Documente Academic
Documente Profesional
Documente Cultură
Pressure Measurement
Table of Content
Objectives............................................................................................................................... 3
Pressure Measurement.......................................................................................................... 4
Types of pressure.............................................................................................................. 4
Pressure Units:.................................................................................................................. 5
a) Imperial units.............................................................................................................. 5
b) S.I. Unit....................................................................................................................... 5
c) Liquid Column............................................................................................................. 6
Pressure Conversions....................................................................................................... 6
Primary measuring elements for the process pressure......................................................7
Bourdon Tubes............................................................................................................... 7
C-type bourdon............................................................................................................... 8
Helical bourdon............................................................................................................... 8
Spiral bourdon................................................................................................................ 9
Bellows Sensors................................................................................................................ 9
Diaphragm Sensors.........................................................................................................15
Resonant-Wire Sensors...................................................................................................18
Strain-Gauge Sensors.....................................................................................................20
Capacitance Pressure Sensors.......................................................................................21
Spring-Loaded Piston Sensors........................................................................................22
Pressure Sensor's protection..............................................................................................23
Diaphragm Seals............................................................................................................. 23
Siphons............................................................................................................................ 26
Throttling Devices............................................................................................................ 26
Pressure-Limiting Valves.................................................................................................29
Pressure measurement devices..........................................................................................30
Manometers..................................................................................................................... 30
The U tube or Double Limb........................................................................................... 30
Pressure Gauges............................................................................................................. 35
Selection of Pressure Gauge...........................................................................................35
Gauge errors................................................................................................................... 37
Precautions................................................................................................................... 37
Pressure Transmitters......................................................................................................38
Suppressed zero.......................................................................................................... 38
Elevated zero................................................................................................................ 38
Pneumatic DP Cell........................................................................................................... 40
Electronic DP cells........................................................................................................... 40
VTC
(Rev.2) 06/02/2003
Page 1 of 57
Pressure Measurement
Capacitance type............................................................................................................. 41
Resonant (Vibrating) wire type.........................................................................................41
Pressure Controllers........................................................................................................46
Electric Pressure Switches..............................................................................................47
Pneumatic Pressure Switches/Pressure Pilots................................................................50
Pneumatic Switching Valves............................................................................................51
Operation...................................................................................................................... 51
Adjustment.................................................................................................................... 51
Pressure Regulator............................................................................................................... 52
ADMA OPCO HSE Regulation..............................................................................................54
Refer to HSE Regulation No. 6 Work to Permit system..............................................55
Refer to HSE Regulation No. 22 Hot and Odd Bolting...............................................55
Refer to HSE Regulation No. 23 General Engineering Safety....................................55
Refer to HSE Regulation No. 7 Isolations..................................................................55
Refer to HSE Regulation No. 7 Isolations..................................................................56
Review Questions.................................................................................................................58
Model Answers..................................................................................................................... 59
VTC
(Rev.2) 06/02/2003
Page 2 of 57
MODULE: I-1
Pressure Measurement
PRESSURE MEASUREMENT
OBJECTIVES
At Completion of this module, the trainee will have understanding of:
1. Pressure definition, types and units.
2. Pressure sensing elements.
3. Principles of pressure sensing elements; bourbon tubes, bellows,
diaphragms, vibrating wires, strain gauges and capacitance sensors.
4. Protection devices for pressure measuring elements.
5. Pressure measurement devices.
6. Function of pressure measurement devices.
7. Select a pressure device for a service.
8. Identify the types of pressure gauge errors.
9. Identify the parts and function of pneumatic and electronic pressure
transmitters.
10. Describe the difference between electronic and smart transmitters.
11. How to Convert 4-20 mA signal to 1-5 vdc signal and why.
12. Calculate an output signal of a pressure transmitter at certain input.
13. Definition of range and span of a transmitter.
14. Field-wiring connection methods of the electronic pressure transmitter.
15. Pressure switches types and function.
16. Pressure regulators construction parts and function.
Related Safety Regulations for Module I-1: PRESSURE MEASUREMENT
Developees have to be familiarised with the following ADMA OPCO HSE
regulations, while studying this module:
Regulation No. 6: Permit to Work system.
Regulation No. 7: Isolation
7.18 (1-10) control systems procedures and isolations.
Regulation No. 22: Hot and Odd Bolting.
Regulation No. 23: General Engineering Safety.
VTC
(Rev.2) 06/02/2003
Page 3 of 57
Pressure Measurement
PRESSURE MEASUREMENT
Oil and gas production operations require that system operating pressures be
regulated to specific pressures in order for the system(s) to work properly.
In addition, safety considerations dictate that system operating pressures be
monitored and controlled to ensure that the pressure limitations of equipment
and piping are not exceeded. In order to meet these objectives, the industry
relies on a variety of devices to generate an output signal which may be used
to adjust or change the observed pressure, The devices used by the oil and
gas industry for sensing operating pressures and generating the needed output
signals are described in this manual. The purpose of this document is to
provide the reader with an understanding of how the different types of device
functions and how they should by applied, in order to satisfy the requirements
of system monitoring and control.
Pressure is defined as the force exerted per unit area of surface.
P = F/A
P = pressure
F = force
A = surface area exposed to the force
In processing plants the hydrocarbon gases and liquids handled in pipes and
vessels exert pressure on the surface area.
Types of pressure
In order to understand various types of pressure the following will be
considered: Pressure Scale reference points, there are two reference points,
the zero point of pressure which is assumed to a perfect vacuum, another point
is atmospheric pressure which varies with altitude above sea level and with
weather conditions.
Absolute pressure scale starts from a zero reference point representing the full
vacuum and extends through atmospheric pressure to the highest limit of
measurable pressure.
Gauge pressure scale starts zero reference point representing the local
atmospheric pressure and extends to a chosen limit applicable to the specific
process system.
Vacuum scale starts from the absolute zero reference point and extends to a
maximum represented by atmospheric pressure.
The above can be expressed as following:
Zero of absolute pressure = perfect vacuum
Absolute Pressure = Pressure above Absolute zero
Gauge Pressure = Absolute Pressure Atmospheric pressure
Vacuum gauge Pressure = Atmospheric Pressure Fluid Pressure
VTC
(Rev.2) 06/02/2003
Page 4 of 57
Pressure Measurement
Pressure Units:
ADMA OPCO uses a variety of pressure units but the two main systems are the
Imperial (British and American) units and the S.I. (System International).
As pressure can be expressed as FORCE divided AREA then the units of
pressure can by expressed as the units of force divided by the units of area.
a)
Imperial units
In the Imperial system the unit of
force is pound force (lbf) and the
unit of area is the inch square (in2).
It follows that the unit of pressure in
the Imperial system is the pound
force divided by the inch square
(lbf/Sq. in) (pounds per square
inch). This is often abbreviated to
PSI.
b)
S.I. Unit
In the S.I. system the unit of force is
the Newton (N) and the unit of area
is the meter square (m2). Therefore the unit of force in the S.I. system is the
Newton per square meter (N/m2). This is a very small unit of pressure and the
VTC
(Rev.2) 06/02/2003
Page 5 of 57
Pressure Measurement
S.I. unit that is more commonly used on the plant is bar. One bar is equal to
100000 N/m2.
c) Liquid Column
Pressure can also be expressed in terms of liquid column height. The Imperial
units are inches water column (in Wc) and the S.I. units are millimeters water
column (mm Wc). Imperial units are inches Wc (or Hg) S.I. unitus are mm Wc
(or Hg).
Pressure Conversions
The table below gives a few examples of different pressure:
IMPERIAL
S.I.
Lbf/in2
lnch Wc
bar
mm Wc
27.73
0.06895
703.1
0.03613
2.487x10-3
25.4
14.504
402.1
10.22x103
1.422x10-3
0.03937
97.98x10-6
Examples:
1. Change 20 psi to bar
1 psi
20 psi
20 psi
=
=
=
0.06895 bar
20x0.06895 bar
1.379 bar
1 bar
1.6 bar
1.6 bar
=
=
=
14.504 psi
1.6 x 14.504 psi
23.2064 psi
=
=
=
25.4 mm
100 x 25.4 mm
2540 mm Wc
=
=
=
0.03937 in Wc
520 x 0.03937 in Wc
20.4724 in Wc.
3. Change 100 in Wc to mm Wc
1 inch
100 inch
100 in Wc
4. Change 520 mm Wc to in Wc
1 mm Wc
520 mm Wc
520 mm Wc
VTC
(Rev.2) 06/02/2003
Page 6 of 57
Pressure Measurement
The closed end of the bourdon tube is attached to a mechanical linkage. The
linkage is connected to a pointer or other output device, see figure 2. There are
three common types of bourdon tubes, the C-shape, the spiral, and the helix.
VTC
(Rev.2) 06/02/2003
Page 7 of 57
Pressure Measurement
C-type bourdon
C-type bourdon tubes are used for ranges as low as 0 - 15 psig (0 - 100 kPa)
and as high as 0 - 1500 psig (0 - 10,000 kPa). They are simple, accurate, and
have good repeatability, but they are bulky and highly subject to damage from
over-ranging. Most C-type bourdon tubes will tolerate only minimal
overpressure.
Helical bourdon
Helical bourdon tubes are used for ranges as low as 0 - 200 psig (0 - 1300 kPa)
up to 0 - 6000 psig (0 - 40,000 kPa). Heavy-duty helical bourdons can
sometimes tolerate as high as ten times the maximum range pressure.
VTC
(Rev.2) 06/02/2003
Page 8 of 57
Pressure Measurement
Spiral bourdon
Spiral bourdon tubes are used for both very low ranges and very high ranges.
Very sensitive units are manufactured to measure as low as 0 -10 psig (0 - 65
kPa). Heavy-duty units can measure up to 0 -100,000 psig (0 -700,000 kPa).
Bellows Sensors
A bellows sensor is an axially flexible, cylindrical enclosure with folded sides.
When pressure is applied through an opening, the closed end extends axially
as shown in figure 3.
VTC
(Rev.2) 06/02/2003
Page 9 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 10 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 11 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 12 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 13 of 57
Pressure Measurement
Diaphragm Sensors
A diaphragm is a thin, flexible, flat or corrugated disk, held in place so that it is
axially flexible. When pressure is applied to one side of the diaphragm it will
deflect. Deflection is proportional to the pressure. The force opposing the
pressure is the sum of the spring constant of the diaphragm, the pressure on
the opposing side of the diaphragm, and the spring constant of any opposing
spring. The sensitivity of a diaphragm increases as the diameter increases. The
axial movement of the diaphragm can rotate a pointer or actuate a controller or
transmitter by attaching the free end to a mechanical linkage.
There are two types of diaphragm elements, elastic and limp. The elastic type
uses the stiffness of the diaphragm to oppose the pressure applied. It is usually
metallic and comes in two different configurations; single and capsular.
The single diaphragm is, as its name implies, a single diaphragm either flat or
with concentric corrugations.
The capsular diaphragm consists of two diaphragms welded together at their
perimeters as shown in figure 8. Capsules can be either convex or nested as
illustrated. Capsules can be mounted in multiples to give more deflection for a
given pressure as shown by figure 9. Evacuated capsules are used for absolute
pressure reference and single diaphragms for very sensitive measurements.
VTC
(Rev.2) 06/02/2003
Page 14 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 15 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 16 of 57
Pressure Measurement
Resonant-Wire Sensors
Resonant-wire sensors are used in electronic pressure transmitters. The
resonant frequency of a vibrating wire is a function of the length, the square
root of the tension, and the mass of the wire. When the length and mass are
constant, it can be said that wire's tension is proportional to pressure then the
resonant frequency will be a function of pressure.
In resonant-wire pressure transmitters, a wire or ribbon under tension is located
in the field of a permanent magnet. The tension on the wire is proportional to
the pressure. An electrical signal with a frequency proportional to the square
root of the tension will be generated. This signal is converted to a 4-20 ma
transmitter output.
This principle is illustrated in figures 10 and 11. Figure 10 is a diagram of the
sensor assembly for a medium-range, gauge pressure transmitter. This sensor
uses a taut wire surrounded by fluid. One end of the wire is connected to the
closed end of a metal tube, which is fixed to the sensor body. The other end of
the wire is connected to a bellows.
Initial tension is applied to the wire by the spring connected between the
bellows and the zero-adjustment screw. The fill fluid transfers the force of
process pressure on the diaphragm assembly to the bellows. This force on the
bellows changes the tension on the wire and thus its resonant frequency.
VTC
(Rev.2) 06/02/2003
Page 17 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 18 of 57
Pressure Measurement
Strain-Gauge Sensors
Strain-gauge pressure sensors are used in most brands of electronic pressure
transmitters. When metallic conductors or semiconductors are subjected to
mechanical strain, a change in resistance will occur. This resistance is then
electrically converted into a 4-20 mA signal proportional to the pressure.
There are many different designs of strain-gauge pressure sensors. The most
common designs use a metallic diaphragm to isolate the process fluid and
exert a force on a force bar as shown in figure 12. This force bar transfers the
diaphragm movement to the strain gauge. Most of the strain elements in
current use are semiconductor type.
Figure 12, Force Balance D/P Cell with Strain Gauge Elements
VTC
(Rev.2) 06/02/2003
Page 19 of 57
Pressure Measurement
Gauge pressure is measured with the backside of the diaphragm left open to
the atmosphere. Absolute pressure is measured by evacuating and sealing the
backside of the diaphragm. Strain gauge pressure sensors can be used for
ranges from 0-30 inches H 2 O (0 -750 mm H 2 0) to 0 -10,000 psig (0 -66,000
kPa). These devices are stable with high speeds of response and are relatively
small. Strain gauge accuracy falls between 0.2 and 0.5 percent of span.
Special designs can handle process temperature to 600F (316C).
VTC
(Rev.2) 06/02/2003
Page 20 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 21 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 22 of 57
Pressure Measurement
The connecting space on the sensor side of the diaphragm is completely filled
with a non-compressible liquid. When process pressure is applied, the
diaphragm is displaced sufficiently to transmit an equal pressure to the
pressure sensor.
The three main components of a diaphragm seal are the top housing, bottom
housing, and diaphragm as shown in figure 16.
VTC
(Rev.2) 06/02/2003
Page 23 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 24 of 57
Pressure Measurement
Siphons
Siphons are generally used to isolate a hot-process media from the pressure
sensor. The siphon is a metal, tubular device shaped to form a plumber's loop,
(a low pocket in the tube). It can either be filled with a high-boiling-point liquid
or process condensate which acts as a barrier to the heat contained in the hot
gases or steam as shown in figure 17. In addition, these devices will act as a
pulsation dampener.
The path the hot vapor takes to the pressure sensor is relatively long and
narrow with a lot of surface area for cooling siphons.
Throttling Devices
Throttling devices are commonly used to dampen high-frequency pressure
fluctuations by putting a restriction in the inlet to the pressure sensor.
Throttling screws are the simplest means of providing a restriction, Throttling
screws are a special screw that comes in several orifice sizes and are inserted
into a tapped hole in the base (socket) of the pressure sensor to provide a flow
restriction as shown in figure 18.
VTC
(Rev.2) 06/02/2003
Page 25 of 57
Pressure Measurement
Pressure snubbers are very common for attenuating pressure fluctuations and
filtering the media. Snubbers are compact fittings with a porous element, which
both restricts the velocity and filters the fluid as shown in figure 19.
The pulsation dampener is another commonly used device. This device is also
sometimes called a pressure snubber, but does not have a filtering element.
There are several designs of pulsation dampeners.
The most common design consists of a bar-stock fitting, (sometimes two fittings
screwed together), as shown in figure 20. As the pressure pulse comes through
the dampener, the piston is forced up and restricts the flow from the large
chamber by closing the outlet of the chamber.
VTC
(Rev.2) 06/02/2003
Page 26 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 27 of 57
Pressure Measurement
Pressure-Limiting Valves
Pressure-limiting valves protect the pressure sensor from overpressure by
blocking the process fluid at a preset limit. There are several designs of
pressure-limiting valves. One common design has the fluid coming in the inlet,
passing around a piston, and out to the pressure sensor as shown in figure 21.
The piston has process pressure on the bottom and atmospheric pressure on
the top. A spring opposes the process pressure. As the pressure increases, it
exerts greater force on the piston and moves the O -ring up to seal the area
around the piston and isolate the pressure sensor. The set point is adjusted by
compressing or releasing the spring and thereby changing the force required to
move the piston.
VTC
(Rev.2) 06/02/2003
Page 28 of 57
Pressure Measurement
Relative Density
Transformer Oil
Water
Dibutyl Phthalate
Carbon Tetrachloride
Mercury
0.864
1.000
1.048
1.606
13.560
VTC
(Rev.2) 06/02/2003
Page 29 of 57
Pressure Measurement
It is essential that the U tube is of uniform bore, otherwise the readings from the
left and right scales will disagree. The applied pressure is equal to the sum of
the tow scale readings.
The range is limited otherwise the tube becomes too long and
cumbersome.
Note:
If mercury is used as the liquid in a manometer then care must be used when
reading the manometer. The meniscus of mercury is convex, by comparison
with other liquids that have a concave meniscus. The reading has to be taken
the top of the meniscus and should always be read at its centre.
Consideration should be made in to the dangers of using mercury in such a
fragile glass container and the proper precautions made available in the event
of a spillage.
VTC
(Rev.2) 06/02/2003
Page 30 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 31 of 57
Pressure Measurement
Inclined Manometer
By using an inclined manometer a greater sensitivity can be achieved. This
instrument is used for measuring very low pressures such as the draft in a
furnace, a chimney or a ventilation duct.
VTC
(Rev.2) 06/02/2003
Page 32 of 57
Pressure Measurement
Manometric Errors
Meniscus
When tube contains a liquid, the surface of the liquid is not flat, but curved this
surface is called the meniscus with mercury the meniscus is convex and with
other liquids it is concave.
When reading a manometer it should from the centre of the meniscus. This is
caused by not viewing the liquid at right angles with the scale.
Parallax
Parallax error can be minimised by viewing the manometer at right angles and
by putting the scale as close to the manometer as possible.
Pressure Gauges
A pressure gauge is a device, which senses pressure and provides a visual
representation of that pressure. Most pressure gauges have bourdon tube
VTC
(Rev.2) 06/02/2003
Page 33 of 57
Pressure Measurement
sensors. Vacuum gauges and low-range gauges often use bellows sensors.
Differential-pressure gauges can use piston or bellows sensors. The preferred
manufacturer and the required range usually dictate the sensor type.
Selection of Pressure Gauge
Pressure gauges should be selected so that the expected operating pressure is
in the centre third of the gauge range. It is also important that the highest
pressure that will ever be applied to the gauge be below the maximum reading.
Usually, the gauge shall be selected so that the gauge maximum is above the
set pressure of the system relief valve and the normal pressure is in the
readable range.
Pressure gauges are sometimes liquid filled. This is to protect the gauge dial
and movement from the atmosphere. The liquid fill also provides some
pulsation or vibration dampening. Glycerine is the most common fill liquid.
Pressure gauges lose accuracy when exposed to hot fluids. When the process
temperature is above approximately 180 F (82 C) a siphon should be
installed. If the process fluid will not condense, at ambient temperature, the
siphon can be filled with a suitable fluid such as ethylene glycol or glycerine.
Differential-pressure gauges are useful when a pressure difference that is small
compared to the static pressure needs to be measured. Differential-pressure
gauges differ from static-pressure gauges in that they have two pressure
connections. Differential gauges must be installed with an equalising valve so
that they will not be over-ranged while disconnecting.
VTC
(Rev.2) 06/02/2003
Page 34 of 57
Pressure Measurement
Gauge errors
VTC
(Rev.2) 06/02/2003
Page 35 of 57
Pressure Measurement
A gauge with a zero error will always read high or low by a constant
amount.
A gauge with a linearity error may read correctly at 0 and 100% but will not
follow a linear path between these points. This is one reason why it is not
sufficient to just check a gauge at its tow and points but to carry out a three
or five point check Checks should be made on both rising and falling
pressures.
Precautions
Tubes for gauge to be used on Acetylene must be made of steel
Gauges.
VTC
Associated fittings for use on oxygen must be kept entirely free of oil.
(Rev.2) 06/02/2003
Page 36 of 57
Pressure Measurement
Pressure Transmitters
Pressure transmitters are used when the controller, recorder, or indicator needs
to be located in a control room or panel where it is undesirable to pipe the
process fluid. They are also used when several devices are to be operated
from a single measurement or when elevated zero is required. The output is
usually 4-20, mA for electronic transmitters or 3-15 psig (20-100 kPa) for
pneumatic transmitters. Other signals can be used if required by the receiver,
but these are the most common and should be used if possible. Pneumatic
pressure transmitter shown in figure 22
Suppressed zero
Suppressed zero occurs when the base value of the measured variable is
above the atmospheric pressure. Most transmitters have this as an option.
Elevated zero is used when the pressure range of interest is to be narrowed for
accurate monitoring and control (better resolution).
Elevated zero
Elevated zero where the base value of the measured variable is below
atmospheric pressure, is sometimes available. Usually, the zero is as near to
perfect vacuum as possible and the unit is called a absolute pressure
transmitter.
The use of pneumatic transmitters is decreasing; however, a number of
manufacturers still make them for the replacement market and some new
installations are still being made. Pneumatic transmission may be
advantageous when existing equipment is pneumatic with which operating
personnel are already familiar.
Electronic transmitters with 4-20 mA outputs are the most common. Typical
electronic pressure transmitter is shown in figure 23.
Pressure transmitters are available in a variety of ranges. The ranges available
vary from one manufacturer to another. Read carefully the manufacturer's
literature before selection.
The range and the span are two different parameters. The span is the actual
pressure range to be measured after the transmitter has been adjusted. The
range is the pressure range within which the span can be adjusted.
Most transmitters have two adjustments, zero and span.
VTC
(Rev.2) 06/02/2003
Page 37 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 38 of 57
Pressure Measurement
Pneumatic DP Cell
A diaphragm that is deflected by the applied differential pressure separates the
HP and LP chambers of a DP cell.
A force bar at the top moves a flapper closer or further away from the nozzle
depending on the pressure difference between the high and low signals. This
movement results in a change in the output pressure from the transmitter that is
proportional to the applied pressure difference.
If the LP side is open to atmosphere, the cell will measure gauge pressure.
If the LP chamber is evacuated and sealed, the cell will measure absolute
pressure.
Electronic DP cells
Electronic DP cells provide a higher level of accuracy then their pneumatic
counterparts. Two sensor systems have gained popularity.
VTC
(Rev.2) 06/02/2003
Page 39 of 57
Pressure Measurement
Capacitance type
In this type of
sensor a movable
diaphragm is fixed
between
two
capacitance
plates. As the
differential pressure is applied the diaphragm will move changing the
capacitance between the plates. This change in capacitance can be used to
change the frequency of on oscillator system where by the change in frequency
is directly related to the pressure applied.
This gives excellent response, resolution, linearity, repeatability, and stability
properties to the instrument.
VTC
(Rev.2) 06/02/2003
Page 40 of 57
Pressure Measurement
(Rev.2) 06/02/2003
Page 41 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 42 of 57
Pressure Measurement
(Rev.2) 06/02/2003
Page 43 of 57
Pressure Measurement
action gradually increases the amount of the correction until the measured
pressure is returned to the set point. A more extensive discussion of control
modes and controller tuning can be found in the manual Controllers and
Control Theory.
A common option for pressure controllers is an auto/manual switch. This is a
valve, which allows the output of a manual regulator to be directed to the end
element (valve actuator) instead of the controller's automatic output. The
transfer can be either bump-less where the outputs are automatically matched
to each other when the auto/manual switch is transferred or manual balance
where the operator must match the manual regulator output to the automatic
output transfer to manual or the set point to the process variable before transfer
to automatic.
Pressure controllers are surface, panel, pipe-stand, or yoke mounted. Surfacemounted controllers are fastened to a wall or other vertical surface. Panelmounted, also called flush-mounted, controllers are mounted in a cut-out in a
control panel.
Pipe-stand mounting occurs where a vertical or horizontal pipe support is
constructed and the controller is provided with a bracket and U-bolts to attach it
to a two-inch pipe-stand. It is not a good idea to support controllers on process
piping. Yoke mounted controllers are fastened to the valve yoke with special
brackets. Yoke mounting is convenient when the valve is accessible.
Electric Pressure Switches
An electric pressure switch senses pressure and opens or closes an electrical
switch element at a set pressure to signal another electrical device. Electric
pressure switches are available in a wide variety of styles.
Most pressure switches trip at a pressure above atmospheric, and are called
gauge pressure or simply pressure switches. Switches can also be
manufactured to trip at a pressure referenced to a complete vacuum and is
called absolute pressure switches. Those set to trip below atmospheric
pressure are called vacuum switches and those, which can be set either above
or below atmospheric pressure, are called compound switches. Some switches
are manufactured so that the trip point is factory set, while others are field
adjustable.
Pressure switches are set to trip at a certain point with rising or falling pressure.
When the pressure is returned to within the acceptable range, the switch does
not reset at exactly the same point that it tripped. The difference in the trip point
and the set point is called dead band or reset or switch differential. The
electrical switch is usually single-pole, double-throw or double-pole, doublethrow. Figure 27 shows these types, as well as others less frequently used. The
number of poles determines the number of separate circuits that can be
controlled by the switch, single pole for one circuit and double-pole for two
circuits. The double-throw term means that a common terminal is connected to
either of two other terminals normally open or normally closed.
VTC
(Rev.2) 06/02/2003
Page 44 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 45 of 57
Pressure Measurement
(Rev.2) 06/02/2003
Page 46 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 47 of 57
Pressure Measurement
Operation
Process pressure is applied to the upper diaphragm chamber, causing the stem
to lower against the spring. When the upper drive collar has been dropped
sufficiently, the MICRO VALVE will snap, thereby reversing the control circuit.
As process pressure decreases, the lower drive collar will raise, contacting the
toggle arm which causes the MICRO VALVE to snap to its' "normal" position.
Adjustment
Operating adjustments are very simple on the CDM pilot. The range spring is
fixed and requires no adjustment. The process pressure required to trip and
release the MICRO VALVE will depend upon the spacing of the drive collars.
The adjustable drive collars provide a convenient means of adjusting the span
of output valve action within the operating range. Tripping pressure can be
adjusted from approximately 6 to 20 psi; with release pressure varying from
approximately 2 to 8 psi.
VTC
(Rev.2) 06/02/2003
Page 48 of 57
Pressure Measurement
PRESSURE REGULATOR
The following paragraph is a description of the operation of a pressure
regulator:
When the diaphragm is balanced both 'a' and 'b' are closed. With pressure
applied to the spring (fully unwound) 'b' is closed and 'a' is open. Any pressure
in the output leaks through the hole in the diaphragm and bleeds to
atmosphere, through the vent. When all the air from the output has been
vented to atmosphere the diaphragm is balanced and both 'a' and 'b' are
closed.
VTC
(Rev.2) 06/02/2003
Page 49 of 57
Pressure Measurement
Fisher Regulator
The spring is compressed to increase the pressure. The diaphragm and valve
are pushed down. This opens 'b' ('a' is still closed) and allows the inlet air to
pass, through the filter, to the output. As the pressure in the output builds up it
will force the diaphragm up. When the diaphragm is balanced both valves is
closed. The diaphragm is balanced when the pressure applied by the spring
(applied on top of the diaphragm) is the some as the output pressure (applied
to the bottom of the diaphragm). If the adjustment is decreased the diaphragm
moves up b closes a opens and some output bleeds to atmosphere. This
continues until the diaphragm is balanced again.
VTC
(Rev.2) 06/02/2003
Page 50 of 57
Pressure Measurement
VTC
(Rev.2) 06/02/2003
Page 51 of 57
Pressure Measurement
Process plant.
b.
c.
(Rev.2) 06/02/2003
Page 52 of 57
Pressure Measurement
a.
b.
c.
Where the process fluids are of a hazardous nature (eg toxic, flammable etc),
particular care should be taken to ensure correct venting and draining, and also
to clean or flush the instrument carefully, prior to effecting work or removal of
the hardware from site for maintenance or repair. Gas testing may be required.
On large items, e.g. control valves, a certificate of cleanness is necessary prior
to delivery to workshops.
d.
If practical, equipment must be made safe before any work is done on it.
The operation of making the equipment safe must be done by a
Competent Control Engineering Person. Care shall be taken when
working on live equipment to ensure avoidance of contact with live
electrical components (refer to Regulation No 19 Working with
Electricity).
b.
VTC
(Rev.2) 06/02/2003
Page 53 of 57
VTC
Pressure Measurement
b.
c.
Where utility fluids are piped to an instrument, the pipe work should be
drained down or vented if the instrument is removed.
d.
(Rev.2) 06/02/2003
Page 54 of 57
Pressure Measurement
REVIEW QUESTIONS
Q1.
Define pressure.
Q2.
Gauge pressure
Absolute pressure
Perfect vacuum
Q3.
Q4.
Q5.
Zero error
Range error
Angularity error
Q6.
Q7.
Q8.
Q9.
VTC
(Rev.2) 06/02/2003
Page 55 of 57
Pressure Measurement
MODEL ANSWERS
A1.
A2.
Force
Area
A3.
The main purpose for measuring pressure are: Safety and Process
control.
A4.
A5.
Zero error: Constant error over the entire scale. Requires realignment of
the pointer on its shaft.
Range error: Constant percentage error over the entire scale. Corrected
by adjustment to the shoulder screw.
Angularity error: Either widens or narrows from the scale center mark.
Corrected by adjusting the connecting link.
A6.
0 to 700 bar.
A7.
VTC
(Rev.2) 06/02/2003
Page 56 of 57
Pressure Measurement
teeth of the rack and pinion and eliminates hysteresis due to lost motion
in this region.
A8
A9.
A10. If an electric conductor is stretched so that its length increases and its
diameter decreases, a corresponding increase in the electrical
resistance results.
VTC
(Rev.2) 06/02/2003
Page 57 of 57