
Data Type
Index
Measurement
Holding Register

40126

Electric Power

Units
kiloWatts

Valid Range
0-65,535

Compressor Run Hours


Note: Value returned must be multiplied by 10 to give run hours.
This output data point indicates the number of run hours for the compressor motor of the compressor selected with
Compressor Select on page 18. (I46)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40175

Time

hours/10

0 -65,535

Compressor #2

This output data point indicates the current compressor 2 run hours. (I107)
Data Type
Index
Measurement
Holding Register

40236

Time

Units

hours/10

Valid Range
0 -65,535

Compressor #3

This output data point indicates the current compressor 3 run hours. (I110)
Data Type
Index
Measurement
Holding Register

18

40239

Time

hours/10

Units

Valid Range
0 -65,535

ED 15063-5

Compressor #4

This output data point indicates the current compressor 4 run hours. (I113)
Data Type
Index
Measurement
Holding Register

40242

Time

Units

hours/10

Valid Range
0 -65,535

Compressor Select
This input data point selects the compressor (number 1, 2, 3 or 4) that is interrogated. The controller returns the
information for the selected compressor. You must first select a compressor, then interrogate the selected compressor.
This data point selects a compressor for the following variables. (I32)
Name

Page

Compressor Current

13

Compressor Discharge Temperature

16

Compressor Percent RLA

17

Compressor Power

14

Compressor Run Hours

18

Compressor Starts

19

Compressor Suction Line Temperature

20

Compressor Voltage

15

Condenser Refrigerant Pressure

21

Condenser Saturated Refrigerant Temperature

21

Evaporator Leaving Water Temperature for Compressor

23

Evaporator Refrigerant Pressure

23

Evaporator Saturated Refrigerant Temperature

23

Oil Feed Pressure

26

Oil Feed Temperature

26

Oil Sump Pressure

26

Oil Sump Temperature

26

Data Type
Holding Register

Index
40161

Measurement
Event Count

Units
NA

Valid Range
0 -65,535

Compressor Starts
This output data point indicates the number of starts for the compressor motor of the compressor selected with
Compressor Select on page 19. (I45)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40174

Count

Starts

0 -65,535

Compressor #2

This output data point indicates the current compressor 2 starts. (I106)
Data Type
Index
Measurement
Holding Register

40235

Count

Units
Starts

Valid Range
0 -65,535

Compressor #3

This output data point indicates the current compressor 3 starts. (I109)
Data Type
Index
Measurement
Holding Register

40238

Count

Units
Starts

Valid Range
0 -65,535

Compressor #4

This output data point indicates the current compressor 4 starts. (I112)
Data Type
Index
Measurement
Holding Register

19

40241

Count

Units
Starts

Valid Range
0 -65,535

ED 15063-5

Compressor Suction Line Temperature


This output data point indicates the current suction line refrigerant temperature for the compressor selected with
Compressor Select on page 19. (A15)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40016

Temperature

F x 10

-40-244F

Compressor #2

This output data point indicates the current compressor 2 suction line temperature. (A88)
Data Type
Index
Measurement
Units
Holding Register

40089

Temperature

F x 10

Valid Range
-40-244F

Compressor Voltage
This output data point indicates the current compressor voltage of the compressor selected with Compressor Select on
page 20. (A29)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40030

Electric Voltage

Volts

0 -65,535

Compressor #2

This output data point indicates the current compressor 2 voltage. (A98)
Data Type
Index
Measurement
Holding Register

40099

Electric Voltage

Units
Volts

Valid Range
0 -65,535

Compressor #3

This output data point indicates the current compressor 3 voltage. (A112)
Data Type
Index
Measurement
Holding Register

40113

Electric Voltage

Units

Volts

Valid Range
0 -65,535

Compressor #4

This output data point indicates the current compressor 4 voltage. (A117)
Data Type
Index
Measurement
Holding Register

40118

Electric Voltage

Units

Volts

Valid Range
0 -65,535

Compressor #5

This output data point indicates the current compressor 5 voltage. (A121)
Data Type
Index
Measurement
Holding Register

40123

Electric Voltage

Units

Volts

Valid Range
0 -65,535

Compressor #6

This output data point indicates the current compressor 6 voltage. (A127)
Data Type
Index
Measurement
Holding Register

20

40128

Electric Voltage

Volts

Units

Valid Range
0 -65,535

ED 15063-5

Condenser Entering Water Temperature


This output data point indicates the current temperature of the entering condenser water. (A7)
Data Type
Holding Register

Index
40008

Measurement
Temperature

Units
F x 10

Valid Range
-40-244F

Condenser Flow Switch Status


This output data point indicates the status of the water flow through the condenser. (D8)
Data Type
Coil

Index
9

Measurement
Flow State

Units

Valid Range
0 = No Flow
1 = Flow

NA

Condenser Leaving Water Temperature


This output data point indicates the current temperature of the leaving condenser water. (A8)
Data Type
Holding Register

Index
40009

Measurement
Temperature

Units
F x 10

Valid Range
-40-244F

Condenser Pump Run Hours


Pump Select

This output data point indicates the number of run hours that the selected condenser pump motor. See Pump Select on
page 21. (I48)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40177

Time

hours

0 -65,535

Pump #2

This output data point indicates the number of run hours that for condenser pump #2. (I104)
Data Type
Index
Measurement
Units
Holding Register

40233

Time

hours

Valid Range
0 -32768

Condenser Refrigerant Pressure


This output data point indicates the current refrigerant pressure in the selected condenser. There is a separate output for
each compressor. See Compressor Select on page 21. (A21)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40022

Pressure (gauge)

psi x 10

-22592 - 22591 psi

Compressor #2

This output data point indicates the current compressor 2 refrigerant pressure. (A93)
Data Type
Index
Measurement
Units
Holding Register

40094

Pressure (gauge)

psi x 10

Valid Range
-22592 - 22591 psi

Condenser Saturated Refrigerant Temperature


This output data point indicates the current saturated refrigerant temperature in the condenser. There is a separate output
for each compressor. See Compressor Select on page 21. (A20)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40021

Temperature

F x 10

-40- 244F

Compressor #2

This output data point indicates the current compressor 2 saturated refrigerant temperature. (A92)
Data Type
Index
Measurement
Units

21

Valid Range

ED 15063-5

Holding Register

40093

Temperature

F x 10

-40- 244F

Condenser Water Flow Rate


This output data point indicates the rate of water flow through the condenser. (A24) Note: Requires field provided flow
measurement device.
Data Type
Holding Register

Index
40025

Measurement

Units

Water Flow Rate

Valid Range

gallons per minute

0 -65,535

Condenser Water Pump Status


This output data point indicates whether the selected pump has been commanded On or Off. See Pump Select on page
22. (D31)
Data Type
Coil

Index
32

Measurement

Units

Flow State

Valid Range
0 = Pump Off Request
1 = Pump On Request

NA

Cool Setpoint
This input data point sets the temperature of the Leaving Chilled Water when the chiller is operating in the Cooling
Mode. The Cooling mode is the normal mode of chiller operation, unless overridden by using the Chiller Mode Setpoint
to change to another mode. (A1)
Note: See the appropriate Operation Manual for specific data range and default value.
Data Type
Index
Measurement
Units
Holding Register

40002

Temperature

F x 10

Valid Range
10 - 120F

Design RPM
This output network variable indicates the Turbocor calculated speed target based on conditions and request demand.
(I125 & I126)
Compressor #1

Data Type
Holding Register

Index
40254

Measurement

Units

Revolutions Per Minute

RPM

Valid Range
0-32768

Compressor #2

Data Type
Holding Register

Index
40255

Measurement

Units

Revolutions Per Minute

RPM

Valid Range
0-32768

Evaporator Entering Water Temperature


This output data point indicates the temperature of the evaporator entering water temperature. (A4)
Data Type
Holding Register

Index
40005

Measurement

Units

Temperature

F x 10

Valid Range
-40 - 245F

Evaporator Flow Switch Status


This output data point indicates the status of water flow through the evaporator. (D7)
Data Type
Coil

Index
8

Measurement
Flow State

Units
NA

Valid Range
0 = No Flow
1 = Flow

Evaporator Leaving Water Temperature for Unit


This output data point indicates the current temperature of the evaporator leaving chilled water. (A6)
22

ED 15063-5

Data Type
Holding Register

Index
40007

Measurement
Temperature

Units
F x 10

Valid Range
-40 - 244F

Evaporator Leaving Water Temperature for Compressor


Compressor Select

This output data point indicates the current temperature of the evaporator leaving chilled water temperature of the
compressor selected with Compressor Select on page 18. (A14)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40015

Temperature

F x 10

-40-244F

Compressor #2

This output data point indicates the current temperature of the evaporator leaving chilled water temperature for
compressor 2. (A87)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40088

Temperature

F x 10

-40-244F

Evaporator Pump Run Hours


Pump Select

This output data point indicates the number of run hours for the selected evaporator pump. There is a separate output for
each pump. See Pump Select on page 27. (I47)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40176

Event Count

Hours

0 - 65,535

Pump #2

This output data point indicates the number of run hours for evaporator pump #2. (I103)
Data Type
Index
Measurement
Units
Holding Register

40232

Event Count

Hours

Valid Range
0 - 65,535

Evaporator Refrigerant Pressure


Compressor Select

This output data point indicates the current refrigerant pressure in the evaporator. There is a separate output for each
compressor. See Compressor Select on page 18. (A17)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40018

Pressure (gauge)

psi x 10

-22592 - 22591 psi

Compressor #2

This output data point indicates the current refrigerant pressure in the evaporator for compressor 2. (A90)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40091

Pressure (gauge)

psi x 10

-22592 - 22591 psi

Evaporator Saturated Refrigerant Temperature


Compressor Select

This output data point indicates the current saturated refrigerant temperature in the evaporator. There is a separate output
for each compressor. See Compressor Select on page 18. (A16)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

23

40017

Temperature

F x 10

-40 - 244F

ED 15063-5

Compressor #2

This output data point indicates the current saturated refrigerant temperature in the evaporator for compressor 2. (A89)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40090

Temperature

F x 10

-40 - 244F

Evaporator Water Flow Rate


This output data point indicates the rate of water flow through the evaporator. (A18) Note: Requires field provided
flow measurement device.
Data Type
Holding Register

Index
40019

Measurement
Water Flow Rate

Units

Valid Range

gallons per minute

0 - 65,535

Evaporator Water Pump Status


This output data point indicates whether the selected pump has been commanded On or Off. See Pump Select on page
27. (D29)
Data Type
Coil

Index
30

Measurement
Flow State

Units

Valid Range
0 = Pump Off Request
1 = Pump On Request

NA

Heat Recovery Entering Water Temperature


This output network variable indicates the current temperature of the water entering the heat recovery section. (A22)
Data Type
Holding Register

Index
40023

Measurement
Temperature

Units
F x 10

Valid Range
-40 - 244F

Heat Recovery Leaving Water Temperature


This output data point indicates the current temperature of the water leaving the heat recovery section. (A23)
Data Type
Holding Register

Index
40024

Measurement
Temperature

Units
F x 10

Valid Range
-40-244F

Heat Setpoint
This input data point provides the heating setpoint when the chiller is operating in the heat mode. The value is ignored if
the controller is in cooling mode. (A5)
Note: See the appropriate Operation Manual for specific data range and default value.
Data Type
Index
Measurement
Units
Holding Register

40006

Temperature

F x 10

Valid Range
50-120F

Ice Setpoint
This input data point sets the temperature of the Leaving Chilled Water when the chiller is operating in the ice mode.
(A50)
Note: See the appropriate Operation Manual for specific data range and default value.
Data Type
Index
Measurement
Units
Holding Register

40051

Temperature

F x 10

Valid Range
15 - 35F

IGV Percentage Open


This output network variable indicates current percent of vanes open for each compressor (0%=closed, 110%=full
capacity-open) (I120 & I124)

24

ED 15063-5

Compressor #1

Data Type
Holding Register

Index
40249

Measurement
Percent

Units
%

Valid Range
0-110%

Compressor #2

Data Type
Holding Register

Index
40253

Measurement
Percent

Units
%

Valid Range
0-110%

Inverter Temperature
This output network variable the current drive temperature. There is one variable for each compressor. (A86 & A106)
Compressor #1

Data Type
Holding Register

Index
40087

Measurement
Temperature

Units

Valid Range

Units

Valid Range

Fx10

Compressor #2

Data Type
Holding Register

Index
40107

Measurement
Temperature

Fx10

Liquid Line Refrigerant Pressure


This output data point indicates the current liquid line refrigerant pressure. (A38)
Data Type
Holding Register

Index
40039

Measurement
Pressure

Units
psi x 10

Valid Range
22592 - 22591 psi

Liquid Line Refrigerant Temperature


This output data point indicates the current liquid line refrigerant temperature. (A36)
Compressor Select

Data Type
Holding Register

Index
40037

Measurement
Temperature

Units
F x 10

Valid Range
-40 - 244F

Compressor #2

Data Type
Holding Register

Index
40105

Measurement
Temperature

Units
F x 10

Valid Range
-40 - 244F

Maximum RPM
This output data point indicates the maximum (choke) RPM. This is the speed the Turbocor compressor calculates
above which the efficiency of the compressor falls off. (I117 & I121)
Compressor #1

Data Type
Holding Register

Index
40246

Measurement
Revolutions Per Minute

Units
RPM

Valid Range
0-32768

Compressor #2

Data Type
Holding Register

Index
40250

Measurement
Revolutions Per Minute

Units
RPM

Valid Range
0-32768

Minimum RPM
This output data point indicates the minimum (surge) RPM. This is the speed Turbocor compressor calculates is the
minimum safe operating speed above onset of stall. (I119 & I123)
Compressor #1

Data Type
25

Index

Measurement

Units

Valid Range
ED 15063-5

Holding Register

40248

Revolutions Per Minute

RPM

0-32768

Compressor #2

Data Type
Holding Register

Index
40252

Measurement
Revolutions Per Minute

Units
RPM

Valid Range
0-32768

Oil Feed Pressure


Compressor Select

This output data point indicates the current compressor oil feed pressure. There is a separate output for each compressor.
See Compressor Select on page 18. (A32)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40033

Pressure

psi

22592 - 22591 psi

Compressor #2

This output data point indicates the current compressor 2 oil feed pressure. (A100)
Data Type
Index
Measurement
Units
Holding Register

40101

Pressure

psi

Valid Range
22592 - 22591 psi

Oil Feed Temperature


Compressor Select

This output data point indicates the current compressor oil feed temperature. There is a separate output for each
compressor. See Compressor Select on page 18. (A34)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40035

Temperature

F x 10

-40 - 244F

Compressor #2

This output data point indicates the current compressor 2 oil feed temperature. (A102)
Data Type
Index
Measurement
Units
Holding Register

40103

Temperature

F x 10

Valid Range
-40 - 244F

Oil Sump Pressure


Compressor Select

This output data point indicates the current compressor oil sump pressure. There is a separate output for each
compressor. See Compressor Select on page 18. (A33)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

40034

Pressure

psi x 10

-22592 - 22591 psi.

Compressor #2

This output data point indicates the current compressor 2 oil sump pressure. (A101)
Data Type
Index
Measurement
Units
Holding Register

40102

Pressure

psi x 10

Valid Range
-22592 - 22591 psi.

Oil Sump Temperature


Compressor Select

This output data point indicates the current compressor oil sump temperature. There is a separate output for each
compressor. See Compressor Select on page 18. (A35)
Data Type
Index
Measurement
Units
Valid Range
Holding Register

26

40036

Temperature

F x 10

-40 - 244F

ED 15063-5

Compressor #2

This output data point indicates the current compressor 2 oil sump temperature. (A103)
Data Type
Index
Measurement
Units
Holding Register

40104

Temperature

F x 10

Valid Range
-40 - 244F

Outdoor Air Temperature


This output data point indicates the current outdoor air temperature. (A39)
Data Type
Holding Register

Index
40040

Measurement
Temperature

Units
F x 10

Valid Range
-40 -2 44F

Pump Select
This input data point selects which pump (Number 1 or Number 2) supplies the data. The controller returns the
information for the appropriate Condenser or Evaporator pump. You must first select a pump then interrogate the
selected pump. See Condenser Pump Run Hours on page 21 and Evaporator Pump Run Hours on page 23. (D19)
Data Type
Coil

Index
20

Measurement
Event Count

Units

Valid Range
0 = Pump #1
1 = Pump #2

NA

Run Enabled
The Run Enabled output data point indicates that the chiller can start if operating conditions are met. (D2)
Data Type
Coil

27

Index
3

Measurement
Chiller State

Units
NA

Valid Range
0 = Off
1 = Run Allowed

ED 15063-5

Alarms
Alarm Classes
Modbus alarms in a MicroTech II unit controller are divided into three classes: Faults, Problems, and Warnings. Fault
alarms have the highest severity level. Problem alarms have medium severity level. Warning alarms have the lowest
severity level.

Fault Alarms
Fault alarms require an acknowledgment from the operator. These alarms indicate that the compressor is shut down.

Problem Alarms
Problem alarms do not cause compressor shutdown but limit operation of the chiller in some way.

Warning Alarms
A warning is enunciated whenever an abnormal condition exists which does not affect chiller operation.

Alarm Handling
One Modbus network variable indicates an alarm condition and one network variable clears alarms. To determine the
particular alarm condition, you must read the status of the 16 Active Alarms Holding Registers.

Alarm Digital Output


This network data point indicates whether an alarm condition has occurred. This variable must be polled for alarm
notification. (D3)
Data Type
Coil

Index
4

Measurement
NA

Units

Valid Range
0 = No Alarm
1 = Alarm

NA

Clear Alarms
This input data point clears all active alarms. It cannot clear all alarms in the Fault category (alarms that shut down the
chiller). They would have to be cleared at the chiller panel. The alarms that cannot be cleared over the network (but can
be cleared at the chiller) are: (D24)
Low Evaporator Pressure
High Condenser Pressure (by pressure sensor)
High Condenser Pressure (by pressure switch)
Low Oil Pressure
Freeze Protection
High Motor Temperature

Note: The above list is for centrifugal chillers. The flow loss alarm is the only alarm that can be remotely
cleared on all other types of chillers.
Data Type
Coil

28

Index
25

Measurement
NA

Units
NA

Valid Range
0 = Normal
1 = Clear Alarm

ED 15063-5

Active Alarms
The Active Alarms Holding Registers contain a single bit for each alarm condition. You must read the status of these
registers to determine the particular alarm condition indicated by the Alarm Digital Output. Table 3 defines the bit
location for each alarm condition. (I1-I16)
Data Type
Holding Registers

Index
40130-40145

Measurement

Units

Alarm Condition

Valid Range
0 = No Alarm
1 = Alarm

NA

Table 3: Modbus Alarms

Description

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47

29

Warnings
Entering Condenser Water Temperature Sensor Fault
Entering Evaporator Water Temperature Sensor Fault
Liquid Line Refrigerant Temperature Sensor Fault
Leaving Condenser Water Temperature Sensor Fault
Repower After Power Loss 1
Repower After Power Loss 2
Repower After Power Loss 3
Repower After Power Loss 4
(Expansion Alarm Warning)
Problems
Low Ambient Temperature Lockout
High Condenser Pressure Inhibit Loading Circuit 1
High Condenser Pressure Inhibit Loading Circuit 2
High Condenser Pressure Inhibit Loading Circuit 3
High Condenser Pressure Inhibit Loading Circuit 4
High Condenser Pressure Unload
High Condenser Pressure Unload Circuit 1
High Condenser Pressure Unload Circuit 2
High Condenser Pressure Unload Circuit 3
High Condenser Pressure Unload Circuit 4
Condenser Water Freeze Protect Comp 1
Condenser Water Freeze Protect Comp 2
Condenser Water Freeze Protect Comp 3
Condenser Water Freeze Protect Comp 4
Condenser Pump #1 Fault
Condenser Pump #2 Fault
High Discharge Temperature Comp 1
High Discharge Temperature Comp 2
High Discharge Temperature Comp 3
High Discharge Temperature Comp 4
Entering Evap Temperature Sensor Fault (EWT reset
active)
Low Evaporator Pressure - Inhibit Loading
Low Evaporator Pressure - Inhibit Loading Circuit 1
Low Evaporator Pressure - Inhibit Loading Circuit 2
Low Evaporator Pressure - Inhibit Loading Circuit 3
Low Evaporator Pressure - Inhibit Loading Circuit 4
Low Evaporator Pressure Unload
Low Evaporator Pressure Unload Circuit 1
Low Evaporator Pressure Unload Circuit 2
Low Evaporator Pressure Unload Circuit 3
Low Evaporator Pressure Unload Circuit 4
High Motor Current On Compressor #1
High Motor Current On Compressor #2
High Motor Current On Compressor #3
High Motor Current On Compressor #4
Evaporator Freeze Protect Comp 1
Evaporator Freeze Protect Comp 2
Evaporator Freeze Protect Comp 3

WSC
WDC
WPV
WMC
WCC
HSC
HDC
TSC

AGZ

ACZ

X
X
X
X

WGZ/
TGZ

X
X
X

AGS

WGS

X
X
2
X

X
5
X
5
X

X
3
X
3
X

X
3
X
3
X

X
5
X
5
X

X
X
X

X
X
X

X
X
X
2
X

X
X
X

X
X

X
X
2
X

X
X

X
X

X
X

X
X
X
X

X
6

X
X

X
5
X
5
X

X
3
X
3
X

X
X

X
5
X
5
X

X
3
X
3
X

X
X

X
X

X
X

X
X
2
X

X
X

X
X

X
X
2
X

X
X

Holding
Register

Bit

40130
40130
40130
40130
40130
40130
40130
40130
40130

1
2
3
4
5
6
7
8
9

40130
40130
40130
40130
40130
40130
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131

10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13

40131

14

40131
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132

15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

ED 15063-5

48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115

30

Evaporator Freeze Protect Comp 4


Evaporator Pump #1 Fault
Evaporator Pump #2 Fault
(Expansion Alarm Problem)
Faults
Outside Ambient Temperature Sensor Fault
Compressor Current Overload Trip #1
Compressor Current Overload Trip #2
Compressor Current Overload Trip #3
Compressor Current Overload Trip #4
Motor Current Imbalance On Compressor #1
Motor Current Imbalance On Compressor #2
Motor Current Imbalance On Compressor #3
Motor Current Imbalance On Compressor #4
Low Motor Current Comp 1
Low Motor Current Comp 2
Low Motor Current Comp 3
Low Motor Current Comp 4
Motor Protection
Motor Protection Circuit 1
Motor Protection Circuit 2
High Motor Temperature Comp 1
High Motor Temperature Comp 2
High Motor Temperature Comp 3
High Motor Temperature Comp 4
Phase Loss At Compressor 1
Phase Loss At Compressor 2
Phase Loss At Compressor 3
Phase Loss At Compressor 4
Phase Reversal At Compressor 1
Phase Reversal At Compressor 2
Phase Reversal At Compressor 3
Phase Reversal At Compressor 4
Overvoltage On Compressor 1
Overvoltage On Compressor 2
Overvoltage On Compressor 3
Overvoltage On Compressor 4
Undervoltage On Compressor 1
Undervoltage On Compressor 2
Undervoltage On Compressor 3
Undervoltage On Compressor 4
Condenser Pressure Sensor Fault
Condenser Pressure Sensor Fault Circuit 1
Condenser Pressure Sensor Fault Circuit 2
Condenser Pressure Sensor Fault Circuit 3
Condenser Pressure Sensor Fault Circuit 4
No Condenser Water Flow
High Condenser Pressure
High Condenser Pressure Circuit 1
High Condenser Pressure Circuit 2
High Condenser Pressure Circuit 3
High Condenser Pressure Circuit 4
No Compressor Stop Comp 1
No Compressor Stop Comp 2
No Compressor Stop Comp 3
No Compressor Stop Comp 4
Discharge Temperature Sensor Fault Circuit 1
Discharge Temperature Sensor Fault Circuit 2
Discharge Temperature Sensor Fault Circuit 3
Discharge Temperature Sensor Fault Circuit 4
High Discharge Temperature Circuit 1
High Discharge Temperature Circuit 2
High Discharge Temperature Circuit 3
High Discharge Temperature Circuit 4
Entering Condenser Water Temperature Sensor Fault
No Evaporator Water Flow
Evaporator Water Freeze Protect
Low Evaporator Pressure
Low Evaporator Pressure Circuit 1

X
X

X
X

X
1
X
1
X

X
X
X

X
X

X
1
X

X
X

X
X

X
1
X

X
X

X
X

X
5
X
5
X

X
3
X
3
X

X
X

X
X

X
7
X

X
1
X

X
5
X

X
X

X
3
X

X
7
X

X
X

X
7
X

X
X

X
X

X
7
X

X
X

X
5
X
5
X

X
3
X
3
X

X
3
X
3
X

X
X
X

X
X

X
X
2
X

X
X
5
X
5
X

X
X

X
X

X
X
2
X

X
X

X
X
2
X

X
X

X
X

X
X

X
X

X
X

X
X
6
X
5
X

X
X
X

X
X

X
X
X

X
3
X

40133
40133
40133
40133

0
1
2
3

40133
40133
40133
40133
40133
40133
40133
40133
40133
40133
40133
40133
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40137
40137
40137
40137

4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3

ED 15063-5

116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176

31

Low Evaporator Pressure Circuit 2


Low Evaporator Pressure Circuit 3
Low Evaporator Pressure Circuit 4
Evaporator Pressure Sensor Fault
Evaporator Pressure Sensor Fault Circuit 1
Evaporator Pressure Sensor Fault Circuit 2
Evaporator Pressure Sensor Fault Circuit 3
Evaporator Pressure Sensor Fault Circuit 4
Ground Fault Protection 1
Ground Fault Protection 2
Ground Fault Protection 3
Ground Fault Protection 4
Below Minimum Lift Pressure Circuit 1
Below Minimum Lift Pressure Circuit 2
Below Minimum Lift Pressure Circuit 3
Below Minimum Lift Pressure Circuit 4
Liquid Line Pressure Sensor Fault Circuit 1
Liquid Line Pressure Sensor Fault Circuit 2
Liquid Line Pressure Sensor Fault Circuit 3
Liquid Line Pressure Sensor Fault Circuit 4
Liquid Line Refrigerant Temperature Sensor Fault
Circuit 1
Liquid Line Refrigerant Temperature Sensor Fault
Circuit 2
Liquid Line Refrigerant Temperature Sensor Fault
Circuit 3
Liquid Line Refrigerant Temperature Sensor Fault
Circuit 4
Re-Start Fault
Re-Start Fault Circuit 1
Re-Start Fault Circuit 2
Re-Start Fault Circuit 3
Re-Start Fault Circuit 4
Leaving Evaporator Water Temperature Sensor Fault
Leaving Evaporator Water Temperature Sensor Fault
Comp 1
Leaving Evaporator Water Temperature Sensor Fault
Comp 2

Leaving Evaporator Water Temperature Sensor


Fault Comp 3
Leaving Evaporator Water Temperature Sensor
Fault Comp 4
Mechanical High Pressure
Mechanical High Pressure Circuit 1
Mechanical High Pressure Circuit 2
Mechanical High Pressure Circuit 3
Mechanical High Pressure Circuit 4
Low Oil Net Pressure Comp 1
Low Oil Net Pressure Comp 2
Low Oil Net Pressure Comp 3
Low Oil Net Pressure Comp 4
High Oil Feed Temperature Comp 1
High Oil Feed Temperature Comp 2
High Oil Feed Temperature Comp 3
High Oil Feed Temperature Comp 4
Low Oil Feed Temperature Comp 1
Low Oil Feed Temperature Comp 2
Low Oil Feed Temperature Comp 3
Low Oil Feed Temperature Comp 4
Oil Feed Temperature Sensor Fault Comp 1
Oil Feed Temperature Sensor Fault Comp 2
Oil Feed Temperature Sensor Fault Comp 3
Oil Feed Temperature Sensor Fault Comp 4
Low Oil Level Circuit 1
Low Oil Level Circuit 2
Low Oil Level Circuit 3
Low Oil Level Circuit 4
High Oil Pressure Difference Circuit 1
High Oil Pressure Difference Circuit 2

X
3
X
3
X

X
X

X
5
X
5
X

X
7
X

X
2
X

40137
40137
40137
40137
40137
40137
40137
40137
40137
40137
40137
40137
40138
40138
40138
40138
40138
40138
40138
40138

4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7

X
X

X
X
2
X

X
X

X
X

X
1
X

X
X

X
X
2
X

X
X

40138

40138

40138

10

X
6
X

X
X
2
X

40138

11

40138
40138
40138
40138
40139

12
13
14
15
0
1

40139

40139

40139

40139

40139
40139
40139
40139
40139
40139
40139
40139
40139
40139
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40141

6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0

X
5
X
5
X

X
3
X
3
X

X
X

X
5
X
5
X

X
X

X
1
X

X
X

X
3
X
3
X

X
X

X
X
2
X

X
X

X
X
2
X

X
X

X
X

X
X

X
X

X
X

X
X

X
X

ED 15063-5

177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240

32

High Oil Pressure Difference Circuit 3


High Oil Pressure Difference Circuit 4
Oil Feed Pressure Sensor Fault Comp 1
Oil Feed Pressure Sensor Fault Comp 2
Oil Feed Pressure Sensor Fault Comp 3
Oil Feed Pressure Sensor Fault Comp 4
Oil Sump Pressure Sensor Fault Comp 1
Oil Sump Pressure Sensor Fault Comp 2
Oil Sump Pressure Sensor Fault Comp 3
Oil Sump Pressure Sensor Fault Comp 4
Oil Sump Temperature Sensor Fault Comp 1
Oil Sump Temperature Sensor Fault Comp 2
Oil Sump Temperature Sensor Fault Comp 3
Oil Sump Temperature Sensor Fault Comp 4
Phase Voltage Protection
Starter Fault Compressor 1
Starter Fault Compressor 2
Starter Fault Compressor 3
Starter Fault Compressor 4
No Starter Transition Comp 1
No Starter Transition Comp 2
No Starter Transition Comp 3
No Starter Transition Comp 4
No Oil Pressure Start Comp 1
No Oil Pressure Start Comp 2
No Oil Pressure Start Comp 3
No Oil Pressure Start Comp 4
Low Subcooling Circuit 1
Low Subcooling Circuit 2
Low Subcooling Circuit 3
Low Subcooling Circuit 4
Surge High Suct SH-Running Comp 1
Surge High Suct SH-Running Comp 2
Surge High Suct SH-Running Comp 3
Surge High Suct SH-Running Comp 4
Surge High Suct SH-Starting Comp 1
Surge High Suct SH-Starting Comp 2
Surge High Suct SH-Starting Comp 3
Surge High Suct SH-Starting Comp 4
Suction Temperature Sensor Fault Circuit 1
Suction Temperature Sensor Fault Circuit 2
Suction Temperature Sensor Fault Circuit 3
Suction Temperature Sensor Fault Circuit 4
Vanes Open No Start Comp 1
Vanes Open No Start Comp 2
Vanes Open No Start Comp 3
Vanes Open No Start Comp 4
(Expansion Alarm- Fault)
COMP SHUTDOWN Comp Fault #1
COMP SHUTDOWN Comp Fault #2
COMP SHUTDOWN Comp Fault #3
COMP SHUTDOWN Comp Fault #4
C-Stop - General Comp Fault#1
C-Stop - General Comp Fault#2
C-Stop - Communication Fault #1
C-Stop - Communication Fault #2
C-Stop - Interlock Fault #1
C-Stop - Interlock Fault #2
C-Stop - Bearing Fault #1
C-Stop - Bearing Fault #2
C-Stop - Motor Fault #1
C-Stop - Motor Fault #2
C-Stop - Drive Fault #1
C-Stop - Drive Fault #2
C-Stop - Internal Control Err#1
C-Stop - Internal Control Err#2
Warn-Chiller Capacity Limited
U-Stop - Check Valve Fault #1

X
X
X

X
X

X
X

X
X

X
X
2
X

X
X

X
1
X

X
X

X
X

X
2
X
2
X

X
X

X
X
2
X

X
X

X
X

X
X

X
X

X
8
X

40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40144
40144
40144
40144
40144

X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8

ED 15063-5

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4

241 U-Stop - Check Valve Fault #2


242 U-Stop - LB Valve Fault #1
243 U-Stop - LB Valve Fault #2

X8
X8
X8

-AGS C Vintage Only


-AGS B Vintage Only
3
-ACZ Dual Circuit Only
4
-ACZ Single Circuit Only
5
-AGZ Dual Circuit Only
6
-AGZ Single Circuit Only
7
-Solid State Starter Option required. Not available on WMC.
8
-Should be No Start - Interlock Switch on WMC chillers.
2

33

ED 15063-5

Index of Detailed Point Information


A

Active Alarms ................................................... 9, 12, 29


Active Setpoint ..................................................... 10, 14
Actual Capacity ................................................ 9, 10, 14
Actual RPM .......................................................... 10, 14
Alarm Digital Output ........................................ 9, 12, 28

Evaporator Entering Water Temperature ..............11, 22


Evaporator Flow Switch Status .............................11, 22
Evaporator Leaving Water Temperature for
Compressor .......................................................11, 23
Evaporator Leaving Water Temperature for Unit .11, 22
Evaporator Pump Run Hours ................................11, 23
Evaporator Refrigerant Pressure ...........................12, 23
Evaporator Saturated Refrigerant Temperature.....12, 23
Evaporator Water Flow Rate .................................12, 24
Evaporator Water Pump Status .............................12, 24

C
Capacity Limit Output .......................................... 10, 14
Capacity Limit Setpoint .................................... 9, 10, 14
Cavity Temperature .............................................. 10, 15
Chiller Enable ................................................... 9, 10, 15
Chiller Limited ..................................................... 10, 15
Chiller Local/Remote ........................................... 10, 15
Chiller Mode Output............................................. 10, 15
Chiller Mode Setpoint ...................................... 9, 10, 16
Chiller Power ........................................................ 10, 16
Chiller Status .................................................... 9, 10, 16
Clear Alarms ..................................................... 9, 12, 28
Compressor 2 Active Capacity Limit ......................... 16
Compressor 2 Active Capacity Limit ......................... 10
Compressor Current.............................................. 10, 16
Compressor Discharge Temperature .............. 10, 15, 17
Compressor Percent RLA ..................................... 10, 17
Compressor Power................................................ 10, 18
Compressor Run Hours ........................................ 10, 18
Compressor Select ................................................ 11, 19
Compressor Starts ................................................. 11, 19
Compressor Suction Line Temperature ................ 11, 19
Compressor Voltage ............................................. 11, 20
Condenser Entering Water Temperature .............. 11, 21
Condenser Flow Switch Status ............................. 11, 21
Condenser Leaving Water Temperature ............... 11, 21
Condenser Pump Run Hours ................................ 11, 21
Condenser Refrigerant Pressure ........................... 11, 21
Condenser Saturated Refrigerant Temperature ..... 11, 21
Condenser Water Flow Rate ................................. 11, 22
Condenser Water Pump Status ............................. 11, 22
Cool Setpoint .................................................... 9, 11, 22

H
Heat Recovery Entering Water Temperature ........12, 24
Heat Recovery Leaving Water Temperature .........12, 24
Heat Setpoint .........................................................12, 24
I
Ice Setpoint ...........................................................12, 24
IGV Percentage Open ...........................................11, 24
Inverter Temperature .............................................11, 25
L
Liquid Line Refrigerant Pressure ..........................12, 25
Liquid Line Refrigerant Temperature ...................12, 25
M
Maximum RPM.....................................................11, 25
Minimum RPM .....................................................11, 25
O
Oil Feed Pressure ..................................................12, 26
Oil Feed Temperature ...........................................12, 26
Oil Sump Pressure .................................................12, 26
Oil Sump Temperature ..........................................12, 26
Outdoor Air Temperature ......................................12, 27
P
Pump Select...........................................................12, 27

Design RPM ......................................................... 11, 22

Run Enabled ..........................................................12, 27

34

ED 15063-5

This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinMcQuay.com.

Daikin McQuay
(800) 432-1342, www.DaikinMcQuay.com

35

ED 15063-5