Abstract of data considered for power evacuation

Sl. No.
1
2
3
4
5
6
7
8
9
10

Abstract of data considered for power evacuation


Details
Beawar Cement plant details
Ras Cement Plant details
Ras power plant
SMP (Shree Mega Project) power plant
Generator details
AVR details
Governor details
Transformer details
Load details
Transmission Line data

Excel Sheet
Beawar
Ras Cement
Ras PP
SMP
Gen
AVR
GOV
Trafo2/Trafo3
Load
Tline

Plant details

Grid details

Grid demand

Overall plant Power factor measured at Grid bus


GRID fault level

Grid frequency variation

Grid Substation details of Beawar 132/220kV GSS

lant details
Topographical details of SMP plant
Details on GPP operation plan & contribution at peak/off-peak conditions
whether SMP is CPP or IPP?
Power export from SMP is within the state or outside the state

rid details
Grid Voltage Variation in kV
Minimum Voltage
Maximum Voltage
Nominal Voltage

rid demand
Contract demand in MVA
Minimum Drawl from the grid in MVA
Maximum Drawl from the grid in MVA
Minimum export to the grid in MVA
Maximum export to the grid in MVA

verall plant Power factor measured at Grid bus

RID fault level


Minimum
Maximum

rid frequency variation


Minimum
Maximum
Average/Nominal

rid Substation details of Beawar 132/220kV GSS


incoming and outgoing transmission lines
loading of S/S
bay availability information

Data Requirement- Beawar C


Sl. No.
1
2
3
4
5

6
7

Data Requirement- Beawar Cement pla


Required data

Complete generator details of 2 x 19 MW + 1 x 6 MW TGs and 1 x 3MW + 1 x 18MW GPPs in the form

Complete AVR and governor model details for all TGs and GPPs in the format as described in sheets 'A

Details of individual generator transformers and interconnecting transformers in the format as describ
Details of cement plant loads and generator auxiliary loads, at respective bus sections

Conductor type, length and parameters used in 132kV line between Beawar cement plant and Beawa

Conductor type, length and parameters used in 132kV line between Beawar cement plant and RAS ce
with Tower configurations, D.C/S.C, height of bottom conductor and phase spacing ( all if available) fo
Detailed SLD of the Beawar Cement plant

Check list

Data Requirement- Ras Cem


Sl. No.
1
2
3
4
5
6
7
8

Data Requirement- Ras Cement plant


Required data

Complete generator details of 4 x 18 MW TG and 1 x 25MW GPP in the format as described in sheet 'G

Complete AVR and governor model details for all TGs and GPP in the format as described in sheets 'AV

Details of individual generator transformers and interconnecting transformers in the format as describ
Details of cement plant loads and generator auxiliary loads, at respective bus sections

Conductor type, length and parameters used in 132kV line between Beawar cement plant and RAS ce

Cable length, size, no of cores, runs and parameters used in 132kV cable between Ras cement plant a
described in sheet - 'Tline'
Detailed SLD of the Ras Cement plant

Line CTs, PTs and other equipment details of the 132 kV line between RAS cement plant and Beawar c

Check list

Data Requirement- Ras po


Sl. No.
1
2
3
4
5
6
7

Data Requirement- Ras power plant


Required data
Complete generator details of 2 x 50 MW TGs and in the format as described in sheet 'Gen'

Complete AVR and governor model details for TGs in the format as described in sheets 'AVR' and 'GOV

Details of generator transformers and interconnecting transformers in the format as described in shee
Details of power import/export to Ras Cement plant
Details of generator auxiliary loads, at respective bus sections
Detailed SLD of the Ras power plant

Conductor type, length and parameters used in 220kV LILO line between Beawar GSS and Merta in th
configurations, D.C/S.C, height of bottom conductor and phase spacing ( all if available) for proper cal

Check list

Data Requirement- SMP po


Sl. No.
1
2
3
4
5
6
7
8
9
10

Data Requirement- SMP power plant


Required data
Complete generator details of 2 x 150 MW TGs and in the format as described in sheet 'Gen'

Complete AVR and governor model details for TGs in the format as described in sheets 'AVR' and 'GOV

Details of generator transformers and interconnecting transformers in the format as described in shee
Details of power import/export from existing cement plant and Ras power plant
Details of generator auxiliary loads, at respective bus sections
Detailed SLD and equipment details of the SMP power plant
Location of SMP,
GPP operation plan & contribution at peak/off-peak
Whether SMP is IPP /do they want to sell power to State/within state/outside state

Conductor type, length and parameters used in 400 kV LILO line between KOTA and Merta in the form
configurations, D.C/S.C, height of bottom conductor and phase spacing ( all if available) for proper cal

Check list

Sl. No.

Data required

IEEE type number of the model used in the AVR

Details and values of the limiters used in AVR if available-example is shown below

Typical AVR Model for 120 MW unit


The block diagram of AVR model and time constant for 120 MW unit are as per
figure 1 and table 1 respectively.

Figure 1: Block diagram of AVR model for 120MW generator


Table 1: AVR data
Constant

Name

AVR type

As per IEEE standards

Trec

Input rectifier time constant

T4

Amplifier time constant-1

T2

Exciter time constant

T3

Regulator stabilizing circuit time constant-1

T5

Regulator stabilizing circuit time constant-2

k1

Amplifier gain

VRmin

Minimum amplifier output

VRmax

Maximum amplifier output

Efdmin

Minimum field voltage in pu

Efdmax

Maximum field voltage in pu

Typical AVR Model for 18 MW unit

Vref
VT

+
-

SE

VRmax

ka

Vref
+

VT

SE

VRmax

1 sTrec
+

ka
1 sTa

+
VRmin

Vs

skf

1 sT 1 sT
f1

f2

Figure 2 Block diagram of AVR model for 18MW generator


Table 2 : AVR Data for 18MW TG
Constant

Description

Trec

Rectifier time constant

Ta

Amplifier time constant 1

Te

Exciter time constant

Tf1

Regulator stabilizing circuit time constant

Tf2

Regulator stabilizing circuit time constant

Ka

Amplifier gain

Ke

Exciter Constant

Kf

Regulator stabilizing circuit gain

Vse1

Saturation function at 0.75 times maximum field voltage

Vse2

Saturation function at maximum field voltage

Vrmax

Maximum amplifier output

Vrmin

Minimum amplifier output

Efdmax

Maximum field voltage

Efdmin

Minimum field voltage

1
ke sT

ample is shown below

Value
120 MW
TYPE - 1
0.02
0.01
0.18
1.3
0.11
200
-4.3
4.3
0
2.7

SE
+

Efd

SE
+

1
ke sTe

G
Value
0.02
0.02
0.8
1
0.1
25
1
0.01
0.5
0.86
5.58
0
3
0

Efd

Table No 4: Generator Data


Sl No

Beawar Cement Plant

Generator Name

TG1 & 2

TG3

3MW TG

GPP1 (3MW)

MW rating

18.50

19

2.5

18

MVA rating

20.56

22

7.5

2.91

22.5

No. of units

Rated voltage in kV

6.6

11

11

6.6

6.6

Rated power factor

0.9

0.8

0.8

0.85

0.8

Armature Resistance (Ra) in pu

0.0072

0.01743

0.093641

0.044207

0.04

Negative Sequence Reactance

0.22

0.17

0.16

0.163

0.1273

Zero Sequence Reactance

0.15

0.1

0.084

0.0416

0.058

Direct Axis Reactance (Xd) in pu

1.668

1.35

1.66

1.52

1.52

10

Direct Axis Transient Reactance (Xd') in pu

0.1853

0.247

0.21

0.215

0.154

11

Direct Axis Sub- Transient Reactance (Xd") in pu

0.1237

0.191

0.166

0.1335

0.1224

12

Quadrature Axis Reactance (Xq) in pu

1.9

1.27

1.58

1.35

13

Quadrature Axis Transient Reactance (Xq') in pu

0.45

1.26

1.57

1.25

14

Quadrature Axis Sub- Transient Reactance ( Xq") in pu

0.16

0.166

0.15

0.12

15

Direct Axis Transient Open Circuit Time Constant (Tdo)

5.9

5.3

5.3

16

Direct Axis Sub Transient Open Circuit Time Constant (Tdo)

0.021

0.045

0.03

0.03

17

Quadrature Axis Transient Open Circuit Time Constant (Tqo)

3.5

5.3

18

Quadrature Axis Sub Transient Open Circuit Time Constant (Tqo)

0.1

0.042

0.026

0.03

22

Total Inertia Constant (Generator+Exciter+Turbine) in MJ/MVA

1.78

1.781

1.78

23

NGR/NGT value in Ohms

44

63.51

63.51

38

11

38

Sl. No.

Data required

Number of stages in governor action

Details and values of the limiters used in Governor if available

a) Governor:
1) Make
2) Type (Electronic or Electromechanical or Electrohydraulic)

Turbine Governor Model - 120MW


The block diagram of Governor model and the time constants for 120MW are as per
figures 1 (a) & (b) & tables 1 (a) & (b) respectively.
P-up
C max

+
Pref

ref
1+sT2
0 k1(1+sT 1)

Pmax
1/S

1/T 3
-

Pmin

C min
P-dn

Figure 1(a): Block diagram of governor model for 120 MW generator


Table 1 (a): Steam governor data for 120 MW generator
Sl No

Value

Constant

120 MW

1 K1 (droop)

0.05

2 T1 (sec)

0.35

3 T2 (sec)

0.05

4 T3 (sec)

0.1

5 Pmax (pu)

1.05

6 Pmin (pu)

0.1

7 Cmax (Rate of valve opening) - pu/sec

0.3

8 Cmin (Rate of valve closing) - pu/sec

-1
P

k1+k2

k3+k4

k5+k6

k7+k8

Ps
1/(1+sT 1 )

1/(1+sT 2)

(1/1+sT3)

(1/1+sT 4)

P5

k1+k2

k3+k4

k5+k6

k7+k8

Ps
1/(1+sT 1 )

1/(1+sT 2)

(1/1+sT3)

(1/1+sT 4)

Figure 1(b): Block diagram of turbine model for 120 MW generator

Table 1 (b): Steam turbine data for 120 MW generator


Sl No

Constant

Value

Power extraction at HP turbine

Description

k1 + k2

0.3

Power extraction at IP turbine

k3 + k4

0.397

Power extraction at LP turbine

k5 + k6

0.303

HP section time constant

T1

0.1

IP section time constant (including reheat)

T2

10

LP section Time constant

T3

0.14

Not applicable

T4

999

Turbine Governor Model - 18MW


The block diagram of Governor model and the time constants for 18MW is as per figures
2 & table 2 respectively.

Figure 2: Block diagram of turbine model for 18 MW generator

Table 2: Steam turbine data for 18 MW generator


Sl. No.

Description

Constant

Value

Droop
Phase compensation

s
T1

0.05

2
3

Phase compensation

T2

0.03

Servo time constant

T3

0.1

HP section time constant

Thp

0.26

Rate of change of valve


Opening (pu/sec)

Gpup

0.1

Rate of change of valve


Closing (pu/sec)

Gpdown

-1

Maximum power limit

Pmax

1.05

Minimum power limit

Pmin

0.1

Load Details
Sl. No.
1
2
3
4
5
6
7
8
9
10
11
12

Load
Name

Average Load
Load in A

Load in
MW

Minimum Load
Load in
MVAR

Load in A

Load in
MW

Load Details

mum Load
Load in
MVAR

Peak Load
Load in A

Load in
MW

Connected Load
Load in
MVAR

Load in A

Load in
MW

Load in
MVAR

Sl. No.

Transformer Name

MVA Rating
Primary Voltage in kV
Secondary Voltage in kV
% Positive seq Impedance
% Zero seq Impedance
Winding Config
Type of tap change (On load or Off-load)
Tap Position

Total no of taps
Nominal tap
Set tap

Min & Max Tap range in pu (or) %


Tap Voltage

2.5 Aux Tr01

Transformer Data
3

2.5 Aux Tr6 MVA AUX


02

GT-1

GT-2

TR-01

TR-02

2MVA (3 nos1 MVA-aux for GPP Aux TRTR01,TR3,TR4 2MVA (TR5)


3MW boiler
01
)

GPP Aux TR02

TR03
(proposed)

2.5
6.9
0.433

2.5
6.9
0.433

6
11
6.9

20/25/31.5
11
6.9

20/25/31.5
11
6.9

20/25
6.9
132

20/25
6.9
132

2
6.9
0.433

2
6.9
0.433

1
6.9
0.433

2
6.6
0.433

2
6.6
0.433

25
132
6.6

7.3

7.3

7.121

13.68/12.55/11.84

13.68/12.55/11.84

9.2/11.5

9.2/11.5

6.53

5.85

5.38

8.42

8.64

9.5

Dyn11
Off-load

Dyn11
Off-load

Dyn1
Off-load

DYn1
On-load

DYn1
On-load

Ynyn0
On-load

Ynyn0
On-load

Dyn11
Off-load

Dyn11
Off-load

Dyn11
Off-load

Dyn11
Off-load

Dyn11
Off-load

YnYn0
OLTC

17

17

21

21

21
11

oltc

oltc

oltc

3
5to+5%

3
5to+5%

4
5to+5%

oltc
10to+10%

10to+10%

4
5to+5%

4
5to+5%

5to+5%

5to+5%

5to+5%

-15% to
+10%

Min in kV
Max in kV
NGR Value in Ohm

38.1

38.1

38.1

36.5

36.5

38.1
Auxil fr cement plant

Three Winding Transformer data


1

Manufacturer Name

Substation name

From location

To location

Primary MVA Rating

Secondary MVA Rating

Tertiary MVA Rating

Primary voltage rating

Secondary voltage rating

10

Tertiary voltage rating

11

Positive Seq. Percentage Impedance (HV-LV)

12

Positive Seq. Percentage Impedance (LV-TV)

13

Positive Seq. Percentage Impedance (HV-TV)

14

Total no of taps

15

Tap range in % (or) kV

16

Type of tap change (On load or Off-load)

17

Winding Connection (Primary Side)

18

Winding Connection (Secondary Side)

19

Winding Connection (Tertiary Side)

20

NGR value in ohms

Transmission Line / Cable Data


Sl No
1
2
3
4
5
6

From location

To location

Cable type /
Conductor

Distance in
meters

Breaker (in
kA)