Documente Academic
Documente Profesional
Documente Cultură
All the electrical equipment must be protected against internal and external
faults, a well a abnormal conditions which may endanger the equipment or
the system. Appropriate relays and devices have to be provided, to detect the
fault and potentially dangerous conditions and to isolate the concern
equipment at the earliest in order to minimize the damage.
The basic requirements of sensitivity, selectivity and speed
have to be met by provision of carefully selected relays and relaying
schemes. Since failure of a protection to operate cannot be ruled out, and it
can lead to damage of costly equipment, it is necessary to provide back ups
in the form of redundancy of relays, local or upstream back up relay etc.
However, continuity of power generation is also of utmost importance, and it
dictates that the risk of tripping (due to maloperation of the protection) when
a tripping is not really necessary, be minimized. This risk is related directly
to te number of relays and other elements in the protection scheme and its
complexity. Therefore, superfluous relays and devices must not to be
provided, and the protection schemes must be made as simple as possible.
Redundancy and back ups must also be minimized and tendency of overprotection checked.
The protection relays must be connected to automatically isolate the
endangered equipment if the damage is imminent or short circuit has already
occurred. However, in cases where the equipment or system is not
immediately endangered and can continue in service for some more time, the
protective devices should be connected to initiate only an alarm. This would
enable the plant operator to take the corrective steps and prevent a tripping,
or to prepare for outage of equipment (by changing over to standby
provisions or bringing down the unit load).
It is also important that the control room operator is not burdened
or confused with too many alarms. The alarm fascia on the UCB is therefore
to be used for annunciating only those abnormal conditions for which the
UCB operator has to take some distinct preventive or restorative action.
While tripping of all main equipment has to be annunciated in UCB, the
cause of tripping need not to be annunciated unless the UCB operator must
know it immediately to decide his future course of action. It is generally
adequate to register the cause of DAS printout, CRT display and / or with
INTRODUCTION TO MOTORS:
In present there is wide range of motors and its
characteristics are taken into existence. The present day tendency is to
employ motors to limit their thermal margins and characteristics of motor
starting current to flow for time in excess of motor starting time.
Usually in most of applications we use induction motor due
to its inherent good characteristics, easy speed control and good protection
scheme. The three phase induction motor principle is that the three phase
voltage produces current in the stator windings which sets up a rotating
magnetic field. The field flux cuts the short circuited rotor conductor and
induces a current in it. The interaction of flux and current produces torque
which causes rotation. A torque increase until it reaches maximum value, the
value at this point is known as full load torque. A further increase in speed
causes the torque to decrease until it would become zero if 100% speed
could be reached. At zero speed the torque is in excess of that demanded by
the fan and hence the motor accelerates. The speed increases studily as the
excess torque is roughly the same value up to 30% speed. After 40% speed
there is a large excess of torque so that the machine accelerates quickly until
it delivers the amount of torque required by the fan. If the fan dampers were
closed then the required torque is far less, the excess torque and therefore the
acceleration is greater and the machine runs up to speed quickly and delivers
the amount of the torque required by the fan.
The squirrel cage induction motor operation is simple to
understand as well as the speed and torque variation is simple.
The protection of motor will be so far simple. While
applying protection motor characteristics should be carefully considered.
The conditions for which motor protection is required can be divided into
two categories.
1. External conditions
2. Internal faults
Unbalanced supply voltages
Under voltage
Single phasing
29
MF4
28
TIE2A
27
MF4
26
MF4
Mill-7E
TO ash slurry
SWBD#OCB
INCOMER
FROM
UAT
Tie to stn.
Swbd OCA
6.6KV switchgear
MILL
25
MF4
24
MF4
23
MF5
22
MF2
21
TRF1
20
TFR1
19
MF1A
18
MF6
BCW pump
17
MF9
15
TRF3
14
TRF3
13
TRF3
11
MF3
10
9
8
MFE
TIE1A
TRF2
BPT1
MF2
TRF3
MF1D
TRF2
FPT1
1FI
Coal conveyor
FD fan
FD fan
1280
PA Fan
2940
CEP
962
MILL
583
1200
2750
900
525
6000
6600
6600
6600
Frequency(Hz)
50
50
50
50
+/-10.0
+/-3to5
+/-10.0
+/-3to5
+/-10.0
+/-3to5
+/-10.0
+/-3to5
80
80
85
90
995
1493
1486
589
126.5
42.0
273.0
59.0
96.5
31.0
68.0
33.0
0.86
0.83
0.76
0.04
0.13
0.97
0.9
0.87
0.05
0.11
0.85
0.82
0.74
0.017
0.208
0.72
0.66
0.54
0.0179
0.356
600
460at80%@
RV
600
460at80%
@RV
600
498at85%
@RV
450
405at90%
@RV
96.6
96.6
96.0
96.8
96.8
96.4
95.8
95.8
95.2
94.1
94.1
93.2
150/1A
315/1A
125/1A
75/1A
Permissible
variation of
Voltage %
Freq %
Min perms starting
voltage %
Rated speed(RPM)
At Rated volt & freq
Full load current
(A)
No load current
p. f. at load
100%
75%
50%
no load
starting
Starting current (%)
at
100% voltage
min stating voltage
Efficiency at rated
volta
100%
75%
50%
CT Ratio
PA FAN:
Definite time over current alarm relay CTU 32
Inverse time over load relay CDGM 12
Sensitive earth fault relay CTUM 13
CEP:
MILL:
Definite time over current alarm relay CTU 32
Inverse time over load relay CDGM 12
Instantaneous over current relay CAG 37
Sensitive earth fault relay CTUM 13
ABBRIVATION:
FIRST LETTER OPERATING QUANTITY:
A- Phase angle comparison.
B- Balanced currents
C- Currents (amps)
D - Differential
E -Direction
F -Frequency
I - Directional current
K Rate of rise of current
M - Manual
O Oil pressure
P Poly phase VA
R Reactive VA
S Slip frequency
T Temperature
V Potential (volts)
W Watts (power)
X Reactance
Y Admittance
Z Impedance
FOURTH LETTER:
M Special variations
First Figure: Indicates the number of units in the relay essential to its
operation not including seal in auxiliary units.
Second Figure: Indicates particular characteristics of one of a group of
similar relay e.g. CDG 11, CDG 12, CDG 13 and CDG 14 are all inverse
time over current relays but with different characteristic curves.
For example
CDG
C-currents
D- Induction disc
G- General or Generator
CTUM
C-current
T-Transistor
U-Definite time
M-special variations
RELAYS:
A relay is a device which detects the fault and supplies information to
the breaker for circuit interruption. A typical relay circuit can be divided into
in to three parts.
1. The primary winding of a current transformer which is connected in
series with circuit to be protected. The primary winding often
consists of main conductor itself.
2. Second circuit is secondary winding of CT connected to relay
operating coil.
3. The third circuit is tripping circuit, which consists of source of
supply, trip coil of circuit breaker and the relay stationary contacts.
Under normal load conditions, the emf of secondary winding of CT
is closed to relay contacts. This keeps the trip coil of circuit breaker
Application:
The type CAG 37 is a highest instantaneous
Overcurrent unit with low transient over reach and a high drop off /
pick up ratio.
Because of its infinitely variable settings and immunity
to offset transients, this relay has special advantages for protection
of feeders connected to high MV sources. Where lines are fed from
high MV sources, the impedance of the line causes a sharp
reduction in the fault current as the distance between the fault and
source increases.
Conventional instantaneous over current protection gives
good discrimination an economy on these lines, but a relay set to
detect symmetrical faults at the far end will over reach and cause
tripping for off set faults which are out side the protective zone.
The over current setting must, therefore, be raised in proportion to
the reach of the relay, with consequent loss of coverage for
symmetrical faults at the far end of the line.
General description:
The relay comprises of a standard DC hinged armature
unit fed via a single phase transformer and full wave bridge
rectifier. A residual screw is fitted with armature of the relay to
achieve a high drop off / pick up ratio. A potentiometer is
connected in parallel to the relay coil and adjustment of this varies
ALARM
TRIP
TECHNICAL DATA:
Current ratings:
Settings
1A or 5A
200 800 %, } continuously
500 2000 %} adjustable
Operating time:
See Fig 1
Thermal rating
Continuous:
o
Short time:
Burden:
200 800 %
Version
200%
800%
500 2000 %
Version
500%
2000%
At Rated current
At setting current
0.22VA 0.054VA
1.0 VA
3.5 VA
0.03VA
1VA
0.011
5VA
Application:
Stand by earth fault protection of neutral Earthing resistance and other
applications requiring long line delay.
General Description:
A non directional heavily damped induction relay which has an
adjustable long inverse definite minimum time / current characteristics. The
relay has a high torque moment combined with low over shoot. The relay
disc is so shaped that, as it rotates, the driving torque increases an off sets
the changing restraining torque of the control spring. This feature combine
with the high torque of the relay induces good contact pressure given at
currents near pick up. Damping of the disc moment is by a removable high
retentivity permanent magnate.
R
Y
B
GND
ALARM
TR I P
One unique method of winding the operating coil ensures that the time /
current characteristics are identical on each of the two current taps. Selection
of the required current setting is by means of a plug setting bridge which has
a single insulated plug. The higher current tap is automatically connected
when the plug is with drawn from the plug, allowing the setting to be
changed while in service without risk of open circuiting the current
transformers.
The relay operating time can be adjusted by the moment of the disc
back stop which is controlled by rotating a knurled Moulded disc at the base
of graduated time multiplier scale.
Type CDG 12 is a single pole relay and is available in this version.
TECHNICAL DATA:
Current ratings:
Settings:
Starting current:
Closing currents:
Resetting current:
General Description:
The operation is illustrated by block diagram shown in figure
When the positive peak of the input signal exceeds the reference
level the time delay circuit starts and after a preset time drives the output
relay.
INPUT
TRANSFORMER
LEVEL
DETECTOR
HIGHSET LEVEL
DETECTOR
HIGHSET OUTPUT
Instantaneous high set unit, when fitted, uses alternate half cycle for
measurement and through a separate level detector drives a separate output
relay. The static circuitry is fully protected against high transient voltages.
TECHNICAL DATA:
A. C. Burden:
TRANSIENT SUPPRESSOR
CURRENT
SETTING
OUTPUT
51I1
50
50L
50
51i2
TO DDCMIS
SPARE
R
Y
B
GN
SURGE
ARRESTE
CT
50N
2
6.6KV 3Ph
R
Y
B
51i1
50
V
C
50
51i2
B
TO DDCMIS
SPARE
C
T
R
Y
B
GN
87M
50N
2
51I1
50
50
51i2
TO DDCMIS
SPARE
R
Y
B
GN
SURGE
ARRESTE
CT
50N
2
Cs
C N T
51i2
86
50N2
43SS
52a
51i1
51i1
86
52Tc
51I1
Cs
C N T
51i2
86
87
M
50N2
43SS
52a
51i1
51i1
86
52Tc
TRIPPING CIRCUIT