ED15063-5
Group: Controls
Part Number: ED 15063
Date: June 2013
Supersedes: ED15063-4
MicroTech II
Chiller Unit Controller
Protocol Information
Modbus Protocol
WSC
WDC
WPV
HSC
HDC
TSC
WMC
WCC
AGZ
ACZ
WGZ
AGS
WGS
TGZ
Table of Contents
TABLE OF CONTENTS........................................................................................................................................................ 2
LIMITED WARRANTY .............................................................................................................................................................. 4
NOTICE .................................................................................................................................................................................. 4
REVISION HISTORY ............................................................................................................................................................... 4
SOFTWARE REVISION ........................................................................................................................................................... 4
REFERENCE DOCUMENTS .................................................................................................................................................... 4
INTRODUCTION .................................................................................................................................................................... 6
CHILLER MODELS ................................................................................................................................................................. 6
CONTROLLER DATA POINTS ................................................................................................................................................. 6
MODBUS PROTOCOL INFORMATION ............................................................................................................................ 7
COMPATIBILITY ...................................................................................................................................................................... 7
PROTOCOL DEFINITIONS ...................................................................................................................................................... 7
VALID FUNCTION CODES ...................................................................................................................................................... 7
VALID ERROR CODES ........................................................................................................................................................... 8
MODBUS DATA POINT ........................................................................................................................................................... 8
EXAMPLE DATA POINT: CHILLER ENABLE ............................................................................................................................ 8
CONFIGURING THE UNIT CONTROLLER ................................................................................................................................ 8
SET UP THE UNIT FOR NETWORK CONTROL ........................................................................................................................ 8
TYPICAL APPLICATION: MINIMUM INTEGRATION ..................................................................................................... 9
DISPLAY IMPORTANT DATA POINTS ..................................................................................................................................... 9
COMPREHENSIVE DATA POINT TABLES ................................................................................................................... 10
MODBUS DATA POINTS ....................................................................................................................................................... 10
DETAILED DATA POINT INFORMATION ...................................................................................................................... 13
ACTIVE SETPOINT ............................................................................................................................................................... 14
ACTUAL CAPACITY .............................................................................................................................................................. 14
ACTUAL RPM ...................................................................................................................................................................... 14
CAPACITY LIMIT OUTPUT .................................................................................................................................................... 14
CAPACITY LIMIT SETPOINT ................................................................................................................................................. 14
CAVITY TEMPERATURE ....................................................................................................................................................... 15
COMPRESSOR DISCHARGE TEMPERATURE ....................................................................................................................... 15
CHILLER ENABLE ................................................................................................................................................................ 15
CHILLER LIMITED................................................................................................................................................................. 15
CHILLER LOCAL/REMOTE ................................................................................................................................................... 15
CHILLER MODE OUTPUT ..................................................................................................................................................... 15
CHILLER MODE SETPOINT .................................................................................................................................................. 16
COMPRESSOR 2 ACTIVE CAPACITY LIMIT ............................................................................................................................ 16
CHILLER STATUS ................................................................................................................................................................ 16
CHILLER POWER .................................................................................................................................................................. 16
COMPRESSOR CURRENT .................................................................................................................................................... 16
COMPRESSOR DISCHARGE TEMPERATURE ....................................................................................................................... 17
COMPRESSOR PERCENT RLA ............................................................................................................................................ 17
COMPRESSOR POWER ....................................................................................................................................................... 18
COMPRESSOR RUN HOURS ................................................................................................................................................ 18
COMPRESSOR SELECT .......................................................................................................................................................... 19
COMPRESSOR STARTS ....................................................................................................................................................... 19
COMPRESSOR SUCTION LINE TEMPERATURE ................................................................................................................... 20
COMPRESSOR VOLTAGE .................................................................................................................................................... 20
CONDENSER ENTERING WATER TEMPERATURE ............................................................................................................... 21
CONDENSER FLOW SWITCH STATUS ................................................................................................................................. 21
2
ED 15063-5
ED 15063-5
Limited Warranty
Consult your local Daikin McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local
Daikin McQuay Representative, go to www.daikinmcquay.com.
Notice
2013 Daikin McQuay, Minneapolis MN. All rights reserved throughout the world.
Daikin McQuay reserves the right to change any information contained herein without prior notice. The user is
responsible for determining whether this product is appropriate for his or her application.
The following are trademarks or registered trademarks of their respective companies. Modbus is a registered
trademark of Gould, Inc. Windows is a registered trademark of Microsoft Corporation. MicroTech II is a registered
trademark of Daikin McQuay.
Revision History
ED 15063-0
ED 15063-1
ED 15063-2
ED 15063-3
ED 15063-5
Preliminary release.
Added points for Solid State Starter Current, Voltage, Power and Power Factor
Corrected some incorrect register listings
Changed doc to have only Holding Registers and Coils
Added WGS and WMC data
Added WMC, HSC HDC, and TSC to front page and Chiller Model table
Added WCC to front page and Chiller Model table
Corrected Modbus Alarms table
Added Compressor Current, Compressor Power and Compressor Voltage to the
Compressor Select Table
Added TGZmodel to all applicable tables. Removed reference to OITS panel and
added reference to unit keypad details in the Set up unit for network control
section. Added Index column to Comphrenesive Data Point table; corrected Chiller
Status holding register in table and also in detailed data section. Removed reference
to Chiller On/Off--use Run Enabled instead.
Added individual compressor data points.
Software Revision
This edition documents all versions of the standard MicroTech II Chiller Unit Controller firmware and all subsequent
revisions until otherwise indicated.
Reference Documents
Company
Number
Title
Source
McQuay International
www.mcquay.com
McQuay International
OM CentrifMicro II
McQuay International
IM 743
McQuay International
IMM AGS
IMM AGSB
McQuay International
IOMM ACZ/AGZ
McQuay International
IOMM ACZ
McQuay International
www.mcquay.com
www.mcquay.com
www.mcquay.com
www.mcquay.com
www.mcquay.com
IOMM AGZ
IOMM AGZ1
www.mcquay.com
McQuay International
IOMM WGZ
www.mcquay.com
McQuay International
IOMM WPV
www.mcquay.com
ED 15063-5
McQuay International
OM AGS
McQuay International
IOMM TSC
McQuay International
OMM TGZ
Modbus-IDA.ORG
Modbus-IDA.ORG
www.mcquay.com
www.mcquay.com
www.mcquay.com
www.Modbus.org
www.Modbus.org
ED 15063-5
Introduction
This document contains the necessary information to incorporate a MicroTech II Chiller Unit Controller from Daikin
McQuay into your Building Automation System (BAS). It includes all necessary Modbus variables and corresponding
MicroTech II Chiller Unit Controller data points. Modbus terms and principles are not defined. Refer to the appropriate
specifications for definitions and details.
Chiller Models
The following table lists the model designators of Daikin McQuay Chiller units and the corresponding description.
WSC Water-Cooled Centrifugal, Single-Compressor
WDC Water-Cooled Centrifugal, Dual-Compressor
WPV Water-Cooled Centrifugal, Single-Compressor
HSC
Water-Cooled Single-Compressor Centrifugal, Heat Recovery
HDC Water-Cooled Dual-Compressor Centrifugal, Heat Recovery
TSC
Water-Cooled Single-Compressor Centrifugal, Templifier
WMC Water-Cooled Centrifugal, Magnetic Bearing
WCC Water-Cooled Centrifugal, Counterflow
AGZ
Air-Cooled Global Scroll
ACZ
Air-Cooled Scroll Condensing Unit
WGZ Water-Cooled Global Scroll
AGS
Air-Cooled Global Screw
WGS Water-Cooled Global Screw
TGZ
Templifier Water Heater
ED 15063-5
Protocol Definitions
The Modbus protocol is a standardized Application Level (OSI Level 7) protocol used in interoperable Industrial Control
networks. Modbus provides the communication infrastructure necessary to integrate products manufactured by different
vendors and to integrate control services that are now independent.
It specifies how requests from the client are sent to a server and how servers reply. The client constructs a PDU (protocol
data unit) and sends it to a specific server or broadcasts it to all servers. The PDU contains a function code that defines
the action the client is requesting from the server(s). The PDU also includes a data field that further defines the action to
the server, for example, the location of the data to be read.
A normal reply from a server includes the same function code and a response data field. In the case of a read operation,
the response data field contains the requested data. In the case of a write operation, the response data field contains an
echo of the write data of the request command. If the server detects an error in the transmission, the reply to the client
includes and exception function code and the response data field contains an exception code.
Controllers can communicate on standard Modbus networks using one of two transmission modes: ASCII or RTU. Users
select the serial port communication parameters (baud rate, parity mode, etc), during configuration of the controller. The
mode and serial parameters must be the same for all devices on a Modbus network. Transmission mode determines how
information is packed into the message fields and decoded. In RTU mode, each byte contains two hexadecimal
characters, and in ASCII mode, each byte contains one ASCII character. The MicroTech II Chiller Unit Controller uses
the RTU mode only.
The MicroTech II Chiller Unit Controller uses the following data structure: 8 data bits, 1 or 2 stop bits, and no parity bit.
It uses data transmission rates from 1200 to 19200 bps.
Description
Definition
04 (0x04)
05 (0x05)
This function code reads status from 1 to 2000 contiguous coils in a remote
device.
This function code reads status from 1 to 2000 contiguous discrete inputs in a
remote device.
This function code reads the contents of a contiguous block of holding registers in
a remote device.
This function code reads from 1 to approx. 125 contiguous input registers in a
remote device.
This function code writes a single output to either ON or OFF in a remote device.
06 (0x06)
15 (0x0F)
16 (0x10)
01 (0x01)
Read Coils
02 (0x02)
03 (0x03)
This function code forces each coil in a sequence of coils to either ON or OFF in
a remote device.
This function code writes a block of contiguous registers (1 to approx. 120
registers) in a remote device.
ED 15063-5
Illegal Function
Illegal Data Address
Illegal Data Value
The function code received in the query is not an allowable action for the server (or slave).
The data address received in the query is not an allowable address for the server (or slave).
A value contained in the query data field is not an allowable value for server (or slave).
Index
Measurement
Units
Valid Range
Coil
Chiller State
NA
0 = Disable (Off)
1 = Enable (On)
Data Type
Data is represented as either single-bit elements or 16-bit elements. A single-bit element is referred to as a Discrete Input
when it refers to read-only data and as a Coil when it refers to read-write data. A 16-bit element is referred to as a Input
Register when it refers to read-only data and as an Holding Register when it refers to read-write data.
Index
There can be as many as 65,536 elements of each data type in a Modbus device. Data elements are numbered from 1 to
65,536 in each type. Data elements are addressed with an index in the range from 0 to 65,535. The index is not the
address of the data element in the unit controller memory. The index is used in Modbus PDUs to specify the location of
the data in the unit controller. This means, for example, that data element number 1 is addressed using index 0 in the
PDU.
Valid Range
Some properties are standard data types and some are enumerated sets. If the property value represents a range of values,
e.g., temperature or pressure, a range of values is given. If the property value is an enumerated set, all enumerated values
and corresponding meaning are given.
1.
2.
8
Disable the chiller. The chiller should not be operating while performing this setup.
At the chiller unit keypad:
ED 15063-5
a. In the Set Unit Setpoint screen 14, set the BAS Protocol to Modbus. Use the Manager Password of 2001.
b. In the Set Unit Setpoint screen 1, set the Control Source to Local.
Verify with the chiller/control company technician that the chiller is operational on BAS.
In the Set Unit Setpoint screen 1, set the Control Source to BAS.
3.
4.
1.
2.
3.
4.
Model
Menu Screen
Password
AGZ-A
ACZ-A
AGZ-B
ACZ-B
7
2001
6
2001
10
2001
7
2001
AGS-A,
B, DP
12
8945
AGS-C
AGS-D
WGS
WGZ/TGZ
16
8453
17
8745
15
8745
10
2001
NOTE: Models AGZ-A/B, ACZ-A/B, and WGZ have one unit controller, while models AGS-B/C and WGS have one
unit controller and multiple circuit controllers. Unit settings for AGS-B/C and WGS models are adjusted on the unit
controller.
No.
Configuration
No.
5
6
Temperatures
Evaporator Entering
Water Temperature (16)
Evaporator Leaving
Water Temperature (16)
Condenser Entering
Water Temperature (15)
Condenser Leaving
Water Temperature (15)
No.
Setpoints
No.
Alarms
11
10
12
13
You can display any number of additional data points based on job requirements or individual preference. See Modbus
Data Points on page 8 for lists of all Modbus Variables available to the network. For a more detailed description of all
available data points, see the Detailed Data Point Information section on page 13 of this document.
ED 15063-5
Page
Read/
Write
14
14
14
R
R
R
14
14
15
R
W
R
Data Type
Index
Description
Holding Register
Holding Register
40003
40011
-40- 199F
0 - 160%
0-32678
Holding Register
Holding Register
Holding Register
Holding Register
40247
40251
40043
40004
0 - 160%
0 - 160%
40086
40106
2
7
6
40148
40146
0=Off, 1=On
0=Not Limited, 1=Limited
0=Remote, 1=Local
1=ICE, 2=COOL, 3=HEAT
1=ICE, 2=COOL, 3=HEAT
40108
15
15
15
15
16
R/W
R
R
R
R/W
Holding Register
Holding Register
Coil
Coil
Coil
Holding Register
Holding Register
16
Holding Register
16
Holding Register
40147
Chiller Power
Compressor Current
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6
16
16
R
R
Holding Register
40245
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
40027
40096
40110
40115
40120
40125
Compressor Discharge
Temperature
Compressor Select
Compressor #2
17
Holding Register
Holding Register
40020
40092
17
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
40026
40095
40109
40114
40119
40124
Compressor Power
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6
Compressor Run Hours
Compressor Select
Compressor #2
Compressor #3
18
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
40028
40097
40111
40116
40121
40126
Holding Register
Holding Register
Holding Register
40175
40236
40239
10
18
-460- 621F
-460- 621F
0 -110%
0 - 65,535
0 - 65,535
ED 15063-5
Network Control
Property
Compressor #4
Compressor Select
Compressor Starts
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor Suction Line
Temperature
Compressor Select
Compressor #2
Compressor Voltage
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6
*Condenser Entering Water
Temperature (7)
Condenser Flow Switch Status
*Condenser Leaving Water
Temperature (8)
Condenser Pump Run Hours
Pump Select
Pump #2
Condenser Refrigerant
Pressure
Compressor Select
Compressor #2
Condenser Saturated
Refrigerant Temperature
Compressor Select
Compressor #2
Page
Read/
Write
18
19
R/W
R
20
20
Holding Register
Holding Register
40242
40161
Holding Register
Holding Register
Holding Register
Holding Register
40174
40235
40238
40241
Holding Register
40016
-40- 244F
Holding Register
40089
-40- 244F
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
Holding Register
40030
40099
40113
40118
40123
40128
Description
See page 13
0 - 65,535
0 - 65,535
20
Holding Register
40008
-40 - 244F
21
Coil
21
Holding Register
40009
-40 - 244F
21
R
Holding Register
Holding Register
40177
40233
0 - 65,535
0 - 32767
Holding Register
Holding Register
40022
40094
Holding Register
40021
-40 - 244F
Holding Register
40093
-40 - 244F
Holding Register
40025
Holding Register
Holding Register
40254
40255
Holding Register
Holding Register
40249
40253
Holding Register
Holding Register
40087
40107
Holding Register
Holding Register
40246
40250
40248
40252
32
40002
21
21
22
Design RPM
22
11
Index
Data Type
24
R
25
25
25
0-32678
0-32678
22
22
R
R/W
Holding Register
Holding Register
Coil
Holding Register
22
Holding Register
40005
-40 - 244F
22
Coil
22
Holding Register
40007
-40 - 244F
23
R
Holding Register
40015
-40 - 244F
ED 15063-5
Network Control
Property
Read/
Write
Page
Compressor Select
Compressor #2
Evaporator Pump Run Hours
Pump Select
Pump #2
Evaporator Refrigerant
Pressure
Compressor Select
Compressor #2
23
23
24
Index
Description
Holding Register
40088
-40 - 244F
Holding Register
Holding Register
40176
40232
0 65,535
0 65,535
Holding Register
Holding Register
40018
40091
Holding Register
Holding Register
40017
40090
Holding Register
40019
30
-40 - 244F
-40 - 244F
0 - 65,535 (Requires field provided flow
measurement device)
0=Pump Off Request, 1=Pump On Request
40023
-40 - 244F
40024
-40 - 244F
40006
40051
50 - 120F
15 - 35F, Default=25F
40039
40037
40105
-40- 244F
-40- 244F
40033
40101
40035
40103
-40 - 244F
-40 - 244F
40034
40102
40036
40104
40040
20
3
-40 - 244F
-40 - 244F
-40 - 244F
0=Pump No. 1, 1=Pump No. 2
0=OFF, 1=Run Allowed
23
Evaporator Saturated
Refrigerant Temperature
Compressor Select
Compressor #2
Data Type
12
Page
Read/Write
28
28
29
Data Type
Index
Description
Coil
R/W
Coil
25
Holding Register
4013040145
ED 15063-5
Data Point
Active Alarms
Active Setpoint
Actual Capacity
Actual RPM
Alarm Digital Output
Capacity Limit Output
Capacity Limit Setpoint
Cavity Temperature
Chiller Enable
Chiller Limited
Chiller Local/Remote
Chiller Mode Output
Chiller Mode Setpoint
Chiller Status
Compressor Current***
Compressor Discharge Temperature
Compressor Percent RLA
Compressor Power***
Compressor Run Hours
Compressor Select
Compressor Starts
Compressor Suction Line Temperature
Compressor Voltage***
Condenser Entering Water Temperature
Condenser Flow Switch Status
Condenser Leaving Water Temperature
Condenser Pump Run Hours
Condenser Refrigerant Pressure
Condenser Saturated Refrigerant Temperature
Condenser Water Flow Rate
Condenser Water Pump Status
Cool Setpoint
Design RPM
Evaporator Entering Water Temperature
Evaporator Flow Switch Status
Evaporator Leaving Water Temperature for
Compressor
Evaporator Leaving Water Temperature for Unit
Evaporator Pump Run Hours
Evaporator Refrigerant Pressure
Evaporator Saturated Refrigerant Temperature
Evaporator Water Flow Rate
Evaporator Water Pump Status
Heat Recovery Entering Water Temperature
Heat Recovery Leaving Water Temperature
Heat Setpoint
Ice Setpoint
IGV Percentage Open
Inverter Temperature
Liquid Line Refrigerant Pressure
Liquid Line Refrigerant Temperature
Maximum RPM
Minimum RPM
Network Clear Alarm
Oil Feed Pressure**
Oil Feed Temperature**
Oil Sump Pressure**
Oil Sump Temperature**
Outdoor Air Temperature
Pump Select
Run Enabled
WSC/WDC/WPV/WMC
/WCC/HSC/TSC/HDC
AGZ
ACZ
WGZ/TGZ
AGS
WGS
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X*
X*
X
X*
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X*
X
X
X
X
X
X*
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
13
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ED 15063-5
Active Setpoint
This output data point indicates the current value of the Leaving Water Temperature setpoint. Based on the operating
mode of the chiller, this value is derived from the Cooling Setpoint, Ice Setpoint or Heating Setpoint. The default mode
is Cooling and is used unless changed by the Chiller Mode Setpoint. (A2)
Data Type
Holding Register
Index
40003
Measurement
Temperature
Units
F x 10
Valid Range
-40-199F
Actual Capacity
This output data point indicates the percent of capacity the chiller is currently producing. It may be more or less than the
nominal capacity of the chiller. (A10)
Data Type
Holding Register
Index
40011
Measurement
Percent of chiller capacity
Units
% x 10
Valid Range
0% to 160%
Actual RPM
This variable indicates the actual speed of the compressor. (I118 & I122)
Compressor #1
Data Type
Holding Register
Index
40247
Measurement
Revolutions Per Minute
Units
RPM
Valid Range
0-32768
Compressor #2
Data Type
Holding Register
Index
40251
Measurement
Revolutions Per Minute
Units
RPM
Valid Range
0-32768
Index
40043
Measurement
Percent of maximum capacity
Units
% x 10
Valid Range
0% to 160%.
14
Index
40004
Measurement
Percent of maximum capacity
Units
% x 10
Valid Range
0% to 160%.
ED 15063-5
Cavity Temperature
This output data point indicates the current temperature of the compressors motor stator cavity. (A85 & A105)
Compressor #1
Data Type
Holding Register
Index
40086
Measurement
Temperature
Units
Valid Range
Units
Valid Range
Fx10
Compressor #2
Data Type
Holding Register
Index
40106
Measurement
Temperature
Fx10
Index
40020
Measurement
Temperature
Units
F x 10
Valid Range
-460-621F
Compressor #2
Data Type
Holding Register
Index
40092
Measurement
Temperature
Units
F x 10
Valid Range
-460-621F
Chiller Enable
This input data point enables the chiller to run if operating conditions are satisfied, or disables the chiller from running.
(D1)
Data Type
Coil
Index
2
Measurement
Chiller State
Units
Valid Range
0 = Disable (Off)
1 = Enable (On)
NA
Chiller Limited
This output data point indicates whether chiller operation is limited in some way. If conditions exist that limit operation,
the chiller may be prevented from reaching the Leaving Water Temperature setpoint. (D6)
Data Type
Coil
Index
7
Measurement
Status
Units
Valid Range
0 = Not Limited
1 = Limited
NA
Chiller Local/Remote
The Local/Remote output data point indicates whether the chiller is in local control or allowed to be controlled remotely
over the network. (D5)
Data Type
Coil
Index
6
Measurement
Mode
Units
Valid Range
0= Remote
1 = Local
NA
15
Index
Measurement
Units
Valid Range
ED 15063-5
Holding Register
40148
HVAC Mode
1. ICE
2. COOL
3. HEAT
NA
Index
40146
Measurement
Units
HVAC Mode
Valid Range
1. ICE
2. COOL
3. HEAT
NA
Index
40108
Measurement
Units
Percent
NA
Valid Range
0-100%
Chiller Status
This output data point indicates the current state of the chiller. (I18)
Data Type
Holding Register
Index
40147
Measurement
Chiller State
Units
Models
Valid Range
NA
Chiller Power
This variable indicates the totalized compressor kilowatts. (I116).
Data Type
Index
Measurement
Holding Register
40245
Electric Power
Units
kiloWatts
Valid Range
0-1000
Compressor Current
Compressor Select
This output data point indicates the compressor current of the compressor selected with Compressor Select on page 18.
(A26)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40027
Electric Current
Amperes
0 -65,535
Compressor #2
40096
Electric Current
Units
Amperes
Valid Range
0 -65,535
Compressor #3
16
40110
Electric Current
Units
Amperes
Valid Range
0 -65,535
ED 15063-5
Compressor #4
40115
Electric Current
Units
Amperes
Valid Range
0 -65,535
Compressor #5
40120
Electric Current
Units
Amperes
Valid Range
0 -65,535
Compressor #6
40125
Electric Current
Units
Amperes
Valid Range
0 -65,535
40020
Temperature
F x 10
-460-621F
Compressor #2
This output data point indicates the compressor 2 discharge temperature. (A91)
Data Type
Index
Measurement
Units
Holding Register
40092
Temperature
F x 10
Valid Range
-460-621F
40026
Percent RLA
% x 10
0 -110%
Compressor #2
This output data point indicates the compressor 2 percent RLA. (A94)
Data Type
Index
Measurement
Holding Register
40095
Percent RLA
Units
% x 10
Valid Range
0 -110%
Compressor #3
This output data point indicates the compressor 3 percent RLA. (A108)
Data Type
Index
Measurement
Holding Register
40109
Percent RLA
Units
% x 10
Valid Range
0 -110%
Compressor #4
This output data point indicates the compressor 4 percent RLA. (A113)
Data Type
Index
Measurement
Holding Register
40114
Percent RLA
Units
% x 10
Valid Range
0 -110%
Compressor #5
This output data point indicates the compressor 5 percent RLA. (A118)
Data Type
Index
Measurement
Holding Register
17
40119
Percent RLA
Units
% x 10
Valid Range
0 -110%
ED 15063-5
Compressor #6
This output data point indicates the compressor 6 percent RLA. (A123)
Data Type
Index
Measurement
Holding Register
40124
Percent RLA
Units
% x 10
Valid Range
0 -110%
Compressor Power
This output data point indicates the current compressor power of the compressor selected with Compressor Select on
page 18. (A27)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40028
Electric Power
kiloWatts
0-65,535
Compressor #2
This output data point indicates the current compressor 2 power. (A96)
Data Type
Index
Measurement
Holding Register
40097
Electric Power
Units
kiloWatts
Valid Range
0-65,535
Compressor #3
This output data point indicates the current compressor 3 power. (A110)
Data Type
Index
Measurement
Holding Register
40111
Electric Power
Units
kiloWatts
Valid Range
0-65,535
Compressor #4
This output data point indicates the current compressor 4 power. (A115)
Data Type
Index
Measurement
Holding Register
40116
Electric Power
Units
kiloWatts
Valid Range
0-65,535
Compressor #5
This output data point indicates the current compressor 5 power. (A120)
Data Type
Index
Measurement
Holding Register
40121
Electric Power
Units
kiloWatts
Valid Range
0-65,535
Compressor #6
This output data point indicates the current compressor 6 power. (A125)
Data Type
Index
Measurement
Holding Register
40126
Electric Power
Units
kiloWatts
Valid Range
0-65,535
40175
Time
hours/10
0 -65,535
Compressor #2
This output data point indicates the current compressor 2 run hours. (I107)
Data Type
Index
Measurement
Holding Register
40236
Time
Units
hours/10
Valid Range
0 -65,535
Compressor #3
This output data point indicates the current compressor 3 run hours. (I110)
Data Type
Index
Measurement
Holding Register
18
40239
Time
hours/10
Units
Valid Range
0 -65,535
ED 15063-5
Compressor #4
This output data point indicates the current compressor 4 run hours. (I113)
Data Type
Index
Measurement
Holding Register
40242
Time
Units
hours/10
Valid Range
0 -65,535
Compressor Select
This input data point selects the compressor (number 1, 2, 3 or 4) that is interrogated. The controller returns the
information for the selected compressor. You must first select a compressor, then interrogate the selected compressor.
This data point selects a compressor for the following variables. (I32)
Name
Page
Compressor Current
13
16
17
Compressor Power
14
18
Compressor Starts
19
20
Compressor Voltage
15
21
21
23
23
23
26
26
26
26
Data Type
Holding Register
Index
40161
Measurement
Event Count
Units
NA
Valid Range
0 -65,535
Compressor Starts
This output data point indicates the number of starts for the compressor motor of the compressor selected with
Compressor Select on page 19. (I45)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40174
Count
Starts
0 -65,535
Compressor #2
This output data point indicates the current compressor 2 starts. (I106)
Data Type
Index
Measurement
Holding Register
40235
Count
Units
Starts
Valid Range
0 -65,535
Compressor #3
This output data point indicates the current compressor 3 starts. (I109)
Data Type
Index
Measurement
Holding Register
40238
Count
Units
Starts
Valid Range
0 -65,535
Compressor #4
This output data point indicates the current compressor 4 starts. (I112)
Data Type
Index
Measurement
Holding Register
19
40241
Count
Units
Starts
Valid Range
0 -65,535
ED 15063-5
40016
Temperature
F x 10
-40-244F
Compressor #2
This output data point indicates the current compressor 2 suction line temperature. (A88)
Data Type
Index
Measurement
Units
Holding Register
40089
Temperature
F x 10
Valid Range
-40-244F
Compressor Voltage
This output data point indicates the current compressor voltage of the compressor selected with Compressor Select on
page 20. (A29)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40030
Electric Voltage
Volts
0 -65,535
Compressor #2
This output data point indicates the current compressor 2 voltage. (A98)
Data Type
Index
Measurement
Holding Register
40099
Electric Voltage
Units
Volts
Valid Range
0 -65,535
Compressor #3
This output data point indicates the current compressor 3 voltage. (A112)
Data Type
Index
Measurement
Holding Register
40113
Electric Voltage
Units
Volts
Valid Range
0 -65,535
Compressor #4
This output data point indicates the current compressor 4 voltage. (A117)
Data Type
Index
Measurement
Holding Register
40118
Electric Voltage
Units
Volts
Valid Range
0 -65,535
Compressor #5
This output data point indicates the current compressor 5 voltage. (A121)
Data Type
Index
Measurement
Holding Register
40123
Electric Voltage
Units
Volts
Valid Range
0 -65,535
Compressor #6
This output data point indicates the current compressor 6 voltage. (A127)
Data Type
Index
Measurement
Holding Register
20
40128
Electric Voltage
Volts
Units
Valid Range
0 -65,535
ED 15063-5
Index
40008
Measurement
Temperature
Units
F x 10
Valid Range
-40-244F
Index
9
Measurement
Flow State
Units
Valid Range
0 = No Flow
1 = Flow
NA
Index
40009
Measurement
Temperature
Units
F x 10
Valid Range
-40-244F
This output data point indicates the number of run hours that the selected condenser pump motor. See Pump Select on
page 21. (I48)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40177
Time
hours
0 -65,535
Pump #2
This output data point indicates the number of run hours that for condenser pump #2. (I104)
Data Type
Index
Measurement
Units
Holding Register
40233
Time
hours
Valid Range
0 -32768
40022
Pressure (gauge)
psi x 10
Compressor #2
This output data point indicates the current compressor 2 refrigerant pressure. (A93)
Data Type
Index
Measurement
Units
Holding Register
40094
Pressure (gauge)
psi x 10
Valid Range
-22592 - 22591 psi
40021
Temperature
F x 10
-40- 244F
Compressor #2
This output data point indicates the current compressor 2 saturated refrigerant temperature. (A92)
Data Type
Index
Measurement
Units
21
Valid Range
ED 15063-5
Holding Register
40093
Temperature
F x 10
-40- 244F
Index
40025
Measurement
Units
Valid Range
0 -65,535
Index
32
Measurement
Units
Flow State
Valid Range
0 = Pump Off Request
1 = Pump On Request
NA
Cool Setpoint
This input data point sets the temperature of the Leaving Chilled Water when the chiller is operating in the Cooling
Mode. The Cooling mode is the normal mode of chiller operation, unless overridden by using the Chiller Mode Setpoint
to change to another mode. (A1)
Note: See the appropriate Operation Manual for specific data range and default value.
Data Type
Index
Measurement
Units
Holding Register
40002
Temperature
F x 10
Valid Range
10 - 120F
Design RPM
This output network variable indicates the Turbocor calculated speed target based on conditions and request demand.
(I125 & I126)
Compressor #1
Data Type
Holding Register
Index
40254
Measurement
Units
RPM
Valid Range
0-32768
Compressor #2
Data Type
Holding Register
Index
40255
Measurement
Units
RPM
Valid Range
0-32768
Index
40005
Measurement
Units
Temperature
F x 10
Valid Range
-40 - 245F
Index
8
Measurement
Flow State
Units
NA
Valid Range
0 = No Flow
1 = Flow
ED 15063-5
Data Type
Holding Register
Index
40007
Measurement
Temperature
Units
F x 10
Valid Range
-40 - 244F
This output data point indicates the current temperature of the evaporator leaving chilled water temperature of the
compressor selected with Compressor Select on page 18. (A14)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40015
Temperature
F x 10
-40-244F
Compressor #2
This output data point indicates the current temperature of the evaporator leaving chilled water temperature for
compressor 2. (A87)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40088
Temperature
F x 10
-40-244F
This output data point indicates the number of run hours for the selected evaporator pump. There is a separate output for
each pump. See Pump Select on page 27. (I47)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40176
Event Count
Hours
0 - 65,535
Pump #2
This output data point indicates the number of run hours for evaporator pump #2. (I103)
Data Type
Index
Measurement
Units
Holding Register
40232
Event Count
Hours
Valid Range
0 - 65,535
This output data point indicates the current refrigerant pressure in the evaporator. There is a separate output for each
compressor. See Compressor Select on page 18. (A17)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40018
Pressure (gauge)
psi x 10
Compressor #2
This output data point indicates the current refrigerant pressure in the evaporator for compressor 2. (A90)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40091
Pressure (gauge)
psi x 10
This output data point indicates the current saturated refrigerant temperature in the evaporator. There is a separate output
for each compressor. See Compressor Select on page 18. (A16)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
23
40017
Temperature
F x 10
-40 - 244F
ED 15063-5
Compressor #2
This output data point indicates the current saturated refrigerant temperature in the evaporator for compressor 2. (A89)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40090
Temperature
F x 10
-40 - 244F
Index
40019
Measurement
Water Flow Rate
Units
Valid Range
0 - 65,535
Index
30
Measurement
Flow State
Units
Valid Range
0 = Pump Off Request
1 = Pump On Request
NA
Index
40023
Measurement
Temperature
Units
F x 10
Valid Range
-40 - 244F
Index
40024
Measurement
Temperature
Units
F x 10
Valid Range
-40-244F
Heat Setpoint
This input data point provides the heating setpoint when the chiller is operating in the heat mode. The value is ignored if
the controller is in cooling mode. (A5)
Note: See the appropriate Operation Manual for specific data range and default value.
Data Type
Index
Measurement
Units
Holding Register
40006
Temperature
F x 10
Valid Range
50-120F
Ice Setpoint
This input data point sets the temperature of the Leaving Chilled Water when the chiller is operating in the ice mode.
(A50)
Note: See the appropriate Operation Manual for specific data range and default value.
Data Type
Index
Measurement
Units
Holding Register
40051
Temperature
F x 10
Valid Range
15 - 35F
24
ED 15063-5
Compressor #1
Data Type
Holding Register
Index
40249
Measurement
Percent
Units
%
Valid Range
0-110%
Compressor #2
Data Type
Holding Register
Index
40253
Measurement
Percent
Units
%
Valid Range
0-110%
Inverter Temperature
This output network variable the current drive temperature. There is one variable for each compressor. (A86 & A106)
Compressor #1
Data Type
Holding Register
Index
40087
Measurement
Temperature
Units
Valid Range
Units
Valid Range
Fx10
Compressor #2
Data Type
Holding Register
Index
40107
Measurement
Temperature
Fx10
Index
40039
Measurement
Pressure
Units
psi x 10
Valid Range
22592 - 22591 psi
Data Type
Holding Register
Index
40037
Measurement
Temperature
Units
F x 10
Valid Range
-40 - 244F
Compressor #2
Data Type
Holding Register
Index
40105
Measurement
Temperature
Units
F x 10
Valid Range
-40 - 244F
Maximum RPM
This output data point indicates the maximum (choke) RPM. This is the speed the Turbocor compressor calculates
above which the efficiency of the compressor falls off. (I117 & I121)
Compressor #1
Data Type
Holding Register
Index
40246
Measurement
Revolutions Per Minute
Units
RPM
Valid Range
0-32768
Compressor #2
Data Type
Holding Register
Index
40250
Measurement
Revolutions Per Minute
Units
RPM
Valid Range
0-32768
Minimum RPM
This output data point indicates the minimum (surge) RPM. This is the speed Turbocor compressor calculates is the
minimum safe operating speed above onset of stall. (I119 & I123)
Compressor #1
Data Type
25
Index
Measurement
Units
Valid Range
ED 15063-5
Holding Register
40248
RPM
0-32768
Compressor #2
Data Type
Holding Register
Index
40252
Measurement
Revolutions Per Minute
Units
RPM
Valid Range
0-32768
This output data point indicates the current compressor oil feed pressure. There is a separate output for each compressor.
See Compressor Select on page 18. (A32)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40033
Pressure
psi
Compressor #2
This output data point indicates the current compressor 2 oil feed pressure. (A100)
Data Type
Index
Measurement
Units
Holding Register
40101
Pressure
psi
Valid Range
22592 - 22591 psi
This output data point indicates the current compressor oil feed temperature. There is a separate output for each
compressor. See Compressor Select on page 18. (A34)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40035
Temperature
F x 10
-40 - 244F
Compressor #2
This output data point indicates the current compressor 2 oil feed temperature. (A102)
Data Type
Index
Measurement
Units
Holding Register
40103
Temperature
F x 10
Valid Range
-40 - 244F
This output data point indicates the current compressor oil sump pressure. There is a separate output for each
compressor. See Compressor Select on page 18. (A33)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
40034
Pressure
psi x 10
Compressor #2
This output data point indicates the current compressor 2 oil sump pressure. (A101)
Data Type
Index
Measurement
Units
Holding Register
40102
Pressure
psi x 10
Valid Range
-22592 - 22591 psi.
This output data point indicates the current compressor oil sump temperature. There is a separate output for each
compressor. See Compressor Select on page 18. (A35)
Data Type
Index
Measurement
Units
Valid Range
Holding Register
26
40036
Temperature
F x 10
-40 - 244F
ED 15063-5
Compressor #2
This output data point indicates the current compressor 2 oil sump temperature. (A103)
Data Type
Index
Measurement
Units
Holding Register
40104
Temperature
F x 10
Valid Range
-40 - 244F
Index
40040
Measurement
Temperature
Units
F x 10
Valid Range
-40 -2 44F
Pump Select
This input data point selects which pump (Number 1 or Number 2) supplies the data. The controller returns the
information for the appropriate Condenser or Evaporator pump. You must first select a pump then interrogate the
selected pump. See Condenser Pump Run Hours on page 21 and Evaporator Pump Run Hours on page 23. (D19)
Data Type
Coil
Index
20
Measurement
Event Count
Units
Valid Range
0 = Pump #1
1 = Pump #2
NA
Run Enabled
The Run Enabled output data point indicates that the chiller can start if operating conditions are met. (D2)
Data Type
Coil
27
Index
3
Measurement
Chiller State
Units
NA
Valid Range
0 = Off
1 = Run Allowed
ED 15063-5
Alarms
Alarm Classes
Modbus alarms in a MicroTech II unit controller are divided into three classes: Faults, Problems, and Warnings. Fault
alarms have the highest severity level. Problem alarms have medium severity level. Warning alarms have the lowest
severity level.
Fault Alarms
Fault alarms require an acknowledgment from the operator. These alarms indicate that the compressor is shut down.
Problem Alarms
Problem alarms do not cause compressor shutdown but limit operation of the chiller in some way.
Warning Alarms
A warning is enunciated whenever an abnormal condition exists which does not affect chiller operation.
Alarm Handling
One Modbus network variable indicates an alarm condition and one network variable clears alarms. To determine the
particular alarm condition, you must read the status of the 16 Active Alarms Holding Registers.
Index
4
Measurement
NA
Units
Valid Range
0 = No Alarm
1 = Alarm
NA
Clear Alarms
This input data point clears all active alarms. It cannot clear all alarms in the Fault category (alarms that shut down the
chiller). They would have to be cleared at the chiller panel. The alarms that cannot be cleared over the network (but can
be cleared at the chiller) are: (D24)
Low Evaporator Pressure
High Condenser Pressure (by pressure sensor)
High Condenser Pressure (by pressure switch)
Low Oil Pressure
Freeze Protection
High Motor Temperature
Note: The above list is for centrifugal chillers. The flow loss alarm is the only alarm that can be remotely
cleared on all other types of chillers.
Data Type
Coil
28
Index
25
Measurement
NA
Units
NA
Valid Range
0 = Normal
1 = Clear Alarm
ED 15063-5
Active Alarms
The Active Alarms Holding Registers contain a single bit for each alarm condition. You must read the status of these
registers to determine the particular alarm condition indicated by the Alarm Digital Output. Table 3 defines the bit
location for each alarm condition. (I1-I16)
Data Type
Holding Registers
Index
40130-40145
Measurement
Units
Alarm Condition
Valid Range
0 = No Alarm
1 = Alarm
NA
Description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
29
Warnings
Entering Condenser Water Temperature Sensor Fault
Entering Evaporator Water Temperature Sensor Fault
Liquid Line Refrigerant Temperature Sensor Fault
Leaving Condenser Water Temperature Sensor Fault
Repower After Power Loss 1
Repower After Power Loss 2
Repower After Power Loss 3
Repower After Power Loss 4
(Expansion Alarm Warning)
Problems
Low Ambient Temperature Lockout
High Condenser Pressure Inhibit Loading Circuit 1
High Condenser Pressure Inhibit Loading Circuit 2
High Condenser Pressure Inhibit Loading Circuit 3
High Condenser Pressure Inhibit Loading Circuit 4
High Condenser Pressure Unload
High Condenser Pressure Unload Circuit 1
High Condenser Pressure Unload Circuit 2
High Condenser Pressure Unload Circuit 3
High Condenser Pressure Unload Circuit 4
Condenser Water Freeze Protect Comp 1
Condenser Water Freeze Protect Comp 2
Condenser Water Freeze Protect Comp 3
Condenser Water Freeze Protect Comp 4
Condenser Pump #1 Fault
Condenser Pump #2 Fault
High Discharge Temperature Comp 1
High Discharge Temperature Comp 2
High Discharge Temperature Comp 3
High Discharge Temperature Comp 4
Entering Evap Temperature Sensor Fault (EWT reset
active)
Low Evaporator Pressure - Inhibit Loading
Low Evaporator Pressure - Inhibit Loading Circuit 1
Low Evaporator Pressure - Inhibit Loading Circuit 2
Low Evaporator Pressure - Inhibit Loading Circuit 3
Low Evaporator Pressure - Inhibit Loading Circuit 4
Low Evaporator Pressure Unload
Low Evaporator Pressure Unload Circuit 1
Low Evaporator Pressure Unload Circuit 2
Low Evaporator Pressure Unload Circuit 3
Low Evaporator Pressure Unload Circuit 4
High Motor Current On Compressor #1
High Motor Current On Compressor #2
High Motor Current On Compressor #3
High Motor Current On Compressor #4
Evaporator Freeze Protect Comp 1
Evaporator Freeze Protect Comp 2
Evaporator Freeze Protect Comp 3
WSC
WDC
WPV
WMC
WCC
HSC
HDC
TSC
AGZ
ACZ
X
X
X
X
WGZ/
TGZ
X
X
X
AGS
WGS
X
X
2
X
X
5
X
5
X
X
3
X
3
X
X
3
X
3
X
X
5
X
5
X
X
X
X
X
X
X
X
X
X
2
X
X
X
X
X
X
X
X
2
X
X
X
X
X
X
X
X
X
X
X
X
6
X
X
X
5
X
5
X
X
3
X
3
X
X
X
X
5
X
5
X
X
3
X
3
X
X
X
X
X
X
X
X
X
2
X
X
X
X
X
X
X
2
X
X
X
Holding
Register
Bit
40130
40130
40130
40130
40130
40130
40130
40130
40130
1
2
3
4
5
6
7
8
9
40130
40130
40130
40130
40130
40130
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
40131
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
40131
14
40131
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
40132
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ED 15063-5
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
30
X
X
X
X
X
1
X
1
X
X
X
X
X
X
X
1
X
X
X
X
X
X
1
X
X
X
X
X
X
5
X
5
X
X
3
X
3
X
X
X
X
X
X
7
X
X
1
X
X
5
X
X
X
X
3
X
X
7
X
X
X
X
7
X
X
X
X
X
X
7
X
X
X
X
5
X
5
X
X
3
X
3
X
X
3
X
3
X
X
X
X
X
X
X
X
2
X
X
X
5
X
5
X
X
X
X
X
X
X
2
X
X
X
X
X
2
X
X
X
X
X
X
X
X
X
X
X
X
X
6
X
5
X
X
X
X
X
X
X
X
X
X
3
X
40133
40133
40133
40133
0
1
2
3
40133
40133
40133
40133
40133
40133
40133
40133
40133
40133
40133
40133
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40134
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40135
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40136
40137
40137
40137
40137
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
ED 15063-5
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
31
X
3
X
3
X
X
X
X
5
X
5
X
X
7
X
X
2
X
40137
40137
40137
40137
40137
40137
40137
40137
40137
40137
40137
40137
40138
40138
40138
40138
40138
40138
40138
40138
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
X
X
X
X
2
X
X
X
X
X
X
1
X
X
X
X
X
2
X
X
X
40138
40138
40138
10
X
6
X
X
X
2
X
40138
11
40138
40138
40138
40138
40139
12
13
14
15
0
1
40139
40139
40139
40139
40139
40139
40139
40139
40139
40139
40139
40139
40139
40139
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40140
40141
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
X
5
X
5
X
X
3
X
3
X
X
X
X
5
X
5
X
X
X
X
1
X
X
X
X
3
X
3
X
X
X
X
X
2
X
X
X
X
X
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ED 15063-5
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
32
X
X
X
X
X
X
X
X
X
X
X
2
X
X
X
X
1
X
X
X
X
X
X
2
X
2
X
X
X
X
X
2
X
X
X
X
X
X
X
X
X
X
8
X
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40141
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40142
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40143
40144
40144
40144
40144
40144
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
X8
ED 15063-5
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
X8
X8
X8
33
ED 15063-5
C
Capacity Limit Output .......................................... 10, 14
Capacity Limit Setpoint .................................... 9, 10, 14
Cavity Temperature .............................................. 10, 15
Chiller Enable ................................................... 9, 10, 15
Chiller Limited ..................................................... 10, 15
Chiller Local/Remote ........................................... 10, 15
Chiller Mode Output............................................. 10, 15
Chiller Mode Setpoint ...................................... 9, 10, 16
Chiller Power ........................................................ 10, 16
Chiller Status .................................................... 9, 10, 16
Clear Alarms ..................................................... 9, 12, 28
Compressor 2 Active Capacity Limit ......................... 16
Compressor 2 Active Capacity Limit ......................... 10
Compressor Current.............................................. 10, 16
Compressor Discharge Temperature .............. 10, 15, 17
Compressor Percent RLA ..................................... 10, 17
Compressor Power................................................ 10, 18
Compressor Run Hours ........................................ 10, 18
Compressor Select ................................................ 11, 19
Compressor Starts ................................................. 11, 19
Compressor Suction Line Temperature ................ 11, 19
Compressor Voltage ............................................. 11, 20
Condenser Entering Water Temperature .............. 11, 21
Condenser Flow Switch Status ............................. 11, 21
Condenser Leaving Water Temperature ............... 11, 21
Condenser Pump Run Hours ................................ 11, 21
Condenser Refrigerant Pressure ........................... 11, 21
Condenser Saturated Refrigerant Temperature ..... 11, 21
Condenser Water Flow Rate ................................. 11, 22
Condenser Water Pump Status ............................. 11, 22
Cool Setpoint .................................................... 9, 11, 22
H
Heat Recovery Entering Water Temperature ........12, 24
Heat Recovery Leaving Water Temperature .........12, 24
Heat Setpoint .........................................................12, 24
I
Ice Setpoint ...........................................................12, 24
IGV Percentage Open ...........................................11, 24
Inverter Temperature .............................................11, 25
L
Liquid Line Refrigerant Pressure ..........................12, 25
Liquid Line Refrigerant Temperature ...................12, 25
M
Maximum RPM.....................................................11, 25
Minimum RPM .....................................................11, 25
O
Oil Feed Pressure ..................................................12, 26
Oil Feed Temperature ...........................................12, 26
Oil Sump Pressure .................................................12, 26
Oil Sump Temperature ..........................................12, 26
Outdoor Air Temperature ......................................12, 27
P
Pump Select...........................................................12, 27
34
ED 15063-5
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinMcQuay.com.
Daikin McQuay
(800) 432-1342, www.DaikinMcQuay.com
35
ED 15063-5