Refrigeration and Air Conditioning Controls

Data sheet

Pulse solenoid valve for liquid injection


type EVRP 0.4 to 1.4
Introduction

Danfoss has developed a solenoid valve type


EVRP 0.4 to 1.4, which can reduce the
superheat in 2-stage refrigeration systems or
solve the low temperature problems in R 22
plant with single stage compressors when
injecting refrigerant into the suction chamber
or the suction manifold.
The EVRP 0.4 to 1.4 pulse solenoid valve can
be continously controlled via an impulse
modulated signal from a control unit.

Ordering

Application

Type

Code No.

EVRP 0.4
EVRP 0.5
EVRP 0.65
EVRP 0.85
EVRP 1.0
EVRP 1.2
EVRP 1.4

032F4000
032F4001
032F4003
032F4005
032F4007
032F4009
032F4011

Connections

/8 inch.
ODM-solder

Media
temperature

40 to
+70 C

MOPD

25 bar

Kv-value
m3/h
0.0065
0.01
0.017
0.027
0.035
0.05
0.06

Example 1
2-stage refrigeration system built up with a
combined LP/HP compressor.
In this case the discharge gas temperature on
the HP side is used as indirect temperature
signal to the solenoid valve.
In this example an EVRP 0.4 to 1.4 valve is
used, see fig. 1

LP: Low pressure


HP: High pressure
PI: Intermediate pressure

Custom-designed
controller

Fig. 1

May 1998

RD.3K.A1.02

Data sheet

Application

EVRP 0.4 to 1.4

Example 2
2-stage refrigeration system with 2
separate refrigerating compressors
in series.
In this set up a solution with
solenoid valve, type EVRP 0.4 to
1.4, the discharge gas temperature
on the HP side can be used as
indirect temperature signal to the
solenoid valve, see fig. 2.

Dimensions

LP: Low pressure


HP: High pressure
PI: Intermediate pressure

Custom-designed
controller

Fig. 2

Danfoss code no.: 032F4007

All dimensions in mm

Technical data

Type:
Media:
Capacity:

EVRP 1.0
R 12, R 22, R 502, R 134a
0.035 m3/h

Pressures:
Min. opening diff. pressure:
Max. opening diff. pressure:
Max. working pressure:
Max. test pressure:
Liquid temperature:
Ambient temperature:
Connections:
Weight (valve):
Min. average life cycle:

0 bar
25 bar
28 bar
36 bar
40 +70C
40 +80C
3
/8 inch. ODM solder
0.35 kg
50 106 cycles

RD.3K.A1.02

Data sheet

EVRP 0.4 to 1.4

Coils for a.c.

MOPD = 21 bar
Code no.

Valve
type

EVRP

Voltage

Frequency

with 1 m
3-core
cable

with
terminal box

V
12
24
42
48
115
220
240
380
420
24
115
220
240

Hz
50
50
50
50
50
50
50
50
50
60
60
60
60

IP 67
018Z6256
018Z6257
018Z6258
018Z6259
018Z6261
018Z6251
018Z6252
018Z6253
018Z6254
018Z6265
018Z6260
018Z6264
018Z6263

IP 67
018Z6706
018Z6707
018Z6708
018Z6709
018Z6711
018Z6701
018Z6702
018Z6703
018Z6704
018Z6715
018Z6710
018Z6714
018Z6713

with AMP
plug and
protective
cap
IP 20
018Z6181
018Z6182
018Z6183
018Z6184
018Z6186
018Z6176
018Z6177
018Z6178
018Z6179
018Z6190
018Z6185
018Z6189
018Z6188

110
220

50/60
50/60

018Z6280
018Z6282

018Z6730
018Z6732

018Z6192
018Z6193

1)

Appendix
no.

21
32

2)

Consumption

15
16
17
18
22
31
33
37
38
14
20
29
30

21 VA
Inrush:
44 VA

1)

when replacing a coil with terminal box, it is sufficient to change the coil unit itself. Therefore order coil with
AMP plug and protective cap. 2) The appendix no., clearly designates type of current, voltage and frequency.

Concerning d.c. coils and special a.c. coils, please contact Danfoss.

Accessories
AMP socket, code no. 042NO156

RD.3K.A1.02

Data sheet

EVRP 0.4 to 1.4

RD.3K.A1.02

Danfoss A/S AC-SP/MR 05-1998