Documente Academic
Documente Profesional
Documente Cultură
Design Project # 01
Project title: Harmonic Filter Study
Course Title: Modern Power System Modeling
Course No: EEE 6202
Course Teacher: Ms. Tajrin Ishrat
Submitted By:
Name: Mohammad Ashifur Rahman
Student ID: 11MEE010P
Program: M.Sc. in EEE, 2nd Semester
Session: 2011-12
Date of Submission: 11/12/2014.
Design Project
Harmonic Filter Study
Consider the simplified distribution system of a local industrial plant shown in the
one-line diagram of Fig.1. The plant's non-linear load is fed from a 1500kVA,
5.98% impedance service transformer (TR1) to step the 12,470V down to 480V
which is bused throughout the plant. An individual load of 906 kVA is shown
connected to the (PCC) point of common coupling, which is the bus connected to
the secondary of the service TR1 transformer. The load's power factor is
approximate 0.6.
The existent filter is a 1400 kVAR unit, tuned to 4.8th harmonic, installed in
parallel with the plant's nonlinear load. This filter was initially designed to serve
multiple functions for the plant: it improves the power factor and reduces the
harmonic distortion. Unfortunately the existent filter has had multiple failures
including bad capacitor cells, blown fuses, and over-heated reactors (inductors).
Ultimately the filter unit was shut down and remained off line. The plant
contracted a consultant company to determine the required tuning frequency and
the correct size (reactive power) of the harmonic filter. The consultant made
measurements of the plant main service for seven days (a summary of these
measurements are given in Appendix), and developed a harmonic study. The
consultant's conclusions were that the size of the harmonic filter needs to be 700
kVAR with 4.7th tuned reactors, with recommended 200 kVAR fixed via a manual
control and 500 kVAR switched in 50 kVAR ten steps.
Based on the data provided in Appendix perform your own harmonic filter study,
and complete the following requirements for the distribution system (Fig.1):
I. Assume that the plant must improve the (old) power factor to 0.9 (new value), in
order to avoid penalties. Determine the capacitor bank total reactive power
required for the power factor correction (PFC). Then, calculate the capacitance C
per-phase, of a connected capacitor bank in parallel with the load, at
fundamental frequency of 50 Hz.
II. Determine the current distortion limits by using Table 1 (see Appendix). Based
on total demand distortion (TDD) and distortion of each individual relevant
harmonic, determine if the proposed 4.7th tuned filter is a good choice and the only
requirement needed to maintain harmonic current distortion within the limits
recommended by IEEE 519-1992 standard. Make your recommendation(s)
regarding what harmonic filtering (tuning frequency or frequencies) is needed for
this distribution system.
III. Check the voltage distortion limits, recommended by IEEE 519-1992 standard
in Table 2, based on individual voltage distortion and the total voltage distortion
(THD) calculations.
IV. Perform the harmonic filter design in accord with the recommendation(s)
you made in step (II). If the 5th current harmonic must be eliminated, then consider
in your design the filter proposed by the consultant company, 700 kVAR with
4.7th tuned reactors. The harmonic filter design should contain the following
calculations:
Appendix:
Design Project Input Data
Introduction
There are several harmonic sources in the distribution systems. These are loads with nonlinear
characteristics. The converters, pulse width modulated converters, cyclo- converters, arc furnaces,
static var compensators and switched mode power supplies are typical nonlinear loads producing
harmonics. In our project we used six pulse bridges as a nonlinear load. The effect of harmonics on the
power system depends on the characteristics of some important contributing factors that discussed
below:
System short circuit rating:
A system with a large short circuit capacity will produce a low voltage distortion. A system with a
lower short circuit rating will produce a large voltage distortion. The system short circuit rating
depends on the amount of generation, transmission voltage level, number of parallel lines and other
system characteristics.
Load characteristics:
The resistive component of the load produces damping in the circuit and hence reduces voltage
magnification. The reactive component of the load can shift the point at which the resonance occurs.
Hence a reactive load can amplify the voltage magnification. A lightly loaded system is likely to have
less damping and hence a higher voltage distortion. A heavily loaded system is likely to offer a better
damping.
Acceptance Criteria:
Power factor:
Harmonic filters:
Procedurers
fundamental frequency of 50 Hz
1
1
2.12mF
Xc * w 1.5 * 314
We need to minimize the filter impedance to filter the 5th harmonic distortion current. This can be
achieved by setting the inductive reactance (XL235) equal to capacitive reactance (XC235). Then the
impedance at the filtering frequency is decreased as shown in this formula
Z = R + j (XL-XC).
XC235 = XL235 = 0.21 /Ph