Documente Academic
Documente Profesional
Documente Cultură
com
Abstract
A power swing may be caused by any sudden change in the configuration or the loading of an electrical network. During a power swing, the
impedance locus moves along an impedance circle with possible encroachment into the distance relay zone, which may cause an unnecessary
tripping. In order to prevent the distance relay from tripping under such condition, a novel power swing blocking (PSB) scheme is proposed in this
paper. The proposed scheme uses an adaptive neuro-fuzzy inference systems (ANFIS) for preventing distance relay from tripping during power
swings. The input signals to ANFIS, include the change of positive sequence impedance, positive and negative sequence currents, and power swing
center voltage. Extensive tests show that the proposed PSB has two distinct features that are advantageous over existing schemes. The first is that
the proposed scheme is able to detect various kinds of power swings thus block distance relays during power swings, even if the power swings
are fast or the power swings occur during single pole open conditions. The second distinct feature is that the proposed scheme is able to clear the
blocking if faults occur within the relay trip zone during power swings, even if the faults are high resistance faults, or the faults occur at the power
swing center, or the faults occur when the power angle is close to 180 .
2007 Elsevier B.V. All rights reserved.
Keywords: Power swing; Distance protection; Fuzzy logic
1. Introduction
Distance relays, which respond to changes in impedance,
will be affected by system power swings. These swings or
oscillations occur following a system disturbance such as load
change or fault clearance. As the generators attempt to find a
stable operating angle relative to each other, they overshoot
the fault position and continue to oscillate until steady state
is achieved. The extent of the oscillation depends upon the
severity of the disturbance and the characteristics of the system. The oscillation rate is determined by the inertia of the
system and impedances between different generators. When the
generators at both ends of a line protected by distance relays
oscillate, the impedance seen by the relays varies along some
locus. This locus can enter the characteristics of distance relays,
0378-7796/$ see front matter 2007 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2007.09.007
and cause the relays to trip if additional steps are not taken
[1].
When a power swing occurs, a change appears in the relative
voltage phase angle (i.e., power angle) between two groups of
generators. At a relay location, the measurable electrical quantities of voltage, current, apparent impedance, active power, and
reactive power will then vary as a function of this angle. When
a fault occurs, however, these quantities change abruptly. Such
behaviors are used in conventional power swing blocking (PSB)
devices as criteria to block or unblock the tripping [24]. However, the conventional power swing schemes have the following
problems:
They are not able to detect very fast power swings.
They are not able to distinguish faults with high grounding
resistance from power swings.
They are not able to clear the blocking of distance relay for
symmetrical faults that occur during power swings.
1139
They are not able to operate for a power swing during single
pole open condition.
Some of the existing PSB schemes are surveyed as follows.
In [5], the author uses a dual criterion based on the derivative of
measured resistance with respect to time to distinguish short circuit faults from power swings. However, it is difficult to choose
the setting value for the derivative of the resistance since it is
very small. In addition, the scheme may fail to trip high resistance short circuit faults that occur during power swings. Ref. [6]
presents an algorithm that is able to detect very fast power swings
(with a swing frequency of 5 Hz or higher). The algorithm also
attempts to immediately clear the blocking when a fault occurs.
However, the block clearing principle cannot function accurately
when the phase angle of relay voltage is close to 0 or 180 . Even
though the duration of this period is very short, the relay may
still malfunction if a fault occurs during this period. Some power
swing detectors are based on the superimposed components of
current or the change rate of measured impedance [7]. Although
these detectors are fast, they cannot operate for those faults with
very small superimposed components of currents. One example
is when the faults occur at the power swing center and when
the power angle is close to 180 . The detector proposed in [8]
is based on the discontinuity of the power swing center voltage (PSCV). However, this detector cannot detect the faults that
occur when the power angle is close to 180 , since those faults
cannot cause enough discontinuity of PSCV. Ref. [9] presents
two methods, one of which utilizes two impedance relays with
concentric circle characteristics and the other utilizes PSCV to
realize the swing blocking. The methods can effectively distinguish power swings from short circuit faults and trip faults with
a minimum actual delay depending on the fault occurrence time
and the actual swing frequency. These methods are very fast but
cannot distinguish high resistance faults from power swings.
Protection relaying is just as much a candidate for the application of pattern recognition. The majority of power system
protection techniques are involved in defining the system state
through identifying the pattern of the associated voltage and
current waveforms measured at the relay location. This means
that the development of adaptive protection can be essentially
treated as a problem of pattern recognition or classification, in
which artificial intelligences (AIs) are powerful. AIs possess
excellent features such as generalization capability, noise immunity, robustness, and fault tolerance. Consequently, the decision
made by an AI-based relay will not be seriously affected by
variations in system parameters. AI-based techniques have been
used in power system protection and encouraging results have
been obtained [1015].
In this paper, an adaptive neuro-fuzzy inference system
(ANFIS) approach is used as pattern classifier for detecting
power swings and a very accurate PSB scheme is designed. It
will be shown that with appropriate choice of input signals, the
ANFIS-based PSB scheme can be both reliable and accurate.
The rest of the paper is organized as follows. Section II
presents the proposed PSB scheme with emphasis on the choice
of input signals to ANFIS. The proposed scheme is tested in
Section III to evaluate its ability to detect power swings under
1140
(1)
(2)
(3)
(4)
1141
Table 1
Patterns generation
Condition
Slow and fast power swing with and without faults, different faults without power swing
(single phase to ground, phase-to-phase to ground, phase-to-phase, three-phase)
V p (n)
Ip (n)
(5)
(6)
Fig. 7. The PSB output for a power swing with fsm = 5 Hz.
Fig. 8. The PSB output for a power swing with fsm = 0.2 Hz and a three-phase
fault t = 280 ms.
1142
(degree)
0.1
1
2
2
5
2
5
3
4
0.2
0.3
1
3
4
0
10
10
5
10
20
10
10
20
5
5
10
10
0
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
Block
output linear functions (consequent parameters). The parameters are obtained using the ANFIS learning algorithm, which is
a hybrid algorithm based on gradient descent and least-square
estimate.
(degree)
60
180
100
0
130
180
90
180
60
(degree)
30
270
270
90
90
60
90
210
90
fsm: maximum slip frequency, : initial power angle, : fault inception angle, PSC: power swing center.
Reset
Reset
Reset
Reset
Reset
Reset
Reset
Reset
Reset
Block
Block
Block
Block
Block
Block
Block
Block
Block
1143
Table 4
Test results for earth faults with high fault resistance
Rf ()
(degree)
100
100
90
80
100
120
110
70
95
0
45
30
45
60
0
60
30
45
Block
Block
Block
Block
Block
Block
fashion, and the output remains stable after the power swing
is identified. Fig. 8 shows R and X seen by distance relay and
the PSB output for a power swing with fsm = 0.2 Hz. The power
swing is caused by a three-phase fault at line CB. A three-phase
fault is then applied to line AB (circuit 1) at t = 280 ms. As
shown in Fig. 8, the PSB output decreases to zero after the second fault occurs. Therefore, the relay will reset in response to
an internal three-phase fault during a power swing. Results in
Figs. 7 and 8 show that the proposed PSB scheme is accurate
and reliable.
3.4. Comparison with conventional power swing blocking
The conventional PSB schemes often utilize an impedancebased method due to the fact that the impedance locus changes
slower during a power swing than when a fault occurs. MHO
power swing detection is one of the conventional PSB schemes
and used in this paper for comparing the ANFIS-based PSB
scheme with the conventional PSB schemes.
1144
obtained for different power swings with and without the presence of fault.
3.4.1. Power swings with different slip frequencies
Table 2 shows the test results of the two schemes during power
swings with different slip frequencies and initial power angles.
As shown in Table 2, the proposed scheme is able to operate
for all conditions but the MHO scheme is unable to detect fast
power swings.
3.4.2. Faults during power swings
Table 3 shows the test results of the proposed scheme and
the MHO scheme for different three-phase faults during power
swings with different conditions. The power swing center is at
line AB (circuit 1) and 110 km from the relay location under
the testing condition. Table 3 shows that the proposed scheme
is always able to detect faults during power swings at different
conditions, while the MHO scheme does not reset for any cases
and the distance relay remains blocked. It should be pointed out
that the proposed scheme can even detect faults that occur at the
power swing center or faults that occur while the power angle is
180 .
3.4.3. High resistance faults during power swings
Table 4 shows the test results of both schemes for different
earth faults with high fault resistance. It is shown that the MHO
scheme blocks some earth faults but the proposed scheme does
not block under any conditions.
The above studies show that the proposed scheme is better
than the conventional MHO scheme in the detection of power
swings and faults during power swing and the stability for high
resistance faults.
Fig. 14. Outputs of PSB and distance relay for disturbance caused by fault F in
line DT.
1145
Fig. 15. Disturbances F1 in line DT (10 ms) and F2 in line ST (620 ms).
The logic unit issues suitable order based on results from phase
selection, power swing blocking unit, and impedance measuring
units.
The proposed PSB scheme has been tested for several multimachine systems, one of which is shown in Fig. 12. A relay is
installed in line ST at bus S. An external fault F occurs at 10 ms
and clears at 400 ms. The first and second zone of distance relay
and impedance measured by the relay are shown in Fig. 13.
The fault falls into the second zone of distance relay (point F).
The clearance of fault F causes a power swing. After the fault
clearance (point C) the impedance locus moves from path 1 to
path 2.
Fig. 14 shows the output of the proposed PSB scheme and the
output of the AB measuring unit of the distance relay (zone 1 and
2) for the above disturbance. The output of PSB is 0 before fault
clearance (400 ms), but changes to 1 when it detects a power
swing about 80 ms after the fault clearances. The AB unit of the
distance relay is 0 for 110 ms after the fault clearance, and then
changes to 1 again. The distance relay would have operated if
there were no PSB unit. Therefore, this PSB unit increases the
security of power system protection.
Fig. 15 shows another scenario of the previous network,
where an internal fault F2 occurs in line ST during a power
swing caused by an external fault F1 that occurs in line DT.
Fig. 16 shows the impedance loci in RX diagram. The output of the proposed PSB scheme and the output of the AB
Fig. 17. Outputs of PSB and distance relay for disturbances caused by faults F1
and F2.
Fig. 16. Impedance seen by distance relay for disturbances in line DT and line
ST.
[1] E. Kimbark, Power System Stability, vol. 2, John Wiley & Sons, 1997.
[2] A. Mechraoui, D. Thomas, The influence of power swing on transmission line distance protection, measurement of power and voltage phasor
oscillation at the relaying point, UPEC 93 2 (1993) 585588.
1146