S280-85-2
Figure 1.
Typical Kyle three-phase recloser suspended from a KA146W5 pole-mounting hanger.
86844KMA
Contents
Safety Information ..................................................... 2
Introduction ............................................................ 3
Single Pole-Mounting Hanger and Tank-Lifting Windlass Assembly and Installation Instructions
SAFETY
FOR LIFE
SAFETY
FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively
promote safe practices in the use and maintenance of our products through our service literature, instructional training
programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,
marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high voltage lines and equipment and support our Safety For Life mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a substitute for proper training or adequate experience in the
safe operation of the equipment described. Only competent technicians, who are familiar with this equipment
should install, operate, and service it.
A competent technician has these qualifications:
Is thoroughly familiar with these instructions.
Is trained in industry-accepted high- and low-voltage
safe operating practices and procedures.
Is trained and authorized to energize, de-energize,
clear, and ground power distribution equipment.
Is trained in the care and use of protective equipment
such as flash clothing, safety glasses, face shield,
hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe installation and operation of this equipment, be sure to read
and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements
that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual.
DANGER: Hazardous voltage. Contact with high
voltage will cause death or severe personal injury.
Follow all locally approved safety procedures when
working around high and low voltage lines and equipment.
G103.3
WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read
and understand the contents of this manual. Improper
operation, handling or maintenance can result in death,
severe personal injury, and equipment damage. G101.0
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only.
G102.1
S280-85-2
SAFETY
FOR LIFE
PRODUCT INFORMATION
Introduction
This manual contains assembly and installation instructions for the KA146W5 Single Pole-Mounting Hanger and
the KA146W2 Tank-Lifting Windlass.
Additional Information
These instructions cannot cover all details or variations in
the equipment, procedures, or process described, nor to
provide directions for meeting every possible contingency during installation, operation, or maintenance. For
additional information, contact your Cooper Power
Systems representative.
Quality Standards
ISO 9001:2000 Certified Quality Management System
Description of Operation
The Kyle KA146W5 suspension-type hanger enables
the mounting of Kyle three-phase reclosers, GW and
GWC sectionalizers, and VRV oil switches on single
poles. No crossarms are required.
The KA146W2 tank-lifting windlass is easily attached as
a unit to the back of the mounting hanger with only two
bolts. The windlass simplifies lowering the recloser tank
for inspection and maintenance, but can not be used for
lowering the entire recloser.
Single Pole-Mounting Hanger and Tank-Lifting Windlass Assembly and Installation Instructions
A grounding connector is furnished to ground the complete equipment through the KA146W5 mounting frame.
Reclosers with line-to-ground closing coil connections
must use the ground connector on the recloser head
casting to help assure proper operation.
TABLE 1
Mounting Hanger and Clearance Dimensions
Unit Type
Bushing
Creepage
VW, VWE, W, WE
Std. or 17"
8-1/2
25-7/8
11-3/8
VW, VWE, W, WE
Std. or 17"
13-1/4
25-5/8
11-3/8
13
25-1/16
11-3/8
Std. w/bcts
17-1/2
25-1/16
11-3/8
26-1/2"
17-1/8
25-1/8
11-3/8
26-1/2"
13-1/4
21-15/16
15-1/16
Dimension (in.)
B
C
w/BCTs
VWV, VWVE,
Std.
VWV27,VWVE27
WV, WVE, WVE27
VWV, VWVE,
VWV27, VWVE27,
WV, WVE, WVE27
VWV, VWV27,
VWV38, VWVE
VWVE27, VWVE38,
WV, WV27, WV38,
WVE, WVE27, WVE38
WV38X, WVE38X,
VWV38X, VWVE38X,
GW, GWC, VRV
Std.
13
25-1/8
11-3/8
RX, RXE
Std. or 17
7-7/8
25-5/8
11-3/8
RX RXE
Std. or 17
12-5/8
25-5/8
11-3/8
13
25-1/16
11-3/8
17-1/2
25-1/8
11-3/8
w/bcts
RV, RVE
Std.
RV, RVE
Std. w/BCTs
Figure 2.
Outline dimensions of KA146W5 pole-mounting hanger and KA146W2 tank-lifting windlass.
4
S280-85-2
SAFETY
FOR LIFE
1. Dismantle the shipping bundle and check the components against the bill of material and the exploded
view diagram and parts (Figure 3).
3. Attach support channels (2 and 3) to outboard support angle (1), against side to be located away from
pole. Insert a round spacer (4) between angle and
channels. Fasten with 1/2-13 x 2 inch bolts (13),
beveled washers (12), lockwashers (15), and nuts
(16).
4. Inboard support
Follow all approved safety practices for rigging and lifting. Lift the load smoothly, and do not allow it to shift.
WVE38X
and
VWVE38X
Single Pole-Mounting Hanger and Tank-Lifting Windlass Assembly and Installation Instructions
Description
Part No.
1
2
3
4
5
6
7
8
9
10
11
Support angle
Support channel, right-hand
Support channel, left-hand
Washer
Brace, right-hand
Brace, left-hand
Vertical angle, right-hand
Vertical angle, left-hand
Pole mount, upper
Pole mount, lower
Washer for pole bolts
(not shown )
Bevel washer
Hex bolt,1/2-13 x 2 in.
Hex bolt,1/2-13 x 1-1/2 in.
Lockwasher, 1/2-in.
Hex nut, 1/2-13 UNC-2B
Ground connector
Lifting decal
KP308W
KP134WV
KP135WV
KP2028A61
KP306W
KP307W
KP277W
KP292W
KA174W1
KA174W2
2
1
1
4
1
1
1
1
1
1
DT28X
KP448R1
K730101150200Q
K730101150150Q
K900801050000Z
K880201113050Q
KP1596R
KP310W
2
6
6
23
29
21
1
2
12
13
14
15
16
17
18
Qty
Figure 3.
Exploded view and parts list for KA146W5 pole-mounting hanger.
6
S280-85-2
SAFETY
FOR LIFE
10
11
12
Figure 4.
Exploded view and parts list for KA146W2 tank-lifting windlass.
1. The gear box and spool (4), spool assembly (5), pipe
(6), and roll pins (7) may already be assembled to the
support angle (8). If not, assemble as shown in
Figure 4. Use two 1-inch bolts (1 ) and lockwashers
(2) to fasten the gear box to the support angle. The
spool assembly includes hardware.
13
14
15
16
Description
Part No.
Qty
KP1085
KP1107
KP1214
KA151W
KA15CE1
KP1054CE11
KP1313
KP294W
4
4
2
1
1
1
4
1
KP3015A28
KA148W
KA147W
KP293W
KA121 R
KA592R3
KP1031 R
KP1354
1
2
2
1
2
Figure 5.
KA146W2 tank-lifting windlass installed on a hanger.
7
Single Pole-Mounting Hanger and Tank-Lifting Windlass Assembly and Installation Instructions