Sunteți pe pagina 1din 4

Preliminary Report on Airconditioning System for Parsvnath Metro Mall, Seelampur

Delhi.
1.

General :
This report outlines the basis of design, estimated requirements, Proposed system, other
requirements and estimated cost.

2.

Area to be Airconditioned :
Ground and Mezzanine floor of each left and right wing to be air-conditioned.

3.

Basis of Design :

3.1

Out side conditions

Summer

43.3O CDB; 23.9O CWB

Monsoon

35.0O CDB; 28.3O CWB

Winter

7.2O CDB;

5.0O CWB

3.2

Inside conditions

Summer
&
Monsoon

22.2O C for Auditorium


23.8O C +/- 1O C for other areas
RH not exceeding 65%

3.3

Light

Shop
Other area

:
:

6.0 w/sqft.
2.0 w/sqft.

3.4

Occupancy

60 sqft./person

3.5

Fresh air

1.5 a/c per hour or 17 cfm


per person whichever is
higher.

3.6

Roof insulation

4.

Estimated Requirement :

All the exposed roof to be


insulated with 50 mm thick
expanded polystyrene / or
equivalent insulation.

Based on above design data, the estimated requirements are as follows.

-:2:-

-----------------------------------------------------------------------------------------------------------------S.No. Name of area


Area
Summer
Monsoon
Sqft
TR
TR
-----------------------------------------------------------------------------------------------------------------A Right Wing
1.

Ground Floor

Shops Show rooms


5228
36.05
38.72
Atrium
570
5.42
6.51
Corridor
1593
4.90
5.80
-----------------------------------------------------------------------------------------------------------------Subtotal
7,391
46.37
51.03
-----------------------------------------------------------------------------------------------------------------2.

Mezzanine Floor

Shops
5228
40.45
42.15
Corridor
1740
6.85
7.30
-----------------------------------------------------------------------------------------------------------------Subtotal
6,968
47.30
49.45
-----------------------------------------------------------------------------------------------------------------Total
14,359
93.67
100.48
-----------------------------------------------------------------------------------------------------------------B Left Wing
3.

Ground Floor
Shopping Hall

4.

6779

44.75

48.42

Mezzanine Floor

Shopping Hall
6530
50.26
52.50
-----------------------------------------------------------------------------------------------------------------Subtotal
13,309
95.01
100.92
-----------------------------------------------------------------------------------------------------------------Grand Total
27,668
188.68
201.40
Sqft.
TR
TR
------------------------------------------------------------------------------------------------------------------:3:-

Total requirements of each wing


Taking 20% derating of the
aircooled system
Net requirement

100 TR

120 TR

5.

System Design :

5.1

It is proposed to install central chilled water system to aircondition the entire shopping
area of left and right wing.

5.2

Main airconditioning plant will be consist of 4 Nos. 60 TR (Nominal) capacity aircooled


reciprocating chillers along with 6 Nos. chilled water pumps (two standby).

5.3

The main plant will be installed in the Service area in open space.

5.4

Main plant will supply chilled water to various areas on each floor using M.S. `C class
insulated chilled water piping.

5.5

All shopping Hall will have unitary AHU according to requirements. Other area will also
be feeded by AHUs.

5. 6

G.I. sheet steel ducting will be used to supply conditioned air to various area supply and
return air grill/diffuser will be of extruded Aluminium duly powder coated.

5.7

The system will be complete with electrical panel board with cabling and earthing.

6.

Power Requirements :
Complete system of airconditioning will require 400 kw of 3 Ph, 415 volts, 50 Hz A.C.
supply and 3 Ph/1 Ph supply will be needed for AHU.

7.

Water Requirements :
As the system is aircooled, water is not required.

8.

Estimated Cost :
Shopping Complex

8.1

8.2

Chilling unit
60 TR each (Recip.)

Chilled water pumps

4 Nos.
-:4:-

Rs.

50,00,000

6 Nos.

Rs.

2,00,000

8.3

Ducting, insulation and


grills

Lot.

Rs.

16,00,000

8.4

AHUs /FCU

Lot.

Rs.

25,00,000

8.5

Piping and insulation

Lot.

Rs.

15,00,000

8.6

Electrical panel board with


cabling and earthing

L.S.

Rs.

Total

ABID HUSAIN CONSULTANTS

(ABID HUSAIN)
800/28072005

4,00,000
---- ----------Rs. 1,12,00,000
---------------