PL 810 Power Link Module for LD 800P
Benefits
Power Link Module PL 810 for PROFIBUS DP/PA Linking Device LD 800P
Function
The Power Link Module and the head station HS 8x0 form
a Linking Device LD 800P. The Power Link Module can
only be operated with the head station HS 810, HS 820 or
HS 840. PL 810 can be mounted within zone 2.
The Power Link Module supplies PROFIBUS PA devices
powered by the bus.For the data transmission between
Power Link Module and head station a wire link has to be
made between Power Link Module terminals and head
station terminals
The communication is seamless. The Power Link Module
does not have to be programmed. The PROFIBUS PA
segment has a baud rate of 31.25 kbit/s in accordance with
IEC 61158-2.
FieldIT
Tecnical Data
Power
Nominal voltage
Nominal current
Ripples
Galvanic separation
CH/PROFIBUS DP
20 ... 35 V DC
790 mA ... 400 mA
< 10 %
Function isolation, designed isolation voltage 50 Veff
PROFIBUS PA/Power
CH/Power
89/336/EWG
EN 61326
EG94/9
EN 50021
-20 ... 60 C (253 ... 333 K)
< 75 %
Terminals
up to 2,5 mm
80 mm x 115 mm x 107 mm
320 g
IP20
3BDD011711R0201
FieldIT
Notes
Note:
Informationen on installation of PROFIBUS PA can be taken from PTO PROFIBUS user organization
guidelines.
Number of PA devices, current consumption of the participants:
The maximum combined current consumption of the connected PROFIBUS PA devices must be lower than
the nominal current of the Linking Device. The modulation current used by the PROFIBUS PA devices to
transmit data does not have to be considered.
International certificates, declarations of conformity and User Instructions can be retrieved via the search
button
under http://www.abb.com.
Dimensions
3BDD011711R0201
FieldIT
Accessories
For PROFIBUS PA applications ABB Automation Products offers the following accessories:
Application example