HVF VCB
HVG VCB
VCB
4◀
HVF Type
HVF
◆ With rigid structure and minimized moving parts, HVF breaker operation mechanism features
reduced maintenance requirements providing high reliability and long-life expectancy.
◆ The breakers are more compactly designed in size with high performance vacuum interrupters, which
are made with the special contact material and the advanced vacuum technology.
◆ This series are certificated by New IEC publication 62271-100, ANSI C 37 and other domestic standards.
Operating Mechanism
<Fig.1> Front view of HVF VCB
HVF circuit breakers have motor-spring energy stored
mechanisms of the rigid structure. It consists of the
charging mechanism, the closing spring, the trip spring,
the motor, solenoids, auxiliary switches, spring charged
and on/off indicators as shown in Fig.1. Manual Charge Hole Name Plate
Pole Part
The pole parts are placed on the rear side of the Frame Cap
operating mechanism. The internal side of the pole Upper Pole Support
parts are well enclosed by the tubular type insulation
frame as shown in Fig.2.
Vacuum Interrupter
This prevents dust on the internal insulation material
which is highly resistant to tracking.
Lower Contact
HVG Type
HVG
◆ HVG Vacuum circuit-breakers are very compact, so that it is possible to reduce the switchgear
size and to minimize its insulation space.
◆ This type has the compact structure, which can be easily maintained, so it requires minimized
maintenance.
Operating Mechanism
HVG vacuum circuit breakers have the simplified motor <Fig.3> Front view of HVG VCB
spring energy stored mechanism which consists of the
closing spring, the motor, link mechanisms solenoids, Control Jack
auxiliary switches and indicators as shown in Fig.3.
Close Button
Manual Charge Hole
The closing spring can be charged manually or
electrically, and released mechanically with the manual Name Plate
closing push button or electrically through the remote VCB Handle
Open Button
electrical control. On/Off Indicator
Counter
Draw In & Out
The released closing spring is automatically recharged Interlock Handle
by the charging motor, and capable of the operating
sequences“open-close-open”which is required when
Spring Charge Indicator Draw In & Out Plate Housing Box
unsuccessful auto-reclosing operation is attempted.
Pole Part
Insulation Frame
The pole parts are mounted on the rear side of the
Upper Terminal
operating mechanism in the insulation frame.
Vacuum Interrupter
Frequency (Hz) 50 / 60
3150 3150
Tripping Supply Voltage (V) DC 48, 60, 110, 125, 220 / AC 110, 125, 220
Control
Current (A) Refer to Table 3 (see page 15)
145 145
Frequency (Hz) 50 / 60
2500
3150
Tripping Supply Voltage (V) DC 48, 60, 110, 125, 220 / AC 110, 125, 220
160
※ 1) Type number in the square“ ” . Shall be listed as shown in the line for the rated current.
2) Power-frequency withstand voltage 65 kV is available on request.
VCB
8◀
Frequency (Hz) 50 / 60
3000 3000
Short-time Withstand Current (kA) 50 (2 sec) 40 (2 sec) 31.5 (3 sec) 40 (3 sec) 31.5 (3 sec) 25 (3 sec)
Tripping Supply Voltage (V) DC 24, 48, 60, 110, 125, 220 / AC 110, 125, 220
Control
Current (A) Refer to Table 3 (see page 15)
400 400
※ 1) Type number in the square“ ”
. Shall be listed as shown in the line for the rated current.
2) HVF705 type can be applicable to IEC 62271-100 standard.
Vacuum Circuit Breaker ◀9
Frequency (Hz) 50
3150 3150
Tripping Supply Voltage (V) DC 48, 60, 110, 125, 220 / AC 110, 125, 220
Control
Current (A) Refer to Table 3 (see page 15)
Frequency (Hz) 50 / 60
Fixed Type 52 63 65 65 65 65
Weight (kg)
Draw-out Type 52 67 70 70 70 70
Vacuum Circuit Breaker ◀ 11
Type of Mounting
As the standard version, the fixed type and three kinds of withdrawable type circuit breaker can
be provided on request.
The draw-out type breakers consist of truck, mechanical interlock, control terminal, and various
accessaries.
FS Cradle Draw-out type VCB with F type cradle (Nonmetallic partition with shutter)
GS Cradle Draw-out type VCB with G type cradle (Metallic partition & bushing with shutter)
※ Besides the standard version of draw-out circuit breakers, specially designed breakers like those for are available on
request, such as ANSI standards or retrofit.
◆ CO - 15 sec - CO
◆ O - 0.3 sec - CO - 3 min - CO
Switching Unloaded Transformer
◆ O - 15 sec - CO - 3 min - CO By the special contact materials, the chopping current of the
(O : Open, C : Close) vacuum circuit breakers is only 4 to 5 A, so overvoltage is
limited when transformers disconnected at no load condition.
Current Carring Capacity
HYUNDAI vacuum circuit breakers may be operated at ambient
Switching of Motors
temperatures between -25℃ and +40℃. The rated normal Long electrical lifetime at rated current lets HYUNDAI vacuum
currents determined according to IEC standards at an ambient circuit breakers be the excellent solution for high voltage
temperature of 40℃. motors.
When the breakers are operated at different termperature, the Surge absorber is recommended on these motors, which have
correction on operating current must be considered. Fig.9 less insulation level or less than 600 A starting current. Even
shows appropriate operating currents at different ambient though low surge occurrence is the feature of HYUNDAI
temperature. vacuum circuit breakers, the motor and the circuit itself can be
However, the diagram applies only to open type switchgear, so protected efficiently by the surge absorber.
metal enclosed switchgear load curents shall be reduced
accordingly.
Interruption of Transient Recovery Voltage
<Fig.9> Load characteristic curve HYUNDAI vacuum circuit breakers can break the accident
current properly at down steam of transformers, generators,
and current limit chokes, whose rising rates of transient
recovery voltage are higher than IEC Standard, even up to
10 kV/㎲.
1 - 630 A
2 - 1250 A
3 - 1600 A
4 - 2000 A
5 - 2500 A
6 - 3150 A
Vacuum Circuit Breaker ◀ 13
A metal-vapor arc discharge in the vacuum is initiated by If the metal vapor arc discharge can be maintained within
the current to be interrupted as the contacts open. The a certain level, the current is supposed to be chopped
current flows through this metal-vapor plasma until the prior to current zero.
next zero transition.
This chopping current must be controlled in order to
The arc extinguishes in the vicinity of the current zero, prevent build-up of unduly high overvoltages when
and the conductive metal-vapor condenses within a few inductive circuits are switched. The sintered CrCu contact
microseconds on the metal surfaces. limits the chopping current up to 4-5 A.
As a result, the dielectric strength in the contact gap is
rapidly rebuilt. The geometry and size of the contact are designed
differently according to breaking current and interrupter
The rapid build-up of the dielectric strength at the contact type.
gap enables the arc to be safely extinguished even if
contact separation takes place shortly before a current
zero transition. The maximum arcing time for the last pole
to clear is therefore only up to 15 ms.
1
2
5
6
7
10
11
<Table 1> Arc Quenching Medium
Service Life
HYUNDAI vacuum circuit breaker needs minimum maintenance due to the simple operating mechanism
and robust construction.
Vacuum circuit breaker shall be maintained periodically to ensure the perfect performance during
mechanical and/or electrical lifetime.
Please refer to the instruction manual for the detailed information.
HYUNDAI VCB adopts short-time duty charging motor, Closing solenoid and tripping solenoid operate latching
and the specification is stipulated on Table 3. mechanism for VCB springs, so the VCB can be
Since the motor operating time is short, the maximum controlled remotely.
value and inrush current are disregarded. The specification is mentioned on Table 3.
The solenoids unlatch the closing spring and opening
spring to close and open the VCB, respectively.
Auxiliary Contacts
Standard Accessories
HVF Type
<Fig.16>
GS Cradle ES / FS Cradle
Charging Handle Control Jack Lead Cable (2.5m, 1.5SQ) Control Jack Connector for C, D Type
for A, B Type Control Jack Control Jack
HVG Type
<Fig.17>
Fixing Plate (Fixed Type) Control Jack Lead Cable (2.5m, 1.5SQ)
Vacuum Circuit Breaker ◀ 17
Additional Option
HVF Type
Mechanism Operated Cell Switches (MOC) Earthing Switch Operation Indicator Contact
Additional Option
Vacuum Checker
Control Circuit
Optional Circuit
Control Circuit
XO
21
13
S21 S3
22 14 6 13
61 K1 S1 21 23 31 33 41 43 51 63 71 73 83 81
S1 4 14 Y1 S1
A1 62 22 24 32 34 42 44 52 64 72 74 84 82
8
M1 1 K1
A2 K1 7
5 53 22 32 42 52
13 21
R S1 S8
A1 S5 21 31 41 51
54 14 22
Y9
22 24 34 44 54
A2
S22 S9
12 14 23 33 43 53
21
S8 S9
11 13
XO
1 40 35 14 41 30 34 36 18 17 33 13 38 15 12 19 37 48 11 43 50 51 39 16 53 54 58 56
※ The state of the breaker : spring released; open; the truck is in the test position
HVF 725
XO
21
13
S21 S3
22 14 6 13
61 K1 S1 21 23 31 33 41 43 51 63 71 73 83 81
S1 4 14
Y1 S1
62
A1 22 24 32 34 42 44 52 64 72 74 84 82
8
M1 1
K1
A2 K1 7
5 53
13 21
R S1
A1 S5
54
Y9 14 22
22 A2
S22
21
XO
1 40 35 14 41 30 34 36 18 17 33 13 38 15 12 19 37 48 11 43
※ The state of the breaker : spring released; open; the truck is in the test position
AC Circuit
Layout
Detail A
HVF 1141 150 515 230 210 525 447 611 499 40 581 587 501 50 541 633
HVF 1142 150 515 230 210 525 447 611 499 50 581 587 501 50 541 633
HVF 1151 165 515 234 275 592 447 668 499 50 581 587 501 50 541 633
HVF 1152 165 515 234 275 592 447 668 499 50 581 587 501 50 541 633
HVF 1154 165 515 234 275 592 447 668 499 60 581 587 501 60 541 633
HVF 1162 165 515 234 275 592 447 668 499 50 581 587 501 50 541 633
HVF 1164 165 515 234 275 592 447 668 499 60 581 587 501 60 541 633
HVF 1167 210 610 249 310 630 447 738 549 90 710 587 549 90 640 633
HVF 1372 165 535 234 254 645 447 - - - - - - - - -
HVF 2141 150 515 230 210 525 447 611 499 40 581 587 501 50 541 633
HVF 2142 150 515 230 210 525 447 611 499 50 581 587 501 50 541 633
HVF 2152 165 515 234 275 592 447 668 499 50 581 587 501 50 541 633
HVF 2154 165 515 234 275 592 447 668 499 60 581 587 501 60 541 633
HVF 2162 165 515 234 275 592 447 668 499 50 581 587 501 50 541 633
HVF 2164 165 515 234 275 592 447 668 499 60 581 587 501 60 541 633
HVF 2167 210 610 249 310 630 447 738 549 90 710 587 549 90 640 633
HVF 3141 150 510 230 210 525 447 610 499 40 581 587 501 50 541 673
HVF 3142 150 510 230 210 525 447 610 499 50 581 587 501 50 541 673
HVF 3152 165 515 234 275 592 447 668 499 50 581 587 501 50 541 673
HVF 3154 165 515 234 275 592 447 668 499 60 581 587 501 60 541 673
HVF 3162 165 515 234 275 592 447 668 499 50 581 587 501 50 541 673
HVF 3164 165 515 234 275 592 447 668 499 60 581 587 501 60 541 673
HVF 3167 210 610 249 310 630 447 738 549 90 710 587 549 90 640 673
HVF 3362 254 813 235 254 592 447 - - - - - - - - -
HVF 3364 254 813 235 254 592 447 - - - - - - - - -
HVF 6111 210 560 298 310 688 447 774 549 40 640 587 549 50 647 784
HVF 6112 210 560 298 310 688 447 774 549 50 640 587 549 50 647 784
HVF 6141 210 560 298 310 688 447 774 549 40 640 587 549 50 647 784
HVF 6142 210 560 298 310 688 447 774 549 50 640 587 549 50 647 784
HVF 6144 210 560 298 310 688 447 774 549 60 640 587 549 60 647 784
HVF 7142 275 845 457 403 984 595 - - - - - - - - -
HVF 7144 275 845 457 403 984 595 - - - - - - - - -
HVF 2241/2 210 588 234 275 582 447 - - - - - - - - -
HVF 2252 210 588 234 275 582 447 - - - - - - - - -
HVF 2254 275 786 249 310 630 447 - - - - - - - - -
HVF 2262 210 588 234 275 582 447 - - - - - - - - -
HVF 2264/6/7 275 786 249 310 630 447 - - - - - - - - -
HVF 7252/4/6/7 300 908 583 533 1102 659 - - - - - - - - -
※ Dimension can be revised without notice.
VCB
24 ◀
Layout
Type a b c Detail
Layout
※ Standard Acc’y
Type Main Circuit Terminal
1) MOC Switch 5A+5B
2) TOC Switch 3A+3B
HVF 7052/7054/7056/7057 31.5 kA 1200/2000/2500/3000 A 3) Metal Shutter
4) Insulation Boots 6ea
5) Auto Control Jack 4NO+4NC
HVF 7062/7064/7066/7067 40 kA 1200/2000/2500/3000 A
Type A B C D E F G H I J K L
HVG 1099 8 kA 400 A 443 61
130
HVG 1011 12.5 kA 630 A
348 488 155 296 147 151 450 480 390
HVG 1131/2 20 kA 630 / 1250 A 482 100
140
HVG 1141/2 25 kA 630 / 1250 A
Layout
Type A D E F G H I J K L M N O P
HVG 1099 8 kA 400 A 96 40
130 500
HVG 1011 12.5 kA 630 A
HVG 1131 20 kA 630 A
70 68 320 464 570 155 299 660 530 4- 14
HVG 1132 20 kA 1250 A 136 80
140 540
HVG 1141 25 kA 630 A
HVG 1142 25 kA 1250 A
Type A B C D E F G H I J K L M
HVG 1099 8 kA 400 A 8
540 83 130 220 294 52 230
HVG 1011 12.5 kA 630 A 12
HVG 1131 20 kA 630 A 10
874 550 320 525 660 640
HVG 1132 20 kA 1250 A 15
73 140 223 291 55 227
HVG 1141 25 kA 630 A 10
HVG 1142 25 kA 1250 A 15
Ordering Form
Please stipulate the complete ordering form as shown below. Special design, which is not identified, shall be informed in advance
HV - - --
1 VCB Type HV - - ––
HV - - ––
4 2nd Ordering No. | Motor Control Voltage | 5 3rd Ordering No. | Close Control Voltage | 6 4th Ordering No. | Trip Control Voltage |