Documente Academic
Documente Profesional
Documente Cultură
Volume 3, No. 1
January 2003
Standard Method of
Determining Fire Resistance of Concrete and
Masonry Assemblies
(ACI 216.1-97/TMS
0216-97) 4 contains
equivelent thickness
tables for masonry to
help determine the fire
ratings of masonry assemblies, fire rated control and expansion joint
details, and information on fire ratings for
masonry columns and
lintels.
shown that for concrete masonry wall assemblies, the fire resistance rating is dependent on the aggregate composition of
the concrete masonry unit (CMU) and the CMUs equivalent
thickness. Through a testing program using different aggregate-type CMUs, a database exists of observed fire resistance
ratings as a function of aggregate types. From this database,
conservative equivalent thicknesses were chosen and are used
as minimum requirements. For clay masonry the fire rating is
based on the material type of the clay masonry unit.
(continued on Page 2)
1
TMS Responds
January 2003
Table 1 - Fire resistance rating of concrete masonry assemblies based on Standard Method
for Determining Fire Resistance of Concrete and Masonry Construction Assemblies
(ANSI/ACI 216.1-97/TMS 0216-97), which is commonly referred to as the Equivalent
Thickness Table.
Aggregate type
11/2 hr
2 hr
3 hr
4 hr
2.8
(71)
3.6
(91)
4.2
(107)
5.3
(135)
6.2
(157)
Limestone, cinders
or air-cooled slag
2.7
(69)
3.4
(86)
4.0
(102)
5.0
(127)
5.9
(150)
Expanded clay,
expanded shale or
expanded slate
2.6
(66)
3.3
(84)
3.6
(91)
4.4
(112)
5.1
(130)
Expanded slag or
pumace
2.1
(53)
2.7
(69)
3.2
(81)
4.0
(102)
4.7
(119)
A. Fire resistance ratings between the hourly fire resistance rating periods listed shall be
determined by linear interpolation based on the equivalent thickness value of the concrete masonry assembly.
B. Minimum required equivalent thickness corresponding to the fire resistance ratings for
units made with a combination of aggregates shall be determined by linear interpolation based on the percent by volume of each aggregate used in the manufacture.
TMS Responds
January 2003
This analysis assumes that the units in the wall meet one of the
appropriate ASTM Standards in ACI 216.1/TMS 0216. These
9
5
are ASTM C 34 for hollow clay tile and ASTM C 90 for the
concrete masonry units. Conservative assumptions of the wall
materials with respect fire resistance will be made to provide
least wall condition. The fire resistance rating of the wall
components are determined as shown below.
Response by J. Gregg Borchelt, P.E., Vice President, Engineering and Research at the Brick Industry Association
The fire resistance rating of an existing masonry wall can be
established through a standard referenced by the International
Building Code, ACI 216.1/TMS 0216, Fire Resistance Rating
for Concrete and Masonry Walls 4. This standard uses a
method of determining the fire resistance of composite walls
with a mathematical formula based on the analysis of fire test
reports.
The equation for the fire resistance rating of a composite wall
in ACI 216.1/TMS 0216 is Eq. 2-4:
R = (R10.59 + R20.59 + ... + Rn0.59 )1.7
Eq. 2-4
1 hr
2 hr
3 hr
4 hr
Solid brick or
shaleD
2.7
(69)
3.8
(97)
4.9
(124)
6.0
(152)
3. ASTM E 199-00a, Standard Test Methods for Fire Tests of Building Construction and Materials, American Society for Testing
and Materials, West Conshohocken, PA, 2000.
2.3
(58)
3.4
(86)
4.3
(109)
5.0
(127)
3.0
(76)
4.4
(112)
5.5
(140)
6.6
(168)
5. ASTM C 90-99a, Standard Specification for Loadbearing Concrete Masonry Units, American Society for Testing and Materials,
West Conshohocken, PA, 1999.
6. ASTM C 140-02a, Standard Test Methods for Sampling and Testing Concrete Masonry Units and Related Units, American Society for Testing and Materials, West Conshohocken, PA, 2002
7. ASTM C 216-00, Standard Specification for Structural Clay Facing Tile, American Society for Testing and Materials, West
Conshohocken, PA, 2000.
8. ASTM C 67-00, Standard Test Methods for Sampling and Testing
Brick and Structural Clay Tile, American Society for Testing and
Materials, West Conshohocken, PA, 2000.
9. ASTM C 34-96, Standard Specification for Structural Clay LoadBearing Wall Tile, American Society for Testing and Materials,
West Conshohocken, PA, 1996.
3
TMS Responds
January 2003
Disclaimer
This document is intended to provide explanation of typical and not-sotypical questions regarding masonry design, construction, evaluation and
repair. It is intended for masonry design professionals, architects, engineers, inspectors, contractors, manufacturers, building officials, students,
and others interested in masonry. It is not intended to cover every aspect of
the discussed topics, but rather to focus on key issues that should be considered and addressed. This document should not be used as the sole guide
for designing, constructing, evaluating or repairing masonry. It is imperative to refer to relevant building codes, standards and other industry-related documents. As such, TMS assumes no liability for any consequences
that may follow from the use of this document. In addition, the opinions,
ideas and suggestions given herein are those of the respondent, and not
necessarily those of The Masonry Society.
in. (92 mm), which is the specified thickness of a 4 in. (102 mm)
concrete masonry unit), has a fire resistance rating of 0.647.
Wall Fire Resistance Rating
Substituting these values in to Equation 2-4 yields:
R = (R10.59 + R20.59 + ... + Rn0.59)1.7
R = (0.6220.59 + 0.6470.59)1.7
R = (0.756 + 0.774)1.7 = (1.53)1.7
R = 2.06 hours
Based on these conservative calculations in compliance with
ACI 216.1/TMS 0216, Fire Resistance Rating for Concrete
and Masonry Walls, the wall has a fire resistance rating of at
least 2 hours.
TMS Responds
January 2003