Posted: Wed Feb 06, 2013 3:21 pm
Post subject:
General Sponsor
sriprakash_shastry wrote:
Dear Mr. Dingare,
In PEB buildings the point raised by a fellow SEFIAN is correct. If the rod bracing undergoes
reversal of stresses and goes into compression it will fail. That is why it is important to note
the way the rod bracing is connected to the column. In all PEB buildings were rod bracing is
used it is connected to the PEB columns by means of a hill top washer. A hill top washer has a
bevelled surface which enables the bracing to move. So in the event the rod bracing is tending
to go into compression the bracing will move into a position wherein it cannot accept any
compression.
Joined: 21 Feb 2008
Posts: 4846
Location: Gaithersburg, MD,
U.S.A.
Due to the above rod bracings are designed as pure tension member. However, this does not
absolve the vendor of any liabilities arising out of not pre-tensioning the rod bracing before
installation.
Regards,
Sriprakash
Dear Er Sriprakash,
I was happy to read the technical note on study of cracks in reinforced concrete members
authored by you and your brother in the Jan. 2013 issue of ICJ. Congratulations!
Regards,
NS
Back to top
YOGESH.VADGAVE
SEFI Member
Dear Sefians
In the Pre engineering building which are designed as per MBMA , PEB Vendors provides rod
bracings .
They state following points
1.Rod bracing are designed for Tension only.
2. The Tension rods need not be check by L/rmin.
3. The rod bracing can not take any kind of compression force. because they are providing HILL
side washer .
I have some doubt
1. As X tension rods will act as tension only when if at their joints with rafter one horizontal
member will provided, which will take compression force.
IN PEB shed they are not providing that horizontal member.
then X rod bracing will act as compression and tension.
2. how hill side washer allows tension will only create.
20-01-2015 17:20
2 of 9
http://www.sefindia.org/forum/viewtopic.php?p=57534
Please throw focus on above subject Also guide if any book available for designing as per MBMA
system
Back to top
ibarua
General Sponsor
It is inconvenient for the PEB vendors to consider compression because they want to economize
by providing round bar bracings which will have a very high Le/r ratio. That's why they try to get
around the problem by providing various gadgets to convince us that compressive forces will just
vanish just because certain gizmos are provided.
The assumptions made by PEB vendors are contrary to the actual structural response..
Indrajit Barua.
From: YOGESH.VADGAVE <forum@sefindia.org>
Sent: Wed, 22 May 2013 08:37:18
To: general@sefindia.org
Subject: [SEFI] Re: Bracing rods in PEB - slenderness
Dear Sefians
In the Pre engineering building which are designed as per MBMA , PEB Vendors provides rod
bracings .
They state following points
1.Rod bracing are designed for Tension only.
2. The Tension rods need not be check by L/rmin.
3. The rod bracing can not take any kind of compression force. because they are providing HILL
side washer .
I have some doubt
1. As X tension rods will act as tension only when if at their joints with rafter one horizontal
member will provided, which will take compression force.
IN PEB shed they are not providing that horizontal member.
then X rod bracing will act as compression and tension.
2. how hill side washer allows tension will only create.
Please throw focus on above subject Also guide if any book available for designing as per MBMA
system
Posted via Email
Back to top
dinagaran
Post subject:
SEFI Member
Hi Everyone,
Joined: 15 Sep 2011
Posts: 1
20-01-2015 17:20
3 of 9
http://www.sefindia.org/forum/viewtopic.php?p=57534
5. Technically, only one diagonal member will be effective in transferring the force.
6. Now the question comes, when there is no horizontal member provided how the force will
flow?. The answer is when force hits the starting point of bracing and when there is no horizontal
member, then the force will try to push the frame. But the frame is longitudinally arrested by
means of purlins and flange braces. Thus the resistance is offered by the row of purlin just above
the bracing point.
6. Technically we design the purlin above bracing node for compression + bending. Based on the
force we provide either simple purlin or strut purlin (laced purlin) or strut tube.
I got convinced by doing a small model in sticks and cardboard.
You can try the same.
Note : PEB is a concept not a product.
Regards,
Dinagaran
Back to top
sandeep_chauhan
Post subject:
General Sponsor
Dear All,
Roof & wall bracing ofen consist of double diagonals which are so
slender as to have negligible capacity in compression. such members
include pretensioned rods and cables. In the design of double
diagonal tension bracing, one of each pair of diagonals is assumed to
act in tension & other diagonal is ignored(depending on direction of
wind/Seismic load ).
Joined: 27 Mar 2012
Posts: 110
Regards
Sandeep Chauhan
bracing-2.jpg
Description:
Filesize:
39.16 KB
Viewed:
355 Time(s)
bracing-1.jpg
Description:
Filesize:
98.6 KB
Viewed:
357 Time(s)
20-01-2015 17:20
4 of 9
http://www.sefindia.org/forum/viewtopic.php?p=57534
Back to top
krane
SEFI Member
Dear All,
Joined: 29 Nov 2009
Posts: 7
Rod bracing is the most prevailing solution for structural cross bracing in metal building systems.
Because of low weight, simple erection, rod bracing is commonly considered the most efficient
election for the braced frame diagonals and roof bracing.
Coming to the force transfer, diagonal tension will be carried by rod which will be active
depending on force transfer. Compression force component at the end of rod will be taken care by
strut purlin member or separate strut member.
Attachment : the web slot connection is the preferred solution due to its simplicity and low relative
cost. Each rod assembly consists of rod, ductile hillside washer, flat hardened washer and a hex
nut. The configuration has a self adjustment capability as each side if the rod protruding through
the web slot may be tightened until the required straightness is achieved.
Numerous numbers of technical papers are available and test conducted to prove this technology.
Quote:
22nd May 2013
Yes, the X bracings will have both tensile & compressive forces -- one diagonal leg of the X will
be in tension and the other in compression, which will be reversed when the wind reverses its
direction.
It is inconvenient for the PEB vendors to consider compression because they want to
economize by providing round bar bracings which will have a very high Le/r ratio. That's why
they try to get around the problem by providing various gadgets to convince us that
compressive forces will just vanish just because certain gizmos are provided.
20-01-2015 17:20
5 of 9
http://www.sefindia.org/forum/viewtopic.php?p=57534
The assumptions made by PEB vendors are contrary to the actual structural response..
Indrajit Barua.
From: YOGESH.VADGAVE
Sent: Wed, 22 May 2013 08:37:18
To: general@sefindia.org (general@sefindia.org)
Subject: [SEFI] Re: Bracing rods in PEB - slenderness
Dear Sefians
In the Pre engineering building which are designed as per MBMA , PEB Vendors provides rod
bracings .
They state following points
1.Rod bracing are designed for Tension only.
2. The Tension rods need not be check by L/rmin.
3. The rod bracing can not take any kind of compression force. because they are providing
HILL side washer .
I have some doubt
1. As X tension rods will act as tension only when if at their joints with rafter one horizontal
member will provided, which will take compression force.
IN PEB shed they are not providing that horizontal member.
then X rod bracing will act as compression and tension.
2. how hill side washer allows tension will only create.
Please throw focus on above subject Also guide if any book available for designing as per
MBMA system
SEFI Member
Dear All,
Rod bracing is the most prevailing solution for structural cross bracing in metal building systems.
Because of low weight, simple erection, rod bracing is commonly considered the most efficient
election for the braced frame diagonals and roof bracing.
Coming to the force transfer, diagonal tension will be carried by rod which will be active
depending on force transfer. Compression force component at the end of rod will be taken care by
strut purlin member or separate strut member.
Attachment : the web slot connection is the preferred solution due to its simplicity and low relative
cost. Each rod assembly consists of rod, ductile hillside washer, flat hardened washer and a hex
nut. The configuration has a self adjustment capability as each side if the rod protruding through
the web slot may be tightened until the required straightness is achieved.
Numerous numbers of technical papers are available and test conducted to prove this technology.
20-01-2015 17:20
http://www.sefindia.org/forum/viewtopic.php?p=57534
Progressive Member
Dear Krane, Can you please send some detailings in pdf formats?
Joined: 18 Jun 2011
Posts: 41
Rod bracing is the most prevailing solution for structural cross bracing in metal building systems.
Because of low weight, simple erection, rod bracing is commonly considered the most efficient
election for the braced frame diagonals and roof bracing.
Coming to the force transfer, diagonal tension will be carried by rod which will be active
depending on force transfer. Compression force component at the end of rod will be taken care by
strut purlin member or separate strut member.
Attachment : the web slot connection is the preferred solution due to its simplicity and low relative
cost. Each rod assembly consists of rod, ductile hillside washer, flat hardened washer and a hex
nut. The configuration has a self adjustment capability as each side if the rod protruding through
the web slot may be tightened until the required straightness is achieved.
Numerous numbers of technical papers are available and test conducted to prove this technology.
General Sponsor
The method suggested by the responder is convenient for the PEB vendor and therefore is
popular. Whatever one claims, one diagonal leg of the 'X' will be in compression. The solution is to
prevent the deflection of the column top under wind load and not to transfer any horizontal action
to the purlin, something that a purlin member is not designed to sustain.
The web slot connection is but a convenient way of dealing with the problem, and in my opinion is
not a solution.
However, I welcome details of authenticated tests conducted by an independent agency on actual
physical models for my study and appreciation.
Indrajit Barua.
6 of 9
20-01-2015 17:20
7 of 9
http://www.sefindia.org/forum/viewtopic.php?p=57534
Rod bracing is the most prevailing solution for structural cross bracing in metal building systems.
Because of low weight, simple erection, rod bracing is commonly considered the most efficient
election for the braced frame diagonals and roof bracing.
Coming to the force transfer, diagonal tension will be carried by rod which will be active
depending on force transfer. Compression force component at the end of rod will be taken care by
strut purlin member or separate strut member.
Attachment : the web slot connection is the preferred solution due to its simplicity and low relative
cost. Each rod assembly consists of rod, ductile hillside washer, flat hardened washer and a hex
nut. The configuration has a self adjustment capability as each side if the rod protruding through
the web slot may be tightened until the required straightness is achieved.
Numerous numbers of technical papers are available and test conducted to prove this technology.
SEFI Member
Dear Yogesh,
Joined: 13 Mar 2011
Posts: 17
It is nice that you have raised some basic issue related to transfer of forces.
It is basic question on use of rod as bracing not only PEB but in structure in general including Sag
rod in roof and cladding.
The concept is historical , when we had to do manual analysis of structure. Structural analysis
software was not developed.
3. There has to be a tie beam connecting the columns of braced frame and this will be further
connecting other columns so that horizontal force generated at any column is transferred to the
braced bay (effective diagonal as tension force).
20-01-2015 17:20
8 of 9
http://www.sefindia.org/forum/viewtopic.php?p=57534
4. The tie beam connecting the braced columns shall be subjected to compressive force.
5. If tie beam is not provided, nearest available purlin in slope roof or floor beam in case of flat
roof/floor will act as tie beam(say virtual tie beam). The connection between column and virtual
tie beam will be eccentric through a beam/ top chord of truss will be not be d to top of column,
thus beam/ top chord of truss will be subjected to horizontal moment.
6. Available commercial software on structural analysis has option to define a member as "tension
only member" to simulate above in analysis model. Similarly off set option can be used in
analysis model to account for eccentricity.
Oldest First
Go
All times are GMT
Page 3 of 5
Jump to: SEFI General Discussion
Translation: Translate topic
Go
Go
You cannot post new topics in this forum
You cannot reply to topics in this forum
20-01-2015 17:20
9 of 9
http://www.sefindia.org/forum/viewtopic.php?p=57534
in
in
in
in
in
this
this
this
this
this
forum
forum
forum
forum
forum
tsunami
earthquake
WalesOnline - Tsunami Relief Cardiff: 45 pictures of an amazing day TEN years ago where ...
9NEWS.com - USGS: Fountain earthquake actually didn't happen
powered by
powered by
20-01-2015 17:20