Sunteți pe pagina 1din 11

http://www.skm.com/applicationguides17.

html

1-8

Chosen by 39 of the top 40 Electrical Engineering Firms in the world.

HOME

PRODUCTS

Frequently Asked Questions

SUPPORT

DOWNLOADS

Application Guides

TRAINING

CONTACT

Power System Study Specs

CUSTOMER SER

Tech Support

PTW

Overcurrent Coordination Setting Guidelines Motors


The information presented in this application guide is for review, approval, interpretation and application by a registered professional eng
and liability resulting from the use and interpretation of this information.
Reproduction of this material is permitted provided proper acknowledgement is given to SKM Systems Analysis Inc.
Introduction
The proper selection and coordination of protective devices is mandated in article 110.10 of the National Electrical Code. To fulfill this req
is required. The electrical engineer is always responsible for this analysis. It is an unfortunate fact of life that many times the engineer wh
will not set the devices. Therefore, compromises are inevitable.
There are three fundamental objectives to overcurrent coordination that engineers should keep in mind while selecting and setting protec
The first objective is life safety. Life safety requirements are met if protective devices are rated to carry and interrupt maximum ava
and interrupt maximum available fault currents. Life safety requirements are never compromised.
The second objective is equipment protection. Protection requirements are met if overcurrent devices are set above load operating l
curves. Feeder and transformer damage curves are defined in applicable equipment standards. Motor and generator damage curves (po
normally provided in the vendor data submittal package. Based on system operating and equipment sizing practices equipment protecti
The last objective is selectivity. Selectivity requirements are met if in response to a system fault or overload, the minimum area of th
service. Again, based on system operating and equipment selection practices selectivity is not always possible.
Purpose
The purpose of this guide is to provide overcurrent protective device setting guidelines for motors to meet the objectives listed above.
MV Motor Switchgear Feeder Unit
Industry standard overcurrent protection schemes for MV induction and synchronous motors fed from switchgear circuit breakers include
50/51). The 50/51 relay characteristics are plotted on a phase time-current curve (TCC) along with the motor starting and damage curve
The purpose of the 50/51 relay is to allow the motor to start and run, and to protect the motor and cable from overloads and faults. To a
above and to the right of the motor starting curve, and to the left and below the rotor, stator and cable damage curves, and the amp rat
Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n
Device

Function

Recommendations

CT

Size

125-150% of FLA

51

Pickup

115-125% of FLA

Comments

Set below motor stator damage c


Set at or below cable ampacit

51

Time Dial

2-10 seconds above knee of


motor curve

Set below motor rotor damage c


Set below cable damage curv

1 of 11

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

50

Pickup

200% of LRA

Set below cable damage curv


Cable damage curve must be abo
maximum fault current at 0.1 sec

Fig. 1 MV motor switchgear feeder unit - one line

2 of 11

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

Fig. 2 MV motor switchgear feeder unit - phase TCC


MV Motor Fused Starter Feeder Unit
Industry standard overcurrent protection schemes for MV induction and synchronous motors fed from fused starters include an overcurre
fuses (device 50). R rated fuses melt at 100 times the R rating and 20 seconds. Both the fuse and relay characteristics are plotted on a p
damage curves, and the feeder damage curve.
The purpose of the fuse-relay combination is to allow the motor to start and run, and to protect the motor and cable from overloads and
combined curve must be above and to the right of the motor starting curve, and to the left and below the rotor, stator and cable damage
Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n
Device

Function

Recommendations

CT

Size

125-150% of FLA

51

Pickup

115-125% of FLA

Comments

Set below motor stator damage c


Set at or below cable ampacit

51

Time Dial

2-10 seconds above knee of


motor curve

Set below motor rotor damage c


Set below cable damage curv

50

Fuse Size

RRating > 1.1*LRA/100


AMPRating > FLA

Set below cable damage curv


Cable damage curve must be abo
maximum fault current at 0.01 se

Fig. 3 MV motor fused starter feeder unit - one line

3 of 11

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

Fig. 4 MV motor fused starter feeder unit - phase TCC


LV Motor Circuit Breaker Feeder Unit
Industry standard phase overcurrent functions purchased with circuit breakers serving LV motors include long time pickup, long time dela
PCBs, ICCBs, MCCBs and TMCBs. Short time pickup and short time delay functions are not used. The CB characteristics are plotted on a p
curve and safe stall point, and the feeder damage curve.
The purpose of the CB is to allow the motor to start and run, and to protect the motor and cable from overloads and faults. To accomplis
the right of the motor starting curve, and to the left and below the motor safe stall point, cable damage curve and amp rating. Note it is
amp rating due to breaker tolerances.
Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

4 of 11

Device

Function

Recommendations

Comments

LV CB

LTPU

125% of FLA

Set at or below cable ampacit

LV CB

Time Dial

2-10 seconds above knee of


motor curve

Set below motor safe stall poi

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

LV CB

INST

200% of LRA

Set below cable damage curv


Cable damage curve must be above
defined by the maximum fault curren
PCB instantaneous clear curv

Fig. 5 LV motor circuit breaker feeder unit - one line

5 of 11

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

Fig. 6 LV motor power circuit breaker feeder unit - phase TCC


LV Motor MCP Starter Feeder Unit
Industry standard phase overcurrent protection is provided in MCP starter units by two discrete components, a thermal overload relay an
is a circuit breaker with the thermal element removed. The overload and MCP characteristics are plotted on a phase TCC along with the m
the feeder damage curve.
The purpose of the overload-MCP combination is to allow the motor to start and run, and to protect the motor and cable from overloads
overload-MCP combined curve should be above and to the right of the motor starting curve, and to the left and below the motor safe sta
rating. Note it is not always possible to be below the cable amp rating due to overload tolerances.
Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

6 of 11

Device

Function

Recommendations

Comments

OL

Pickup

125% of FLA if SF > 1.15


115% of FLA if SF = 1.00

Set at or below cable ampacit

OL

Time Dial

Fixed assume Class 20

Set below motor safe stall poi

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

MCP

Size

125-160% of FLA

MCP

Pickup

200% of LRA

Set below cable damage curv

Cable damage curve must be above


defined by the maximum fault curren
PCB instantaneous clear curv

Fig. 7 LV motor MCP starter feeder unit - one line

7 of 11

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

Fig. 8 LV motor MCP starter feeder unit - phase TCC


LV Motor Fused Starter Feeder Unit
Industry standard phase overcurrent protection is provided in fused starter units by two discrete components, a thermal overload relay a
characteristics are plotted on a phase TCC along with the motor starting curve and safe stall point, and the feeder damage curve.
The purpose of the overload-fuse combination is to allow the motor to start and run, and to protect the motor and cable from overloads a
overload-fuse combined curve should be above and to the right of the motor starting curve, and to the left and below the motor safe sta
rating. Note it is not always possible to be below the cable amp rating due to overload tolerances.
Suggested margins are listed below that have historically allowed for safe operation of the motor and cable while reducing instances of n

8 of 11

Device

Function

Recommendations

Comments

OL

Pickup

125% of FLA if SF > 1.15


115% of FLA if SF = 1.00

Set at or below cable ampacit

OL

Time Dial

Fixed assume Class 20

Set below motor safe stall poi

Fuse

Size

175% of FLA

Set below cable damage curv

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

Cable damage curve must be above


defined by the maximum fault current
seconds

Fig. 9 LV motor fused starter feeder unit - one line

9 of 11

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

Fig. 10 LV motor fused starter feeder unit - phase TCC


References
Other Application Guides offered by SKM Systems Analysis at www.skm.com
Electrical Transmission and Distribution Reference Book, ABB Power T&D Company, Raleigh, North Carolina, 1997
Protective Relaying Theory and Applications, 2nd Edition, Marcel Dekker, New York, 2004
The latest revision of:

IEEE Std 242, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (IEEE Buff
IEEE Std 620, IEEE Guide for the Presentation of Thermal Limit Curve for Squirrel Cage Induction Machines
IEEE Std C37.96, IEEE Guide for AC Motor Protection
NEMA MG-1, Motors and Generators

back to Application guides

10 of 11

9/5/2013 1:56 PM

http://www.skm.com/applicationguides17.html

Home

Products

Support

Downloads

Training

Contact

Customer Service

Career Opportun

Copyright 2012. SKM Systems Analysis Inc. All rights reserved.

11 of 11

9/5/2013 1:56 PM

S-ar putea să vă placă și