Sunteți pe pagina 1din 2

Mini & Micro Series, 19 inch shelf

DC Power System
-48 VDC, 1kW to 4kW
Introduction:
The next generation power system NetSure 211 series is optimized for 3G, FTTx, data
networks, transmission equipments and access network terminals which requires small, reliable, and easily adaptable
-48V DC Power system with excellent performance, high reliability and high power density. The system provides the
optimal solution for your business critical applications in the power requirement range of 2 kW to 4kW.

Features

Standard 19 inch sub rack with light weight, saving room space and installation cost

Full front operation, convenient for maintenance

Rectifier comply with EU ROHS, China ROHS, EMC EN55022 class B while meeting domestic and international
standards such as CE, UL and NEBS

Extra wide input voltage range, strong power grid adaptability

Wide operating temperature range for rectifier and controller, hot swappable, online maintenance

The monitoring module can save up to 200 pieces of historical alarm records, and 10 sets of battery test data
records.

Perfect battery management effectively prolongs battery service life


RS232 port, Ethernet, dry contacts and other communication ports provided, flexible networking is enabled to
achieve remote monitoring functions

The system has complete fault protection and fault alarm functions

Details:

NetSure 211 C23

NetSure 211 C45

DI/DO/temperature probe terminals AC input terminals

Rectifier

Rectifier

Monitoring module

Load MCB Battery MCB

NetSure 211 C46

Load socket
Rectifier

Dry contact and temperature


probe connection terminal

Monitoring module DC output terminals

DI/DO/temperature probe
DC positive busbar
connection terminal
AC input MCB Monitoring module Load MCB
Battery MCB

Battery socket

Battery terminals

Rectifier

R48-1000

Controller

M522B,M523B, M221B

Numbers of Rec.

Dimensions
(W X D X H mm)

1U high
437 289 43

2U high
437 289 88

3U high
437 289 132

Weight

7 kg

12.5 kg

13 kg

AC input

Single phase, input current of each rectifier 7A

AC distributions

L + N + PE/220V

S1:

L + N + PE/220V,

L + N + PE/220V

no AC input MCB
S2:

L + N + PE/220V,
1 40A/2P MCB

DC distributions

Maximum output

10 outputs:

S1: 4 20A/1P, 4 25A/1P MCB

8 10A, 2 20A fuse

S2: 2 20A/1P, 2 10A/1P MCB

32A/1P, 1 50A/1P MCB

40A

80A

80A

1 30A Bat fuse

S1: 2 63A/1P MCB

2 30A/1P MCB

7 outputs: 4 16A/1P, 2

current
Battery routes

S2: 1 63A/1P MCB

Rectifier R48-1000

Input
Input voltage

80 to 300Vac (Permitted Variation);

Frequency

200 to 250Vac (Nominal)

45 to 65Hz
0.99

Power factor
Output
Output DC voltage

-42 to -58Vdc

Output current

20.83 A @ -48Vdc

Output voltage range

-42.3Vdc ~ -57.6Vdc

Rated output voltage

-53.5Vdc

Output power

1000W@Vout > 48Vdc

Efficiency

92%

Temperature Range

-40 to +75 or -40 to +167 (Operating)

Controller: SCU+ series of M522B, M523B, M221B

M521B, M522B

M221B

M521B

M522B

M221B

Display

LCD with 8X16 characters

LCD with 8X16 characters

No display

Communication

RS232, Ethernet

RS232

RS232, Ethernet

2 battery currents, 1 load

2 battery currents, 1 load current,

current, 1 bus voltage, 1 battery

1 bus voltage, 1 battery voltage, 2 temperatures

Interface
Analog inputs

voltage, 2 temperatures,
3 AC voltages

Digital inputs
Outputs
Protocol

12 load fuses, 6 battery fuses, 2


bi-stable contactor statues, 2
user inputs
2 LVD mono or bistable
contactors, 2 user relay outputs

2 load fuses, 2 battery fuses,


bi-stable contactor statues, 2 user inputs
2 LVD mono or bistable contactors, 2 user relay outputs

HTTP, SNMP, YDN23, EEM, SocTpe, Rsoc