PRINCIPIOS DE GENERACION
INTRODUCCION A GENERADORES
OLYMPIAN
PRUEBAS Y EVALUACIONES EN GRUPOS
ELECTROGENOS
PUESTA EN MARCHA DE UN GRUPO
ELECTROGENO.
Principios de electricidad
La estructura de la materia
La corriente elctrica
Ley de OHM
LA INTENSIDAD DE LA CORRIENTE ELCTRICA QUE CIRCULA POR UN
CONDUCTOR ELCTRICO ES DIRECTAMENTE PROPORCIONAL A LA
DIFERENCIA DE POTENCIAL APLICADA E INVERSAMENTE
PROPORCIONAL A LA RESISTENCIA DEL MISMO
LEY DE WATTS
SISTEMA TRIFASICO
Potencia Aparente S
Potencia Activa P
Potencia Reactiva Q
Factor de Potencia
ELECTROMAGNETISMO
GENERACION DE ENERGIA
BB
TIME
Nbr.
Description
No.
Nbr.
Description
Stator assembly
107
Rotor assembly
124
Terminal plate
15
Fan
198
Regulator(AVR)
16
207
Rubber
28
Earth terminal
290
Housing
30
DE flange
291
Adaptation shaft
33
292
Rotor magnets
36
N.D.E.bracket
293
Stator
37
Tie rod
294
Fixing screw
41
D.E.terminal box
295
Tie rod
47
N.D.E.terminal box
296
48
297
End plate
49
20
320
Hub
51
322
Coupling disc
59
Inspection door
323
70
NDE bearing
324
79
325
90
343
91
347
98
Corner plate
349
O ring seal
100
Exciter armature
Fixing screw
1
Clamping washer
Spacer shim
ALTERNATOR PRINCIPLE
STATOR
WINDING
ROTOR
WINDING
ALTERNATOR PRINCIPLE
EXCITER FIELD
RECTIFIERS
STATOR
WINDING
ROTOR
WINDING
DIRECT
CURRENT
ALTERNATING
CURRENT
SHUNT PRINCIPLE
EXCITER FIELD
RECTIFIERS
STATOR
WINDING
ROTOR
WINDING
AVR
DIRECT
CURRENT
ALTERNATING
CURRENT
P.M.G.
RECTIFIERS
ROTOR
WINDING
A.V.R.
ALTERNATING
CURRENT
DIRECT
CURRENT
AREP PRINCIPLE
EXCITER FIELD
RECTIFIERS
STATOR
WINDING
ROTOR
WINDING
AVR
DIRECT
CURRENT
EXCITATION SYSTEMS
SHUNT + PMG
ADVANTAGES
DISADVANTAGES
AREP
SHUNT
High starting
capacity
High starting
capacity
Short-circuit
capability
Short-circuit
capability
Self protected
against short circuit
Intrinsic build-up
No extra length
No extra length
Extra
length
Specific winding
No short- circuit
capability
High number
of components
Low starting
capacity
Added cost
Sensitive to
distorting loads if
thyristor controlled
VOLTAGE
12 WIRE RECONNECTABLE MACHINE
EXAMPLE: STANDARD WINDING N 6 - 3 PHASE/ 2/3 PITCH.
VOLTAGE
12 WIRE RECONNECTABLE MACHINE
EXAMPLE: STANDARD WINDING N 6 - 3 PHASE/ 2/3 PITCH.
VOLTAGE
12 WIRE RECONNECTABLE MACHINE
EXAMPLE: STANDARD WINDING N 6 - SINGLE PHASE
(FF) CONNECTION
Alternator Labelling.
L L 2 0 1 4 H
Core Length
Manufacturer:
L = Leroy Somer
Number of Poles
Engine:
L= Perkins
A = Lister 3 Phase
B = Lister 1 Phase
Alternator Series:
1 = 1000
2 = 2000
etc.
Excitation:
1 = Shunt
2 = AREP
3 = PMG
Issue:
0 = First issue
L1
100
L2
120
140
80
L2
L3
L3
L1
L2
L3
70
90
100
120
120
DIRECT
CURRENT
ALTERNATING
CURRENT
MULTIMETER
MORE THAN
10,000 OHMS
MULTIMETER
LESS THAN
100 OHMS
Insulation Test.
1.Minimum acceptable value of insulation to earth is one Megohm.
2.The AVR MUST be disconnected before meggering the windings.
3.Megger the :- Main stator
Main rotor
Exciter stator
Exciter rotor
Meggering is only necessary if the generator has become wet or has not
been used for a long time.
Use a 500V Dc insulation tester.