Fire can cause overpressure of storage or vessel. Either liquid vaporization of wetted vessel or
vapor expansion of unwetted vessel due to heat input will increase the pressure. Heat input rate
of fire exposure is not calculable from standard of heat transfer fundamental. Fortunately, OSHA
regulations specify standards which are to be followed for particular material in storage vessel
and API also provides formulas for calculating heat input rate which are to be followed for
particular condition of process vessel.
The following picture presents OSHA Venting Requirement of Fire Exposure to Storage Vessel.

Triyanto SR
View my complete profile

For flammable and combustible liquid, heat input refers to NFPA 30 as follow.
Depressuring (4)
Diary (1)

1/27/2015 2:47 PM

Process Engineer: Fire Case - Heat Input Rate

2 of 5

http://process-eng.blogspot.ca/2012/04/fire-heat-input-rate.html

Flare (3)
Gas Processing (1)
PID (7)
Piping (7)
PSV (16)
Pump (5)
Simulation (4)
STHE (1)

Note :
1. Information in table applies to liquified components ; see original standard for nonliquified gases

1st Depressuring Tutorial

2. CGA = Compressed Gas Association


NFPA = National Fire Protection Association
ANSI = American National Standard Association

2nd Depressuring Tutorial


3.Heat Input expressed in BTU/hr, with area in square feet.
3rd Depressuring Tutorial
4.See source documents for details of area calculations

2014 (2)
2012 (21)
October (1)
September (5)
July (1)
May (2)
April (9)
Relieving Condition
Exceed Design
Temperature
Useful HYSYS Short
Cut
Rigorous Method for
Fire Case
Fire Case - Heat
Input Rate
Reflux Failure Case
Tube Rupture Case
Blowdown PSV
Gas Blowby Case

My friend, if you want to check the correctness of value in above table, please refers to original reference,
Guidelines for Pressure Relief and Effluent Handling System, AMERICAN INSTITUTE OF CHEMICAL ENGINEERS
(AICHE), Table 3.3-1 (page 131 of 538). You can find that book in our library.
API STD 521 provides formulas for calculating heat input rate to process vessel containing liquid.
Q = 21.000 FA^0.82
Where adequate drainage and firefighting equipment do not exist, equation below should be used,
Q = 34,500 FA^0.82
Regarding a drainage, as long as the amount of liquid which is spilled out around the vessel is possibly decrease,
use the first formula ( = heat flux 21000).
F is environment factor. The value F = 1 for bare vessel. Refer to API STD 521 Table 5 (page 17) for other than bare
vessel.
A is wetted area of the vessel.
The value of A ^0.82 reflect that not 100% vessel area exposed by fire. It is true for large vessel, for small
vessel, we can use assumption that 100 % vessel area is totally exposed by fire.
For example, for small bare vessel, the equation to be Q = 21.000 A.
My friend, please note, based on the formula, when 82% fraction area is applied the heat flux is 21.000
BTU/ft^1.64/hr or 34500 BTU/ft^1.64/hr. And when 100% fraction area is applied, the unit will be BTU/ft^2/hr. This
understanding will useful in perform depressuring simulation using HYSYS.
The above formula is for pool fire case which has heat flux of 21.000 BTU/ft1.64/hr. Whereas, based on API STD
521, the heat flux for jet fire is 95.500 BTU/ft2/hr (average). From the unit of heat flux for jet fire, its show that 100%

1/27/2015 2:47 PM

Process Engineer: Fire Case - Heat Input Rate

3 of 5

http://process-eng.blogspot.ca/2012/04/fire-heat-input-rate.html

Block Outlet Case


March (3)

fraction area is used (for jet fire is localized heat flux).


Hope this drawing helps you get better understanding of pool fire and jet fire

2011 (8)

My Office - IKPT
Process Simulation
Encyclopedic for Engineer
Cheresources
Gas Production Process
Chemical & Process Technology
Smart Process Design
Chemical Engineer Resources

And below is jet fire

257664

Built Up Back Pressure


Calculation
Built Up and Superimpossed Back
Pressure
Minimum Flow System
Accumulation and Overpressure
PSV Calculation - Kd,Kc,Kb factor
PSV Installation-Guide
Gas Blowby Case
Reducer Suction Pump System
PSV Sizing

My friend, in this posting we discuss about heat input rate of fire exposure for process vessel. The following are the
important point,

Basic Depressuring - Why 15

1. For adequate drainage and fire fighting exist, use formula Q = 21.000 FA^0.82

1/27/2015 2:47 PM

Process Engineer: Fire Case - Heat Input Rate

4 of 5

http://process-eng.blogspot.ca/2012/04/fire-heat-input-rate.html

minutes ?
There was an error in this gadget

2. For small vessel, use 100% fraction area is exposed by fire, therefore Q =21.000 FA. In my understanding, vessel
with wetted area less than 200 ft2 can be considered small vessel (see NFPA 30)
3. For wetted vessel, overpressure caused by liquid evaporation, the relieving load capacity can be calculated as
heat input divided by latent heat of vaporization. (W = Q/Hv).
4. Heat flux of jet fire is very high (95.500 BTU/ft2/hr average), and in localized area.
5. I suggest you to sizing PSV on fire case for pool fire case only.
6. The relieving temperature can be higher than the vessel collapse temperature. Vessel will collapse before
increasing pressure reach PSVs set pressure. Therefore, actually, PSV doesnt provide sufficient protection.
Depressuring is one of the additional protections against fire. (We will discuss about fire case depressuring
both for pool and jet fire in other posting)
My friend, thank you for reading, please correct me if I'am Wrong.

You might also like:

Rigorous Method
for Fire Case

Relieving Condition
Exceed Design
Temperature

Basic Depressuring
- Why 15 minutes ?

PSV
Installation-Guide

PSV Calculation Kd,Kc,Kb factor

Linkwithin

Anonymous Jun 12, 2013, 7:31:00 PM


Informative page, thank you.
Reply

Anonymous Nov 14, 2013, 12:01:00 AM


Thanks very much. Very helpful
Reply

Anonymous Nov 25, 2013, 7:05:00 PM


good artical..helpful
Reply

1/27/2015 2:47 PM

Process Engineer: Fire Case - Heat Input Rate

5 of 5

http://process-eng.blogspot.ca/2012/04/fire-heat-input-rate.html

Anonymous Dec 2, 2013, 11:52:00 AM


Thanks for helpful information. :)
Could you give me a answer for below two questions?
1. In API 521 fire case, both wetted and unwetted, I can calculate the mass flow by paragraph
5.15.2.2.1(wetted) & 5.15.2.2.2(unwetted).
Also, I can find equation for effective discharge area of the valve in un-wetted case. but can't for wetted
case.
In wetted case, should I use a equation on API 520 para.3.6.2.1.1 for effective discharge area?
2. If answer is 'yes' for above question 1, why equation for effective area on those two case are different??
Reply