Contents

Page

Circuit and people protection


MCBs
Miniature circuit breakers DPE06. ..............................................................................................................................
Miniature circuit breakers DS1 and DS. .................................................................................................................
Miniature circuit breakers DH. .......................................................................................................................................
Miniature circuit breakers TDH and accessories.............................................................................................
Electrical accessories for EcoPlus and TemDin2. ..........................................................................................
Mechanical accessories for EcoPlus and TemDin2. .....................................................................................

7
8
10
12
13
14

RCDs
Residual current circuit breakers FIEP and ZFP. ............................................................................................
Residual current circuit breakers ZFP and accessories. ...........................................................................
Residual current circuit breakers ZD06 Add-on-block for DS and DH. ...........................................

15
15
16

RCBOs
Residual current circuit breakers with overcurrent protection ZDH. ..................................................
Residual current circuit breakers with overcurrent protection ZDS. ..................................................
Residual current circuit breakers with overcurrent protection FCOP. ..............................................

17
17
18

Command and control


Contactors CDO and CDR. ..............................................................................................................................................
Contactors CDI and poles spacer CNCP. .............................................................................................................
Motor operator ZFR...............................................................................................................................................................
Pushbuttons PD, PDL..........................................................................................................................................................
Switches and changeover switches WDM. ..........................................................................................................
Mains disconnect switches DDF..................................................................................................................................
Socket-outlet HD. ....................................................................................................................................................................

19
20
21
21
21
22
22

Programming and measurement


Time switches RDA, RDD. ...............................................................................................................................................
Staircase switch SDS016C..............................................................................................................................................
Pilots LD. .......................................................................................................................................................................................
Bell+buzzer+transformer TDB.......................................................................................................................................
Light sensitive switch RDA. .............................................................................................................................................
Digital measurement instruments MDD. ................................................................................................................
Active energy meter MDA.................................................................................................................................................
Analogue ammeters and voltmeters MDA. ..........................................................................................................
Current transformer TDC. .................................................................................................................................................

23
24
24
24
24
25
25
26
26

Modular protection
Safety transformers TDS...................................................................................................................................................
Disconnector fuse holders FD. ......................................................................................................................................
Surge arresters TM................................................................................................................................................................
Permanent overvoltage protection TD2YD ..........................................................................................................
Permanent overvoltage protection and Transient surge protection solutions ...........................

27
27
28
29
30

Data subject to change without notice

Miniature circuit breakers DPE06

Circuit and People Protection

Short-circuit capacity

6kA (EN 60898)

Miniature circuit breakers DPE06


Poles

EcoPlus

In
(A)

DIN
mod.

Type C
Reference

Type B
Reference

DPE06C10006

DPE06B10006

Tripping characteristic

10

DPE06C10010

DPE06B10010

C and B

16

DPE06C10016

DPE06B10016

20

DPE06C10020

DPE06B10020

25

DPE06C10025

DPE06B10025

32

DPE06C10032

DPE06B10032

40

DPE06C10040

DPE06B10040

50

DPE06C10050

DPE06B10050

63

DPE06C10063

DPE06B10063

1+N

DPE06C11006

DPE06B11006

1+N

10

DPE06C11010

DPE06B11010

1+N

16

DPE06C11016

DPE06B11016

1+N

20

DPE06C11020

DPE06B11020

1+N

25

DPE06C11025

DPE06B11025

1+N

32

DPE06C11032

DPE06B11032

1+N

40

DPE06C11040

DPE06B11040

1+N

50

DPE06C11050

DPE06B11050

1+N

63

DPE06C11063

DPE06B11063

DPE06C20006

DPE06B20006

10

DPE06C20010

DPE06B20010

16

DPE06C20016

DPE06B20016

20

DPE06C20020

DPE06B20020

25

DPE06C20025

DPE06B20025

32

DPE06C20032

DPE06B20032

40

DPE06C20040

DPE06B20040

50

DPE06C20050

DPE06B20050

63

DPE06C20063

DPE06B20063

DPE06C30006

DPE06B30006

10

DPE06C30010

DPE06B30010

16

DPE06C30016

DPE06B30016

20

DPE06C30020

DPE06B30020

25

DPE06C30025

DPE06B30025

32

DPE06C30032

DPE06B30032

40

DPE06C30040

DPE06B30040

50

DPE06C30050

DPE06B30050

63

DPE06C30063

DPE06B30063

DPE06C40006

DPE06B40006

10

DPE06C40010

DPE06B40010

16

DPE06C40016

DPE06B40016

20

DPE06C40020

DPE06B40020

25

DPE06C40025

DPE06B40025

32

DPE06C40032

DPE06B40032

40

DPE06C40040

DPE06B40040

50

DPE06C40050

DPE06B40050

63

DPE06C40063

DPE06B40063

Technical
Data
Rated voltage
Frequency
Calibration temperature
Terminal capacity
Electrical endurance
Mechanical endurance
Poles
Mounting
Standards
Accessories on page 13.

230/400V~
50/60Hz
30oC
1-25mm2
30,000
40,000
1p 1p+N 2p 3p 4p
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
EN 60898

Circuit and People Protection

Short-circuit capacity

Miniature Circuit Breakers DS 6kA


1+N in 1 module

6kA (EN 60898)

Poles

Tripping characteristic

C
Technical
Data
Rated voltage
230V~
Frequency
50/60Hz
Calibration temperature 30oC
Terminal capacity
16mm2 exible / 25mm2 rigid
Electrical endurance 30,000
Mechanical endurance 40,000
Poles
1p+N
Mounting
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards
EN 60898

In
(A)

DIN
mod.

Type
C

1+N

DS041NC006

1+N

10

DS041NC010

1+N

16

DS041NC016

1+N

20

DS041NC020

1+N

25

DS041NC025

1+N

32

DS041NC032

1+N

40

DS041NC040

Note: Terasaki recommends


the Pozidrive 2 use.

Accessories on page 13.

Short-circuit capacity

6kA (EN 60898)


Tripping characteristic

C, B and D
Technical
Data
Rated voltage
230V/400V~, 240V/415V~
Frequency
50/60Hz
Calibration temperature 30oC
Terminal capacity
35mm2
Electrical endurance
30,000
Mechanical endurance 40,000
Poles
1p 1p+N 2p 3p 3p+N 4p
Mounting
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards
EN 60898, EN 60947-2
UNE 20317
NOTE: Suitable for use at 240/415V. / Suitable for isolation.

Accessories on page 13.

Note: Terasaki recommends


the Pozidrive 2 use.

Poles

In
(A)

DIN
mod.

Type
B

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N
1+N

0.3
0.5
0.75
1
1.6
2
2.5
3
3.5
4
6
8
10
13
16
20
25
32
40
50
63
0.3
0.5
0.75
1
1.6
2
2.5
3
3.5
4
6
8
10
13
16
20
25
32
40
50
63

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

DS06C10006
DS06C10008
DS06C10010
DS06C10013
DS06C10016
DS06C10020
DS06C10025
DS06C10032
DS06C10040
DS06C10050
DS06C10063
DS06C11006
DS06C11008
DS06C11010
DS06C11013
DS06C11016
DS06C11020
DS06C11025
DS06C11032
DS06C11040
DS06C11050
DS06C11063

DS06B10006
DS06B10008
DS06B10010
DS06B10013
DS06B10016
DS06B10020
DS06B10025
DS06B10032
DS06B10040
DS06B10050
DS06B10063
DS06B11006
DS06B11008
DS06B11010
DS06B11013
DS06B11016
DS06B11020
DS06B11025
DS06B11032
DS06B11040
DS06B11050
DS06B11063

DS06D100V3
DS06D100V5
DS06D100V7
DS06D10001
DS06D101V6
DS06D10002
DS06D102V5
DS06D10003
DS06D103V5
DS06D10004
DS06D10006
DS06D10008
DS06D10010
DS06D10013
DS06D10016
DS06D10020
DS06D10025
DS06D10032
DS06D10040
DS06D10050
DS06D10063
DS06D110V3
DS06D110V5
DS06D110V7
DS06D11001
DS06D111V6
DS06D11002
DS06D112V5
DS06D11003
DS06D113V5
DS06D11004
DS06D11006
DS06D11008
DS06D11010
DS06D11013
DS06D11016
DS06D11020
DS06D11025
DS06D11032
DS06D11040
DS06D11050
DS06D11063

Circuit and People Protection

Short-circuit capacity

6kA (EN 60898)


Tripping characteristic

C, B and D
Technical
Data
Rated voltage
230V/400V~, 240V/415V~
Frequency
50/60Hz
Calibration temperature 30oC
Terminal capacity
35mm2
Electrical endurance
30,000
Mechanical endurance 40,000
Poles
1p 1p+N 2p 3p 3p+N 4p
Mounting
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards
EN 60898, EN 60947-2
UNE 20317
NOTE: Suitable for use at 240/415V. / Suitable for isolation.

Accessories on page 13.

Note: Terasaki recommends


the Pozidrive 2 use.

Miniature Circuit Breakers DS 6kA


Poles

In
(A)

DIN
mod.

Type
B

2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
3+N
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

0.3
0.5
0.75
1
1.6
2
2.5
3
3.5
4
6
8
10
13
16
20
25
32
40
50
63
0.3
0.5
0.75
1
1.6
2
2.5
3
3.5
4
6
8
10
13
16
20
25
32
40
50
63
0.3
0.5
0.75
1
1.6
2
2.5
3
3.5
4
6
8
10
13
16
20
25
32
40
50
63
0.3
0.5
0.75
1
1.6
2
2.5
3
3.5
4
6
8
10
13
16
20
25
32
40
50
63

2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

DS06C20006
DS06C20008
DS06C20010
DS06C20013
DS06C20016
DS06C20020
DS06C20025
DS06C20032
DS06C20040
DS06C20050
DS06C20063
DS06C30006
DS06C30008
DS06C30010
DS06C30013
DS06C30016
DS06C30020
DS06C30025
DS06C30032
DS06C30040
DS06C30050
DS06C30063
DS06C31006
DS06C31008
DS06C31010
DS06C31013
DS06C31016
DS06C31020
DS06C31025
DS06C31032
DS06C31040
DS06C31050
DS06C31063
DS06C40006
DS06C40008
DS06C40010
DS06C40013
DS06C40016
DS06C40020
DS06C40025
DS06C40032
DS06C40040
DS06C40050
DS06C40063

DS06B20006
DS06B20008
DS06B20010
DS06B20013
DS06B20016
DS06B20020
DS06B20025
DS06B20032
DS06B20040
DS06B20050
DS06B20063
DS06B30006
DS06B30008
DS06B30010
DS06B30013
DS06B30016
DS06B30020
DS06B30025
DS06B30032
DS06B30040
DS06B30050
DS06B30063
DS06B31006
DS06B31008
DS06B31010
DS06B31013
DS06B31016
DS06B31020
DS06B31025
DS06B31032
DS06B31040
DS06B31050
DS06B31063
DS06B40006
DS06B40008
DS06B40010
DS06B40013
DS06B40016
DS06B40020
DS06B40025
DS06B40032
DS06B40040
DS06B40050
DS06B40063

DS06D200V3
DS06D200V5
DS06D200V7
DS06D20001
DS06D201V6
DS06D20002
DS06D202V5
DS06D20003
DS06D203V5
DS06D20004
DS06D20006
DS06D20008
DS06D20010
DS06D20013
DS06D20016
DS06D20020
DS06D20025
DS06D20032
DS06D20040
DS06D20050
DS06D20063
DS06D300V3
DS06D300V5
DS06D300V7
DS06D30001
DS06D301V6
DS06D30002
DS06D302V5
DS06D30003
DS06D303V5
DS06D30004
DS06D30006
DS06D30008
DS06D30010
DS06D30013
DS06D30016
DS06D30020
DS06D30025
DS06D30032
DS06D30040
DS06D30050
DS06D30063
DS06D310V3
DS06D310V5
DS06D310V7
DS06D31001
DS06D311V6
DS06D31002
DS06D312V5
DS06D31003
DS06D313V5
DS06D31004
DS06D31006
DS06D31008
DS06D31010
DS06D31013
DS06D31016
DS06D31020
DS06D31025
DS06D31032
DS06D31040
DS06D31050
DS06D31063
DS06D400V3
DS06D400V5
DS06D400V7
DS06D40001
DS06D401V6
DS06D40002
DS06D402V5
DS06D40003
DS06D403V5
DS06D40004
DS06D40006
DS06D40008
DS06D40010
DS06D40013
DS06D40016
DS06D40020
DS06D40025
DS06D40032
DS06D40040
DS06D40050
DS06D40063

Circuit and People Protection

Miniature Circuit Breakers DH 10kA

Short-circuit capacity

10kA (EN 60898)


Tripping characteristic

C, B and D
Technical
Data
Rated voltage
230V/400V~
Frequency
50/60Hz
Calibration temperature 30oC
Terminal capacity
35 mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Poles
1p 1p+N 2p 3p 3p+N 4p
Mounting
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards
EN 60898
NOTE: Suitable for use at 240/415V.

Accessories on page 13.

Note: Terasaki recommends


the Pozidrive 2 use.

10

Poles

In
(A)

DIN
mod.

Type
B

0.3

DH06D100V3

0.5

DH06D100V5

0.75

DH06D100V7

DH06D10001

1.6

DH06D101V6

DH06D10002

2.5

DH06D102V5

DH06D10003

3.5

DH06D103V5

DH06D10004

DH06C10006

DH06B10006

DH06D10006

DH06C10008

DH06B10008

DH06D10008

10

DH06C10010

DH06B10010

DH06D10010

13

DH06C10013

DH06B10013

DH06D10013

16

DH06C10016

DH06B10016

DH06D10016

20

DH06C10020

DH06B10020

DH06D10020

25

DH06C10025

DH06B10025

DH06D10025

32

DH06C10032

DH06B10032

DH06D10032

40

DH06C10040

DH06B10040

DH06D10040

50

DH06C10050

DH06B10050

DH06D10050

63

DH06C10063

DH06B10063

DH06D10063

1+N

0.3

DH06D110V3

1+N

0.5

DH06D110V5

1+N

0.75

DH06D110V7

1+N

DH06D11001

1+N

1.6

DH06D111V6

1+N

DH06D11002

1+N

2.5

DH06D112V5

1+N

DH06D11003

1+N

3.5

DH06D113V5

1+N

DH06D11004

1+N

DH06C11006

DH06B11006

DH06D11006

1+N

DH06C11008

DH06B11008

DH06D11008

1+N

10

DH06C11010

DH06B11010

DH06D11010
DH06D11013

1+N

13

DH06C11013

DH06B11013

1+N

16

DH06C11016

DH06B11016

DH06D11016

1+N

20

DH06C11020

DH06B11020

DH06D11020

1+N

25

DH06C11025

DH06B11025

DH06D11025

1+N

32

DH06C11032

DH06B11032

DH06D11032

1+N

40

DH06C11040

DH06B11040

DH06D11040

1+N

50

DH06C11050

DH06B11050

DH06D11050

1+N

63

DH06C11063

DH06B11063

DH06D11063

0.3

DH06D200V3

0.5

DH06D200V5

0.75

DH06D200V7

DH06D20001

1.6

DH06D201V6

DH06D20002

2.5

DH06D202V5

DH06D20003

3.5

DH06D203V5

DH06D20004

DH06C20006

DH06B20006

DH06D20006

DH06C20008

DH06B20008

DH06D20008

10

DH06C20010

DH06B20010

DH06D20010

13

DH06C20013

DH06B20013

DH06D20013

16

DH06C20016

DH06B20016

DH06D20016

20

DH06C20020

DH06B20020

DH06D20020

25

DH06C20025

DH06B20025

DH06D20025

32

DH06C20032

DH06B20032

DH06D20032

40

DH06C20040

DH06B20040

DH06D20040

50

DH06C20050

DH06B20050

DH06D20050

63

DH06C20063

DH06B20063

DH06D20063

Circuit and People Protection

Short-circuit capacity

10kA (EN 60898)


Tripping characteristic

C, B and D
Technical
Data
Rated voltage
230V/400V~
Frequency
50/60Hz
Calibration temperature 30oC
Terminal capacity
35 mm2
Electrical endurance 30,000
Mechanical endurance 40,000
Poles
1p 1p+N 2p 3p 3p+N 4p
Mounting
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards
EN 60898
NOTE: Suitable for use at 240/415V.

Accessories on page 13.

Note: Terasaki recommends


the Pozidrive 2 use.

Miniature Circuit Breakers DH 10kA


Poles

In
(A)

DIN
mod.

Type
B

0.3

DH06D300V3

0.5

DH06D300V5

0.75

DH06D300V7

DH06D30001

1.6

DH06D301V6

DH06D30002

2.5

DH06D302V5

DH06D30003

3.5

DH06D303V5

DH06D30004

DH06C30006

DH06B30006

DH06D30006

DH06C30008

DH06B30008

DH06D30008

10

DH06C30010

DH06B30010

DH06D30010

13

DH06C30013

DH06B30013

DH06D30013

16

DH06C30016

DH06B30016

DH06D30016

20

DH06C30020

DH06B30020

DH06D30020

25

DH06C30025

DH06B30025

DH06D30025

32

DH06C30032

DH06B30032

DH06D30032

40

DH06C30040

DH06B30040

DH06D30040

50

DH06C30050

DH06B30050

DH06D30050

63

DH06C30063

DH06B30063

DH06D30063

3+N

0.3

DH06D310V3

3+N

0.5

DH06D310V5

3+N

0.75

DH06D310V7

3+N

DH06D31001

3+N

1.6

DH06D311V6

3+N

DH06D31002

3+N

2.5

DH06D312V5

3+N

DH06D31003

3+N

3.5

DH06D313V5

3+N

DH06D31004

3+N

DH06C31006

DH06B31006

DH06D31006

3+N

DH06C31008

DH06B31008

DH06D31008

3+N

10

DH06C31010

DH06B31010

DH06D31010

3+N

13

DH06C31013

DH06B31013

DH06D31013

3+N

16

DH06C31016

DH06B31016

DH06D31016

3+N

20

DH06C31020

DH06B31020

DH06D31020

3+N

25

DH06C31025

DH06B31025

DH06D31025

3+N

32

DH06C31032

DH06B31032

DH06D31032

3+N

40

DH06C31040

DH06B31040

DH06D31040

3+N

50

DH06C31050

DH06B31050

DH06D31050

3+N

63

DH06C31063

DH06B31063

DH06D31063

0.3

DH06D400V3

0.5

DH06D400V5

0.75

DH06D400V7

DH06D40001

1.6

DH06D401V6

DH06D40002

2.5

DH06D402V5

DH06D40003

3.5

DH06D403V5

DH06D40004

DH06C40006

DH06B40006

DH06D40006

DH06C40008

DH06B40008

DH06D40008

10

DH06C40010

DH06B40010

DH06D40010

13

DH06C40013

DH06B40013

DH06D40013

16

DH06C40016

DH06B40016

DH06D40016

20

DH06C40020

DH06B40020

DH06D40020

25

DH06C40025

DH06B40025

DH06D40025

32

DH06C40032

DH06B40032

DH06D40032

40

DH06C40040

DH06B40040

DH06D40040

50

DH06C40050

DH06B40050

DH06D40050

63

DH06C40063

DH06B40063

DH06D40063

11

Circuit and People Protection

Short-circuit capacity

10kA (EN 60947-2)


Technical
Data
Rated voltage
240V/415V~
Frequency
50/60Hz
Rated insulation voltage 500V~
Calibration temperature 30oC
Terminal capacity
max. 35mm2 exible conductor
max. 50mm2 rigid cable
Electrical endurance
10,000
Mechanical endurance 10,000
Poles
1p
2p
3p 4p
Mounting
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
Standards
UNE-EN 60898 and IEC 947-2: 10kA
Suitable for isolation

Miniature Circuit Breakers TDH 10kA


80, 100 and 125A
Miniature Circuit Breakers TDH
Tripping curves
The TDH series of Miniature Circuit Breakers are manufactured in
accordance with EN 60947-2.
- Curve C: magnetic trip threshold = 5 - 10 In
- Curve D: magnetic trip threshold = 10 - 20 In

Poles

In
(A)

DIN
mod.

Trip
D

80A

1.5

TDHC1080

TDHD1080

100A

1.5

TDHC1100

TDHD1100

125A

1.5

TDHC1125

TDHD1125

80A

TDHC2080

TDHD2080

100A

TDHC2100

TDHD2100

125A

TDHC2125

TDHD2125

80A

4.5

TDHC3080

TDHD3080

100A

4.5

TDHC3100

TDHD3100

125A

4.5

TDHC3125

TDHD3125

80A

TDHC4080

TDHD4080

100A

TDHC4100

TDHD4100

125A

TDHC4125

TDHD4125

Note: Terasaki recommends


the Pozidrive 2 use.

Accessories for TDH series


Alarm or auxiliary contact
1/2 module device for monitoring the status of TDH breakers
(open/closed), or trip condition on overload operation.
DIN mod.
Max. rated current:
Terminal capacity

6A-230V~
0.5 to 4 exible cable
1 to 6 rigid cable.

DIN
mod.

Description

Reference

1/2

1NO + 1NC

TDHAUX

1/2

1NO + 1NC

TDHAL

Can be coupled on the left side of MCB TDH (80, 100, 125A).

Shunt trip (SHT) and Undervoltage release (UVT)


Shunt trip allowing remote opening of the circuit via a push button or
similiar device. Undervoltage release enables the
automatic trip of the MCB if the supply voltage
drops below 35~70% of Ue.
DIN mod.
Terminal capacity

1
0.5 to 4 exible cable
1 to 6 rigid cable.

Can be coupled on the left side.

DIN
mod.

Description

Reference

230V~

TDHSHT230

230V~

TDHUVT230

RCD add-on block


Types adjustable in time an sensitivity.
Sensitivities
Type
DIN modules width
Terminal capacity

30, 300, 500 and 1000mA


AC
6
max. 35mm2 exible cable
max. 50mm2 rigid cable
Right side add-on TDH (80, 100, 125A)

Poles

Sensitivity
(mA)

Timer
(ms)

Reference

30

Instantaneous

ZD1252030AC

Adjustable
300-500-1000
30
300
Adjustable
300-500-1000

Adjustable
0-60-150
Instantaneous
Instantaneous
Adjustable
0-60-150

2
4
4
4

12

ZD1252000AC
ZD1254030AC
ZD1254300AC
ZD1254000AC

Electrical accessories for EcoPlus and TemDin2

Circuit and People Protection

Accessories for EcoPlus DPE series

Technical
Data

EcoPlus

Auxiliary contact
Auxiliary contact DPEAUX1
1/2 DIN module width
Double contact NO+NC signal
Terminal capacity
1-4mm2
Mounting
left side

Shunt trip DPESHT


1 DIN module width
Terminal capacity
Mounting

DIN
mod.

Description

Reference

1/2

Double aux contact NO+NC

DPEAUX1

EcoPlus

Shunt trip
DIN
mod.
1
1

1-25mm2
right side

Description

Reference

Shunt trip 230Vac


Shunt trip 48Vdc

DPESHT230
DPESHT48

Accessories for TemDin2 DS and DH series


Mounted on to the left side of the MCB.

Rated voltage
Rated current
Frequency
Calibration temperature
Performance
AC14
Ue
Ie
AC15
Ue
Ie
Terminal capacity
Electrical endurance
Mechanical endurance
Standards EN62019
EN60947-5-1

Two change over contacts that include both funtions described below:
AUX - Auxiliary contact: for monitoring the status of the protective
device (open/closed).

230V/400V~
6A
50/60Hz
30oC

AL - Signal or auxiliary contact: for signalling the automatic tripping


of the protective devices (overload or short-circuit for MCBs).

YD alarm or auxiliary contact


230V
8A
230V
5A
2.5 mm2
30,000
40,000

400V
5A
400V
3A

DIN
mod.
1
1
1
1
1
1

Description

Reference

Contact Aux/Al changeover


Contact Aux/AI NO
Contact Aux/AI NC
Contact Aux changeover
Contact Aux NO
Contact Aux NC

YDA40
YDA10
YDA01
YDX40
YDX10
YDX01

YDS shunt trip


YDS shunt trip allowing remote opening of the circuit via a
pushbutton or other control device.
Type

Frequency
Calibration temperature
Rated voltage
Terminal capacity
Standards

Shunt trip YDS


50/60Hz
30oC
Operating voltage
70-110% Ue
2.5mm2
EN60947-1

Undervoltage release YDU


Frequency
50/60Hz
Calibration temperature
30oC
Performance
Tripping voltage 0.55Ue(+/-10%)
Resetting voltage >=0.55Ue(+/-10%)
Tripping time adjustable 0-300mseg
Terminal capacity
2.5mm2
Standards
EN 60947-1

YDS04
YDS01

YDS40
YDS10

Rated voltage
12Vac
24Vac
48Vac
12Vdc
24Vdc
48Vdc
110Vac
230Vac
414Vac
110Vdc
230Vdc
250Vdc

Tripping current (A)


2
2.4
6.6
2.2
3
7
0.4
0.7
1.2
0.4
0.8
0.8

YDU undervoltage release


YDU undervoltage release enables the automatic trip of the MCB or
RCBO if the supply voltage drops below 45~65% of Ue.
Type
YDU02
YDU04
YDU23

Rated voltage
24Vac
24Vdc
48Vac
48Vdc
230Vac
230Vdc

Consumption at the Rated voltage (mA)


23
25
14
19
5
6

YDO overvoltage release


DIN
mod.

Single phase overvoltage release with protection


against permanent overvoltage for MCB tripping.
For surge protection use, please refer to page 29.

Description
Overvoltage release with protection against
phase-N 230Vac permanent overvoltage,
tripping voltage 276Vac.

Reference

YDO276

13

Mechanical accessories for EcoPlus and TemDin2

Circuit and People Protection

Technical
Data

EcoPlus

YDK padlocking device


Description

This device allows the breaker to be padlocked either


in open or close positions, and also allows the MCB
trip being in close position.

Padlocking device

Material busbars
Material of insulation
Cross-section of busbars

YDKS

Rotary handle ODR

Rotary handle, external, lockable and depth


adjustable. Not necessary to cut the shaft.
Easy and fast mounting on the MCB front side, by
a clic, tools not needed.

Standards

Reference

Description

Reference

Rotary handle

ODR1

DE 0660 part 500


DIN EN 60439-1; 1994
E-CU-F25
PC/ABS-Blend
UL 94-VO
10, 12, 16 and 20mm2

Maximum operating voltage


500V
Nominal voltage
415V
Surge voltage
4kV
Short-circuit strength
25kA
Climate stability
DIN 40046 IEC 68-2
Group of insulation
VDE0110, part 1; 4/1997 (IEC 664)
- overvoltage category
III
- degree of soiling
2

Insulated busbar
Poles
12
57
6x2
28x2
4x3
4x3
19x3
3x4
14x4
27x2
1

Reference

Description
Fork/Pin type busbar 1p 210mm
Fork/Pin type busbar 1p 1000mm
Fork/Pin type busbar 2p 210mm
Fork/Pin type busbar 2p 1000mm
Fork/Pin type busbar 3p 210mm
Fork/Pin type busbar 3p 210mm
Fork/Pin type busbar 3p 1000mm
Fork/Pin type busbar 4p 210mm
Fork/Pin type busbar 4p 1000mm
Fork/Pin type busbar 3p phase/N 1000mm
Fork/Pin type terminal
Protection cover pin/fork (5 units)
End cap busbar 2p/10
End cap busbar 3p/10
End cap busbar 2p and 3p/16
End cap busbar 4p/16

Fork type
s=12mm2
s=20mm2
s=10mm2
s=16mm2
s=10mm2
s=16mm2
s=16mm2
s=16mm2
s=16mm2
s=16mm2
s=25mm2

Pin type
s=10mm2
s=16mm2
s=10mm2
s=16mm2
s=10mm2
s=16mm2
s=16mm2
s=16mm2
s=16mm2
s=16mm2
s=25mm2

G1L21012
G1L100020
G2L21010
G2L100016
G3L21010
G3L21016
G3L100016
G4L21016
G4L100016
GRSTN100016
AS25GN
CTPH5
EKC2
EKC3
EKC23
EKC4

Current carrying capacity

1 pole

2, 3, 4 poles

Feed-in from the end


cross section mm2

10

12

16

20

10

16

max. current
IS/phase (A)

63

65

80

90

63

80

100

110

130

150

100

130

Feed-in from
the middle
max. current
IS/phase (A)
max. feed-in current
IE/phase

14

Depends on the cross section for connection

If you feed-in from the middle you have to observe that the sum of the outgoings in not higher than the max. current of the
busbars Is/phase.

S1L21010
S1L100016
S2L21010
S2L100016
S3L21010
S3L21016
S3L100016
S4L21016
S4L100016
SL123N100016
AS25SN
CTPH5
EKC2
EKC3
EKC23
EKC4

Residual Current Circuit Breakers FIEP and ZFP

Circuit and People Protection

Type AC
Protection against sinusoidal leakage current.
Applied in domestic and commercial installations.
Type A
Protection against sinusoidal and recti ed leakage currents with or without a DC component.
Applied in commercial and industrial installations.
Type Ai
High Immunity
Earth leakage range designed to avoid nuisance tripping caused by high frequency currents, capacitive
currents, overvoltages and transient currents. Developed to ensure the appropriate protection in electronic
equipment, computers, inverters, electronic lightning and converters.

Type

RCCBs FIEP

AC
Sensitivity

30mA

Poles

In
(A)

DIN
mod.

Sensitivity
(mA)

Reference

2
2

25
40

2
2

30
30

FIEP252003
FIEP402003

Type

Reference
ZFP162001AC

Technical
Data
Rated voltage
Frequency
Tripping time
Terminal capacity

230V~
50/60Hz
< 30ms
35mm2

Standards

EN 61008

Type

AC, A, A-Selective and Ai


Sensitivity

10, 30, 100 and 300mA


Technical
Data
Rated voltage
Frequency
Types
Standard
Terminal capacity

2 poles
230V/265V~
50/60Hz
AC
A
A-S
S
EN 61008
Flexible cable conductor 35 mm2
and rigid cable 50 mm2, with a
degree of protection of IP20
Tripping time
< 30ms
Nuisance tripping resistance
Type AC, A - 250A 8/20 s
Type A-S - 3000A 8/20 s
0.5 s -100kHz-200A
Type Ai - 3000A 8/20 s
Type Ai-S - 5000A 8/20 s
0.5 s -100kHz-200A

RCCBs ZFP 2P
No.
poles

In
(A)

No. Mod.
DIN

Sensitivity
(mA)

16

10

AC

25

30

AC

ZFP252003AC

40

30

AC

ZFP402003AC

63

30

AC

ZFP632003AC

80

30

AC

ZFP802003AC

100

30

AC

ZFP1002003AC

25

100

AC

ZFP25201AC

40

100

AC

ZFP40201AC

63

100

AC

ZFP63201AC

25

300

AC

ZFP25203AC

40

300

AC

ZFP40203AC

63

300

AC

ZFP63203AC

80

300

AC

ZFP80203AC

100

300

AC

ZFP100203AC

25

30

ZFP252003A

40

30

ZFP402003A

63

30

ZFP632003A

80

30

ZFP802003A

100

30

ZFP1002003A

25

300

ZFP25203A

40

300

ZFP40203A

63

300

ZFP63203A

80

300

ZFP80203A

100

300

ZFP100203A

40

300

A-S

ZFP40203AS

63

300

A-S

ZFP63203AS

40

30

Ai

ZFP402003AI

63

30

Ai

ZFP632003AI

40

300

Ai-S

ZFP40203SAI

63

300

Ai-S

ZFP63203SAI

15

Circuit and People Protection

Type

AC, A and A-Selective, Ai

Residual Current Circuit Breakers ZFP and ZD06


RCCBs ZFP 4P
No.
poles

In
(A)

No. Mod.
DIN

Sensitivity
(mA)

Type

Reference

25

30

AC

ZFP254003AC

Sensitivity

40

30

AC

ZFP404003AC

10, 30, 100, 300 and 500mA

63

30

AC

ZFP634003AC

80

30

AC

ZFP804003AC

100

30

AC

ZFP1004003AC

25

100

AC

ZFP25401AC

40

100

AC

ZFP40401AC

63

100

AC

ZFP63401AC

100

100

AC

ZFP100401AC

25

300

AC

ZFP25403AC

40

300

AC

ZFP40403AC

63

300

AC

ZFP63403AC

80

300

AC

ZFP80403AC

100

300

AC

ZFP100403AC

63

500

AC

ZFP63405AC

25

30

ZFP254003A

40

30

ZFP404003A

63

30

ZFP634003A

80

30

ZFP804003A

100

30

ZFP1004003A

25

300

ZFP25403A

40

300

ZFP40403A

63

300

ZFP63403A

80

300

ZFP80403A

100

300

ZFP100403A

40

300

A-S

ZFP40403AS

63

300

A-S

ZFP63403AS

40

30

Ai

ZFP404003AI

63

30

Ai

ZFP634003AI

40

300

Ai-S

ZFP40403SAI

63

300

Ai-S

ZFP63403SAI

Technical
Data
Rated voltage
Frequency
Types
Standard
Terminal capacity

4 poles
400V/455V~
50/60Hz
AC
A
A-S
S
EN 61008
Flexible cable conductor 35 mm2
and rigid cable 50 mm2, with a
degree of protection of IP20
Tripping time
< 30ms
Nuisance tripping resistance
Type AC, A - 250A 8/20 s
Type A-S - 3000A 8/20 s
0.5 s -100kHz-200A
Type Ai - 3000A 8/20 s
Type Ai-S - 5000A 8/20 s
0.5 s -100kHz-200A

Auxiliary contacts

DIN module
Terminal capacity

1/2
Flexible and rigid cable 2.5mm2

Rated current voltage 5A-240V~


Mounted on to the right side of ZFP RCCBs and FCOP RCBOs

Type

AC
Sensitivity

30 and 300mA
Technical
Data
Frequency
50/60Hz
2 and 3 DIN module width
Terminal capacity
25mm2 exible
35mm2 rigid
Standards
EN 61009

16

No. Mod.
DIN

Description

1/2
1/2

Changeover Aux
Changeover Aux/Al

Referencia
AUXZF1
AUXZF2

AUXZF1: Provides the status of the protection device, OPEN-CLOSED (H)


AUXZF2: This auxiliary can operate as an auxiliary contact (function H) or a signal
contact (function S). The user can change the function at the moment of installation.

ZD06 RCD Add-on block


In
(A)

Poles

Sensitivity
(mA)

40

30

ZD06402003AC

40

300

ZD0640203AC

40

30

ZD06404003AC

40

300

ZD0640403AC

Reference

Instantaneous. Mounted on to the right side of DS and DH MCBs.

Residual Current Circuit Breakers with


Overcurrent Protection ZDH and ZDS

Circuit and People Protection

Short-circuit capacity

10kA
Tripping characteristic

C and B
Type

AC and A

ZDH RCBO (single module RCBO + neutral tail)


In
(A)

DIN
mod.

Sensitivity
mA

Type

30

10

16

20
25

Trip curve
C

AC

ZDH41P06C003AC

ZDH41P06B003AC

30

AC

ZDH41P10C003AC

ZDH41P10B003AC

30

AC

ZDH41P16C003AC

ZDH41P16B003AC

30

AC

ZDH41P20C003AC

ZDH41P20B003AC

30

AC

ZDH41P25C003AC

ZDH41P25B003AC

32

30

AC

ZDH41P32C003AC

ZDH41P32B003AC

40

30

AC

ZDH41P40C003AC

ZDH41P40B003AC

Sensitivity

30

ZDH41P06C003A

ZDH41P06B003A

30mA

10

30

ZDH41P10C003A

ZDH41P10B003A

16

30

ZDH41P16C003A

ZDH41P16B003A

20

30

ZDH41P20C003A

ZDH41P20B003A

25

30

ZDH41P25C003A

ZDH41P25B003A

32

30

ZDH41P32C003A

ZDH41P32B003A

40

30

ZDH41P40C003A

ZDH41P40B003A

Technical
Data
Rated voltage
230V/240V~
Frequency
50/60Hz
Calibration temperature
30oC
Tripping curve
C and B
Sensitivity
30mA
Type
AC and A
Terminal capacity
16mm2 exible / 25mm2 rigid
Standards
EN 61009

Short-circuit capacity

6kA
Tripping characteristic

ZDS RCBO
Poles

In
(A)

DIN
mod.

Sensitivity
mA

Type

1+N

30

AC

ZDS0462003AC

1+N

10

30

AC

ZDS04102003AC

1+N

16

30

AC

ZDS04162003AC

Reference

1+N

20

30

AC

ZDS04202003AC

Type

1+N

25

30

AC

ZDS04252003AC

AC

1+N

32

30

AC

ZDS04322003AC

1+N

40

30

AC

ZDS04402003AC

Sensitivity

1+N

300

AC

ZDS046203AC

30 and 300mA

1+N

10

300

AC

ZDS0410203AC

1+N

16

300

AC

ZDS0416203AC

1+N

20

300

AC

ZDS0420203AC

1+N

25

300

AC

ZDS0425203AC

1+N

32

300

AC

ZDS0432203AC

1+N

40

300

AC

ZDS0440203AC

Technical
Data
Rated voltage
230/240V~
Frequency
50/60Hz
Calibration temperature
30oC
Tripping curve
C
Sensitivity
30 and 300 mA
Type
AC and A
Terminal capacity
25mm2 exible / 35mm2 rigid
Electrical endurance 20,000
Mechanical endurance 20,000
Standards
EN 61009

Note: Terasaki recommends


the Pozidrive 2 use.

Accessories on page 13.

17

Residual Current Circuit Breakers with


Overcurrent Protection FCOP

Circuit and People Protection

Short-circuit capacity

6kA
Tripping characteristic

C and B
Sensitivity

30, 300mA

In
(A)

DIN
mod.

(mA)

30

10

16

20

Curve

Reference
Type A

Type AC

FCOPC6003A

FCOPC6003AC

30

FCOPC10003A

FCOPC10003AC

30

FCOPC16003A

FCOPC16003AC

30

FCOPC20003A

FCOPC20003AC

25

30

FCOPC25003A

FCOPC25003AC

32

30

FCOPC32003A

FCOPC32003AC

40

30

FCOPC40003A

FCOPC40003AC

300

FCOPC603A

FCOPC603AC

10

300

FCOPC1003A

FCOPC1003AC

16

300

FCOPC1603A

FCOPC1603AC

Type

20

300

FCOPC2003A

FCOPC2003AC

AC, A

25

300

FCOPC2503A

FCOPC2503AC

32

300

FCOPC3203A

FCOPC3203AC

40

300

FCOPC4003A

FCOPC4003AC

30

FCOPB6003A

FCOPB6003AC

10

30

FCOPB10003A

FCOPB10003AC

16

30

FCOPB16003A

FCOPB16003AC

20

30

FCOPB20003A

FCOPB20003AC

25

30

FCOPB25003A

FCOPB25003AC

32

30

FCOPB32003A

FCOPB32003AC

40

30

FCOPB40003A

FCOPB40003AC

300

FCOPB603A

FCOPB603AC

10

300

FCOPB1003A

FCOPB1003AC

16

300

FCOPB1603A

FCOPB1603AC

20

300

FCOPB2003A

FCOPB2003AC

25

300

FCOPB2503A

FCOPB2503AC

32

300

FCOPB3203A

FCOPB3203AC

40

300

FCOPB4003A

FCOPB4003AC

Technical
Data
Rated voltage
230/240V~
Frequency
50/60Hz
Calibration temperature
30oC
Tripping curve
C and B
Sensitivity
30, 300mA
Type
AC, A
Terminal capacity
25mm2 exible / 35mm2 rigid
Electrical endurance 20,000
Standards
EN 61009

Technical
Data
DIN module
1/2
Terminal capacity
Flexible and rigid cable 2.5mm2
Rated current voltage 5A-240V~
Mounted on to the right side of ZFP RCCBs and FCOP RCBOs

Technical
Data
DIN module
1
Terminal capacity
Flexible and rigid cable 2.5mm2
Mounted on to the right side of FCOP RCBO

18

FCOP RCBO

Auxiliary contacts
No. Mod.
DIN

Description

1/2
1/2

Changeover Aux
Changeover Aux/Al

Referencia
AUXZF1
AUXZF2

AUXZF1: Provides the status of the protection device, OPEN-CLOSED (H)


AUXZF2: This auxiliary can act as an auxiliary contact (function H) or a signal contact
(function S). The user can change the function at the moment of installation.

Shunt trip (SHT) and Undervoltage trip (UVT)


No. Mod.
DIN

Rated
voltage

Reference

230V~

SHTZF230

230V~

UVTZF230

Contactors CDO and CDR

Command and Control

Technical
Data
Rated current AC1
Rated voltage
Frequency
Min/max.ambient T at
installation point

25A
250V
50/60Hz

32A

Used for the remote switching of circuits up to 32A, with double recti ed coil,
ensuring silent operation whilst increasing electrical endurance. Visual indication
of the contactor switch position via front indication. Sealable clamping terminal with
captive screw.
Main contact and auxiliary contact blocks can be clipped on to the left-hand side of
the contactor without any necessary tooling, in the following combination:
Auxiliary contact block + Main contact block + Contactor

Contactor with manual operation

-20/45oC

Terminal capacity
1.5mm2 min. / 10mm2 max.
Coil specifications
- Command voltage
230V~
- Supply voltage range %Un
85-110%
- Consumption AC (VA)
Coil power loss
4
4.5
Pick up power
4
4.5
- Maximum coil holding voltage time
unlimited
Standards
EN 60947-4-1

In

DIN

No.

(A)

mod.

contacts

25 250V~
32 250V~

1
1

2 NO
2 NO

Reference
CDO20325
CDO20332

STOP - Contacts permanently open


AUTO - Normal operation
PERM. - Contacts permanently closed

Combination table
Contactor
1 Pole

2 Poles

Main contact
block CDC
2 Poles

1
1
-

1
1

1
1

Total No.
of
poles

DIN
mod.
CDO or CDR+CDC

Aux. contact
block CDA
(max)

1
2
3
4

1
1
2
2

2
2
1
1

Contactor without manual operation

25
32
25
32

In

DIN

No.

(A)

mod.

contacts

1
1
1
1

1 NO
1 NO
2 NO
2 NO

250V~
250V~
250V~
250V~

Reference
CDR10325
CDR10332
CDR20325
CDR20332

CDC main contact block


CDC main contact blocks are 2 pole and rated at 25 or 32A. If you t a CDC block
with a CDR or CDO 1pole contactor, you get a 3 poles contactor and if you use a 2
poles CDR or CDO contactor you get a 4 poles contactor. The CDC block is clipped
on the left side of the contactor, without need of any screw or additional wiring.

Technical
Data
Rated current AC1
25/32A
Rated voltage
400V~
Frequency
50/60Hz
Min/max.ambient T at installation point -20/45oC
Terminal capacity
1.5mm2 min. / 10mm2 max.
Standards
EN 60947-4-1

In

DIN

No.

(A)

mod.

contacts

25 400V~

2 NO

CDC2520

32 400V~

2 NO

CDC3220

Reference

CDA auxiliary contact block


CDA module auxiliary blocks allow additional contacts for signalling and
synchronisation with other devices. Auxiliary contact blocks can be tted to
CDR, CDO contactors and ID impulse relays without any necessary tools. A
maximum of 2 blocks can be tted to the contactor depending on the type and
number of main contact blocks.

Technical
Data
Rated current AC1
Rated voltage
Frequency
Min/max.ambient T at installation point
Terminal capacity
Standards

5A
250V~
50/60Hz
-20/45oC
6mm2 max.
EN 60669-2-2

In

DIN

No.

(A)

mod.

contacts

5 250V~

1/2

1NO+1NC

Reference
CDA0520

19

Contactors CDI
Poles spacer CNCP

Command and Control

Technical
Data
Rated current AC1
20A
25A
40A
63A
Rated voltage
230 V
400 V
Frequency
50 / 60 Hz
Min/max.ambient T at installation point
-20 / 45oC
Terminal capacity
1.5/10 mm2 max.
2.5/25mm2 max.
Coil specifications
- Command voltage
24, 220/240 V
- Supply voltage range % Un
85-110%
- Consumption AC (VA)
Holding
2.2-4.2
4-6
6-8
Inrush
7-9
14-18
33-45
- Fuse protection
35A
63A
80A
Standards
IEC 947-4-1, EN 60947-4-1, VDE 0660,
IEC 947-5-1, EN 60947-5-1

Used in commercial and industrial applications for loads up to 20A and between
63A, with visual indication of contactor position. Sealable clamping terminals with
captive screws.
4 poles
contactor

Total No.
of poles

DIN mod.
CDI+CDI

Block CDI
(max)

2 or 3 + 1/2

CDI Contactor with coil at 24Vac

20
25
40
63

In

DIN

(A)

mod.

230V~
400V~
400V~
400V~

Contacts

Reference

2 NA
4 NA
4 NA
4 NA

CDI22024
CDI42524
CDI44024
CDI46324

1
2
3
3

CDI Contactor with coil at 230Vac

20
20
25
40
63

In

DIN

(A)

mod.

230V~
230V~
400V~
400V~
400V~

Contacts

Reference

1 NA
2 NA
4 NA
4 NA
4 NA

CDI10620
CDI20620
CDI40625
CDI40640
CDI40663

1
1
2
3
3

Auxiliary contact block


Technical
Data
Rated current AC1
3A
Rated voltage
230V~
Frequency
50/60Hz
Min/max.ambient T at installation point -20/45oC
Terminal capacity
2.5mm2 max.
Standards
IEC 947-4-1, EN 60947-4-1, VDE 0660,
IEC 947-5-1, EN 60947-5-1

CDI module auxiliary blocks allow additional contacts for signalling and
synchronisation with other devices. Auxiliary contact blocks can be tted to CDI
contactors without any necessary tools.

In

DIN

(A)

mod.

3A 230V~

1/2

Contacts

Referencia

1NO+1NC

CDI0620

CNP spacer module


CNP spacers can be tted on either side of the TemDin2 device and allow the safe
dissipation of heat when several devices are mounted side by side
on the same rail.

20

DIN
mod.

Description

Reference

1/2

Spacer

CNCP

Command and Control

RCD with
motor operator
Type

AC
Sensitivity

10, 30 and 300mA


Technical
Data
Poles
Dimensions
Operating voltage
Connection times

2, 4 poles
ZFR 2 poles: 5 modules
ZFR 4 poles: 7 modules
230/240V - 50/60Hz
10, 20, 30, 60, 120, 600sec.

Motor operator ZFR, Pushbuttons PD and PDL


Switches and Changeover switches WDM
Motor operator ZFR
The Motor operator ZFR allows the coupled RCCB automatic
self-reclosing, in case of tripping. 6 reset operations are made,
in the event that the leakage persists, before the earth leakage
protector stops. Dry contact included (remote signal).
Poles

In
(A)

Sensitivity
(mA)

Type

Reference

2
2
2
2
2
2

16
25
40
63
80
100

10
30
30
30
30
30

AC
AC
AC
AC
AC
AC

ZFR162001AC
ZFR252003AC
ZFR402003AC
ZFR632003AC
ZFR802003AC
ZFR1002003AC

2
2
2
2
2

25
40
63
80
100

300
300
300
300
300

AC
AC
AC
AC
AC

ZFR25203AC
ZFR40203AC
ZFR63203AC
ZFR80203AC
ZFR100203AC

4
4
4

25
40
63

30
30
30

AC
AC
AC

ZFR254003AC
ZFR404003AC
ZFR634003AC

4
4
4
4
4

25
40
63
80
100

300
300
300
300
300

AC
AC
AC
AC
AC

ZFR25403AC
ZFR40403AC
ZFR63403AC
ZFR80403AC
ZFR100403AC

Motor operator for A and Ai types, please contact Terasaki.

Technical
Data

PD & PDL pushbuttons


PD pushbutton
Description

Rated current AC12


25A
Rated voltage
230V
Frequency
50/60Hz
Terminal capacity
1mm2 min. / 10mm2 max.
Insulation voltage
250V
Inpulse withstand test voltage
4KV
Standards
EN 60669-1 / EN 60947-5-1

Pushbutton
Pushbutton
Pushbutton
Pushbutton
Double pushbutton
Double pushbutton

Contacts

DIN
mod.

Reference

1NO

PD11A

1NC
2NO
1NO/NC
2NO
1NO + 1NC

1
1
1
1
1

PD11B
PD12A
PD12C
PD22A
PD22C

PDL pushbutton with neon signal lamp


Description
Pushbutton+ Pilot neon green 230V
Pushbutton+ Pilot neon red 230V
Pushbutton+ Pilot neon white 230V
Pushbutton+ Pilot neon green 230V
Pushbutton+ Pilot neon red 230V
Pushbutton+ Pilot neon white 230V

Technical
Data

DIN
mod.

Reference

1NO
1NO
1NO
1NC
1NC
1NC

1
1
1
1
1
1

PDL11AG
PDL11AR
PDL11AW
PDL11BG
PDL11BR
PDL11BW

WDM switches and changeover switches


Description

Rated current AC12


25A
Rated voltage
230/400V
Frequency
50/60Hz
Terminal capacity
1mm2 min. / 10mm2 max.
Insulation voltage
400V
Inpulse withstand test voltage
4KV
Standards
EN 60669-1

Contacts

Contacts

Switch 1 pole
1NO
Switch 2 pole
2NO
Switch 3 pole
3NO
Switch 4 pole
4NO
Changeover 1-2 1 pole
Changeover 1-2 2 pole
Changeover with zero position 1-0-2 1 pole
Changeover with zero position 1-0-2 2 pole

DIN
mod.

Reference

1
1
1
1
1
1
1
1

WDM11A
WDM12A
WDM13A
WDM14A
WDM21C
WDM22C
WDM31C
WDM32C

21

Mains Disconnect Switches DDF


Socket-outlet HD

Command and Control

DDF mains disconnect switches

Technical
Data
Rated voltage
Frequency
Insulation voltage
DDF32A
Rated current In
32A
Rated making and breaking capacity
Short-circuit capacity Icm
Category
Temperature
Terminal capacity
Mounting
Standards

230V/400V~
50/60Hz
660V~
DDF63A
63A
3Ie
700A
AC-22
30oC

Nominal current ratings from 32 to 100A


Mains disconnect switches allow switching and isolation
of main circuits. They must be used in conjunction with a
protective device, i.e. a fuse or MCB, enabling protection
against overload or
short circuit conditions.

DDF100A
100A

35 mm2
35mm symmetrical DIN rail
(EN 50022-DIN 46277)
EN 60947-3

Accessories on page 13. Suitable aux. contact only.

Poles

In
(A)

DIN
mod.

Reference

32A

DDF1010032

63A

DDF1010063

100A

DDF1010100

32A

DDF1020032

63A

DDF1020063

100A

DDF1020100

32A

DDF1030032

63A

DDF1030063

100A

DDF1030100

32A

DDF1040032

63A

DDF1040063

100A

DDF1040100

Note: Terasaki recommends


the Pozidrive 2 use.

Socket-outlet HD
Technical
Data
Rated voltage:
250V
Rated current In:
16A
No. of poles:
2P+ TTL
(side earth leakage degree of protection)
Terminal capacity:
6mm2
Degree of protection:
IP20
Temperature:
-20...+55oC
Screws:
Pozidrive 2
Terminal capacity
min:
1x1mm2
max:
Mounting:
Standards:

22

1x6mm2 or 2x2.5mm2
35mm symmetrical DIN rail
IEC 60884-1
BS EN C61112-1
NF C61-303 (86)

In

Operating

DIN

(A)

voltage (Ue)

mod.

16

250V

Reference
HD16A

Programming and measurement

RDA24 analogue timer (daily)

Technical
Data
Rated voltage
230V
Frequency
50/60Hz
Max. Switched current rating
16(3)A/250V~
Minimum ON/OFF setting
30 minutes
Consumption
1.5 W
Time accuracy
+/- 5 min/year
Temperature range
-10/50oC
Ingress protection degree
- without clamps-cover
IP20
- with clamps-cover
IP30
- panel mounting
IP40
Terminal capacity
1.5mm2 min. / 2.5mm2 max.

Analogue time switches allow the pre-programmed switching


of electrical circuits from user de ned settings. Programming
is made through manual adjustment of the timers slide tappet.
Modular casing for din or wall mounted applications.
Manual ON/OFF

Description

DIN
mod.

Reference

2
2

RDA24
RDA24R

Analogue Time switch 24h


Analogue Time switch 24h reserve time

RDD07 single module digital timer (weekly)

Technical
Data
Rated voltage
230V
Frequency
50/60Hz
Max. Switched current rating
16(3)A/250V~
Minimum ON/OFF setting
15 minutes
Precision
+/- 0.5 sec/day
Quartz frequency
32.768Hz
Operating temperature
0/50oC
Storing temperature
-10/50oC
Battery reserve (for date and hour) 15 days
Recharge time to needed save data 72 hours
Pretection degree
IP40
Terminal capacity
1mm2 min. / 2.5mm2 max.

Digital timers allow the pre programmed switching of electric


circuits through a weekly time programme. The LCD display shows
the present time, in year, month and day, programmed switching
interval, relay ON / OFF status and manual operation. Key on relays
front panel is used for manual ON/ OFF.

Description

DIN
mod.

Reference

Digital weekly time switch 1 circuit

RDD07

RDD07A digital time switch

Technical
Data
Rated voltage
Frequency
Max. Switched current rating
Change over contact
Number of programs
Time intervals programmable

Analogue Time Switches RDA


Digital Time Switches RDD

230V
50/60Hz
16(3)A/250V~
voltage free
20 On and 20 Off
1sec. - 99 sec.
1min. - 59 min.
1h - 24 h
1day - 7 days
every minute
end of minute
+/- 0.5 sec./day
32.768Hz
0/50oC
-10/50oC
15 days
72 hours

Variable and programs updated


Channel activation
Precision
Quartz frequency
Operating temperature
Storing temperature
Battery reserve (for date and hour)
Minimum recharge time
Ingress protection degree
- without clamps-cover
IP20
- with clamps-cover
IP30
- panel mounting
IP40
Terminal capacity
1.5 mm2 min. / 2.5mm2 max.

Digital time switch with automatic summer and winter time


saving adjustment for set dates. Digital timers allow the pre
programmed switching of 1 or 2 electric circuits through a weekly
time programme. LCD display shows current program status,
current date and time. Modular casing for Din or wall mounted
applications.

Description

DIN
mod.

Reference

Digital weekly time switch auto 1 circuit

RDD07A

Digital weekly time switch auto 2 circuits

RDD07A2

23

Programming and measurement

Staircase SDS, Pilots LD, Bell + buzzer + ransformer TDB


and Light sensitive switch RDA
SDS staircase switches

Technical
Data

Staircase switches allow the timed management of lighting or


ventilation circuits used in stairwells or hallways.

Rated voltage
230V~
Frequency
50/60Hz
Max. Switched current rating
16A
Contact type
NO (witch potential)
Time lag adjustable
20sec~10min
N mximo de pulsadores luminosos
40mA
Switching capacity
- incandescents lamps
2000w
- fluorescence serial compensated
750w
- fluorescence parallel compensated
750w
- resistive load cos=1
2000w
Terminal capacity
2.5mm2 min. / 4mm2 max.

In
(A)

DIN
mod.

Reference

16A 230V

SDS016C

LD pilots

Technical
Data
Rated current AC12
Rated voltage
Frequency
Lamp
Lamp power
Insulation voltage
Rated impulse voltage
Terminal capacity
Standards

SDS016B with 3 position handle for automatic, stop and


permanent duty. The switching function is contactor enabled
and offers silent operation, high switching capacity and good
endurance values for incandescent or uorescent loads.
Suitable for 3 or 4 wire systems.

Used to signal the status of the electric circuits: motors, fan,


pump, heater, etc. Available with different coloured lenses.

20A
230V
50/60Hz
Neon 230V
0.6w
250V
4KV
1 mm2 min. / 10mm2 max.
EN 60947-5-1

Description

Reference

Pilot green neon 230V

LD1G

Pilot red neon 230V


Pilot white neon 230V
Pilot double red&green neon 230V

LD1R
LD1W
LD2C

TDB bell + buzzer + transformer


TBD Bell/buzzer is used for audible signalling in domestic and
commercial installations. The device has a double insulated
envelope by construction and complies with EN 60 742, which
can be used be classi ed as transformers for bells. This
means it is conceived to power bells or similar intermittent
warning devices.

Technical
Data
Primary voltage
Secondary voltage
Frequency
Terminal capacity
Standars

230V~
12V~
50/60Hz
4 mm2
EN 60742

230V
50/60Hz
16(3)A/250V~

2000w/230Vac /cos=1
720w/230Vac /cos=0,8
200w/230Vac /cos=0,9
2 ~ 100 lux
2 ~ 1000 lux
2 ~ 10000 lux
Delay time - switching ON
8 seconds
- switching OFF
38 seconds
Operating temperature limit of the module
0/55oC
Operating temperature limit of the photocell
-20/50oC
Terminal capacity
1mm2 min./2.5mm2 max.

24

DIN
mod.

230 V~

Reference
TDB23R

RDA24P light sensitive switch

Technical
Data
Rated voltage
Frequency
Max. Switched current rating
Maximum pilotable power
- tungsten lamp
- fluorescent lamp
- DUO type lamp
Activation threshold

Primary
voltage

Light sensitive switches allow the control of electric circuits


by measuring ambient light intensity. Detected via a separate
photocell, the switch changes state when the light intensity
drops below a preset level. Connected to the switch through
a 4 ~9mm diameter wire, the photocell is suitable for IP65
application.
The switch has an ON/OFF time delay avoiding
nuisance operation via unstable light sources such as
headlights or lightning ashes. Modular casing for Din
or wall mounted applications.

Description
Light sensitive switch
Photocell (spare unit)

DIN
mod.
2

Reference
RDA24P
RDAP

Programming and measurement

Digital measurement instruments MDD


Active energy meter MDA
Digital voltmeter
Modular digital voltmeter for AC voltage measurement with 3 digits LED
display.

Digital ammeter
Modular digital ammeter for AC current measurement with 3 digits LED
display.

Technical
Data
Voltmeter
Rated voltage
Frequency
Description
Precision @ 25OC (%)
Power comsuption
Terminal capacity
Standards

Ammeter
230V~
50/60Hz
3 digits LED 7 segments - h= 10mm
0.00 to 500V
0.05 to 5A
1.5VA
2VA
1.5mm2 min./4mm2 max.
EN 61010-1, EN 60688

Description

DIN
mod.

Reference

2
2

MDD06V2
MDD06A2

Digital Voltmeter
Digital Ammeter

Digital frequency meter


This device allows the monitoring of frequencies from 1 to 999Hz and is
equipped with automatic load selection.
Frequency meter
Wattmeter
Rated voltage
230V~
Frequency
50/60Hz
Description
3 digits red display LED 7 segments - h= 9mm
Precision @ 25OC (%)
+/-0.2% f.s.d.
+/- 2% f.s.d.
1 digit
+/- 2 digit
Cos0.7
Power comsuption
4VA
Terminal capacity
1.5mm2 min./ 4mm2 max.
Standards
EN 61010-1, EN 50081-1, EN 50082-1

Digital wattmeter
Measurement of active power circuits in single or three phase systems,
with balanced / non-balanced load characteristics.
Primary load selection by front dip switch, automatic
decimal point selection.
Description

DIN
mod.

Reference

2
2

MDD00F
MDD06W

Digital Frequency meter


Digital Wattmeter

Three-Phase LCD multimeter


Rated voltage
Frequency
Description
Precision @ 25OC (%)
Relay contact
Standards

63A/500V~
50/60Hz
LCD display backlight white colour
8 + 8, 2 lines
0.5% f.s.d. 2 digits
NO contact max V... max I... max P
1000V 0.5A 20VA
EN 61010-1, EN 60688

Using buttons makes it possible to scroll through the measurement


pages in a natural way.
During programming, the instrument itself proposes the various setting
possibilities present in the model in question, so it is not necessary to
have the instruction manual always at hand.
The instrument can also be used as a priority relay.
Description
Three-phase LCD multimeter

DIN
mod.

Reference

MDD06P4

MDA Active energy meter

Rated voltage
Frequency
Description
Precision @ 25OC (%)
Consumption
Terminal capacity
Standards

230V~
50/60Hz
Display mechanical 5+1 digit - h=4mm
2% f.s.d. +/- 2 digit Cos0,7
6VA 1.5w (capacitive)
1.5 mm2 min / 4mm2 max
EN 61010-1, EN 50081-1, EN 50082-1

Single phase energy meter with 6-digit display and 0.1k w resolution.
Green LED indication for power input and ashing red LED for load
consumption (640 imp/kwh). Units have modular casing for Din or wall
mounted applications.

Description
Active Energy meter

DIN
mod.

Reference

MDA00E

25

Programming and measurement

Technical
Data
Rated voltage
Rated current

Ammeter
Voltmeter

300 and 500 Vac


15, 25 and 40A direct
50 to 1000A / CT

15~100 Hz
1.5 f.s.d.

Frequency
Precision @ 25C (%)
Overload
- Permanent
1.5Ie
1.2Ve
- 5 seconds
10 Ie
2 Ve
Comsuption
0.3~1VA
1.5~3VA
Operating temperature
-25/40oC
Testing voltage
2000V 50Hz during 1 minute
Standards
IEC 51, VDE 0410, DIN 43780,
UNE 60051, BS 89, EN 50081,
EN 50082, CEI 1010, EN 61010

Analogue measurement instruments MDA


Current Transformer TDC
MDA analogue ammeters and voltmeters
Current and voltage measurement for ac circuits. Easy scale change
for different transformer ratios.

DIN
mod.
3
3
3
3
3
3

Description
Analogue voltmeter 300V
Analogue voltmeter 500V
Analogue Ammeter 15A
Analogue Ammeter 25A
Analogue Ammeter 40A
Analogue Ammeter X/5A

Reference
MDA03V
MDA05V
MDA01A
MDA02A
MDA04A
MDA06A

MDA06A interchangeable scales for analogue meters


Description

Reference

Scale 50A
Scale 75A
Scale 100A
Scale 150A
Scale 200A
Scale 250A
Scale 300A
Scale 400A
Scale 500A
Scale 600A
Scale 800A
Scale 1000A

MDC050A
MDC075A
MDC100A
MDC150A
MDC200A
MDC250A
MDC300A
MDC400A
MDC500A
MDC600A
MDC800A
MDC1000A

TDC current transformer


Technical
Data
Rated voltage
720V max.
Primary rated current
from 50 to 1000A
Secondary rated current
5A
Frequency
50/60Hz
Test voltage
3kV (1min/50Hz)
Rated short-time thermal current
Ith: limited to primary bar
Rated dynamic current
Idin = 2.5 Ith
Continuous overload
1.2 In
Standars
IEC 185, UNE 60064-1, VDE 0414, IEC 801/1-3,4

Current transformers allow measurement of high line currents of up


to 1000A with 5A secondary output ratios for use with low input range
meters.
The CT are cable/bus-bar type. The self-extinguish plastic case offers
excelent resistance to mechanical and thermal stress. Every CT enclose
a fastening system to rail DIN as standard.
Description
Iprim=50A
Iprim=75A

Class 3 - 1VA
busbar: 20x5mm
cable: 16mm

Iprim=100A

Iprim=150A
busbar: 30x10mm
cable: 22mm
Iprim=200A

Iprim=250A

Iprim=300A

busbar: 40x10mm
cable: 30mm

Iprim=400A

Iprim=500A
busbar: 60x10mm
cable: 51mm
Iprim=600A

Iprim=800A
busbar: 80x10mm
cable: 65mm
Iprim=1000A

26

Reference

Note: Fastening system to rail DIN included.

Class 1 - 1.5VA
Class 3 - 2.5VA
Class 1 - 2.5VA
Class 3 - 3.75VA
Class 0.5 - 1.5VA
Class 1 - 2.5VA
Class 3 - 3.75VA
Class 0.5 - 2.5VA
Class 1 - 3.75VA
Class 3 - 5VA
Class 0.5 - 5VA
Class 1 - 7.5VA
Class 3 - 10VA
Class 0.5 - 7.5VA
Class 1 - 10VA
Class 3 - 15VA
Class 0.5 - 10VA
Class 1 - 15VA
Class 3 - 20VA
Class 0.5 - 15VA
Class 1 - 20VA
Class 3 - 30VA
Class 0.5 - 15VA
Class 1 - 20VA
Class 3 - 30VA
Class 0.5 - 15VA
Class 1 - 20VA
Class 3 - 30VA
Class 0.5 - 15VA
Class 1 - 20VA
Class 3 - 30VA

TDC050
TDC075
TDC100
TDC150

TDC200

TDC250

TDC300

TDC400

TDC500

TDC600

TDC800

TDC000

Safety Transformers TDS


Disconnector fuse holders FD

Modular protection

Technical
Data
Primary voltage
Frequency
Terminal capacity
Standars

230V~
50/60Hz
4 mm2
EN 60742

TDS safety transformers


Safety transformers are used for the distribution of very low voltages: this guarantees
high protection against electrocution.
Short-circuit proof and failsafe transformers offer great reliability in terms of their
galvanic separation between primary and secondary circuits.
Short-circuit proof transformers are protected from the over temperatures consequent
in overload and short circuit conditions, by their own incorporated protective device.
When normal operating conditions are returned and the transformer temperature is
returned to within operating limits, the transformer will function correctly.
Failsafe transformers on the other hand can no longer function, following anomalous
use or fault.

Primary
voltage
230V~
230V~
230V~

Secondary
voltage
12V~
12/24V~
12/24V~

= F Failure-proof

Technical
Data
FDS08/FDI08 FDS10/FDI10
FDS14
FDS22
Utilization category
AC-22B
AC-21B
Rated voltage
400V
690V
Rated impulse withstand voltage Uimp
8kV
Rated current
20A
25A
50A
100A
Rated making breaking capacity 60A
75A
150A
150A
Rated conditional short circuit current 50kA
100kA
100kA
100kA
Frequency
50Hz
Maximum power dissipation
2.6w
3w
5w
9.5w
Terminal capacity
25mm2 max.
35mm2 max. 50mm2 max.
Fuse size
8x31
10x38
14x51
22x58
Standards
IEC 60947-1, IEC 60947-3

Nominal
power
15VA
15VA
40VA

DIN
mod.
2
2
4

Reference
TDS015F
TDS015R
TDS040R

= R Short circuit proof

FD disconnector fuse holders


Fuses guarantee a high level of protection against
overload and short circuit conditions, in control, signalling
and installation networks. FD disconnector fuse holders
are suitable for gL, gG and aM type fuses.
Poles

In
(A)

Voltage
(V)

1P
1P+N
2P
3P
3P+N
1P
1P+N
2P
3P
3P+N
1P
1P+N
2P
3P
3P+N
1P
1P+N
2P
3P
3P+N
1P
1P+N
2P
3P
3P+N
1P
1P+N
2P
3P
3P+N

20A
20A
20A
20A
20A
20A
20A
20A
20A
20A
25A
25A
25A
25A
25A
25A
25A
25A
25A
25A
50A
50A
50A
50A
50A
100A
100A
100A
100A
100A

400V~
400V~
400V~
400V~
400V~
400V~
400V~
400V~
400V~
400V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~
690V~

DIN
Indicator
mod.
1
2
2
3
4
1
2
2
3
4
1
2
2
3
4
1
2
2
3
4
1.5
3
3
4.5
6
2
4
4
6
8

LED
LED
LED
LED
LED
LED
LED
LED
LED
LED
-

Reference
FDS0810
FDS0811
FDS0820
FDS0830
FDS0831
FDI0810
FDI0811
FDI0820
FDI083
FDI0831
FDS1010
FDS1011
FDS1020
FDS1030
FDS1031
FDI1010
FDI1011
FDI1020
FDI1030
FDI1031
FDS1410
FDS1411
FDS1420
FDS1430
FDS1431
FDS2210
FDS2211
FDS2220
FDS2230
FDS2231

27

Surge Arresters TM

Modular protection

TM Main line and critical load protection


Surge arresters provide protection against destructive overvoltage sources in systems incorporating sensitive electrical or electronic
equipment. Overvoltages can be generated by lighting strike induced currents, electrical motors, frequency converters and power supply
switching operations.
TM20I
Rated voltage (V~)
Maximum voltage (V~)
Frequency
Imax (820s)
Protection level Vp(1)
Poles
Type
Thermal fuse healty indication
Operating temperature
Connection
Response time
Terminal capacity
Replacement module
Connected protection

Poles
Type
Thermal fuse healty indication
Operating temperature
Connection
Response time
Terminal capacity
Replacement module
Connected protection

TM20IIII
400/230V
540/270V

1
2
4
Single pole plug-in
Multi-pole monoblock
LED
LED
LED
-30oC / 70oC
In parallel
5ns
50mm2
TM20IR

MCB C Type - 32A or 35A gL/gG fuse

TM45I
Rated voltage (V~)
Maximum voltage (V~)
Frequency
Imax (820s)
Protection level Vp(1)

TM20II
230V
270V
50/60Hz
20kA
960V

TM45IS
230V
270
50/60Hz

TM45II

1
2
4

DIN
mod.
1
Replacement module
2
5

Type

Reference

plug-in
monoblock
monoblock

TM20I
TM20IR
TM20II
TM20IIII

Type

Reference

plug-in
plug-in

TM45I
TM45IS
TM45IR
TM45II
TM45IIIIS

TM45IIIIS
400/230V
540/270V

45kA
1000V
1
1
2
4
Single pole plug-in
Multi-pole monoblock
LED
LED + S(2)
LED
LED + S(2)
-30oC / 70oC
In parallel
5ns
50mm2
TM45IR
TM45IR

MCB C Type - 32A or 35A gL/gG fuse

TM65I
TM65IS
TM80IIIIS
TM35SPI(3)
Rated voltage (V~)
230V
400/230V
230V
Maximum voltage (V~)
270V
540/270V
255V
Frequency
50/60Hz
Imax (820s)
65kA
80kA
35kA(10/350)
Protection level Vp(1)
1200V
<4kV
Poles
1
1
4
1
Type
Single pole plug-in
monoblockspark-gap
Thermal fuse healty indication
LED
LED + S(2)
LED + S(2)

Operating temperature
-30oC / 70oC
Connection
In parallel
Response time
5ns
Terminal capacity
50mm2
Replacement module
TM65IR
Connected protection TM65 and TM80
MCB C type - 63A or 63A gL/gG fuse
Connected protection TM35SPI
MCB C type - 100A or 125A gL/gG fuse
Note:
(1) Vp: Residual voltage value when a transient current (8/20s) is equal to the
rated current.
(2) References with S indicated that have double indication: LED + dry contact
(remote signal).
(3) Spark gap type: follow current=1,5kA, Insulation resistance 1000M.

28

Poles

Poles
1
1
2
4

Poles
1
1

DIN
mod.
1
1
Replacement module
2
5

Imax
(8/20s)

65kA
65kA
Replacement module
4
80kA
1
35kA(10/350)

monoblock
monoblock

DIN
mod.

Type

Reference

1
1

plug-in
plug-in

5
1

monoblock
spark gap

TM65I
TM65IS
TM65IR
TM80IIIIS
TM35SPI

Permanent Overvoltage Protection TD2YD

Modular protection

TD2YDO Series

Permanent Overvoltage Protector


In
(A)

Equipments for single phase and three phase


lines with integrated MCBs from 25A to 63A

Arrangement

20

The TD2YDO protects all the equipments


dowstream connected against permanent
overvoltage, induced by network voltage
increase.

TD2YDO220

25
32

TD2YDO225
Main MCB 1P+N
+

40
50

YDO276 single phase OVT (Overvoltage


Release) with protection against permanent
overvoltage for MCB tripping, when network
voltage permanently exceeds 276V.

TD2YDO240

1 OVT YDO276

TD2YDO240
TD2YDO250
TD2YDO263

20

TD2YDO420

32

TD2YDO425
Main MCB 3P+N
+

40
50
TD2YDO440

TD2YDO232

63

25

MCB breaking capacity 6kA at 400V~


UA Single phase element 255-275V
Response time
275V t 0.8s
400V t 0.3s
Operating voltage Ue
Single phase 230V~
3-phase 230/400V~

Reference

3 OVT YDO276

63

TD2YDO432
TD2YDO440
TD2YDO450
TD2YDO463

Permanent Overvoltage Protector with UVT

TD2YDU Series

In
(A)

Permanent overvoltage protectors with UVT


for TEMPORARY SUPPLY (emergency stop
with positive safety - NC contact)

20
25
32

YDO276 single phase OVT (Overvoltage


Release) with protection against permanent
overvoltage for MCB tripping, when network
voltage permanently exceeds 276V.

40
50
TD2YDUO40

YDU single phase UVT (Undervoltage release)


enables the automatic trip of the MCB when
the supply voltage drops below 45-85% of Ue.

63

Main MCB 1P+N


+
1 UVT YDU23
+
1 OVT YDO276

20
25
32

MCB breaking capacity 6kA at 400V~


UA Single phase element 255-275V
275V t 0.8s
Response time
400V t 0.3s
Operating voltage Ue
Single phase 230V~
3-phase 230/400V~

Arrangement

40
50
TD2YDU20

Reference

TD2YDUO20
TD2YDUO25
TD2YDUO32
TD2YDUO40
TD2YDUO50
TD2YDUO63

TD2YDU20
Main MCB 3P+N
+
1 UVT YDU23

63

TD2YDU25
TD2YDU32
TD2YDU40
TD2YDU50
TD2YDU63

Indirect Permanent Overvoltage Protector

MCB 1P
6

TD2YDO106

3 OVT YDO276
TD2YDO106

A complete protection solution can be achieved by the combination of Permanent overvoltage protectors
and Transient surge protectors. Please see the installation examples for single and 3-phase lines.

Transient Surge Protector


When a transient surge is induced, the protector TM20 prevents the equipment downstream installed on
the electrical network damage. Transient protection will be of 20kA.
Model
UC (50/60Hz)
UP (1,2/50)
IN (8/20) / Imx. (8/20) / tA
Dimensions An x Al x F

TM20II
275V - 50 60Hz
1.2kV (L-N)
1.5kV (N-PE)
5kA / 20kA / <25ns (L-N); <100ns (N-PE)
36 x 90 x 69mm

TM20IIII
275/400V - 50 60Hz
1.2kV 1,5kV
5kA / 20kA / <25ns
72 x 90 x 69mm

29

30
ICP MCB
(Spanish
Standards)

MCB

Single phase
R
S
T

MCB

RCCB

ICP MCB
(Spanish
Standards)

RCCB

Main MCB + PERMANENT


PROTECTION TD2YDO4...

ICP MCB
(Spanish
Standards)

MCB
MCB

MCB

RCCB

Main MCB+UVT
TD2YDU..

N
RCCB

Main MCB + PERMANENT


PROTECTION TDYDO2...

Single phase

RCCB

RCCB

Mushroom
Mus
button
b
1 NC

TM20IIII

MCB + PERMANENT PROTECTION


TD2YDO106

RCCB

MCB

TM20IIII

RCCB

MCB

L
RCCB

MCB

RCCB

ICP MCB
(Spanish
Standards)

Main MCB + PERMANENT


PROTECTION TD2YDUO..

TM20II
L

MCB

TM20II

Mushroom button
1 NC

Modular protection

Permanent Overvoltage Protection TD2YD


and Transient Surge Protection TM

Installation examples

Permanent Overvoltage Protection + Transient Surge Protection

3-phase

Permanent Overvoltage Protection with UVT + Transient Surge Protection

3-phase

N
N

MCB

Technical Information

Page
Circuit Protection
General characteristics. ......................................................................................................

32

Tripping characteristics. ......................................................................................................

33

Power loss. .........................................................................................................................

33

Let-throught energy I2t curves. ............................................................................................

34

In uence of ambient temperature and height. ....................................................................

36

Selectivity. ...........................................................................................................................

36

The use of MCBs in special conditions. ..............................................................................

37

Technical characteristics for accessories YD. ....................................................................

38

General characteristics TDH. ..............................................................................................

39

People Protection
Technical classi cation. ......................................................................................................

40

Technical characteristics: ZFP and FIEP. ...........................................................................

41

Technical characteristics: ZDH, FCOP and ZDS. ...............................................................

42

Command and Control


Contactors CDR, CDO and CDI. ........................................................................................

43

RCCB with self-reclosing system ZFR. ...............................................................................

44

Pushbuttons, switches and changeover switches PD, PDL and WDM. .............................

45

Programming and Measurement


Time switches RDA and RDD. ............................................................................................

46

Staircase switch SDS and Light sensitive switch RDA. ......................................................

47

Digital measurement instruments MDD. .............................................................................

48

Analogue measurement instruments MDA. ........................................................................

50

Modular Protection
Surge arresters TM. ............................................................................................................

51

31

Technical Data

General Characteristics DPE, DS and DH series

Circuit protection

Installation and Normal service conditions


Ambient temperature: -5oC to +40oC. For speci c applications at ambient temperatures values other than
the ones mentioned above, please use the correction factors in table 5.
Humidity: 50% at a maximum temperature of +40oC.
Altitude: 2000 max.
Transport and storage ambient temperature: between -25oC and +70oC.
Mounting: directly on to 35mm DIN rail.
Connection: dual terminal for cable, busbar or crimp.
Cable terminations: stirrup type and the terminal
screw can be tightened using a Philips head
screwdriver or 5mm at blade screwdriver.
Wire section (rigid or flexible): 35mm2.
Torque: 1.7 to 2Nm.
TemDin2 breakers can be line fed from either the
top or bottom end of the device

Note: Terasaki recommends


the Pozidrive 2 use.

Standards: Manufactured in accordance with EN 60898 and EN 60947 where applicable.


Conforming with low voltage directive (72/23/CEE)
Rated Voltage (Ue):

Single pole
Single pole with neutral
Two, three and four pole

230/400 V~
230 V~
400 V~

NOTE: Suitable for use at 240/415V.


Degree of protection: IP20, as de ned in EN 60529.
Rated current (In):
Types B and C 6 - 8 - 10 - 13 - 16 - 20 - 25 - 32 - 40 - 50 - 63A
Type D 0.3 - 0.5 - 0.75 - 1 - 1.6 - 2 - 2.5 - 3 - 3.5 - 4 - 6 - 8 - 10 - 13 - 16 - 20 - 25 - 32 - 40 - 50 - 63A
Tripping time: 8 to 20ms.
Impulse withstand test voltage Uimp: Shock wave 1.2/50s

Rated insulation voltage (Ui): 660V AC.

Insulating distance: Clearance distances of 50mm have been established for the DS series, and 80mm for the DH MCB series
Energy limiting class:

DS series Tripping curve B-C / Class 3

DH series

Tripping curve B-C / Class 3

Breaking capacity:

DS series

DH series

Standard EN 60898 10kA

B-C Standard EN 60898 6kA

MCBs to EN 60898: DS series: Breaking Capacity: 6kA of ICN and ICS with cos0.65-0.7
DH series: Breaking Capacity: 10kA ICN with ICS 7.5kA up to 32A and 6kA ICN and ICS for 40, 50 and 63A, in both cases cos=0.45-0.5
Endurance: Electrical - 30,000 operations. Mechanical - 40,000 operations
Mechanical shock and impact: The breakers have been subjected to accelerations of up to 22g without provoking the mechanical tripping.
Temperature rise:
Maximum permitted temperature as per EN 60898
Terminals for external connections
External parts which can be touched
Other external parts
Motor protection: The protection of motors against the effects
of an internal short circuit must be ensured, allowing at the same
time the presence of short duration overcurrents (starting) without
causing tripping of the protection element.
This element must also ensure protection of the line, of the
contactor and of the thermal relay associated to the motor.

32

Table 1
TemDin2 series selection table
for 4 pole squirrel cage motors.

Type B, C and D
60oC + ambient temperature
40oC + ambient temperature
60oC + ambient temperature
380 / 415V
Kw
0.37
0.55
0.75
1.1
1.5
2.2
3.7
4
7.5
9
10
11
15
18.5
22
25
30

50/60Hz
HP
0.5
0.75
1
1.5
2
3
5
5.5
10
12
13.5
15
20
25
30
34
40

Type D
In
1.6
2
2.5
3
4
6
10
10
20
20
25
25
32
40
50
50
63

Magnetic
trip
20
25
31.5
37.5
50
75
125
125
250
250
313
313
400
500
625
625
788

DPE, DS and DH series


B, C and D tripping characteristics according EN 60898

5
6

7
8

9
10

Steady current value


Int = 1.13 In : t > 1h
Steady current value
It = 1.45 In : t < 1h
2.55 In: t < 1m (In 32A)
t < 2m (In > 32A)
2.55 In: t> 1s
Type B
3 In : t 0.1s
5 In : t < 0.1s
Type C
5 In : t 0.1s
10 In : t < 0.1s
Type D
10 In : t 0.1s
20 In : t < 0.1s

Application selection for MCB tripping characteristics


Type B characteristics are suitable for moderately inductive loads having that have little or no switching surges i.e. electric heating, water heating,
ovens etc.
Type C characteristics MCBs can be used in general applications such as lighting, ring/ radial socket outlets and small motors.
Installations where the equipment is likely to produce abnormally high inrush currents, such as transformers, welding machines or induction motors
are suited to type D characteristics.

Power loss
Power loss values as de ned by EN 60898. Per pole values shown.

DPE series EcoPlus

DS and DH series
In
0.3
0.5
0.75
1
1.6
2
2.5
3
3.5
4
6
8
10
13
16
20
25
32
40
50
63

Drop voltage
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A

3.032
2.309
1.114
1.062
0.745
0.449
0.489
0.412
0.333
0.325
0.326
0.185
0.185
0.130
0.147
0.148
0.135
0.102
0.082
0.073
0.113

V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V

Power loss
0.91
1.15
0.84
1.06
1.19
0.90
1.22
1.24
1.17
1.30
1.96
1.48
1.85
1.69
2.35
2.96
3.38
3.26
3.28
3.65
7.12

W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W

Maximum power
loss by Standard
3
W
3
W
3
W
3
W
3
W
3
W
3
W
3
W
3
W
3
W
3
W
3
W
3
W
3.5 W
3.5 W
4.5 W
4.5 W
6
W
7.5 W
9
W
13 W

B, C

In
A
6

R
m
25.4

P
W
0.99

10

14.1

1.35

16

7.45

2.03

20

5.00

1.97

25

4.05

2.78

32

2.95

3.65

40

2.35

4.89

50

1.82

6.98

63

1.14

8.78

Table 3

Table 2

33

Technical Data

Tripping Characteristics

Circuit protection

Technical Data

Let-throught energy I2t curves

Circuit protection

Let-throught energy I2t curves


Protection of conductors against the effects of an overcurrent is ensured when the
following is ful lled:
It < Kq
I = current r.m.s. (A)
short circuit conditions
t = breaking time (sec.)
K = material factor
q = cable section (mm)

Example:
K2q2 = 29,756A2s for an electrical line with a copper conductor (1.5 mm2) PVC
covered. If we want to protect this line with a DS-B 6kA, its I2t must be lower that the
conductor K2q2, ; 6A at 16A

DS series

34

Values for isolated conductor


K2 q2 (A2 s)

PVC
K=115
3.306
0.5
7.439
0.75
13.225
1
29.756
1.5
82.656
2.5
211.600
4
476.100
6
1,322.500
10
3,385.600
16
8,265.625
25
35 16,200.625

mm

Copper conductor (Cu)

Rubber
K=141
4.970
11.183
19.881
44.732
124.256
318.096
715.716
1,988.100
5,089.536
12,425.625
24,354.225

Table 4

DH series

EPR K=143
5.112
11.503
20.449
46.010
127.806
327.184
736.164
2,044.900
5,234.900
12,780.625
25,050.025

DPE series EcoPlus

DS1 series

A2 sec.

I2t Curves

A2 sec.

Amps

A2 sec.

Amps

Amps

35

Technical Data

Let-throught energy I2t curves

Circuit protection

Technical Data

Influence of ambient temperature and height

Circuit protection

DS and DH series
Ambient compensation

Load compensation for breaker grouping

At temperatures out with the breakers calibrated value +300C +/-50C,


the load capacity of the device will vary inversely as a function of its
operating ambient temperature. Therefore operation at temperatures
higher than 300C will reduce the MCBs loading capacity.

Breakers mounted side by side and subject to near, or full loading


simultaneously can generate high temperatures in small or poorly
ventilated enclosures. Load reduction must be taken into account. The
following tables are guidelines to prevent potential overloading:
- For a single row the table 5 can be used
- In two-row distrubution boards the reduction is approximately of a 25%
- In three-row distribution boards the reduction is approximately of a 30%

Table 5

4
5
No. of breakers

Table 6

Influence of height (altitude)

Height

If the height of the installation site exceeds 2,000m, the reduction of the
dielectric strength and the cooling effect of the air should be considered.
NEMA and ANSI Standards establish some speci c values that can be
taken as a reference:

Selectivity

Permanent
max. I
1.00
0.99
0.96

< 2,000m
< 2,600m
< 3,900m
Table 7

Clearance
rated U
1.00
0.95
0.80

Limit value of the selectivity MCB/MCB

Discrimination or selectivity exists between two protective devices


connected in series when the operation of the downstream device is
such that the fault condition is cleared without operation of the upstream
device

In (A)

The characteristics of the downstream device should be that clearance


of the fault condition limits the current (let through value) to a value
below the magnetic threshold of the upstream device.

Type DSC up
6
10 16

20

25

32

40

50

63

8.1

8.1

8.2

8.2

8.3

8.3

8.0

10

8.0
7.1

16
Partial selectivity is said to occur when the selective operation of the
downstream device is at a value between the threshold of the upstream
devices magnetic trip setting but not exceeding the downstream
devices rated breaking capacity. At values above this both devices may
operate.

Type

20

DSB

25

down

7.1

7.5

7.5

7.6

7.6

7.7

7.0

7.0

7.5

7.5

7.6

7.6

5.4

5.5

5.6

5.7

5.7

5.4

5.5

5.6

5.7

32

5.1

40
Full selectivity is said to occur when it is selective up to a prospective
value of fault current equal to the downstream devices breaking
capacity.

5.2

5.3

5.1

5.1

50

5.1

63
Table 8

In (A)

Type DSD up
6
10 16

20

25

32

40

50

63

12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5

10

12.1 12.1 12.1 12.1 12.1 12.1 12.1

16

10.1 10.1 10.1 10.1 10.1 10.1

Type

20

10.1 10.1 10.1 10.1 10.1

DSC

25

10.2 10.2 10.2 10.2

down

32

10.2 10.2 10.2

40
50

In (A)

Type DSD up
6
10 16
6

20

25

32

40

50

10.2 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0

10 10.0 10.2 10.5 10.5 10.5 10.8 10.8 10.8 10.8


16

10.0 10.2 10.5 10.5 10.8 10.8 10.8 10.8

Type

20

10.0 10.2 10.5 10.5 10.8 10.8 10.8

DSB

25

10.0 10.2 10.5 10.5 10.8 10.8

down

32

10.0 10.2 10.5 10.5 10.8

10.2 10.2

40

10.0 10.2 10.5 10.5

10.2

50

10.0 10.2 10.5

63

10.0 10.2

63
Table 9

Table 10
The limit value of the selectivity is referred to the number of
times of the up breaker rated current value (In).

36

Example: Up DS-D 10A, Down DS-C 1A


corresponds to 10.9
10.9In x 10A = 109A

63

Non selective zone


For other tripping characteristics, please contact Terasaki.

The use of breakers in DC circuits


The thermal characteristics for TemDin2 breakers are unaffected by the type of current applied, that is either direct current or alternating current.
The magnetic trip value increases by 40%. For example, in the case of a breaker of tripping characteristic B and 10A rated current, its magnetic
tripping value will be between 30A and 50A in alternating current. The magnetic tripping value for this very same breaker in direct current will be
between 42.4A and 70.7A.

The breaking capacity of the breaker is also affected. The breaking capacity is maintained in 6kA (for the range DS06) and in 10kA (for the range DH06)
for circuits with a constant time L/R = 0.015 sec., but bearing in mind the following table that indicates the number of poles that should participate in
the break.

V 48V

48V < V 110V

110V < V 150V

150V < V 200V

1p

2p

3p

4p

The breaker poles distribution among the polarities depends on the type of system. According to the earth location, it should be analyzed the most
unfavourable fault that requires a larger number of poles in series for the short circuit voltage range that the table indicates. After that, apply the breaker
with the necessary number of poles.
When the source has a polarity put to earth, a supplementary pole in the said polarity can be used in order to carry out the load isolation.
Examples of different system types and faults (A, B or C) that cause consequences:

Example: Say, a source of 120V


Case 1) according to the table, 3 poles in series for the A and B fault are required. A 3-pole breaker in series should be put in the positive polarity or
a 4-pole breaker with the fourth pole in the negative polarity to assure the isolation.
Case 2) 3 poles in series for the defect A are required (120V short circuit voltage) or 2 poles in series for the faults B or C (60V short circuit voltage) in
each polarity. In such a way that with a 4-pole breaker with 2 poles in series in each polarity the most unfavourable case is covered.
Case 3) 3 poles in series are required for the fault A. A 3-pole breaker in series in any polarity is required or 2 in one and the other pole in the other
polarity.

Influence of non standard frequencies


For operational frequencies greater than 50/60Hz, the effect of these non-standard frequencies must be taken into consideration. Thermal
characteristics are independent from variation in frequency. Magnetic tripping values are directly affected by frequency. As a reference, for
frequencies of 100, 200, 300 and 400Hz, the values at which the magnetic tripping occurs become increased in a 10, 20, 30 and 40% respectively.

Use at other voltages


The maximum rated operational voltage for TemDin2 MCBs is 440V~ with a reduction in breaking capacity of 10%. Supply voltages lower than the
assigned value can be applied.
Supply voltages up to 750V can be applied in special conditions of service and short circuit current rates. Please contact Terasaki for further details.

Phase Imbalance
In three phase circuits designed for single phase distribution through to nal load, consideration should be placed for protection of the neutral
conductor. TemDin2 4 pole MCBs have integral neutral pole protection and offers adequate protection against overloaded neutral conductors,
when phase imbalance conditions are present. Commercial installations such as hotels, banks and public buildings are often subject to high neutral
currents via equipment consuming non-linear loads and also require protection to be present in the neutral line.

37

Technical Data

The use of MCBs in special conditions

Circuit protection

Technical Data

Technical characteristics for accessories YD

Circuit protection

Accessories for DS and DH series


Up to three accessories can be clipped together on
the left hand side of a breaker.
1. Under voltage release YDU
2. Shunt trip YDS
3. Auxiliary contact and remote contact status indicator YD
4. Breaker DS or DH

NOTE: Make sure that break out plate A is removed and the dollies of both the auxiliary device and associated breaker are in the OFF position
before clipping them together.

Alarm or Auxiliary contact YDA


AUX/AL

Test device

There are 2 different operational modes. On the frontal side there is a shaft
with a cam that selects each function
mode (see picture). It must be used a
small size flat-end screwdriver. To be
fitted on the left side.

On the low-left hand of the frontal side there is a test lever allowing
11-13 contacts to be checked without tripping the main breaker.
With the main breaker in ON position by pushing the test lever from
the bottom to the top, you can verify if contacts 11-13 open.
AUX

AL

AUXILIARY operational mode


When the main breaker changes position (ON/OFF), either manually or because and automatic
tripping, always auxiliary contacts also change position.
When the main breaker is in ON position, auxiliary contacts 11-12 are in NO position, and
auxiliary contacts 11-13 are in NC position.
When the main breaker is in OFF position, auxiliary contacts 11-12 are in NC position, and
auxiliary contacts 11-13 are in NO position.

ON

OFF

OFF

Trip

ALARM operational mode


When the main breaker is in ON position, auxiliary contacts 11-12 are in NO
position, and auxiliary contacts 11-13 are in NC position.
When the main breaker is from ON position to OFF position manually changed,
auxiliary contacts do not change position.
When the main breaker changes from ON position to OFF position, because
an automatic tripping, auxiliary contacts change position and there is a tripping
indicator on the frontal side that shows red colour.

ON

In this case auxiliary contacts 11-12 and 11-13 move to NC and NO position
respectively.

Shunt trip YDS

Undervoltage release YDU

Shunt Trip is a main circuit breaker accessory that allows remote opening. There is a magnetic relay that when the coil is energized acts over
its mechanism and it trips the main breaker.
There are 3 different terminals C1, C2 and 12
It is only possible to energize the relay
(terminals C1 and C2) when the main
breaker and the SHT are in ON position.
There is a protection switch that after the
relay is energized, the internal mechanism
trips it and the relay circuit becomes open
(see diagram).
There is also, an auxiliary contact 12-C1
that allows to show the status of SHT and
the main breaker.
38

The Under Voltage Trip release has


two terminals, D1 and D2, between
which it must be applied a voltage
>=0.55Ue (+/-10%).
On the central-top hand of the frontal
side there is a time delay function
potentiometer that allows a delay of
up 300msec. User can manage it with
a small size flat-end screwdriver.

TDH series
Standards: 10kA, in accordance with UNE-EN 60898 and IEC 60947-2. Thermal calibration: 30C. Suitable for isolation, shown by a green indicator
on the toggle. Simultaneous contacts closing independent of the handling speed.
Rated operational voltage Ue (V): 400V

Insulation voltage Ui (V): 500V

Rated impulse voltage (Uimp (kV): 2500V


Power loss: MCB rated current (A)/Watts loss per pole (W) 80A/8W, 100A/10W
Temperature derating: If the circuit breaker is required to operate in a higher ambient temperature than 30C it will require progressively less
current to trip within the designated time/current zone.
Correction factor
In (A)

30C

35C

40C

45C

50C

55C

60C

80

80

76

72

68

64

60

56

100

100

95

90

85

80

75

70

Current limiting at 400V

Accessories for TDH series


Auxiliary contacts
TDHAUX

Shunt trip (SHT)


TDHAL

1xO1xC
230V~ 6A
AC-1

RCD add on block

2P

Undervoltage trip (UVT)

TDHSHT230

TDHUVT230

Consumption: 8VA
Tolerance:
Un -15%
230V~

Consumption: 3VA
Latching voltaje Un 230~:
between 35-70%
230V~

4P

Standards: In accordance with EN 61009-1 and EN 60947-2.


Rated voltage: -15 +10%. 2-pole 230V, 4-pole 230/400V

39

Technical Data

General characteristics TDH series

Circuit protection

Technical Data

Technical classification

People protection

RCCB classification

Tripping curve
type AC

Type AC
Type AC RCCBs are designed to clear sinusoidal residual
current which occur suddenly or slowly rise in magnitude.
Residual current
0.5 x In
1 x In
2 x In
5 x In

Tripping time
t=
t < 300 ms
t < 150 ms
t 40 ms

Type Ai
High immunity to nuisance tripping
Electric equipment incorporates more and more electronic components
which causes nuisance tripping to the conventional 30mA RCDs type
A or AC (always in the most critical moment like weekends, areas with
no people presence) due to overvoltages or high frequency currents
produced by atmospheric disturbances, lighting equipment (electronic
balasters), computers, appliances, connections to long cables which
induce a high capacity to ground, etc.

Tripping curve
type A

Some times the lter incorporated on the standard RCDs type A or AC


which are protected to prevent nuisance tripping against peak currents
up to 250A 8/20 s, does not avoid 100% unwanted tripping.
Installations with lighting equipment incorporating electronic
balasters or computers.
The most typical problem in these installations is the tripping of the RCD
when switching the equipment ON-OFF. It is recommended that, in
case several devices are installed in the same line, the sum of all leakages shall not exceed 1/3 lDn since any disturbance in the line can trip
the RCD. For this kind of installation it is recommended either to split up
circuits or use RCDs type Ai.
RCDs type Ai have a tripping characteristic according to EN 61008/61009.
All RCDs have a high level of immunity to transient currents, against
current impulses of 8/20 s according to EN 61008/61009.
Type A, AC ...................250 A 8/20 s
Type S ........................3000 A 8/20 s
Type Ai ...........................3000 A 8/20 s
RCDs have a high level of immunity against alternating currents of high
frequency according to EN 61008/61009

Type S S
RCDs type A or AC have instantaneous tripping. In order to provide
full people protection in vertical installation with more than one circuit,
as well as to ensure the service in the installation in case of earth
leakage in one of the circuits or to avoid unwanted tripping because of
harmonics, high connection currents due to the use of motors, reactive
loads, or variable speed drives, we need to use selective RCDs at the
top of the installation.
Any RCD type S is selective to any other instantaneous RCD installed
downstream with lower sensitivity.

Residual current
0.5 x In
1 x In
2 x In
5 x In

at point on wave 0o

at point on wave 90o


0.25 x In
1.4 x In
2.8 x In
7x In

at point on wave 135o

40

t=
t < 300 ms
t < 150 ms
t 40 ms

Residual pulsating direct current

0.35 x In
1.4 x In
2.8 x In
7 x In

1. Selective type RCCBs.


2. Standard type RCCBs.

Tripping time

Sinusoidal residual current

0.11 x In
1.4 x In
2.8 x In
7 x In

t=
t < 300 ms
t < 150 ms
t 40 ms

t=
t < 300 ms
t < 150 ms
t 40 ms

t=
t < 300 ms
t < 150 ms
t 40 ms

Application: This range provides the protection against overload and short-circuit currents and protects people against earth fault currents: direct or
indirect contact, re...

ZFP Series

FIEP Series

Standards: In accordance with EN 61008 and suitable for isolation.


Sensitivities: 10, 30, 100 and 300A

In accordance with: EN 61008


Rated current: 25 and 40A

ZFP RCCBs optional use for type A


and type AC
.
For 300mA sensitivities available type A with selective S time delay
function.

Rated voltage: 230V~


Sensitivities: 30mA

Resistant against unwanted tripping due to surge effect

.
No. of poles: 2

Rated current: Range from 16, 25, 40, 63, 80 and 100A
Type: Type AC
Rated voltage: 230/400V~ (2P) and 400/415V~ (4P) at a frequency of
50/60Hz

Mounting: 35mm symmetrical DIN rail


(EN50022-DIN46277).

Mounting: 35mm symmetrical DIN rail (EN50022-DIN46277).


Operating temperature: Min. operating temperature -25C.

Dimensions: 2 DIN modules


(1 DIN module=17.8mm)

Power loss per pole

Tripping time: < 30ms.

ZFP
In (A)

16

25

40

63

80

100

Z (mOhm)

9.95

3.75

2.15

1.30

1.3

0.9

Pw (W)

2.55

2.33

3.43

5.16

8.3

8.7

Mechanical endurance: 20,000 operations.


Resistant against unwanted tripping due to
surge effect
.
Residual making and breaking capacity:
Im = Im = 500A

AUXZF Auxiliary contacts


Rated current

In

5A

Rated voltage AC

Un

240V

Max. current

AC 14

240V

5A

DC 12

60V

1A

48V

2A

24V

4A

Min. operating voltage AC

24V

DC

24V

AC

10mA

DC

200mA

Electrical endurance

operations

10,000

Torque

Nm

0.5

Min. operating current

AUXZF1
Auxiliary contact

AUXZF2
Signal contact

41

Technical Data

Technical characteristics for ZFP and FIEP Series

People protection

Technical Data

Technical characteristics

People protection

ZDH and FCOP Series


Standards: In accordance with IEC 61009.

Power loss per pole

Thermal setting In: 6, 10, 16, 20, 25, 32 and 40A


Residual current Im: 30 and 100mA

ZDH

Tripping characteristic: C and B

In (A)

10

16

20

25

32

40

50

63

Minimum operating voltage UBmin: 100V


Mechanical/electrical endurance: 20,000/10,000

Z (mOhm)

45.8

16.4

10.6

7.3

5.4

3.2

2.6

1.9

1.4

Pw (W)

1.65

1.7

2.7

2.9

3.3

3.4

4.2

4.8

5.6

Tropicalisation acc. to IEC 60068-2-28/2-30: 95% RH at 55oC


Terminal capacity flexible/rigid cable:
ZDH - Bottom terminal: 16-25mm2
FCOP - Top: 16-25mm2 / Bottom: 25-35mm2

Power loss per pole

No. of poles:
ZDH - 1+N (1 module)
FCOP - 1+N (2 module)

In (A)

10

16

20

25

32

40

Z (mOhm)

53

16.5

9.8

7.1

5.8

4.7

3.6

Nuisance tripping resistance: 250A 8/20s

Pw (W)

1.9

1.6

2.5

2.8

3.5

4.8

5.8

FCOP

Ambient temperature: -5oC up to 55oC


Residual making and breaking capacity:
ZDH - Im=10,000A
FCOP - Im=7,500A

Accessories for FCOP Series

Short-circuit capacity: Icm=10,000 at 230V

To be added on the right side.


Auxiliary contacts, please refer to ZFP RCCBs Aux. contacts
Ref. AUXZF on page 41.

Selectivity class: 3

Nominal voltage

Shunt trip
(SHT)

Undervoltage trip
(UVT)

SHTZF230

UVTZF230

AC

110/415V

230V

DC

110/125V

230V

Tripping voltage Un (10%)

0.5V

Minimum voltage AC / DC Un

0.85V

Tripping time

<10ms

Power consumption
ZDH

FCOP

0 300ms
3VA

Coil impedance

290

Electrical endurance (operations)

2000

2000

Torque

2Nm

2Nm

ZDS I2t Curves

ZDS Series
Standards: In accordance with IEC 61009.
Rated voltage: 230/240~
Frequency: 50/60Hz
Breaking capacity: 6kA - class 3
According to EN61009.
Sensitivities: 30 and 300mA.
Type: Type AC
Tripping characteristics: Type C.
No. of poles: I+N (neutral right side)
Rated current: from 6 to 40A
Resistant against unwanted tripping
due to surge effect

ZDS

Terminals: Dual type bottom for cable or busbars connection (fork type).
Mounting: 35mm symmetrical DIN rail (EN50022-DIN46277).
No. of modules: 2
42

CDI Technical Information


De acuerdo con IEC 947-4-1, IEC 947-5-1, VDE 0660, EN 60947-4-1, EN 60947-5-1
Type

20A

25A

40A

63A

Aux. Contact

Main Contacts 5) 6) 7)
Rated insulation voltage Ui
Rated operation voltage Ue
Frequency of operations z
Mechanical life

V AC
V AC
AC1, AC3 1/h
S x 106

440 2)
440
300
1

440 2)
440
300
1

440 2)
440
600
1

440 2)
440
600
1

440 2)
440
600
1

Utilization category AC1


Rated operational current Ie (=Ith)
open at 60C
Contact life
Minimum Switch Voltage
Short time current
Power loss per pole at Ie/AC1

A
S x 106
V/mA
10s-current A
W

20
0.1
24/100
72
2

25
0.1
24/100
72
2

40
0.1
24/100
216
3

63
0.1
24/100
240
7

17/5
0.5

27

30

1.1 4)
-

2.2
2.5
4
0.15

7.5
8
12.5
0.15

8
8.5
15
0.15

7-9
2.2 - 4.2
0.8 - 1.6

14 - 18
4-6
1.6 - 3.2

33 - 45
6-8
2.6

33 - 45
6-8
2.6

0.85 - 1.1

0.85 - 1.1

0.85 - 1.1

0.85 - 1.1

35
3
3

35
3
10

63
3
10

80
3
10

1.5 - 10
1.5 - 6
1.5 - 6
1
0.75 - 2.5
0.5 - 2.5
0.5 - 1.5
1

1.5 - 10
1.5 - 6
1.5 - 6
1
0.75 - 2.5
0.5 - 2.5
0.5 - 1.5
1

2.5 - 25
2.5 - 16
2.5 - 16
1
0.75 - 2.5
0.5 - 2.5
0.5 - 1.5
1

2.5 - 25
2.5 - 16
2.5 - 16
1
0.75 - 2.5
0.5 - 2.5
0.5 - 1.5
1

0.5 - 2.5 3)
0.5 - 2.5 3)
0.5 - 1.5
2
-

V AC
40C A
60C A

440 2)
10
6

220-240V
380-415V
440V

A
A
A

3
2
1.6

24-60V
110V
220V

A
A
A

2
0.4
0.1

gL (gG)

10

7 - 16
6 - 12
10 - 15

9 - 15
4-8
10 - 15

11 - 15
6 - 13
10 - 15

11 - 15
6 - 13
10 - 15

Utilization category AC3


Switching of three-phase motors
Rated operational current Ie
Rated operational power
of three-phase motors
220V
50-60Hz
230-240V
380-415V
Contact life

A
kW
kW
kW
S x 106

Power consumption of coils


AC
operated inrush
holding

VA
VA
W

Operation range of coils


in multiples of control voltage Us (-40 to +40C)
Short circuit protection
max. fuse Coordination-type 1 gL (gG)
Rated short circuit current r
Iq
Cable cross-sections
Main connector
solid or stranded
exible
exible with multicore cable end
Clamps per pole
Magnetic coil
solid or stranded
exible
exible with multicore cable end
Clamps per pole
Auxiliary Contacts 5) 6) 7)
Rated insulation voltage Ui 1)
Thermal rated current Ith
Ambient temperature
Utilization category AC15
Rated operational current Ie

Utilization category DC13


Rated operational current Ie
per pole
Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size
Switching time at control
voltage Us 10%
make time
release time
arc duration

A
kA
kA
mm
mm
mm
mm
mm
mm

ms
ms
ms

1) Apropiados para sistemas de neutro, categoras de sobretensin I a IV, nivel de polucin 3 (industria estndar): Uimp = 8kV.
2) Apropiados para sistemas de neutro, categoras de sobretensin I a III, nivel de polucin 3 (industria estndar): Uimp = 8kV.
3) Seccin de cable mx. con conductor preparado 4) AC7b motor 2 polos 230V 1,1kW
5) Frecuencia nominal 50/60Hz
6) Sobretensin mx. transitoria a la conexin <4kV
7) Ciclo de trabajo: 100%

43

Technical Data

Contactors CDI

Command and Control

Technical Data

Command and Control

RCCB with self-reclosing system ZFR

ZFR Series
Operation mode
a) After a switch-off due to a residual current fault or a manual action,
the RCCB is automatically reclosed once the period of time between
successive reclosing actions has passed. It can also be reclosed by
means of an external electric command applied to (LI).
b) The manual switch (2) (yellow lever) can be locked with a padlock
(6mm passing hole) at the position ON (I) or OFF (O). Fasten the
padlock through the hole (3).
- If the manual switch (2) is locked at the position I, then the ZFR is
ready for its regular use.
- If the manual switch (2) is locked at the position O, then the ZFR
is blocked and neither manual nor automatic reclosing actions are
allowed.
- The switch (2) (yellow lever) in the O position causes the internal
counter of reclosing attempts to be reset to zero
- In case of switch lock, lower the yellow lever and put it up back
again.
Before executing any manipulation over the installation placed
downstream the ZFR unit, the self-reclosing ability must be
disabled by pulling down the manual switch (yellow lever).
c) ZFR type sets are equipped with a group of additional micro-switches
(H) which indicate the position of the RCCB (switched on or off)
regardless the cause of the trip (terminals No. 11, 12 and 14).

Specifications of ZFR Series

Specifications of ZFR Series


Motor
Dimensions
Rated voltage
delay by means
of external command
Auxiliary contact

Relay (built in the motor)


Reclosing actions
Allowable number
Delay Time
Reset Time
RCCB device
Rated voltage (Un)
Current (In)
Sensitivity (Ifm)
Endurance to shock waves
Endurance to short-circuit
Breaking and closing rated
current
Tripping characteristics
Test voltage

Electrical wiring of ZFR series


(a) Connect the phases and/or neutral wire of the line to be protected
to the power terminals of the RCCB.
(b) Connect the power supply for the operation of the motorized
driving system of the RCCB (voltage of 230Vac between the
terminals marked as N and L).

44

Reclosing

Imax: 2 A 250Vac / 2A 24Vdc


Imin: 20mA
Terminal for 2.5mm2 cable

6
10, 20, 30, 60, 120 and 600s
= Reclosing delay
230/400Vac 50/60Hz
40 Aac
30 or 300mA according to model
250A 8/20ms and 200A 0.5ms
6000A as per VDE 0664
500A

Poles
Connection terminals

Type AC (other, please contact)


2p - between 140 and 230Vac
4p - between 190 and 400Vac
2 or 4
35mm2

Protection degree
Storage temperature
Working temperature
Relevant standards
Case colour

IP40 (DIN 40050)


-55oC to +55oC
-25oC to +55oC
EN 61008
RAL 7035

3-phase system

(1) Terminals for commands line:


N- L : Power supply at 230Vac
LI : External reclosing command (optional)
(2) Manual switch (yellow lever):
- Position I: Ready for regular use
- Position 0: All operations are locked.
(3) Passing hole for padlock:
Ability to lock at position 0 or I.
(4) Micro-switch terminals: Indication of the RCCB status: 11, 12 and 14.

3p
220/240V 50/60 Hz
0.3s < t < 1s

1-phase system

Command and Control

PD pushbuttons
5

Terminal numerical order

1NO
1NA

1NC

2NO
2NA

1NO/NC
1NA/NC

1NO+1NC
1NA+1NC

PDL pushbuttons with neon signal lamp


Terminal numerical order

5
X1

X2

X1

X1

X2

X2

1NO
1NA

1NC

WDM switches
5

Terminal numerical order

1NO
1NA

2NO
2NA

3NO
3NA

4NO
4NA

WDM changeovers switches


5

Terminal numerical order

2
UNIPOLAR
1-21-2
SINGLE
POLE

1-2TWO
BIPOLAR
1-2
POLE

2
1-0-2SINGLE
UNIPOLAR
1-0-2
POLE

1-0-2 TWO
BIPOLAR
1-0-2
POLE

45

Technical Data

Pushbuttons, Switches and


Changeover switches

Technical Data

Programming and measurement

RDA24 analogue timer

RDD07 single module digital timer

RDD07A digital time switch

46

Time switches RDA and RDD

RDD07A2 digital time switch

SDS016C Staircase switch


Diagram 3 wires

Diagram 4 wires

RDA24P light sensitive switch

47

Technical Data

Programming and measurement

Staircase switch SDS


Light sensitive switch RDA

Technical Data

Programming and measurement

Digital measurement instruments MDD

MDD06V2 voltmeter / MDD06A2 ammeter


Technical
Data
Input
- Current
- Voltage
Overload
Display
Power comsuption
Operating temperature
Storing temperature

TI/5Aac
<500Vac
1.2 In/Vn
LED + Segments
2VA
0/50oC
(R.H.<90% no condensation)
-10/60oC
(R.H.<90% no condensation)

MDD00F frequency meter


Technical
Data
Input
- Voltage
10~500Vac
Overload
1,2 In/Vn
Position of the decimal point
automatic
Power comsuption
4VA
Operating temperature
0/50oC
(R.H.<90% no condensation)
Storing temperature
-10/60oC
(R.H.<90% no condensation)

MDD06W wattmeter
Technical
Data
Input
- Current
TI/5Aac
- Voltage
<500Vac
Overload
1,2 In/Vn
Position of the decimal point
minidip switch
Power comsuption
minidip switch
Power comsuption
4VA
Operating temperature
0/50oC
(R.H.<90% no condensation)
Storing temperature
-10/60oC
(R.H.<90% no condensation)

48

Wiring diagram for voltmeter

Wiring diagram for ammeter

Digital measurement instruments MDD

MDD06P4 three-phase LCD multimeter


Technical
Data
Voltmetric input
Line-line voltage:
- direct connection
max. 500 V
- permanent overload
120%
- thermal overload (1 s)
150%
- input impedance voltmetric circuits
2ML-N / L-L
Amperometric input
- rated current
63 A
- permanent overload
120%
- thermal overload (1 s)
200%
Voltage measurement
- range of measurement LN
0...290 V
(phase voltage with direct connection)
- precision
0.5% f.s 2 digit
Current measurement
- range of measurement
0.6 ... 63.0 A
- precision in the range of
measurement 0.6 ... 63.0 A
0.5% f.s 2 digit
Frequency measurement
- rated value
50/60 Hz
- range of measurement
45...80 Hz
- precision
0.3% vm 1 digit
- response time
< 300ms
Active power measurement
- range of measurement
50 kW
- precision
1% f.s 2 digit
Reactive power measurement
- range of measurement
50 kvar
- precision
1% f.s 2 digit
Apparent power measurement
- range of measurement
50 kVA
- precision
1% f.s 2 digit
Active energy measurement (Wh)
- resettable import / export hour meters
Two separate
- calculating period
15 minutes
- energy count
999999.9 kWh
- precision with current 0.05...1.0 In
2% fs 2 digit
Reactive energy measurement (varh)
- resettable energy count
999999.9 kVarh
- calculating period
15 minutes
- precision with current 0.05...1.0 In
2% fs 2 digit
Power factor measurement
- range of measurement cos
-1...0...+1
- precision with current 0.1...1.0 In
and voltage 0.8...1.2 Un
2% fs 2 digit
Working time
- Total working time
hh:mm with presence of power supply
- Partial working time
hh:mm from previous reset
Display
- display type
LCD
- no. of characters
8+8 on two lines
Electrical characteristics options
Galvanic insulation
- coil-contact alarm relay
3kV
Mechanical characteristics
- mounting type
guide DIN50022/ ush DIN43700
- protection rating
complete device IP20/ front panel IP30
Relay contact characteristics
- N.O. contact maxV..maxI..maxP
1000V 0.5A 20VA
Ambient conditions
- ambient temperature
0...+45 C
- outer range
-5...+55 C
- storage temperature
-10...+70 C
- relative humidity
10...95 %
- atmospheric pressure
70...110 kPa
Reference standards
- Safety EN 61010-1 300V CAT III
- Precision EN 60688
- Electromagnetic compatibility (immunity) EN 61000-6-2 (ex EN 50082-2)
- Electromagnetic compatibility (emission) EN 61000-6-4 (ex EN 50081-2)
- Protection rating of enclosures (IP Code) EN 60529

PARAMETERS DISPLAYED
- Phase-phase voltage
- Phase-neutral voltage
- Current
- Total equivalent power factor
- Total active power (+/-)
- Total reactive power
- Total apparent power
- Frequency
- Total active energy (import)*
- Total active energy (export)*
- Total reactive energy*
- Total working time*
- Partial working time*
- Phase sequence

L1, L2, L3
L1-N, L2-N, L3-N
I1,I2,I3,In (neutral)
total ind/cap
PW
Pvar
PVA
Hz
+kWh
-kWh
kvarh
hh:mm
hh:mm
(square lighted=NO sequence)

N.O. contact 1000V-0.5A-20VA


*When used as a priority relay.

49

Technical Data

Programming and measurement

Technical Data

Programming and measurement

Analogue measurement instruments MDA

MDA00E active energy meter


Technical
Data
Input
- Current
- Voltage
Overload
Operating temperature

16Aac (48~62 Hz)


230Vac (+10/-15%) by voltimetric input
1,2 In/Vn
0/50oC (H.R.<90% no condensation)

Storing temperature

-10/60oC (H.R.<90% no condensation)

MDA analogue ammeter and voltmeter


VOLTMETER

50

AMMETER

Protection against transient currents

Applications

Transients with high energy and short duration (<50ms) are the most
dangerous and destructive problems in distribution lines -low energy
voltage variations, electromagnetic noise, harmonics, power supply
interruptions and ground faults-. Its random nature, short duration and
high energy involved make them the most dif cult problem to solve.
Associated to lightning, either direct impact or induction are the most
destructive phenomenon.

Electronic equipment becomes more vulnerable to power disturbances


with each new generation. Electronic damage, disruption and downtime
can be prevented.

Due to these surges or changeover operations, the transients origin in


distribution lines is increasing and it causes serious cost damages to
the connected equipment. Furthermore, there is the substitution of the
traditional circuits with relay by printed circuits, which are easily affected
because of their high sensitivity, typical examples are operative life
reduction, malfunction of electronics logic and destruction.

Transient current at 250A (peak current) at point on wave


8/20s (VDE 0664)

Critical loads needing to be protected, with an increasing number of


electronic loads are:
Work stations
Telephone systems
Automated assembly
Medical diagnostic equipment
Industrial machine tools
Electronic gas pumps
Automated integrated controls
TV & radio broadcasting equipments
Telephone & communication equipments
Computers and networks
Domestic
...
Transient current at 200A (peak current) at minimised point on
wave 0,5s-100kHz (pr EN 61.1008)

Protection zones and surge arrester types


In practice, it is very convenient to de ne four protection zones in a building.

Equipment

Zone 3
Zone 1

Zone 2

Distribution
panel
Supply

Zone 0:

Area with more risk, not protected. Direct lighting impact, usually occurred on the
external side of a building, with or without lighting conductor.

Zone 1:

Part of the building protected by its external walls, normally provided with an earth
metal protection.

Zone 2:

Inside either apartments or rooms from the building.

Zone 3:

Equipment, protected by their own metal cover, to be directly protected.

Zone 0

There is a suitable surge arrester type for each zone.

Type 1

High protection. Suitable for incoming supply boards with lighting protection, with wave 10/350s. Residual voltage up to 4kV.
Zone 1

Type 2

Medium protection. Suitable for incoming supply boards without lighting protection and for secondary distribution boards in
general. Residual voltage under 1.5kV. Zone 1 and 2

Type 3

Accurate protection. Suitable for secondary boards located away from the distribution boards that feed them or for Category 1
sensitive equipment, with low insulation level. Zone 2 and 3

51

Technical Data

Surge arresters TM

Modular Protection

Technical Data

Surge arresters TM

Modular Protection

Surge arrester application


Building with lighting protector or aerial supply incoming

Building with underground supply and secondary


distribution in several floors
WITH LIGHTING PROTECTOR
SUPPLY BOARD
Type 1 Protector (high, 65kA, 4kV)
or
Type 2 Protector (medium, 40kA, 1.5kV)

UNDERGROUND SUPPLY
Type 1 Protector (high, 65kA, 4kV)
or
Type 2 Protector (medium, 40kA, 1.5kV)

DISTRIBUTION BOARD
Type 2 Protector (medium, 40kA, 1.5kV)
WITHOUT LIGHTING PROTECTOR
SUPPLY BOARD
Type 2 Protector (medium, 40kA, 1.5kV)

AERIAL SUPPLY

DISTRIBUTION BOARD
Type 3 Protector (accurate, 20kA, 1.5kV)

Type 1 Protector (high, 65kA, 4kV)

When electrical distribution systems are TT or TN-S (neutral to ground and protection earth to ground), the surge arresters must be equipped with
phase-neutral and neutral-ground protection.

When electrical distribution systems are TN (neutral to ground and protection earth to neutral) or IT (isolated neutral and protection earth to
ground) must be protected, in addition, with phase-ground protection. To install a protection device MCB or fuse upstream of the surge arrester is
advisable. At the supply point, the surge arrester must be installed immediately downstream of the main breaker.
Connection of the Terasaki surge arresters range is very simple
because their internal elements are pre-wired.

Type 1

TM65
1P. 65kA, 1,2kV, 5ns
TM80
4P. 80kA, 1,2kV, 5ns
TM35SP 1P. 35kA, 4kV, 5ns (wave 10/350s)

Type 2

TM45

1, 2, 4P. 45kA, 1kV, 5ns

Type 3

TM20

1, 2, 4P. 20kA, 0,96kV, 5ns

TM.....I surge arresters

TM.....II surge arresters


L1

L1

L/N

L/N

GND

GND

GDN

TM...IIII surge arresters

L1

L2

L3

L1
L2
N
L3
L1

GDN

52

L1
L2
N
L3
L2

L3

GDN

GDN