For = 1800 and rectangular hood loss factor = 0.65 from FIGURE 5-15
Acceleration Factor = 1
Acceleration Factor is generally taken as 1 for hoods.
Duct Entry Loss per VP = 1.65
Duct Entry Loss per VP = Duct Entry Loss Factor + Acceleration Factor
Duct Entry Loss = 2.046
Duct Entry Loss = Duct Entry Loss per VP * Duct VP
Other Losses = N / A
Hood Static Pressure (SPh) = 2.046
Hood Static Pressure (SPh) = Slot Static Pressure + Duct Entry Loss +
Other Losses
Straight Duct Length = 15 (Given)
Friction Factor (Hf) = 0.0703
From TABLE 5-5 at V = 4000 fpm and D = 8
Friction Loss per VP = 1.0545
No. of 900 degree elbows = N / A
Elbow Loss Coefficient = N / A
Elbow Loss per VP = N / A
No. of Branch Entries = N / A
Entry Loss Coefficient = N / A
Entry Loss per VP = N / A
Entry Loss per VP = No. of Branch Entries * Entry Loss Coefficient
Special Fittings Loss Factors = N / A
Duct Loss per VP = 1.0545
Duct Loss per VP = Friction Loss per VP + Elbow Loss per VP + Entry
Loss per VP + Special Fittings Loss Factors
Duct Loss = 1. 3080
Duct Loss = Duct Loss per VP * Duct VP
Duct SP Loss = 3.350
SP Loss = Hood Static Pressure + Duct Loss
Other Losses = N / A
Cumulative Static Pressure = 3.350
Governing Static Pressure = -3.350 wg
It is a negative pressure
Corrected Volumetric Flow rate = N / A
Corrected Velocity = N / A
Corrected Velocity Pressure = N / A
Where:
= mechanical efficiency (generally taken as 0.9)
BHP = 3.603 * 1500 / (6362 * 0.9) = 0.94